ROC800
ROC800
ROC800
October 2016
ROC809
ROC827
This manual may be revised periodically to incorporate new or updated information. The revision date
of each page appears at the bottom of the page opposite the page number. A change in revision date
to any page also changes the date of the manual that appears on the front cover. Listed below is the
revision date of each page (if applicable):
Page Revision
All pages October-2016
All pages January-2016
All pages December-2015
All pages July-2014
All pages May-2013
All pages November-2010
All pages June-2009
Initial issue March-2006
ii Revised October-2016
ROC800-Series Instruction Manual
Contents
iv Revised October-2016
ROC800-Series Instruction Manual
Revised October-2016 v
ROC800-Series Instruction Manual
B.9 Two-Stage Valve with Two Limit Switches to ACIO Module............................................................ B-9
Index I-1
vi Revised October-2016
ROC800-Series Instruction Manual
Table 1-1. ROC809 Module Placement (Series 1 CPU vs. Series 2 CPU)
Table 1-2. ROC827 Module Placement (Series 1 CPU vs. Series 2 CPU)
2
With firmware version 2.10 or greater
3
The ROC827 supports a maximum of two MVS modules
4
With firmware version 3.10 or greater
5
With firmware version 3.20 or greater
1.3 Hardware
The ROC809 and ROC827 are highly innovative and versatile units
with an integrated backplane to which the central processor unit (CPU),
power input module, communication modules, and I/O modules
connect. The ROC809 (see Figure 1-1) has nine module slots, of which
three can house communication modules. The ROC827 base unit
(shown on the left-hand side of Figure 1-2) has three I/O module slots.
The ROC800-Series expansion backplanes (EXPs) attach to the
ROC827 base unit (see Figure 1-2). Each EXP provides six additional
I/O module slots. The ROC827 can support up to four EXPs, for a total
of 27 I/O module slots (six slots per EXP plus the three I/O slots on the
ROC827 base unit).
The ROC800s use a Power Input module to convert external input
power to the voltage levels required by the electronics and to monitor
voltage levels to ensure proper operation. Three Power Input modules
12 Volts dc (PM-12), 24 Volts dc (PM-24), and 30 Volts dc (PM-30)
are available. For more information on the Power Input modules, refer
to Chapter 3, Power Connections.
The ROC800s support a variety of communication protocols: ROC Plus,
Modbus, Modbus TCP/IP, Modbus encapsulated in TCP/IP, and
Modbus with Electronic Flow Measurement (EFM) extensions.
Figure 1-1 shows the housing, typical I/O modules, and communication
modules installed in a ROC809. The patented ABS (Acrylonitrile
Butadiene Styrene) plastic housing has wire covers to protect the wiring
terminals. The housing includes DIN rail mounts for mounting the unit
on a panel or in a user-supplied enclosure. Patent 6,771,513 covers the
ROC800 enclosure (refer to www.uspto.gov).
B G
H
D
Module Placement The left-most slots in the ROC809 (Figure 1-1) accommodate the
Power Input module and the CPU module. The remaining nine slots
can accommodate either communication modules or I/O modules (see
Table 1-1).
Note: If you use the optional communications modules, you can only
place those modules in the three slots (1, 2, or 3) immediately to
the right of the Power Input and CPU modules. Place I/O
modules in any available slot.
Figure 1-2 shows a ROC827 base unit (left) and a typical expansion
backplane (EXP) (right) populated with a full complement of six I/O
modules. Each EXP is composed of the same plastic housing as the
ROC827, contains six I/O slots, and has a powered backplane that easily
attaches to the ROC827 and other EXPs.
B
G
H
D
E
A Power Supply Module
B CPU
C LOI (Local Port) EIA-232 (RS-232D)
D Built-in Ethernet (Comm1)
E Built-in EIA-232 (RS-232C) (Comm2)
F Module (1 of 27 max)
G Wire Channel Cover
H Right End Cap
Figure 1-2. ROC827 Base Unit with One Expansion Backplane (separated for clarity)
I/O Modules The ROC800 and EXPs support various types of Input/Output (I/O)
modules, which can satisfy a wide variety of field I/O requirements
(refer to Chapter 4, Input/Output Modules). You can place I/O
modules in any available slot. I/O modules include:
Analog Inputs (AI).
Analog Outputs (AO).
Discrete Inputs (DI).
Discrete Outputs (DO).
Digital Relay Outputs (DOR).
Advance Pulse Module (APM).
Alternating Current I/O (ACIO).
Multi-variable Sensor (MVS I/O).
Highway Addressable Remote Transducer (HART) Module.
Pulse Inputs (PI) High/Low Speed.
Resistance Temperature Detector Inputs (RTD).
Thermocouple (TC) Inputs.
IEC 62591.
APP 485.
Revised October-2016 General Information 1-7
ROC800-Series Instruction Manual
Note: You can install up to two MVS modules per ROC800. This
limit does not apply to the MVS I/O module.
Note: If the real-time clock does not keep the current time when you
remove power, replace the lithium battery.
Analog Input, and #1, Battery to open the System Analog Input
screen). Refer to Table 1-3.
Table 1-3. System Analog Inputs
System AI PM-12 PM-24 PM-30
Point Function Function Function
Number
1 Battery Input Voltage Module Voltage Module Voltage
2 Charge in Voltage Module Voltage Voltage In
3 Module Voltage Module Voltage Module Voltage
4 Not Used Not Used Not Used
5 On Board Temperature On Board Temperature On Board Temperature
1.3.4 Options
The ROC800 allows you to choose from a wide variety of options to
suit many applications.
Optional communication modules include EIA-232 (RS-232) serial
communications, EIA-422/485 (RS-422/485) serial communications,
Multi-Variable Sensor (MVS), dial-up modem communications, and the
HART module (refer to Chapter 5, Communications).
Each MVS module can provide power and communications for up to six
MVS sensors (refer to Chapter 5, Communications).
Optional I/O modules include Analog Inputs (AI), Analog Outputs
(AO), Discrete Inputs (DI), Discrete Outputs (DO), Discrete Output
Relays (DOR), Pulse Inputs (PI), Resistance Temperature Detector
(RTD) Inputs, Thermocouple (T/C) Inputs, Advanced Pulse (APM), and
Alternating Current I/O (ACIO) (refer to Chapter 4, Input/Output
Modules).
The optional application license keys provide extended functionality,
such as the use of the DS800 Development Suite Software (the IEC
61131-3 compliant programming environment) and various user
programs, and enable embedded meter runs. For example, you need to
install a license key with the proper license in the ROC800 to perform
AGA calculations. Refer to Section 1.6, DS800 Development Suite
Software.
The Local Operator Interface (LOI local port) communications terminal
requires the installation of an LOI cable between the ROC800 and your
PC. The LOI port uses an RJ-45 connector with a standard EIA-232
(RS-232D) pin out.
1.5 Firmware
The firmware that resides in Flash Read-Only Memory (ROM) contains
the operating system, ROC Plus communications protocol, and
application software. The CPU module provides battery-backed Static
Random Access Memory (SRAM) for saving configurations, storing
events, alarms, and the historical logs.
ROC800 or ROC800L The ROC800-Series supports either of two sets of firmware. The
original ROC800 firmware is designed primarily to support gas flow
measurements. The ROC800L firmware is designed to support both
liquids and gas flow measurements.
ROC800L The ROC800L firmware provides many of the same capabilities as the
ROC800 firmware. We recommend, however, that the ROC800L
supports only six gas runs (using a single AGA key). History stored in
firmware is limited to measurements from gas meter runs, rather than
liquids. Software supports most liquid-related capabilities; other
firmware functions remain the same.
view the logs, save them to a disk file, or print them using ROCLINK
800 software.
ROC800L To accommodate NIST Handbook 44 (HB 44) requirements, the
firmware in the ROC800L tracks up to 1000 weights and measures
(W&M) events.
Note: For the ROC800L, you configure runs and stations using the
individual user programs.
Note: For a complete and current listing of all supported liquid and/gas
calculations on the ROC800, refer to the technical specifications
ROC800-Series Operating System Firmware (ROC800:FW1).
Notes:
the PM-24 and PM-30 modules, when power falls below the
LoLo alarm point, the CPU goes into sleep mode. In sleep mode,
the backplane still receives power, the DO modules continue to
hold their logic, but nothing controls I/O at this point. If you
need both the increased power capacity offered by the PM-30
and low voltage cutoff, refer to the options provided in the
description of the PM-30 module in Chapter 3 of this manual.
You can build custom displays for the ROC800 that combine both
graphic and dynamic data elements. The displays can monitor the
operation of the ROC800 either locally or remotely.
You can archive historical values for any numeric parameter in the
ROC800. For each parameter configured for historical archiving, the
system keeps time-stamped minute, periodic, and daily data values as
well as yesterdays and todays daily minimum and maximum values.
You can collect history values from the ROC800 using ROCLINK 800
or another third-party host system. You can view history directly from
the ROC800 or from a previously saved disk file. For each history
segment, you can configure the number of periodic history values
archived, the frequency of archiving the periodic values, the number of
daily values archived, and the contract hour.
ROCLINK 800 can create an EFM (Electronic Flow Measurement)
report file that contains all the configuration, alarms, events, periodic
and daily history logs, and other history logs associated with the stations
and meter runs in the ROC800. This file then becomes the custody
transfer audit trail.
The SRBX (Spontaneous-Report-By-Exception) alarming feature is
available for the host communication ports (Local and dial-up modem
ports). SRBX allows the ROC800 to contact the host to report an alarm
condition.
Batch Queuing:
Sequences future batches, if appropriate for your organization. Used
in conjunction with the batching program.
Note: The integrity of metrology results is critical to the measurement
aspects of the ROC800L. You can lock certain configuration
parameters to ensure the accuracy of liquid hydrocarbon
calculations.
The site must comply with class limits of Part 15 of the FCC rules.
Operation is subject to the following two conditions: (1) The device
may not cause harmful interference, and (2) the device must accept
any interference received, including interference that may cause
undesired operation.
2.3 Housing
The housing case is made of a patented Acrylonitrile Butadiene Styrene
(ABS) plastic (U.S. Patent 6,771,513) and the wire channel covers are
made of polypropylene plastic.
Note: The pry holes are located on the sides of the end caps.
2. Place the tip of a flat-blade screwdriver into the bottom pry hole of
the end cap and loosen the end cap by pulling the handle of the
screwdriver away from the backplane.
3. Pivot the front end cap away from the back edge of the housing.
To replace the end caps:
1. Align the back edge of the end cap on the housing.
2. Rotate the end cap towards the housing and snap the end cap into
place.
Note: The tabs on the left side of the wire channel cover should rest in
the slots on the left edge of the channel.
To avoid circuit damage when working inside the unit, use appropriate
Caution electrostatic discharge precautions (such as wearing a grounded wrist
strap).
When working on units located in a hazardous area (where explosive
gases may be present), make sure the area is in a non-hazardous state
before performing procedures. Performing these procedures in a
hazardous area could result in personal injury or property damage.
Figure 2-1. Side View of the ROC800 Figure 2-2. Bottom View of the ROC800
Note: The distance from the mounting panel to the front of the
ROC800 is 174mm (6.85). If you mount the ROC800 inside an
enclosure and want to connect a cable to the LOI or Ethernet
port, ensure adequate clearance for the cable and the enclosure
door. For example, a molded RJ-45 CAT 5 cable can increase
the clearance requirement for the enclosure by 25mm (1).
Note: The EXP may not have attached end caps. If it does, remove
the left-hand end cap.
5. Pivot the back edges of the ROC827 and the EXP toward each other
until they click together.
Note: The plastic locking clips at the back of the EXP click when
the two units securely fasten together.
6. Attach an end cap to the right side of the EXP (if it does not have
one). Do not replace the wire channel covers until you finish
installing and wiring the modules in the EXP.
5. Once you free the plastic locking clips from their securing tabs,
gently pivot the back of the EXP away from the ROC827.
C
D
A Securing Screw
B LED Button
C LOI EIA-232 (RS-232D)
D Status LED
E Ethernet
F EIA-232 (RS-232C)
G Securing Screw
Figure 2-7. CPU Front View (Series 1 and Series 2 CPU Modules)
D H
H
E
F
I
A Battery
B LED Button
C RJ-45 Port
D License Keys
E RESET Button
F RJ-45 Port
G RS-232 Port
H Microprocessor
I Battery backup jumper
Figure 2-8. CPU Connectors (Series 1 and Series 2 CPU Modules)
LED: Press to turn on the LEDs on the CPU module, I/O modules,
and communication modules when the ROC800 has timed out.
The STATUS LED helps indicate the integrity of the ROC800 (refer to
Table 2-2).
Table 2-2. STATUS LED Functions
To save power, you can enable or disable the LEDs on the ROC800
(with the exception of the LED on the power module). Using
ROCLINK 800 (from the ROCLINK 800 menu, select ROC > Flags
and the Advanced tab), you can define how long the LEDs remains on
after you press the LED button on the CPU module. For instance, with
the default setting of five minutes, all LEDs turn off after five minutes.
If you press the LED button, LEDs light and stay lit again for five
minutes. By entering a 0 (zero), the LED always stays lit.
2. Press the CPU firmly into the slot, ensuring the ejector clips rest on
the module rail guides. The connectors at the back of the CPU
module fit securely into the connectors on the backplane.
3. Place the CPU faceplate on the CPU.
4. Tighten the two screws on the faceplate of the CPU module firmly
(see Figure 2-7).
5. Replace the wire channel cover.
6. Review Restarting the ROC800 in Chapter 6, Troubleshooting.
7. Return power to the ROC800 unit.
6. Press the license key into the terminal until it is firmly seated. Refer
to Figure 2-10.
7. Replace the CPU faceplate and tighten the two captive screws.
8. Replace the wire channel cover.
9. Review Restarting the ROC800 in Chapter 6, Troubleshooting.
10. Restore power to the ROC800.
Check the input power polarity before connecting power to the ROC800.
Caution Incorrect polarity can damage the ROC800.
When working on units located in a hazardous area (where explosive
gases may be present), make sure the area is in a non-hazardous state
before performing procedures. Performing these procedures in a
hazardous area could result in personal injury or property damage.
2.8.1 Startup
Before you apply power to the ROC800, assess the power requirements
(including the base unit, EXPs, and any installed modules and
peripheral devices) that comprise the total configuration for your
ROC800. Refer to Determining Power Consumption in Chapter 3,
Power Connections.
Apply power to the ROC800 (refer to Installing a Power Input Module
in Chapter 3, Power Connections). The power input modules LED
2.8.2 Operation
Once startup is successful, configure the ROC800 to meet the
requirements of the application. Once it is configured and you have
calibrated the I/O and any associated Multi-Variable Sensors (MVS,
MVSS, MVSI, and so on), place the ROC800 into operation.
E
A
F
D
G
H
A BAT+ / BAT
B CHG+ / CHG
C AUX+ / AUX
D AUXSW + / AUXSW
E VOK LED
F VOFF LED
G VOVER LED
H TEMP LED
Figure 3-1. 12 Volt dc Power Input Module
The CHG+ and CHG terminals comprise an Analog Input channel that
allows you to monitor an external voltage between 0 to 18 Volts dc. For
example, you can connect a solar panel upstream of the solar regulator
to monitor the output of the solar panel. This allows you to compare the
System AI Point Number 2 for the charging voltage (CHG+) to the
actual battery voltage (BAT+) System AI Point Number 1 and take
action as required. The module has a low-voltage cut-off circuit built-in
to guard against draining power supply batteries. Refer to Automatic
Self Tests in Chapter 1, General Information.
Use the AUX+ / AUX terminals to supply reverse polarity protected
source voltage to external devices, such as a radio or solenoid. Use the
AUXSW+ / AUXSW terminals to provide switched power for external
devices. The AUXSW+ is turned off when the ROC800 detects a
software configurable voltage at the BAT+ / BAT terminals.
Table 3-1 details the specific connection information for the 12 volt dc
(PM-12) Power Input module. Table 3-2 indicates the LED fault
indicators.
Signal LED
VOK Green LED on when voltage is in tolerance on BAT+ and BAT.
VOFF Fault Red LED on when the AUXSW + output are disabled by
the CPU control line.
VOVER Fault Red LED on when AUXSW + is disabled due to excess
voltage on BAT+.
TEMP Fault Red LED on when AUXSW + output are disabled due to
the excess temperature of the Power Input module.
C
A
D
A +/
B AUX+ / AUX
C V12 LED
D V3.3 LED
Figure 3-2. 24 Volt dc Power Input Module
Signal LED
V12 Green LED on when voltage is provided to backplane.
V3.3 Green LED on when voltage is provided to CPU.
D
A
E
B
F
C
G
H
Low Voltage The design of the PM-30 power module (like the PM-24 power
Cutoff module it replaces) does not include the low voltage cutoff feature
present in the PM-12 power module. In the PM-12 module, when
power falls below the set LoLo alarm (a default of 10.1V), the module
ceases to provide power to the backplane. Thus, the module shuts
down CPU operations.
Remote Automation Solutions continues to offer the PM-12 for
installations requiring low voltage cutoff. Neither the PM-24 or the PM-
30 has the low voltage cutoff feature. However, if you need low voltage
cutoff, we suggest one of the following solutions:
Place a low voltage disconnect device between the ROC800 and
power source. Placing a commercially available low voltage
disconnect device between the power source and the ROC800
provides the low voltage cutoff protection. Many low voltage
disconnect devices have user-selectable disconnect values for a
variety of voltages.
LOW
POWER
VOLTAGE
SUPPLY
DISCONNECT
Figure 3-4. Low voltage disconnect device between the ROC800 and
power source
SOLAR
PANEL
LOW SOLAR
VOLTAGE POWER
DISCONNECT REGULATOR
Figure 3-5. Low voltage disconnect device between the solar regulatory
circuitry and the ROC800
POWER
SUPPLY
EXTERNAL
DEVICE
Figure 3-6. Auxiliary Switch (AUX SW) output terminals on the PM-30
PM-24 For the 24 volt dc Power Input module (PM-24), the AUX voltage is
always 12 Volts dc minus ~0.7 Volts. AUX+ / AUX is internally
current-limited by a 0.5 Amp Positive Temperature Coefficient (PTC).
PM-30 For the 30 volt dc Power Input module (PM-30), the auxiliary output
follows the voltage located at BAT+ minus ~1.0 Volts dc, which is the
protection diode voltage drop. For example, if the BAT+ voltage is 13
volts dc, then AUX+ is ~12.3 Volts dc.
For the PM-30 Power Input module, AUX+ / AUX is always on and is
internally current-limited by a .9 Amp Positive Temperature Coefficient
(PTC).
If you need to cycle power to the radio or other device to reduce the
load on the power source (a recommended practice when using
batteries), use a Discrete Output (DO) module to switch power on and
off. (The PM-12 and PM-30 modules on-board AUXSW+ and AUXSW
terminals perform this function.) Refer to the ROCLINK 800
Configuration Software User Manual (for ROC800-Series) (part
D301250X012) or the ROCLINK 800 Configuration Software User
Manual (for ROC800L) (part D301246X012).
Note: You should also identify any devices (such as a touch screen
panel) that may be powered by the same system but not
necessarily by the ROC800.
10. Add the value for the Power System Safety Factor (0.25) to the
value for Total for ROC800 Base Unit, All Modules, and Other
Devices to determine the total estimated power consumption for the
configured ROC800 system.
Refer to Table 3-5 and the value you entered in the Total for ROC800
Base Unit and All Modules line. That is the value against which you
tune your configuration to accommodate your Power Input module. If
your configuration requires more power than the Power Input module
you intend to use, you need to modify your I/O module configuration to
reduce your power requirements.
Tuning Hints Review the content of Tables 3-6 through 3-20. Suggestions to help
you better align the configuration of your ROC800 with the capability
of the Power Input module you intend to use include:
Analog Input
AI Module Base 84 mA @ 12 volts dc 1008 mW
Jumper set for +T @ 12 volts dc
Channels mA current
Channel 1 draw from +T * 1.25 * 12
Channels mA current
Channel 2 draw from +T * 1.25 * 12
Channels mA current
Channel 3 draw from +T * 1.25 * 12
Channels mA current
Channel 4 draw from +T * 1.25 * 12
Jumper set for +T @ 24 volts dc
Channels mA current
Channel 1 draw from +T * 2.50 * 12
Channels mA current
Channel 2 draw from +T * 2.50 * 12
Channels mA current
Channel 3 draw from +T * 2.50 * 12
Channels mA current
Channel 4 draw from +T * 2.50 * 12
Table Total
Duty Cycle The duty cycle is based on the average current flow compared to the
full-scale current flow value. To approximate the duty cycle, estimate
the average current consumption in relation to its maximum range. For
example, if an AI channels current averages 16 mA:
Duty Cycle = Average mA output Maximum mA Output = (16 20) = 0.80
Duty Cycle The duty cycle is based on the average current flow compared to the
full-scale current flow value. To approximate the duty cycle, estimate
the average current consumption in relation to its maximum range. For
example, if an AO channels current averages 12 mA:
Duty Cycle = Average mA output Maximum mA Output = (12 20) = 0.60
19 mA @ 12 volts dc No
DI Module Base 228 mW
Channels Active
Channel 1 3.2 mA @ 12 volts dc 38.4 mW
Channel 2 3.2 mA @ 12 volts dc 38.4 mW
Channel 3 3.2 mA @ 12 volts dc 38.4 mW
Channel 4 3.2 mA @ 12 volts dc 38.4 mW
Channel 5 3.2 mA @ 12 volts dc 38.4 mW
Channel 6 3.2 mA @ 12 volts dc 38.4 mW
Channel 7 3.2 mA @ 12 volts dc 38.4 mW
Channel 8 3.2 mA @ 12 volts dc 38.4 mW
Per Active LED
1.5 mA 18 mW
Maximum 8
Table Total
Duty Cycle The duty cycle is the time on divided by the total time, and is
essentially the percent of time that the I/O channel is active
(maximum power consumption).
Duty Cycle = Active time (Active time + Inactive time)
For example, if a Discrete Input is active for 15 seconds out of every 60
seconds:
Duty Cycle = 15 seconds (15 seconds + 45 seconds) = 15 seconds 60 seconds = 0.25
20 mA @ 12 volts dc No
DO Module 240 mW
Channels Active
Channel 1 1.5 mA 18 mW
Channel 2 1.5 mA 18 mW
Channel 3 1.5 mA 18 mW
Channel 4 1.5 mA 18 mW
Channel 5 1.5 mA 18 mW
Per Active LED
1.5 mA 18 mW
Maximum 5
Table Total
Duty Cycle The duty cycle is the time on divided by the total time, and is
essentially the percent of time that the I/O channel is active
(maximum power consumption).
Duty Cycle = Active time (Active time + Inactive time)
For example, if a Discrete Output is active for 15 seconds out of every
60 seconds:
Duty Cycle = 15 seconds (15 seconds + 45 seconds) = 15 seconds 60 seconds = 0.25
6.8 mA @ 12 volts dc
DOR Module 81.6 mW
No Channels Active
150 mA for 10 mSec 1800 mW
Channel 1
during transition for 10 mSec
150 mA for 10 mSec 1800 mW
Channel 2
during transition for 10 mSec
150 mA for 10 mSec 1800 mW
Channel 3
during transition for 10 mSec
150 mA for 10 mSec 1800 mW
Channel 4
during transition for 10 mSec
150 mA for 10 mSec 1800 mW
Channel 5
during transition for 10 mSec
Per Active LED 18 mW for
1.5 mA
Maximum 5 10 mSec
Table Total
Table 3-13. Power Consumption of the High and Low Speed Pulse Input Module
Power Consumption (mW) Quantity Duty Sub-Total
I/O Module
Description PTYPICAL Used Cycle (mW)
21 mA @ 12 volts dc No
PI Module 252 mW
Channels Active
Channel 1 7.4 mA 88.8 mW
Channel 2 7.4 mA 88.8 mW
Per Active LED
1.5 mA 18 mW
Maximum 4
Jumper set to +T @ 12 1.25 * Measured Current
volts dc Draw at +T Terminal
Jumper set to +T @ 24 2.5 * Measured Current
volts dc Draw at +T Terminal
Table Total
Duty Cycle The duty cycle is the time on divided by the total time, and is
essentially the percent of time that the I/O channel is active
(maximum power consumption).
Duty Cycle = [Active Time * (Signals Duty Cycle)] (Total Time Period)
For example, if a Pulse Input receives a signal for 6 hours over a 24-
hour time period and the signals wave form is on time for 1/3 of the
signals period:
Duty Cycle = [6 hours * (1 3)] (24 hours) = 0.0825
Note: For an MVS sensor, the typical mW per MVS is about 300 mW.
Duty Cycle The duty cycle is the time on divided by the total time. For an MVS,
the sensor is always drawing power, so enter the duty cycle as 1 for
the MVS power calculations. The LEDs can also have an associated
duty cycle, which is essentially the percent of time that the LEDs are
active.
Duty Cycle = Active time (Active time + Inactive time)
For example, if the LEDs are on approximately 20 minutes a day:
Duty Cycle = 20 minutes (24 * 60 minutes in a day) = 20 1440 = 0.014
Note: For an MVS sensor, the typical mW per MVS is about 300 mW.
Duty Cycle An RTD has no associated duty cycle. Consequently, always set 1
as the duty cycle value.
Note: The Series 1 CPU does not support the TC2 module.
Duty Cycle A thermocouple has no associated duty cycle. Consequently, always
set 1 as the duty cycle value.
Duty Cycle An IEC 62591 has no associated duty cycle. Consequently, always set
1 as the duty cycle value.
NRM Module 1
Pm-12 (12V) Joining
780 mW 1
Network
Pm-24 (24V) Joining
720 mW 1
Network
PM-30 (12V) Joining
960 mW 1
Network
Duty Cycle An NRM has no associated duty cycle. Consequently, always set 1
as the duty cycle value.
Total
Although Table 3-5 and Tables 3-6 through 3-20 take into account the
power the ROC800 supplies to its connected devices, be sure to add the
power consumption (in mW) of any other devices (such as radios or
solenoids) used with the ROC800 in the same power system, but which
are not accounted for in Tables 3-6 through 3-18.
Enter that Total value in the Other Devices line of Table 3-5.
Note: If you intend to store the ROC800 for an extended period, also
remove the internal backup battery located on the CPU module
(see Figure 3-9 or Figure 3-10).
A Battery
Figure 3-10. Backup Battery on Series 2 CPU Module
Note: Remove the plastic module cover and wire channel cover, if
present.
1. Slide the Power Input module into the slot.
2. Press the module firmly into the slot. Make sure the connectors at
the back of the Power Input module fit into the connectors on the
backplane.
3. Tighten the two captive screws on the front of the Power Input
module firmly (refer to Figures 3-1 and 3-2).
4. Return power to the ROC800.
5. Replace the wire channel cover.
6. Review Restarting the ROC800 in Chapter 6, Troubleshooting.
Always turn off the power to the ROC800 before you attempt any type
Caution of wiring. Wiring of powered equipment could result in personal injury
or property damage.
To avoid circuit damage when working with the unit, use appropriate
electrostatic discharge precautions, such as wearing a grounded wrist
strap.
Battery Reserve Battery reserve is the amount of time that the batteries can provide
power without discharging below 20% of their total output capacity.
The battery reserve should be a minimum of five days, with ten days
of reserve preferred. Add 24 hours of reserve capacity to allow for
overnight discharge. Space limitations, cost, and output are all factors
that determine the actual amount of battery capacity available.
To determine the system capacity requirements, multiply the system
current load on the batteries by the amount of reserve time required, as
shown in the following equation:
System Requirement = Current Load in Amps * Reserve Hours = _____ Amp Hours
Note: Remove the internal backup battery if you intend to store the
ROC800 for an extended period.
This chapter describes the Input/Output (I/O) modules used with the
ROC800 and expansion backplanes and contains information on
installing, wiring, and removing those modules.
DOC0513A
A Terminal Blocks
Figure 4-1. Typical I/O Module
A
F
B
H
I
C
J
K
D
The I/O modules acquire power from the backplane. Each module has
an isolated DC/DC converter that provides logic, control, and field
power as required. The ROC800 has eliminated the need for fuses on
the I/O modules through the extensive use of current-limited short-
circuit protection and over voltage circuitry. Isolation is provided from
other modules and the backplane, power, and signal isolation. The I/O
modules are self-resetting after a fault clears.
4.2 Installation
Failure to exercise proper electrostatic discharge precautions, such as
Caution wearing a grounded wrist strap may reset the processor or damage
electronic components, resulting in interrupted operations.
When installing units in a hazardous area, make sure all installation
components selected are labeled for use in such areas. Installation and
maintenance must be performed only when the area is known to be non-
hazardous. Installation in a hazardous area could result in personal
injury or property damage.
Each I/O module installs in the ROC800 in the same manner. You can
install any I/O module into any module socket, whether empty or in
place of another module.
Note: After you install a new I/O module or replace an existing I/O
module, it may be necessary to reconfigure the ROC800. To
change configuration parameters, use ROCLINK 800 software
to make changes to the new module. Any added modules (new
I/O points) start up with default configurations. Refer to the
ROCLINK 800 Configuration Software User Manual (for
ROC800-Series) (part D301250X012) or the ROCLINK 800
Configuration Software User Manual (for ROC800L) (part
D301246X012).
Note: The tabs on the top side of the wire channel cover should rest in
the slots on the top edge of the channel.
To avoid circuit damage when working inside the unit, use appropriate
Caution electrostatic discharge precautions (such as wearing a grounded wrist
strap).
When working on units located in a hazardous area (where explosive
gases may be present), make sure the area is in a non-hazardous state
before performing procedures. Performing these procedures in a
hazardous area could result in personal injury or property damage.
Note: Leaving the wire channel cover in place can prevent the
module from correctly connecting to the socket on the
backplane.
Note: If the module stops and will not go any further, do not force
the module. Remove the module and see if the pins are bent.
If the pins are bent, gently straighten the pins and re-insert
the module. The back of the module must connect fully with
the connectors on the backplane.
7. Connect to ROCLINK 800 software and login. The I/O modules are
self-identifying after re-connecting to ROCLINK 800 software.
8. Configure the I/O point.
Note: The AI-16 module provides 16-bit resolution and uses a 24-bit
A/D converter. DIP switches on the AI-16 module (see Figure 4-
6) allow you to select between current and voltage loop input.
Precision A
Resistor
A 12 / 24 V dc Jumper
Figure 4-4. AI-12 Jumper J4 (Shown Set to +12V)
-
-
250 + CURRENT LOOP DEVICE 4-20mA
+ CURRENT LOOP DEVICE 4-20mA
ROC800 POWERED
ROC800 POWERED
DOC0514B
DOC0506C
Figure 4-5. Analog Input Module Field Wiring (AI-12 and AI-16)
You can induce ground loops by tying commons from various modules
Caution together.
The AO module includes a moveable jumper (see Figure 4-7). Set the
jumper to 12V if the transmitter load is 300 or less. Set the jumper to
24V if the transmitter load exceeds 300.
Representative
Field Wiring
Internal Circuit
CURRENT LOOP
CONTROL
CURRENT LOOP
CONTROL
CURRENT LOOP
+V +
CONTROL 250 -
1-5 VOLT CONTROL DEVICE
DOC0505A
You can induce ground loops by tying commons from various modules
Caution together.
The DI module provides a source voltage for dry relay contacts or for an
open-collector solid-state switch.
The DI modules LEDs light when each input is active.
Each DI channel can be software-configured to function as a momentary
or latched DI (see the ROCLINK 800 Configuration Software User
Manual (for ROC800-Series) (part D301250X012 or the ROCLINK 800
Configuration Software User Manual (for ROC800L) (part
D301246X012). A latched DI remains in the active state until reset.
Other parameters can invert the field signal and gather statistical
information on the number of transitions and the time accumulated in
the on- or off-state.
The Discrete Input module is designed for use with dry relay contacts
Caution or solid-state switches. Applied voltage in excess of 24 Vdc may
damage the module.
The DI module senses the current flow, which signals the ROC800
electronics that the relay contacts have closed. The opening of the
contacts interrupts the current flow and the DI module signals the
ROC800 electronics that the relay contacts have opened. Using
ROCLINK 800, you can set the scan rate between 4 and 43200
milliseconds.
The left side of Figure 4-9 displays the internal circuitry while the right
side displays possible field wiring.
DI
+
1 DRY CONTACT
+V -
2 ROC800 POWERED
6.6KW 3
4
5
6
7
OPEN COLLECTOR
+ OR
8 OPEN DRAIN TYPE DEVICE
-
EXTERNALLY POWERED
C OM
8 CHAN
DOC0507A
You can induce ground loops by tying commons from various modules
Caution together.
The Pulse Input module is designed for use with dry relay contacts or
Caution solid-state switches. Applied voltage in excess of 24 Vdc may damage
the module.
The PI modules draw power for the active circuitry from the backplane.
Input signals are optically isolated.
Note: Do not connect wiring to both the Low and High speed
selections for a given channel. This results in unpredictable
operation of the PI module.
A +T 12 / 24 V dc Jumper
Figure 4-10. Pulse Input J4 Jumper (Set to +12 V)
DOC0510B
- +
H METER COIL
COM
+T
2 CHAN
DOC0511A
You can induce ground loops by tying commons from various modules
Caution together.
DO modules draw power for the active circuitry from the backplane,
and are current-limited for protection against excessive current.
5+
COM
5 CHAN
DOC0508A
You can induce ground loops by tying commons from various modules
Caution together.
Note: Since the DOR latches, a power failure does not change the
relays state. The relay retains the state (open or closed) it had
upon failure.
Figure 4-14 displays the field wiring connections to the output circuit of
the DOR module.
DO -
RELAY
Vs +
+ DISCRETE DEVICE
CH 1
S R
CH 2
LATCHING RELAY
NOTE: S = SET -
R = RESET
+
CH 3
- DISCRETE DEVICE
Vs - EXTERNALLY POWERED +
+
CH 4
S R
CONTROL -
-
CH 5
-
5 CHAN
DOC0509A
the RTD module. See Table 4-1, Table 4-2, and Figure 4-15.
The ROC800 provides terminations for a four-wire 100-ohm platinum
RTD with a DIN 43760 curve. The RTD module supports RTDs with
alphas equal to 0.00385 or 0.00392 //C. You can use a two-wire or
three-wire RTD probe instead of a four-wire probe, but they may
produce measurement errors due to signal loss on the wiring.
Wiring between the RTD probe and the ROC800 must be shielded wire,
with the shield grounded only at one end to prevent ground loops.
Ground loops cause RTD input signal errors.
Table 4-1. RTD Signal Routing
Jumper Jumper
Red
Red
Red
White
Jumper
Red
Figure 4-15 and Table 4-2 display the connections at the RTD terminals
for the various RTD probes.
Note: The wire colors for the RTD being used may differ.
You can induce ground loops by tying commons from various modules
Caution together.
PI + PI + MICROMOTION
ROC800 POWERED DEVICE
- OPEN COLLECTOR - 7835 / 7845
+T OR DENSITOMETER
OPEN DRAIN TYPE
- +
METER
COIL
Figure 4-16. Pulse Input Wiring on APM Figure 4-17. Micro Motion (Solartron) 7835/7845
Wiring on APM
PI
PI +
- GENERIC
+T DENSITOMETER - ROC800 POWERED
+ DRY CONTACT
Figure 4-18. Generic Densitometer Wiring on APM Figure 4-19. Input Detector Wiring on APM
DET SW 1 DET SW 2
DET SW 1 DET SW 2
Figure 4-20. Series Detector Switch (Normally Figure 4-21. Series Detector Switch Wiring
Open) Wiring on APM (Normally Closed) on APM
+
- EXTERNALLY POWERED
PREAMP
+T
- +
-
EXTERNALLY
+ POWERED METER
+T PREAMP
COIL 1
DET SW 1 DET SW 2 - +
METER
METER
COIL 2
Figure 4-22. Independent Detector Wiring on APM Figure 4-23. Two-Pulse Turbine Pulse Input Wiring
on APM
+12
10K
NO CONNECTION
EXTERNAL
DEVICE
CONTROL
DIP Switch The APM cards daughterboard contains several DIP switches which
Settings you use to control the modules activities. See Figure 4-25 for the
switch locations and labels; see Table 4-3 for the settings.
S4 S2
S3 S1
S5
1 1
Switch Channel Side Function Switch Position
Left 10 k Pullup to 12 V dc Up
1
Left No Pullup Resistor Down
S2
Right 10 k Pullup to 12 V dc Up
2
Right No Pullup Resistor Down
Left 10 k Pullup to 12 V dc Up
3
2 Left No Pullup Resistor Down
S3
Right 10 k Pullup to 12 V dc Up
4
Right No Pullup Resistor Down
Left 10 k Pullup to 12 V dc Up
Detector 2
Left No Pullup Resistor Down
S4
Right 10 k Pullup to 12 V dc Up
Detector 1
Right No Pullup Resistor Down
Left Pulse Output Up
4
S5 Left Pulse Input Down
N/A Right N/A N/A
1
Descriptors (up/down/right/left) assume that module terminal blocks face upward and daughterboard is visible
(see Figure 4-25)
2
If S1 is down, the 3-channel of this switch is non-functional; the 4-channel still functions normally.
The MVS I/O module consists of interface electronics that provide the
communications link between the ROC800 and the MVS devices. The
interface electronics controls communications with the sensor module,
provides scaling of process variables, aids calibration, stores operating
parameters, performs protocol conversion, and responds to requests
from the ROC800.
Each MVS I/O module provides the communications interface and the
isolated, short-circuit current-limited power required to connect up to
six MVS sensors.
Note: You can install up to two MVS modules per ROC800. This limit
does not apply to the MVS I/O module.
The MVS I/O module automatically creates six points, one for each of
the six possible MVS channels: 1 6 (for one MVS I/O) and 7 12 (for
a second MVS module). The system assigns points based on which
module is in the first slot. For example, if an MVS module is in slot 3,
the system automatically assigns it points 1 6. If you then install a
second MVS module into slot 1, the system re-assigns points so that slot
1 now holds points 1 6 and slot 3 holds points 7 12.
The ROC800 allows six MVS devices to be connected on its
communications bus in a multi-drop connection scheme. You must set
the address of each MVS device prior to final wiring of multiple MVS
devices. For proper operation of multiple MVS devices, each MVS
device must have a unique address. None of the addresses can be 240.
For details on MVS configuration, refer to the ROCLINK 800
Configuration Software User Manual (for ROC800-Series) (part
D301250X012) or ROCLINK 800 Configuration Software User Manual
(for ROC800L) (part D301246X012).
Once you set a unique address for each MVS, connect the MVS units in
a multi-drop arrangement. The only requirement for wiring multi-drop
devices is that you tie all like terminals together. This means all the A
A
B
1000+ meters
(4000+ feet)
Figure 4-29 shows the field wiring diagram for the MVSI/O module.
Four wires run from the MVS module terminal block and connect to the
sensor. The wires should be a minimum size of 22 AWG and a
maximum length of 1220 m (4000 ft).
You can induce ground loops by tying commons from various modules
Caution together.
.
4088B Transmitter The 4088B is Remote Automation Solutions latest transmitter
product. Designed as a drop-in replacement for the MVS205 sensor,
you use ROCLINK 800 to configure and (if necessary) calibrate the
module.
Refer to the following figure to correctly wire up to six 4088B
transmitters to the MVS I/O module.
A
B
EMC issues restrict the use of the AC I/O module only to devices using
Warning a PM-12 power module. You cannot use the AC I/O module in a device
that uses either a PM-24 or PM-30 power module.
Switchable I/O and The module has one bank of six DIP switches on its daughterboard
LEDs (see Figure 4-31), which controls the input/output status of each of the
six channels. Placing a switch in the ON position sets the
corresponding channel to output mode. Placing a switch in the OFF
position sets the channel to input mode. Dual-color light-emitting
diodes (LEDs) indicate the current status for each channel. Red means
AC source is being output. Green means the module has detected AC
on an input channel.
AC Discrete Outputs In output mode, the module provides up to six channels for switching
discrete AC. Each channel uses a solid-state normally open relay rated
at 1.5 Amps. Any AC switched out is directly related to the AC
switched in. Using ROCLINK 800, you can configure the module as
latched, toggled, momentary, or Timed Duration Outputs (TDOs).
Other parameters report the approximate load, over-current
conditions, and AC input status. Discrete outputs can be configured to
either retain the last value on reset or a user-specified fail-safe value.
See Figure 4-33.
EXTERNAL AC
PWR/PERMISSIVE
Vs SOURCE
SOLID-STATE
CONTROL RELAY AC CONTROLLED
DEVICE
Vs
SOLID-STATE
CONTROL RELAY AC CONTROLLED
DEVICE
Note: If the label on your AC I/O module does not indicate 120/240V,
your module is designed for use only with 120V. Additionally,
all AC wiring must be shielded.
AC Discrete Inputs You can configure each channel as an AC input/detector. Each
channel can detect the presence of an AC signal between 90 and 265
Vrms at 47 to 63 Hz. In discrete input mode the module monitors the
status of various AC sources.
You can also software-configure each channel to function as a latched
DI, which remains in active state until reset. Other parameters can invert
the field signal and gather statistical information on the number of
transitions and the time accumulated in the on or off state. The fastest
time that each channel within the module can be read is 20 times per
second. See Figure 4-34.
WAVE AC FIELD
RECTIFIER DEVICE
WAVE AC FIELD
RECTIFIER DEVICE
Note: If the label on your AC I/O module does not indicate 120/240V,
your module is designed for use only with 120V. Additionally,
all AC wiring must be shielded.
Table 4-5. Field Wiring Terminals
Terminal Label Definition
1 AC In AC Input (Permissive Power)
2 N AC Neutral
3 1 Channel 1
4 2 Channel 2
5 3 Channel 3
6 N AC Neutral
7 4 Channel 4
8 5 Channel 5
9 6 Channel 6
10 N AC Neutral
Note: The use of dissimilar metals is not supported. It does not provide
the correct results, as CJC is applied at the module level.
Thermocouples are self-powered and require no excitation current. The
TC module uses integrated short-circuit protected isolated power
supplies and completely isolates the field wiring side of the module
from the backplane.
Figure 4-39. Input Point-to-Point Wiring on Figure 4-40. Input Multi-Drop Wiring on HART-
HART-2 Module 2 Module
The IEC 62591 Interface consists of two parts: the Smart Wireless Field
Link that provides the radio link to the WirelessHART field devices,
and the IEC 62591 Interface Module that installs into the ROC800.
Installation and The IEC 62591 Interface module connects to the Smart Wireless Field
Configuration Link through a four-wire connection. This allows the Smart Wireless
Field Link to be strategically placed away from the controller in the
optimal location for best network performance. The module provides
12 Vdc loop-output to power the Smart Wireless Field Link.
You can install one IEC 62591 Interface module in any slot on a
ROC800. Modules can be easily installed or removed from the module
slots at any time by removing the two captive screws accessible from
the front of the unit.
IEC 62591 Interface modules are hot-swappable, meaning the module
can be removed and another module of the same kind can be installed.
IEC 62591 Interface modules are hot-pluggable, meaning they may be
installed directly into unused module slots under power.
The module has a removable terminal block for convenient wiring and
servicing. The terminal block can accommodate size 24 to 16 American
Wire Gauge (AWG). A USB port is provided on the module to perform
firmware updates and to provide debug information to support
personnel.
Chapter 5 Communications
In This Chapter
This chapter describes the built-in communication ports and the optional
communication modules used with the ROC800.
E
A
B F
Signals Action
CTS Clear To Send indicates the modem is ready to send.
CD Data Carrier Detect (DCD) indicates a valid carrier signal tone detected.
DSR Data Set Ready for ring indicator communication signal.
DTR Data Terminal Ready to answer an incoming call. When off, a connection disconnects.
RTS Ready To Send indicates ready to transmit.
RX Receive Data (RD) signal is being received.
TX Transmit Data (TD) signal is being transmitted.
Modules are self-identifying in the software and all modules are self-
resetting after a fault clears.
Note: With the exception of the HART module, you can install
communication modules only in slots 1, 2, or 3 of the ROC800.
Refer to Figure 5-1 and Table 5-1.
Note: Leaving the wire channel cover in place can prevent the
module from correctly connecting to the socket on the
backplane.
3. Insert the new module through the module slot on the front of the
ROC800 or EXP housing. Make sure the label on the front of the
module is facing right side up. Gently slide the module in place until
it contacts properly with the connectors on the backplane.
Note: If the module stops and will not go any further, do not force
the module. Remove the module and see if the pins are bent.
If so, gently straighten the pins and re-insert the module. The
back of the module must connect fully with the connectors
on the backplane.
4. Gently press the module into its mating connectors on the backplane
until the connectors firmly seat.
5. Tighten the retaining captive screws on the front of the module.
6. Wire the module (refer to Wiring Communication Modules).
RJ-45 Pins
Signal LOI Function Description
on ROC800
Originated by the ROC800 Data Terminal Equipment (DTE) to instruct
Data Terminal
DTR 3 the Data Communication Equipment (DCE) to set up a connection.
Ready
DTE is running and ready to communicate.
Ground Reference ground between a DTE and a DCE and has a value 0 Volts
GND 4
(Common) dc.
RX Receive 5 Data received by the DTE.
TX Transmit 6 Data sent by the DTE.
RTS Request to Send 8 Originated by the DTE to initiate transmission by the DCE.
The LOI terminal requires you to install a D-Sub 9 pin (F) to RJ-45
modular converter between the ROC800 and PC. Refer to Table 5-4.
Table 5-4. RJ-45 to EIA-232 (RS-232) Null-modem Cable Signal Routing
Adaptor Cable Remote Automation Solutions offers an adaptor cable to resolve this
cabling issue. Order CBL8A from your Remote Automation Solutions
salesperson.
Signal Signal
Pin 1 TD+ Pin 1 TD+
Pin 2 TD Pin 2 TD
Pin 3 RD+ Pin 3 RD+
Pin 6 RD Pin 6 RD
Table 5-8. EIA-422 (RS-422) Signal Routing Comm3, Comm4, and Comm5
Signal RS-422 Function Terminal
A RX + Lit when module (Comm3, Comm4, or Comm5) is currently receiving. 1
B RX None. 2
Y TX + Lit when module (Comm3, Comm4, or Comm5) is currently transmitting. 3
Z TX None. 4
COM Common Ground. 5
Table 5-9. EIA-485 (RS-485) Signal Routing Comm3, Comm4, and Comm5
Signal RS-485 Function Terminal
A RX / TX + Lit when module (Comm3, Comm4, or Comm5) is currently receiving. 1
B RX / TX None. 2
Y No Connect Lit when module (Comm3, Comm4, or Comm5) is currently transmitting. 3
Z No Connect None. 4
COM Common Ground. 5
You can induce ground loops by tying commons from various modules
Caution together.
Signal Pin
Tip 3
Ring 4
LED indicators on the module show the status of the Receive (RX),
Transmit (TX), Ring (RI), and Carrier Detect (CD) control lines.
Table 5-14 displays connector signals and their functions.
Signal Function
RX Lit when module (Comm3, Comm4, or Comm5) is currently receiving.
TX Lit when module (Comm3, Comm4, or Comm5) is currently transmitting.
RI Lit when module (Comm3, Comm4, or Comm5) detects a ring.
CD Lit when module (Comm3, Comm4, or Comm5) on carrier detect.
Notes:
If you are installing a modem module, it is recommended that you
install a surge protector between the RJ-11 jack and the outside line.
The dial-up modem is not hot-swappable or hot-pluggable. When
installing a dial-up modem module, you must remove power from
the ROC800.
For further technical information about the MVS or MVS I/O modules,
see the description of the MVS I/O module in Chapter 4.
Chapter 6 Troubleshooting
In This Chapter
6.1 Guidelines
When you are attempting to diagnose a problem with the ROC800:
Remember to write down what steps you have taken.
Note the order in which you remove components.
Note the orientation of the components before you alter or remove
them.
Save the configuration and log data. Refer to Preserving
Configuration and Log Data in this chapter.
Read and follow all Cautions in this manual.
6.2 Checklists
If the LEDs do not display:
By default, LEDs on the communication modules and I/O modules
enter Sleep mode after five minutes.
To turn the LEDs on, press the LED button located on the CPU for
one second.
Note: Using the ROCKLINK 800 software, you can disable this feature
so that the LEDs always remain on.
This procedure, valid on the ROC800 (at firmware version 3.1 or higher)
Caution and the ROC800L (at firmware version 1.00 or higher) also stops any
FSTs, User C programs, and DS800 programs.
1. Press and hold the RESET button on the powered CPU for 5 to 10
seconds. The Status LED flashes when the process completes.
6.2.3 Software
If you are experiencing problems with the ROC800 that appear to be
software-related, try resetting the ROC800.
Warm Start Use a warm start to restart without losing configuration or log data.
To perform a warm start, open ROCLINK 800 software, connect to the
ROC800, and select ROC > Flags.
Refer to the ROCLINK 800 Configuration Software User Manual (for
ROC800-Series) (part D301250X012) or the ROCLINK 800
Configuration Software User Manual (for ROC800L) (part
D301246X012).
Cold Start Use a cold start to restart without a portion of the configuration, log
data, or programming that may be the trouble. To perform a cold start,
open ROCLINK 800 software, connect to the ROC800, and select
ROC > Flags.
Refer to the ROCLINK 800 Configuration Software User Manual (for
ROC800-Series) (part D301250X012) or the ROCLINK 800
Configuration Software User Manual (for ROC800L) (part
D301246X012).
Restore to To restore the ROC800 to factory defaults (that is, as the ROC800
Factory Defaults was delivered to you from the factory without installed user programs,
FLASH memory contents, FSTs, DS800 applications, or
configurations) without connecting to ROCLINK 800, use this
procedure:
1. Remove power from the ROC800.
2. Press and hold the RESET button on the CPU.
Note: If none of these methods solves the problem, contact your local
sales representative.
6.2.4 Powering Up
If you are experiencing trouble with powering up the ROC800:
Check the wiring connections at terminations on the Power Input
module and the wiring at the power source.
Check the internal battery for voltage. Refer to Chapter 3, Power
Connections.
Check the external batteries, if applicable, for voltage.
Note: If none of these methods solves the problem, contact your local
sales representative.
6.3 Procedures
Use the following procedures to resolve various issues with the I/O
modules.
Note: The procedure assumes you are using ROCLINK 800 software.
Equipment Required:
Multimeter
PC running ROCLINK 800 software
Note: If the calculated value and the measured value are the same,
the AI module is operating correctly.
Note: You can also click the graphic image of the module to display
this screen.
Note: You can also click the graphic image of the module to display
this screen.
1. Verify the load current requirement does not exceed the current limit
value of the module.
2. Verify that you have correctly wired the module.
3. Select Configure > I/O > PI Points. The Pulse Input screen
displays.
4. Select the correct Pulse Input Point number.
5. Connect a pulse generator having sufficient output to drive the
module to terminals L+ or H+ and COM. The pulse generator must
synthesize a square wave signal of 50% for every cycle.
6. Connect a frequency counter across terminals L+ or H+ and COM.
7. Set the pulse generator to a value equal to or less than (<=) 10 KHz.
8. Set the frequency counter to count pulses.
9. Verify (using ROCLINK 800 software) that the count read by the
counter and the ROC800 are the same.
10. Remove the test equipment, and reconnect the field device.
7. Select Configure > I/O > RTD Points. The RTD Input screen
displays.
8. Disconnect the RTD and connect one jumper between the terminal
and RET and another jumper between the + terminal and the REF of
the RTD module.
9. Connect either an accurate resistor or decade resistance box with a
value to give a low end reading across the + and terminals.
10. Verify that the Raw A/D Input value changed and reflects the
Adjusted A/D 0% value.
11. Change the resistance to reflect a high temperature as determined by
the temperature-to-resistance conversion chart.
12. Verify that the Raw A/D Input value changed and reflects the
Adjusted A/D 100% value.
13. Remove the test equipment, and reconnect the field device.
Chapter 7 Calibration
In This Chapter
Appendix A Glossary
Note: This is a generalized glossary of terms. Not all the terms may
necessarily correspond to the particular device or software
described in this manual. For that reason, the term ROC is
used to identify all varieties of Remote Operations Controllers
(including ROC800-Series, ROC800L, DL8000, FloBoss
107, and FloBoss 100-Series). Refer to Measurement Units,
Symbols, and Abbreviations (Form A6302) for additional
information.
A
A/D Analog to Digital signal conversion.
ABS Acrylonitrile Butadiene Styrene.
ADC Analog to Digital Converter. Used to convert analog inputs (AI) to a format the flow
computer can use.
AGA American Gas Association. A professional organization that oversees the AGA3
(orifice), AGA5 (heating value), AGA7 (turbine), AGA8 (compressibility), and AGA11
(ultrasonic) gas flow calculation standards. See http://www.aga.org.
AWG American Wire Gauge.
AI Analog Input.
AO Analog Output.
Analog Analog data is represented by a continuous variable, such as an electrical current
signal.
AP Absolute Pressure.
API American Petroleum Institute. See http://www.api.org.
Area A user-defined grouping of database entities.
ASCII American (National) Standard Code for Information Interchange.
Attribute A parameter that provides information about an aspect of a database point. For
example, the alarm attribute is an attribute that uniquely identifies the configured value
of an alarm.
B
BMV Base Multiplier Value, used in AGA7 (turbine) calculations.
BPS Bits Per Second, associated with baud rate.
BTU British Thermal Unit, a measure of heat energy.
Built-in I/O I/O channels that are fabricated into the ROC and do not require a separate option.
Also called on-board I/O.
C
C1D2 Class 1, Division 2 hazardous area
CMOS Complementary Metal Oxide Semiconductor, a type of microprocessor used in a ROC.
Coil Digital output, a bit to be cleared or set.
COL Ethernet Packet Collision.
COM Communications port on a personal computer (PC).
C (continued)
COMM Communications port on a ROC used for host communications. .
Note: On FloBoss 500-Series and FloBoss 407s, COMM1 is built-in for RS-232 serial
communications.
Comm Module Module that plugs into a ROC to provide a channel for communications via a specified
communications protocol, such as EIA-422 (RS-422) or HART.
CF Compare Flag; stores the Signal Value Discrete (SVD).
Configuration Refers either to the process of setting up the software for a given system or the result
of performing this process. The configuration activity includes editing the database,
building schematic displays and reports, and defining user calculations. Typically, the
software setup of a device that can often be defined and changed. Can also mean the
hardware assembly scheme.
Configuration In ROCLINK 800, the graphical display that appears when a configuration file opens. It
Tree is a hierarchical branching (tree-style) method for navigating within the configuration
screens.
CPU Central Processing Unit.
CRC Cyclical Redundancy Check error checking.
Crosstalk The amount of signal that crosses over between the receive and transmit pairs, and
signal attenuation, which is the amount of signal loss encountered on the Ethernet
segment.
CSA Canadian Standards Association. See http://www.csa.ca.
CSMA/CD Carrier Sense Multiple Access with Collision Detection.
CTS Clear to Send modem communications signal.
D
D/A Digital to Analog signal conversion.
DB Database.
dB Decibel. A unit for expressing the ratio of the magnitudes of two electric signals on a
logarithmic scale.
dBm Power ratio in decibels (dB), referenced to one milliwatt (mW), also known as dBmW.
DCD Data Carrier Detect modem communications signal. In addition, Discrete Control
Device A discrete control device energizes a set of discrete outputs for a given
setpoint and matches the desired result against a set of discrete inputs (DI).
DCE Data Communication Equipment.
Deadband A value that is an inactive zone above the low limits and below the high limits. The
purpose of the deadband is to prevent a value (such as an alarm) from being set and
cleared continuously when the input value is oscillating around the specified limit. This
also prevents the logs or data storage location from being over-filled with data.
Device In ROCLINK 800, the graphical display that allows navigation through the PC Comm
Directory Ports and ROC Comm Ports setup screen.
DI Discrete Input.
Discrete Input or output that is non-continuous, typically representing two levels (such as on/off).
DMM Digital multimeter.
DO Discrete Output.
Download The process of sending data, a file, or a program from a PC to a ROC.
DP Differential Pressure.
DRN Distributed RTU Network, in which two or more remotely distributed RTU devices
(RRTUs) are wirelessly connected in a peer-to-peer network to share data.
D (continued)
DRTU A primary component of the Distributed RTU Network, consisting of a FB107 chassis
housing a focused functionality CPU and a Network Radio module (NRM). The DRTU
collects process variables from one or more wellheads and transmits the signals
throughout the designed network.
DSR Data Set Ready modem communications signal.
DTE Data Terminal Equipment.
DTR Data Terminal Ready modem communications signal.
Duty Cycle Proportion of time during a cycle that a device is activated. A short duty cycle
conserves power for I/O channels, radios, and so on.
DVM Digital voltmeter.
DVS Dual-Variable Sensor. A device that provides static and differential pressure inputs to a
ROC.
E
EDS Electronic Static Discharge.
EEPROM Electrically Erasable Programmable Read-Only Memory, a form of permanent memory
on a ROC.
EFM Electronic Flow Metering or Measurement.
EIA-232 Serial Communications Protocol using three or more signal lines, intended for short
(RS-232) distances. Concerning RS232D and RS232C, the letters C or D refer to the physical
connector type. D specifies the RJ-11 connector where a C specifies a DB25 type
connector.
EIA-422 Serial Communications Protocol using four signal lines.
(RS-422)
EIA-485 Serial Communications Protocol requiring only two signal lines. Can allow up to 32
(RS-485) devices to be connected together in a daisy-chained fashion.
EMF Electro-Motive Force.
EMI Electro-Magnetic Interference.
ESD Electro-Static Discharge.
EU Engineering Units. Units of measure, such as MCF/DAY.
F
FCC Federal Communications Commission. See http://www.fcc.gov.
Firmware Internal software that is factory-loaded into a form of ROM. In a ROC, the firmware
supplies the software used for gathering input data, converting raw input data values,
storing values, and providing control signals.
FlashPAC ROM and RAM module for a ROC300-Series unit that contains the operating system,
module applications firmware, and communications protocol.
Flash ROM A type of read-only memory that can be electrically re-programmed. It is a form of
permanent memory (requires no backup power). Also called Flash memory.
FloBoss A microprocess-based device that provides flow calculations, remote monitoring, and
remote control. A FloBoss is a type of ROC.
FM Factory Mutual.
Force Write an ON/OFF, True/False, or 1/0 value to a coil.
FOUNDATION An open architecture for information integration, managed by the Fieldbus Foundation
Fieldbus (www.fieldbus.org).
FPV Compressibility Factor.
F (continued)
FSK Frequency Shift Keypad.
FST Function Sequence Table, a type of user-written program in a high-level language
designed by Emerson Process Managements Flow Computer Division.
Ft Foot or feet.
G
GFA Ground Fault Analysis.
9
GHz Gigahertz, 10 cycles per second
GND Electrical ground, such as used by the ROCs power supply.
GP Gauge Pressure.
H
H1 A Foundation Fieldbus protocol operating at 31.25 kbit/s that interconnects field
devices (such as sensors or I/O devices).
HART Highway Addressable Remote Transducer.
Holding Analog output number value to be read.
Register
HSE Protocol High Speed Ethernet protocol; a communications protocol operating at 100 Mbit/s used
to integrate high-speed controllers (or servers) connected via Ethernet.
Hw Differential pressure.
Hz Hertz.
I, J
IC Integrated Circuit. Also, Industry Canada (more recently known as Measurement
Canada), an organization that grants custody transfer approvals on certain ROC units.
ID Identification.
IEC Industrial Electrical Code or International Electrotechnical Commission. See
http://www.iec.ch.
IEEE Institute of Electrical and Electronic Engineers. A professional organization that, in
conjunction with the International Standards Organization (ISO), establishes and
maintains the Open System Interconnection (OSI) reference model and an international
standard for the organization of local area networks (LANs). Refer to
http://www.ieee.org.
IMV Integral Multiplier Value, used in AGA3 (orifice) calculations.
Input Digital input, a bit to be read.
Input Register Input numeric value to be read.
Local Port Also LOI; the serial EIA-232 (RS-232) port on the ROC through which local
communications are established, typically for configuration software running on a PC.
I/O Input/Output.
I/O Module Module that plugs into an I/O slot on a ROC to provide an I/O channel.
IRQ Interrupt Request. Hardware address oriented.
ISO International Standards Organization. See http://www.iso.ch.
IV Integral Value.
K
KB Kilobytes.
kHz KiloHertz.
L
LCD Liquid Crystal Display.
LDP Local Display Panel, a display-only device that plugs into ROC300-Series units (via a
parallel interface cable) used to access information stored in the ROC.
LED Light-Emitting Diode.
Logical Number The point number the ROC and ROC Plus protocols use for I/O point types are based
on a physical input or output with a terminal location; the point numbers for all other
point types are logical and are simply numbered in sequence.
LNK Ethernet has linked.
LOI Local Operator Interface (or Local Port). Refers to the serial EAI-232 (RS-232) port on
the ROC through which local communications are established, typically for
configuration software running on a PC.
LPM Lightning Protection Module; a device that provides lightning and power surge
protection for ROCs.
LRC Longitudinal Redundancy Checking error checking.
M
m Meter.
mA Milliamp(s); one thousandth of an ampere.
MAC Address Media Access Control Address; a hardware address that uniquely identifies each node
of a network.
Manual mode For a ROC, indicates that the I/O scanning has been disabled.
MAU Medium Attachment Unit.
MCU Master Controller Unit.
Modbus A popular device communications protocol developed by Gould-Modicon.
MPU Micro-Processor Unit.
mm Millimeter.
MMBTU Million British Thermal Units.
msec Millisecond, or 0.001 second.
MVS Multi-Variable Sensor. A device that provides differential pressure, static pressure, and
temperature inputs to a ROC for orifice flow calculations.
mV Millivolts, or 0.001 volt.
mW Milliwatts, or 0.001 watt.
N
NAP Network Access Point; the point in the distributed RTU network at which ROCLINK 800
NEC National Electrical Code.
NEMA National Electrical Manufacturers Association. See http://www.nema.org.
N (continued)
Node A basic structural component of the Distributed RTU Network. A node (usually a FB107
chassis housing a focused-functionality CPU and a Network Radio module) provides a
data collection point that wirelessly transmits data throughout the designed network.
NRM Network Radio module; a module used in both the FloBoss 107 and ROC00-Series
based devices to wirelessly transmit information throughout the distributed RTU
network.
O
OH Off-Hook modem communications signal.
Off-line Accomplished while the target device is not connected (by a communications link). For
example, off-line configuration refers to configuring an electronic file that is later
loaded into a ROC.
Ohms Units of electrical resistance.
On-line Accomplished while connected (by a communications link) to the target device. For
example, on-line configuration refers to configuring a ROC800-Series unit while
connected to it, so that you can view the current parameter values and immediately
load new values.
Opcode Type of message protocol the ROC uses to communicate with the configuration
software, as well as host computers with ROC driver software.
Operator Also LOI or Local Port; the serial EIA-232 (RS-232) port on the ROC through which
Interface local communications are established, typically for configuration software running on a
PC.
Orifice meter A meter that records the flow rate of gas through a pipeline. The flow rate is calculated
from the pressure differential created by the fluid passing through an orifice of a
particular size and other parameters.
P, Q
Parameter A property of a point that typically can be configured or set. For example, the Point Tag
ID is a parameter of an Analog Input point. Parameters are normally edited by using
configuration software running on a PC.
PC Personal Computer.
Pf Flowing pressure.
P/DP Pressure/Differential Pressure.
PI Pulse Input.
PID Proportional, Integral, and Derivative control feedback action.
PIT Periodic Timer Interrupt.
PLC Programmable Logic Controller.
Point Software-oriented term for an I/O channel or some other function, such as a flow
calculation. Points are defined by a collection of parameters.
Point Number The physical location of an I/O point (module slot and channel) as installed in the ROC.
Point Type Defines the database point to be a specific type of point available to the system. The
point type determines the basic functions of a point.
Preset Number value previously determined for a register.
PRI Primary PID control loop.
Protocol A set of standards that enables communication or file transfers between two
computers. Protocol parameters include baud rate, parity, data bits, stop bit, and the
type of duplex.
PSTN Public Switched Telephone Network.
PT Process Temperature.
PTT Push-to-Talk signal.
Pulse Transient variation of a signal whose value is normally constant.
Pulse Interface A module that provides line pressure, auxiliary pressure, and pulse counts to a ROC.
module
PV Process Variable or Process Value.
R
Rack A row of slots on a ROC into which I/O modules can be plugged. Racks are given a
letter to physically identify the location of an I/O channel (such as A for the first rack).
Built-in I/O channels are assigned a rack identifier of A while diagnostic I/O channels
are considered to be in E rack.
RAM Random Access Memory. RAM is used to store history, data, most user programs, and
additional configuration data.
RBX Report-by-exception. RBX always refers to Spontaneous RBX in which the ROC
contacts the host to report an alarm condition.
RR Results Register; stores the Signal Value Analog (SVA).
RFI Radio Frequency Interference.
RI Ring Indicator modem communications signal.
ROC Remote Operations Controller microprocessor-based unit that provides remote
monitoring and control.
ROCLINK 800 Microsoft Windows-based software used to configure functionality in ROC units.
ROM Read-only memory. Typically used to store firmware. Flash memory.
Rotary Meter A positive displacement meter used to measure flow rate, also known as a Roots
meter.
RTC Real-Time Clock.
RTD Resistance Temperature Detector.
RTS Ready to Send modem communications signal.
RTU Remote Terminal Unit.
RTV Room Temperature Vulcanizing, typically a sealant or caulk such as silicon rubber.
RS-232 Serial Communications Protocol using three or more signal lines, intended for short
distances. Also referred to as the EIA-232 standard.
RS-422 Serial Communications Protocol using four signal lines. Also referred to as the EIA-422
standard.
RS-485 Serial Communications Protocol requiring only two signal lines. Can allow up to 32
devices to be connected together in a daisy-chained fashion. Also referred to as the
EIA-485 standard.
RX or RXD Received Data communications signal.
S
SAMA Scientific Apparatus Makers Association.
SCADA Supervisory control and data acquisition; referring to a computer system that monitors
and controls oil and gas pipeline systems.
S (continued)
Script An uncompiled text file (such as keystrokes for a macro) that a program interprets in
order to perform certain functions. Typically, the end user can easily create or edit
scripts to customize the software.
Soft Points A type of ROC point with generic parameters that can be configured to hold data as
desired by the user.
SP Setpoint, or Static Pressure.
SPI Slow Pulse Input.
SPK Speaker.
SRAM Static Random Access Memory. Stores data as long as power is applied; typically
backed up by a lithium battery or supercapacitor.
SRBX Spontaneous Report-By-Exception. SRBX always refers to Spontaneous RBX in which
the ROC contacts the host to report an alarm condition.
SVA Signal Value Analog. Stored in the Results Register, it is the analog value that is
passed between functions in an FST.
SVD Signal Value Discrete. Stored in the Compare Flag, it is the discrete value that is
passed down the sequence of functions in an FST.
System Configured parameters that describe the ROC; set using ROCLINK software.
Variables
T
T/C Thermocouple Input.
TCP/IP Transmission Control Protocol/Internet Protocol.
TDI Time Duration Input.
TDO Time Duration Output.
Tf Flowing temperature.
TLP Type (of point), Logical (or point) number, and Parameter number.
TX or TXD Transmitted Data communications signal.
Turbine meter A device used to measure flow rate and other parameters.
U
Upload Send data, a file, or a program from the ROC to a PC or other host.
USB Universal Serial Bus, a serial bus standard used to connect devices.
V-Z
V Volts.
DANIEL
SENIOR SONIC
METER
6
5
12KHz PI FILTER &
LEVEL DETECTION
4
J4
3
2
1
12KHz PI FILTER &
LEVEL DETECTION
DOC0737A
DANIEL PREAMP
1818A TURBINE
PICKUP METER
COIL
15-28 VDC
12KHz PI FILTER &
B
LEVEL DETECTION SQR. WAVE
D
A
COMMON
E
C
12KHz PI FILTER &
LEVEL DETECTION TURBINE
PICKUP METER
COIL
15-28 VDC
B
SQR. WAVE
D
A
COMMON
E
C
DANIEL PREAMP
1818A
DOC0738A
TURBINE
DANIEL PREAMP PICKUP
METER
1838 COIL
6
5
4
12KHz PI FILTER & 3
LEVEL DETECTION
2
1 PICKUP
TURBINE
12KHz PI FILTER & METER
LEVEL DETECTION COIL
6
5
4
3
2
DOC0739A
1
DANIEL PREAMP
1838
MICRO MOTION
RFT9739
TRANSMITTER
12KHz PI FILTER & 14
LEVEL DETECTION
15
16
17
12KHz PI FILTER &
LEVEL DETECTION 14
15
16
17
MICRO MOTION
RFT9739
TRANSMITTER
DOC0740A
MICRO MOTION
2400S
TRANSMITTER
12KHz PI FILTER & 3
LEVEL DETECTION
4
1
2
12KHz PI FILTER &
LEVEL DETECTION 3
4
1
2
MICRO MOTION
2400S
TRANSMITTER
DOC0741A
MICRO MOTION
RFT9739
TRANSMITTER
14
15
16
17
14
15
16
17
MICRO MOTION
RFT9739
TRANSMITTER
MICRO MOTION
2400S
TRANSMITTER
3
4
1
2
3
4
1
2
MICRO MOTION
2400S
TRANSMITTER
4 - WIRE RTD
3 - WIRE RTD
DANIEL
SENIOR SONIC
METER
6
5
4
J4
3
2
1
6
5
4
J4
3
2
1
DANIEL
SENIOR SONIC
METER
B.7 Daniel 1818A and 1838 Dual Turbine Pre-Amp to APM Module
DANIEL PREAMP
1818A TURBINE
PICKUP
METER
COIL
15-28 VDC
B
SQR. WAVE
D
A
COMMON
E
C
TURBINE
PICKUP METER
COIL
15-28 VDC
B
SQR. WAVE
D
A
COMMON
E
C
DANIEL PREAMP
1818A
TURBINE
DANIEL PREAMP PICKUP
METER
1838 COIL
6
5
4
3
2
1 PICKUP
TURBINE
METER
COIL
6
5
4
3
2
1
DANIEL PREAMP
1838
DANIEL PREAMP
1818A TURBINE
PICKUP
METER
COIL
15-28 VDC
B
SQR. WAVE
D
A
COMMON
E
C
PICKUP
15-28 VDC
B COIL
SQR. WAVE
D
A
COMMON
E
C
DANIEL PREAMP
1818A
TURBINE
DANIEL PREAMP PICKUP
METER
1838 COIL
6
5
4
3 PICKUP
COIL
2
1
6
5
4
3
2
1
DANIEL PREAMP
1838
PERMISSIVE POWER AC L1
PERMISSIVE
NEUTRAL
Index
Attaching an EXP .............................................. 2-11
Numerics Automatic Self Tests ......................................... 1-17
AUX Terminal ...................................................... 3-2
+12 V dc AUX+ and AUX ................................... 3-2, 3-3, 3-8
Analog Input ................................................... 4-8 LEDs ............................................................... 3-3
Pulse Input.................................................... 4-12 Auxiliary
+24 V dc Wiring.............................................................. 3-8
Analog Input ................................................... 4-8 Auxiliary Output ................................................... 3-8
Pulse Input.................................................... 4-12 Auxiliary Output Fuse
+T ........................................................................ 4-8 Installing........................................................ 3-10
12 V dc AUXSW Terminal .................................................. 3-2
Power Input module ....................................... 3-1 AUXSW + and AUXSW ................................ 3-2, 3-10
16-Point Addressing ......................................... 1-14
24 V dc B
Power Input module ....................................... 3-3
3- & 4-Wire RTD ................................................. B-5 Backplane ......................................................... 2-10
30 V dc Backplane, hardware .......................................... 1-5
Power Input module ....................................... 3-4 BAT Terminal ...................................................... 3-2
4088B Transmitter ............................................ 4-25 BAT+ and BAT .................................................. 3-2
8-Point Addressing ........................................... 1-14 Batteries
Replacing Internal ......................................... 3-30
A Wiring External ............................................. 3-29
Battery
AC Discrete Inputs ............................................ 4-26 Backup ............................................................ 1-9
AC Discrete Outputs ......................................... 4-26 High .............................................................. 1-18
AC I/O Module Low ............................................................... 1-18
DIP switches ................................................. 4-25 Storage ......................................................... 3-25
ACIO Module to Two-stage Valve ...................... B-9 Burst Mode ........................................................ 4-32
Acrylonitrile Butadiene Styrene (ABS) ................ 1-5
Addressing C
16-Point ........................................................ 1-14
Addressing Module Slots .................................. 1-14 Calculations
AI modules Liquid hydrocarbons ..................................... 1-17
Troubleshooting .............................................. 6-6 Calibration ........................................................... 7-1
Alarming Central Processing Unit
SRBX/RBX ................................................... 1-21 See CPU ....................................................... 2-13
Analog Inputs ...................................................... 4-7 CHG+ and CHG ................................................ 3-2
+12 and +24 V dc ........................................... 4-8 Clock ................................................................... 1-9
System ............................................................ 1-9 Cold Junction Compensation (CJC) ................. 4-28
Analog Outputs ................................................... 4-9 Comm ports
AO modules Reset ............................................................ 2-16
Troubleshooting .............................................. 6-8 Comm1 through Comm5..................................... 5-1
APM Module Communication
DIP switches ................................................. 4-20 Built-in ............................................................. 5-1
APM Module to Daniel 1818A/1838 Dual Turbine Dial-up modem ............................................. 5-12
Pre-Amps .......................................................... B-7 EIA-232 (RS-232) module .............................. 5-9
APM Module to Daniel 1818A/1838 Turbine Pre- EIA-422/485 (RS-422/485) modules ............ 5-10
Amps ................................................................. B-8 Ethernet .......................................................... 5-7
APM Module to Daniel Senior Sonic Meter ........ B-6 Installing modules ........................................... 5-3
APM Module to Micro Motion RFT9739/2400S Local Port........................................................ 5-5
Transmitters ...................................................... B-4 Modules .......................................................... 5-1
APM modules MVS I/O ........................................................ 5-14
Troubleshooting ............................................ 6-14 Network Radio module ................................. 5-14
APP 485 module ............................................... 4-35 Removing a module ........................................ 5-5
AT Command .................................................... 5-13 Wiring.............................................................. 5-5
2-7. CPU Front View (Series 1 and Series 2 4-26. MVS and MVS I/O Modules ................ 4-21
CPU Modules) ............................................ 2-14 4-27. MVS Wiring (with Terminators) ........... 4-22
2-8. CPU Connectors ................................... 2-15 4-28. MVS Field Wiring................................. 4-23
2-9. License key ........................................... 2-18 4-29. MVS I/O Field Wiring ........................... 4-23
2-10. License Key Installation ...................... 2-19 4-30. MVS Jumper J4
3-1. 12 V dc Power Input module ................... 3-2 (shown not terminated) ............................... 4-24
3-2. 24 Vdc Power Input module .................... 3-4 4-31. MVS I/O to 4088B Wiring .................... 4-25
3-3. PM-30 module ......................................... 3-5 4-32. AC I/O DIP Switches ........................... 4-26
3-4. Low voltage disconnect device between 4-33. AC I/O Module (Output Field Wiring) .. 4-26
ROC800 and power source .......................... 3-6 4-34. AC I/O Module (Input Field Wiring) ..... 4-27
3-5. Low voltage disconnect device between 4-35. Thermocouple Input Module Wiring .... 4-29
solar regulatory circuitry and ROC800 ......... 3-7 4-36. Ungrounded Sheathed ..................... 4-30
3-6. Auxiliary Switch (AUX SW) output 4-37. Grounded ............................................ 4-30
terminals on the PM-30 ................................ 3-7 4-38. Exposed, Ungrounded Unsheathed . 4-30
3-7. Auxiliary Power Wiring for PM-12 4-39. HART-2 Module Input Point-to-Point
Module ........................................................ 3-8 Wiring ......................................................... 4-33
3-8. Auxiliary Power Wiring for PM-24 4-40. HART-2 Module Input Multi-Drop
Module ........................................................ 3-9 Wiring ......................................................... 4-33
3-9. Auxiliary Power Wiring for PM-30 4-41. HART-2 Module Output Wiring ........... 4-33
Module ........................................................ 3-9 4-42. IEC62591 Module Output Wiring ........ 4-34
3-10. Backup Battery on CPU Module ......... 3-26 4-43. APP 485 Module ................................. 4-35
3-11. 12 Volts dc Power Supply and BAT+ / 5-1. Communication Ports .............................. 5-2
BAT- Wiring (PM-12 shown) ..................... 3-28 5-2. RS-485 Communication Module ............. 5-3
3-12. 12 Vdc Power Supply and 5-3. RJ-45 Pin Out .......................................... 5-6
CHG+ / CHG Wiring ................................. 3-29 5-4. 10BASE T-Crossover Cable ................... 5-9
4-1. Typical I/O Module .................................. 4-2 5-5. EIA-422/485 (RS-422/485) Jumpers ..... 5-12
4-2. Optional I/O Module Locations ................ 4-2 5-6. MVS and MVS I/O Modules .................. 5-14
4-3. Installing an I/O Module .......................... 4-6 5-7. Network Radio Module .......................... 5-15
4-4. AI-12 Jumper J4 (at +12V) ...................... 4-8 Firmware ........................................................... 1-11
4-5. Analog Input Module Field Wiring ........... 4-8 ROC800L ...................................................... 1-15
4-6. AI-16 DIP Switches ................................. 4-9 Flow Calculations
4-7. Analog Output Jumper J4 (at +12 V) .... 4-10 Gas ............................................................... 1-16
4-8. Analog Output Module Field Wiring ...... 4-10 Liquid ............................................................ 1-17
4-9. Discrete Input Module Field Wiring ....... 4-11 FOUNDATION Fieldbus Interface ........................... 1-8
4-10. Pulse Input J4 Jumper (at +12V) ........ 4-12 Function Sequence Table (FST)....................... 1-19
4-11. Externally Powered Pulse Input Module Fuse
Field Wiring ................................................ 4-13 Installing........................................................ 3-10
4-12. ROC800-Powered Pulse Input Module
Field Wiring ................................................ 4-13 G
4-13. Discrete Output Module Field Wiring .. 4-14
4-14. Discrete Output Relay Module Gas flow calculations ........................................ 1-16
Field Wiring ................................................ 4-16 Gateway defaults ................................................ 5-7
4-15. RTD Sensor Wiring Terminal Gauges, wire ................................................ 4-7, 5-5
Connections ............................................... 4-17 Graphical Interface............................................ 1-21
4-16. Pulse Input Wiring on APM ................. 4-18 Ground ................................................................ 2-4
4-17. Solartron 7835/7845 Wiring on APM .. 4-18
4-18. Generic Densitometer Wiring on APM 4-19 H
4-19. Input Detector Wiring on APM............. 4-19
Hardware ............................................................ 1-5
4-20. Series Detector Switch Wiring on
Hardware Watchdog ......................................... 1-18
APM ............................................................ 4-19
HART module ................................................... 4-31
4-21. Series Detector Switch Wiring on
HART Pass-Through license key...................... 4-31
APM ............................................................ 4-19
Hazardous Area .................................................. 2-3
4-22. Independent Detector Wiring on
HB44 ................................................................. 1-16
APM ............................................................ 4-19
Historical Database ........................................... 1-15
4-23. Two-Pulse Turbine Pulse Input
Hot-pluggable .................................1-8, 4-3, 4-4, 5-3
Wiring on APM ........................................... 4-19
Hot-swappable ...............................1-8, 4-3, 4-4, 5-3
4-24. Pulse Output Wiring on APM .............. 4-20
Housing ............................................................... 2-5
4-25. DIP Switches on APM ......................... 4-20