Understanding the Modbus Protocol


About
Modbus Protocol Basics
Modbus Functions
Exceptions
Modbus Data Model
Modbus Implementations
Serial Modbus Implementations
IP based Modbus Implementations
Critical Evaluation of the Specification(s)

About

This document introduces the reader to the Modbus protocol. It presents a basic protocol description and
discusses the serial and the TCP based implementations.

Modbus Protocol Basics

Basically Modbus is an application layer protocol (see Figure 1) for communication between devices,
mainly to exchange data typical for the field of automation.

Figure 1: ISO/OSI Context

At this level Modbus is a stateless client-server protocol (e.g. much like HTTP), based on transactions,
which consist of a request (issued by the client) and a response (issued by the server). In the field where
this protocol is usually applied, there exists a concept that is one of the possible schemas governing the
lower level communication behavior on a network using a shared signal cable: Master-Slave. To prevent
confusion, the following directed relations describe Master-Slave in terms of the Client-Server paradigm:
the Master is a Client
the Slave is a Server
A transaction and it's context is visualized in Figure 2.

Figure 2: Modbus Transaction

The stateless communication is based on a simple package, that is called Protocol Data Unit (PDU). The
protocol specification defines three types of PDU's:

1 of 5 12/29/2015 2:22 PM
Understanding the Modbus Protocol http://jamod.sourceforge.net/kbase/protocol.html

Request PDU, consisting of:


1. a code specifying a function (Function Code, 1 byte)
2. and function specific data (Function Data, varying number of bytes)
Response PDU, consisting of:
1. the function code corresponding to the request (Function Code, 1 byte)
2. and response specific data (Response Data, varying number of bytes)
Exception Response PDU, consisting of:
1. the function code corresponding to the request + 0x80 (128), (Error Code, 1 byte)
2. and a code specifying the exception (Exception Code, 1 byte)
Figure 3 presents a visualization of these packages.

Figure 3: Modbus Protocol Data Units (PDU)

Modbus Functions

The specification defines a certain number of functions, each of which is assigned a specific function code.
These are in the range 1-127 (decimal), as 129(1+128)- 255(127+128) represents the range of error codes.
While the first published version of the specification defined different classes of functions (e.g. Class 0,
Class 1, Class 2), the newly released specification (from http://www.modbus.org; see Knowledge Base
Index) defines categories of function codes:
Public
Are guaranteed to be unique and specify well defined functions that are publicly documented. These
are validated by the community and a conformance test exists.
User-Defined
Are available for user-defined functions, thus their codes might not be unique. The specification
defines the code ranges 65-72 and 100-110 for user-defined functions.
Reserved
These are currently used by some companies for legacy products and are not available for public use
(these are not discussed any further in the specification).
The documentation for a function consists of:
1. a description of the function (i.e. what it is good for), it's parameters and return values (including
possible exceptions).
2. the assigned Function Code
3. the Request PDU
4. the Response PDU
5. the Exception Response PDU
The specification further documents defined and assigned public functions.

Exceptions

In certain cases, the response from a slave will be an exception. The primary identification of an
exception response is the error code (function code + 128), which is further specified by the exception
code. Assigned codes and descriptions can be found in the specification.

Modbus Data Model

The basic public functions have been developed for exchanging data typical for the field of automation.
Table 1 contains the basic Modbus data types defined by the specification.

2 of 5 12/29/2015 2:22 PM
Understanding the Modbus Protocol http://jamod.sourceforge.net/kbase/protocol.html

Table 1: Modbus Data Types


Name Type Access Visual
Discrete Input single bit read-only

Discrete Output (Coils) single bit read-write

Input Registers 16-bit word read-only

Holding Registers (Registers) 16-bit word read-write

Note
The specification does not define the ways of organizing the related data in a device. However, the
organization has a direct influence on the addresses used in basic access functions. (Thus always
consult the device's documentation to learn about addressing in basic access functions!)

Modbus Implementations

Basically Modbus has been implemented and used over all types of physical links (wire, fiber and radio)
and various types of lower level communication stacks. However, we will concentrate on the two basic
types of implementations (which are supported by jamod):
1. Serial: Asynchronous Master/Slave
2. IP: Master/Slave

Serial Modbus Implementations

Modbus started it's life in form of an implementation for asynchronous serial network communication. The
application level protocol operates directly on top of a serial interface and serial communication
standards. The most common ones (over wire) are:
RS232 (EIA232):
see The RS232 Standard
RS422/RS485:
see Introduction to RS422 and RS485
RS232 is used for short distance point-to-point communication, the same is valid for RS 422, which is a
bidirectional extension of RS232 for industrial environments, that also supports longer distances.
RS485 can be used for multipoint communication (i.e. multiple devices connected to the same signal
cable), employing the Master-Slave paradigm (one master and n fixed address slaves). Figure 4 visualizes
the possible network setups.

Figure 4: Serial Network Architectures

To enable the actual communication for this setups, the implementation extends the PDU with additional
fields, better said, it wraps the PDU into a package with a header and an error checksum (see Figure 5).
The resulting package is defined by the protocol specification as Application Data Unit (ADU), that has a
maximum package size of 256 bytes.

3 of 5 12/29/2015 2:22 PM
Understanding the Modbus Protocol http://jamod.sourceforge.net/kbase/protocol.html

Note
The maximum package size limitation of 256 bytes applies for all existing Modbus protocol
implementations!

Figure 5: Serial ADU

The header is composed of an address field (1 byte) and the tail is an error checksum over the whole
package, including the address field (i.e. header). For transmission the Modbus message (i.e. ADU) is
placed into a frame that has a known beginning and ending point, allowing detection of the start and the
end of a message and thus partial messages. There exist two transmission modes, which differ in
encoding, framing and checksum:
1. ASCII
Frames are encoded into two ASCII characters per byte, representing the hexadecimal notation of the
byte (i.e. characters 09, AF). The error checksum is represented by a longitudinal redundancy
check (LRC; 1 byte) and messages start with a colon (':', 0x3A), and end with a carriage return line
feed ("CRLF", 0x0D0A). Pauses of 1 second between characters can occur.
2. RTU
Frames are transmitted binary to achieve a higher density. The error checksum is represented by a
cyclic redundancy check (16 bit CRC; 2 byte) and messages start and end with a silent interval of at
least 3.5 character times. This is most easily implemented as a multiple of character times at the
baud rate that is being used on the network. The maximum pause that may occur between two bytes
is 1.5 character times.
jamod is designed to support both transmission modes, using an implementation which is based on the
javax.comm API.

Warning
The RTU implementation does only support the Master side. It is working by the best effort principle,
which means it might not work in a reliable way in a low-lantency real-time context.

It is indeed possible to implement the serial transport based on other serial stack implementations (i.e.
replacements for the Java Comm API implementation) like for example SerialPort ( http://www.sc-
systems.com/products/serialport/serialport.htm). According to the product info it supports around 20
platforms and it has been successfully used to implement the two serial transmission modes in Java
(Master only, see Field Talk/Java, a commercial Master protocol pack from Focus Engineering).

IP based Modbus Implementations

A TCP/IP based Modbus protocol implementation (Modbus/TCP) has been recently committed as an RFC
draft to the IETF. It uses the TCP/IP stack for communication (registered port is 502) and extends the
PDU with an IP specific header (see Figure 6).
The possible network setups are not governed by the specification; it is possible to setup multi-master
systems or realize bidirectional communication (i.e. have nodes that are master and slave at the same
time). However, the user should be well aware that there are implications from deviations of the
Master/Slave schema.

Figure 6: Modbus/TCP ADU

The IP specific header (called MBAP in the specification) is 7 bytes long and composed of the following
fields:
1. the invocation identification (2 bytes) used for transaction pairing; formerly called transaction
identifier
2. the protocol identifier (2 bytes), is 0 for Modbus by default; reserved for future extensions
3. the length (2 bytes), a byte count of all following bytes
4. the unit identifier (1 byte) used to identify a remote unit located on a non-TCP/IP network

4 of 5 12/29/2015 2:22 PM
Understanding the Modbus Protocol http://jamod.sourceforge.net/kbase/protocol.html

Critical Evaluation of the Specification(s)

There are a few points regarding the specification, which are definitely discussable:
1. The specification does not present a consistent naming for all of the basic simple data types. This
propagates to the naming of a number basic data access functions. Probably it would be good to
elaborate one consistent naming schema, to avoid confusion and allow better mind mapping.
2. The Modbus Encapsulated Interface (MEI) is exposed through a documented public function, without
being further explained.
3. The properties of the protocol are perfectly suited for the use of UDP/IP as transport layer protocol:
a. it is stateless,
b. transaction oriented
c. and the package size is limited to 256 bytes, which should be easily transferable over any IP
capable link (including IP over Serial) without the necessity to split the package.
Especially if a real-time communication has to be achieved, it might be of interest to investigate in a
Modbus/UDP implementation.

Note
For learning more about Modbus/UDP, please see: Modbus/UDP Specification.

by Dieter Wimberger