M 560 Manual
M 560 Manual
M 560 Manual
MULTIFUNCTION
TRANSDUCER
M560-AT*
OPERATING MANUAL
1. INTRODUCTION
2. PROGRAMMING PARAMETERS
3. PROGRAMMING ANALOGUE OUTPUTS
4. PROGRAMMING MODBUS REGISTER
SEQUENCE.
5. RS485 COMMUNICATION
6. INSTALLATION
7. CONNECTION DIAGRAMS
8. SPECIFICATION
Revision 4
Date 20-10-2011
Multitek Ltd. Lancaster Way, Earls Colne Business Park,
Earls Colne, Colchester, Essex. CO6 2NS. England.
Tel. (01787) 223228 Fax. (01787) 223607
E-MAIL: Sales@multitek-ltd.com
WEB SITE: WWW.multitek-ltd.com
2
M560 Version 4 update:
RS485 response time decreased to better than 10ms.
Manual Ammendments:
Page 45: Changed 3X Modbus registers to odd numbers.
Page 50: Changed 4X Modbus registers to odd numbers.
Additional 4X registers:
40083 (0x0052) RESET Import kW.h Register (WO)
40085 (0x0054) RESET Export kW.h Register (WO)
40087 (0x0056) RESET Import kVAr.h Register (WO)
40089 (0x0058) RESET Export kVAr.h Register (WO)
40091 (0x005A) RESET kVA.h Register (WO)
40093 (0x005C) RESET Import A.h Register (WO)
1.2 Memory
COMMENTS :
Enter Value of response
time. Minimum value
300mSec.
COMMENTS :
Enter Node Number any
number between 1 & 247.
COMMENTS :
Port selection box appears,
see below.
COMMENTS :
Chose the PC's
communication port click
on Com 1 or Com 2
COMMENTS :
Chose Baud Rate. Either
2400, 4800, 9600, 19200.
COMMENTS :
Choose Parity. Three
options Odd, Even or None.
COMMENTS :
M560 and PC
communicating correctly.
COMMENTS :
M560 and PC not
communicating correctly.
ACTION : None
ACTION : Click on
button.
ACTION : Click on
button.
10
COMMENTS : The
communication pauses.
COMMENTS : The
communication restarts.
COMMENTS : The
communication stops.
12
COMMENTS :
Enter value box is
displayed.
COMMENTS : Enter
security code 080453 and
click on OK button
13
COMMENTS :
M560 communication port is
now unlocked.
14
ACTION : None
COMMENTS : M560 is
programmed for 6600V
(6.6kV)
15
COMMENTS : Enter
11000 (11kV). Click on
O.K.
2.14.2Changing CT ratio.
ACTION : None
COMMENTS : M560 is
programmed to 200/5A
16
ACTION : None
COMMENTS : Relay is
assigned W.h Import. (Watt
Hour Import)
17
COMMENTS : Divisor
selection box is displayed.
18
19
ACTION : Click On
Demand Button.
COMMENTS : "Enter
Value" box is displayed.
ACTION : None.
COMMENTS : M560 is
programmed for a demand
time of 8 minutes.
20
ACTION : None
22
COMMENTS : Example if
node address 30 is required
enter 30 and click OK Button
COMMENTS :
Enter security code 080453
and click on OK Button
23
COMMENTS : These
values must be stored with
the serial number of the
M560 as these numbers are
unique to the M560 under
test.
Note Only complete the following operation in 2.21.3 if
the calibration data has been lost and you have recorded
original calibration data.
COMMENTS : Enter
recorded values into V1, V2,
V3, I1, I2, I3 click on O.K.
24
25
26
27
COMMENTS :
Choose which P.C.
communication port 1 or 2.
Click on Com 1 or Com 2
COMMENTS :
Enter node number of
PowerSig to be addressed.
PowerSig can have any
number between 1 & 247.
Note : All PowerSigs will
respond if set to node 254.
28
ACTION : Click on
Available Outputs Box
COMMENTS :
Using the up and down
cursor on your PC you can
scroll through all the
parameters that are
available. Select the
parameter required for
output 1. Example if Total
Current of system is
required select I sum.
COMMENTS :
Output 1 = I sum (This
appears in Node No1 Box)
29
COMMENTS :
Using the up and down
cursor choose parameter
required for analogue
output 2. Example if Watts
in Phase 3 is required select
W3.
COMMENTS :
Output 2 = W3 (this appears
in Node No1 Box)
ACTION : Click on
Available Outputs Box.
COMMENTS :
Using the up and down
cursor choose parameter
required for analogue
output 3. Example if system
frequency is required choose
Hz.
COMMENTS :
Output 3 = Hz. (This
appears in Node No 1 Box)
Example :
Output 1 (I sum) = 4-20mA.
Output 2 (W3) = +10m-0-10mA- (Note all parameters that
can be read as bipolar (like Watts) the Multd2a program
automatically sets the outputs as bipolar outputs)
Output 3 (Hz) = 0-1mA.
COMMENTS :
Nominal Box is set at 100%
= 20mA . Zero offset box is
set at 0 = 0mA.
31
COMMENTS :
Zero offset box is set at 20%
= 4mA. Output 1 is now set
to 4-20mA.
COMMENTS :
Nominal Box is set at 100%
= 20mA . Zero offset box is
set at 0 = 0mA.
COMMENTS :
Nominal box is set at 50% =
10mA. Output 1 is now set
at to +10mA-0-10mA-.
32
COMMENTS :
Nominal Box is set at 100%
= 20mA . Zero offset box is
set at 0 = 0mA.
COMMENTS :
Nominal box is set at 5% =
1mA. Output 1 is now set at
to 0-1mA.
COMMENTS :
This action sends a pass
code to allow data to be sent
to PowerSig.
ACTION : Click Send
Button.
COMMENTS :
Updates node output settings.
33
COMMENTS :
Reads all parameter
information and
corresponding outputs.
34
4.2 Load disc and open Mbregs, (This is the Modbus Regis-
ters Tool program) and the screen below will be displayed.
COMMENTS :
Choose which communica-
tion port, 1 or 2. Click on
Comms 1 or Comms 2
COMMENTS :
Using Up and Down cursor
you can scroll through all
parameters that are avail-
able and see the order that
they will appear in. This
order can be changed.
36
COMMENTS :
W Sum is highlighted.
COMMENTS :
W Sum (This appears in
Node No. Box)
COMMENTS :
Hz is highlighted.
37
COMMENTS :
Hz (This appears in Node
No. Box)
COMMENTS :
All information in the Node
No. box is sent to the M560
COMMENTS :
All information in the Node
No. box is read and stored
by the M560. This also adds
any of the parameters
not selected into Node No.
Box, these will appear below
the selected parameters.
38
39
40
Data format :
RTU
32 bit, floating point format to IEEE-754 standard, exponent
bias 127, most significant byte transmitted first. There is no
word reversal.
Error Check :
Cyclic Redundancy Check (CRC), Polynomial exclusive
OR value A001h Low byte sent first.
42
43
3X Registers
44
*In 3 wire mode system V1, V2, V3 will have same value as
volts L2-L1, L3-L2, L1-L3
46
Modbus Register Order: Overview (also see section 4 and
help file of M560 software)
[23h][1Eh][23h][1Eh][0000h][002Ah][0102h][0304h][0506h][0708h]
[090Ah][0B0Ch][0D0Eh][0F10h][1112h][1314h][1516h][1718h][191Ah]
[1B1Ch][1D1Eh][1F20h][2122h][2324h][2526h][2728h][29XX]
[CRC(2bytes)]
Example
To obtain all 3 line powers in a 4 wire system on Node 23h
Packet from master :
Start at Power L1 (0020), request 3 regs (0006 words)
[23][04][0020][0006][CRC(2bytes)]
Response from slave format :
[23][04][12 bytes of data(3 regs x 4 bytes)][CRC(2 bytes)]
48
Write
Packet from master :
[Node addr][10][Register start address(2 bytes)][No of
registers(2 bytes)][Byte count][Data (byte count bytes)]
[CRC (2 bytes)]
4X Registers
The registers are listed with their Modbus addresses.
The data held at these addresses are Read-Only, Write-Only
or Read+Write as indicated below.
4X registers are read using function 03h and written using
function 10h.
A sample write packet will look like this:-
49
50
40049 (0x30) I/P V2 GAIN FACTOR (R/W)
40051 (0x32) I/P V3 GAIN FACTOR (R/W)
40053 (0x34) I/P I1 GAIN FACTOR (R/W)
40055 (0x36) I/P I2 GAIN FACTOR (R/W)
40057 (0x38) I/P I3 GAIN FACTOR (R/W)
40059 (0x3A) Future use (ILLEGAL)
40061 (0x3C) Future use (ILLEGAL)
40063 (0x3E) Future use (ILLEGAL)
40065 (0x40) CLEAR GAIN FACTORS (WO)
40067 (0x42) SET PASSCODE (WO)
40069 (0x44) CALIBRATION PASSCODE (WO)
40071 (0x46) D to A PASSCODE (WO)
40073 (0x48) D to A1 OVERRIDE (WO)
40075 (0x4A) D to A2 OVERRIDE (WO)
40077 (0x4C) D to A3 OVERRIDE (WO)
40079 (0x4E) Future use (R/W)
40081 (0x50) Future use (R/W)
40083 (0x52) Future use (R/W)
40085 (0x54) Future use (R/W)
40087 (0x56) Future use (R/W)
40089 (0x58) Future use (R/W)
40091 (0x5A) Future use (R/W)
40093 (0x5C) Future use (R/W)
40095 (0x5E) Future use (R/W)
40097 (0x60) LOCK ACIA SETTINGS (WO)
40099 (0x62) Future use (R/W)
40101 (0x64) Future use (R/W)
40103 (0x66) Future use (R/W)
N.B.
Addresses 40001 to 40003 are common to M550, MultiDin and
MultiGen.
Addresses 40005 to 40019 are common to M550 and MultiDin.
51
Example. To obtain System Volts & System Amps on Node
23h
Packet from master format :
Start at system voltage (0000), request 2 regs (0004 words)
[23][03][0000][0004][CRC(2 bytes)]
52
6.1 Case
CASE DIMENSIONS
rising clamp terminals
35 70
100
Rail fixing
54
55
56
SINGLE PHASE
58
ACCURACY
Specified@ 23 C 10%-Un 10%-In
Parameters unless stated Class 0.3% to IEC 688
Volts and Amps Class 0.25% to IEC 688
Frequency Class 0.1Hz to IEC 688
Power Factor Class 1.0% to IEC 688
Active & Reactive Energy 1% of reading IEC 1036
APPLIED STANDARDS
General IEC 688 BSEN60688, BS4889, IEC 359
EMC Emissions EN61326-1
Immunity EN61326-2
Safety EN61010-1
59
AUXILIARY
AC voltage 115 or 230 or 277volts (15%)
DC voltage 12 / 24 / 48 / 110 / 125 volts
ANALOGUE OUTPUTS
3 outputs Programmable to any 3 parameters (apart
from energy measurements W.h VAr.h VA.h A.h)
Rated value (software selectable)
0-1mA into <10kOhm load
0-5mA into <2kOhm load
0-10mA into <1kOhm load
0-20mA into <0.5kOhm load
4-20mA into <0.5kOhm load
0-10 volts >1kOhm load
Accuracy is relative to a standard 20mA or 10V output.
When outputs specified on order the accuracy will be
applicable to that output.
Load influence <0.1%
Ripple <0.5% peak-peak at full load
Response time <400 msec for 0-99% at full load
Overload <2 x rated value at full load
No load voltage <18 volts
60