The document is a worksheet for calculating loading on an intrinsic safety (I.S.) safety device from connected field devices and cabling. It includes tables to enter parameters of the field device entity, up to four cables, and safety device entity. The calculated loading from the field device and cabling is compared to the safety device's entity parameters to assess if loading conditions are satisfied. If all conditions are met, the safety device loading assessment status is marked as "PASS".

Uploaded by

hafizi07
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
219 views

Is Loop Calculate Table

The document is a worksheet for calculating loading on an intrinsic safety (I.S.) safety device from connected field devices and cabling. It includes tables to enter parameters of the field device entity, up to four cables, and safety device entity. The calculated loading from the field device and cabling is compared to the safety device's entity parameters to assess if loading conditions are satisfied. If all conditions are met, the safety device loading assessment status is marked as "PASS".

Uploaded by

hafizi07
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

I.S.

Loop Calculation Work Sheet

Loop Number:
Field Device Description:
Safety Device Description:
Instrumentation Cable Description: Various Refer to Block Diagram and Cable Schedule Referenced on Sheet 2

I.S. Field Device I.S. Safety Device Entity


Cable 1 Ident Cable 2 Ident Cable 3 Ident Cable 4 Ident
Entity Parameters Parameters
Approval Certificate No. Approval Certificate No.
Part No. Part No. Part No. Part No.
Part No. Part No.
Volts Ui 0 mH / Km 0 mH / Km 0 mH / Km 0 mH / Km 0 Volts Uo 0
mA Ii 0 nF / Km 0 nF / Km 0 nF / Km 0 nF / Km 0 mA Io 0
W Ri . W / Km 0 W / Km 0 W / Km 0 W / Km 0 Lo /Ro 0
Li / Ri . Lc / Rc 0 Lc / Rc 0 Lc / Rc 0 Lc / Rc 0 mW Po 0
mW Pi 0 Length m 0 Length m 0 Length m 0 Length m 0 mH Lo 0
mH Li 0 mH Lc1 . mH Lc2 . mH Lc2 . mH Lc2 . nF Co 0
nF Ci 0 nF Cc1 . nF Cc2 . nF Cc2 . nF Cc2 .
W Rc1 . W Rc2 . W Rc2 . W Rc2 .
Latest Revision
NOTE: Only enter information into shaded areas above

Calculated Loading on I.S. Safety I.S. Safety Device Loading Assessment


I.S. Safety Device
Device = I.S. Field Device Entity + Satisified Assessment Status
Entity Parameters Conditions to be satisfied
Cabling Parameters Yes / No
Ui = 0 Uo = 0 Ui > or = Uo YES PASS
Ii = 0 Io = 0 Ii > or = Io YES PASS
Pi = 0 Po = 0 Pi > or = Po YES PASS
Li + Lc = 0 Lo = 0 Li + Lc < or = Lo YES PASS
Ci + Cc= 0 Co = 0 Ci + Cc < or = Co YES PASS
Li / Ri = 0 Lo / Ro = 0 Li / Ri < or = Lo / Ro YES PASS