Deluge Valve C1

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

Tel: 00-44-8450751042 Fax: 00-44-8450751043 Email: info@fireguard-uk.

com
2nd FLOOR | 145-157 ST.JOHNS STREET | LONDON | EC1V 4P Y | UNITED KINGDOM

DELUGE VALVE MODEL-C1


(CAST STEEL)

TECHNICAL DATA
MODEL C1-Cast Steel
ASTM A 216 WBC
NOMINAL SIZE 200, 150, 100, 80 and
50 NB
SERVICE PRESSURE 1.4 to 17.5 Bar
(20 to 250 PSI)
THREADED OPENING BSPT
MOUNTING Vertical or Horizontal
mounting
FACTORY HYDROSTATIC 35 Kg./sq.cm. (500 PSI)
TEST PRESSURE
FLANGE CONNECTION ANSI B 16.5 #150 FF UL
(RF-Optional)
WET PILOT SPRINKLER As per graph in the LISTED
HEIGHT LIMITATION catalogue 9P76
NET WEIGHT 200 NB - 163 Kg outlet port via opened actuation devices. The top
WITHOUT TRIM 150 NB - 86 Kg chamber pressure cannot be replenished through
100 NB - 56 Kg the restricted inlet port, and the upward force of
80 NB - 38 Kg the supply pressure lifts the clapper allowing the
50 NB - 33 Kg water flow to the system piping network and alarm
FINISH RAL 3000 devices.
APPROVAL UL Listed TRIM DESCRIPTION
The trims are functionally termed as Dry Pilot Trim,
ORDERING 1. Size of valve
Wet Pilot Trim, Electric Trim and Test and Alarm
INFORMATION 2. Flange specification
Trim as per the mehod of actuation of the deluge
3. Valve trim vertical or
valve.
horizontal
4. Trim type The functionality of these trims is described below..

DESCRIPTION a) DRY PILOT TRIM (PNEUMATIC RELEASE)


Deluge Valve is known as a system control valve in Dry pilot operation uses a pilot line of closed
a deluge system, used for fast application of water Sprinkles/QB detectors containing air under
in a spray system. Deluge valve protects areas such pressure, located in the areato be protected. It
as power transformer installation, storage tank, requires regulated dry air supply with main supply
conveyor protection and other industrial application point through restricted orifice. The air pressure
etc. With the addition of foaming agent deluge valve to bemaintained as specified in the catalogue of
can be used to protect aircraft hanger and Dry Pilot Actuator. The pilot line is connected to
inflammable liquid fire. air inlet side of actuator. The top chamber of the
deluge valve is connected to water inlet side of
VALVE OPERATION actuator.
Deluge valve is a quick release, hydraulically When there is an air pressure drop, or due to
operated diaphragm valve. It has three chambers, release of any of the release device on detection
isolated from each other by the diaphragm operated of fire, the diaphragm of actuator is lifted and
clapper and seat seal. While in SET position, water allows the water to drain. This releases the water
pressure is transmitted through an external bypass pressure in the top chamber of the deluge valve,
check valve and restriction orifice from the system allowing the deluge valve to open and water to
supply side to the top chamber, so that supply flow into the system piping & alarm devices.
pressure in the top chamber act across the Recommended air supply pressure for dry pilot
diaphragm operated clapper which holds the seat trim system is 3.5 kg/sq.cm.
against the inlet supply pressure because of the
differential pressure design.On detection of fire the User must install non return valve at air supply
top chamber is vented to atmosphere through the connection to deluge valve trim.

Company Registration No. 5717368 V.A.T No. 883908672 www.fireguard-uk.com


Tel: 00-44-8450751042 Fax: 00-44-8450751043 Email: info@fireguard-uk.com
2nd FLOOR | 145-157 ST.JOHNS STREET | LONDON | EC1V 4P Y | UNITED KINGDOM

In dry pilot trim, an actuator (DPA) is provided. addition with drip valve.
An optional Pneumatic Reset Device (PRD) can
be provided, which acts as a manual reset device TRIM TYPES
in the dry pilot line. The trims are designated as follwing.

b) WET PILOT TRIM (HYDRAULIC RELEASE) W =Wet Pilot trim. D = Dry Pilot Trim
Wet pilot operation uses a pilot line of closed
Sprinklers/QB detectors containing pressurized a) Type ET-W and ET-D
water, supplied through the upstream side of the This type of trim is basic trim required to operate
Deluge valve, through a restricted orifice. All the the deluge valve. A solenoid valve for electric
release lines are connected to a common release remote actuation and pressure switch for
line. Due to release of any one of the release sensing & announciation are optional.
device, the water pressure in the top chamber
b) Type ETW-D and ETD-D
of the Deluge valve drops and the Deluge valve
opens. This trim type is a combination of components
of the ET trim along with the drip and drain trim.
c) ELECTRIC RELEASE TRIM A solenoid valve for electric remote actuation
To actuate a Deluge valve electrically, a solenoid and pressure switch for sensing & announciation
valve is provided to drain the water from the are optional.
top chamber of the Deluge valve. A pressure
c) Type ETW-T and ETD-T
switch is provided to activate an electric alarm,
This trim type is a combination of components of
to shut down the desired equipment or to give
the ET trims along with the test and alarm trim.
"Tripped" indication of the Deluge valve. In addition
In dry pilot trim, an actuator DPA-H1 is provided
to this a pressure switch can also monitor "Low
with optional Pneumatic Reset Device (PRD-1).
air pressure" and "Fire condition" when used in
A solenoid valve for electric remote actuation
dry pilot air line.
and pressure switch for sensing & announciation
d) TEST AND ALARM TRIM are optional.
This trim is supplied with a test valve is provided
d) Type NT-W and NT-D
to test thenormal operation of the sprinkler
This trim type is a combination of components
alarm bell. The sprinkler alarmcan be supplied
of the ET trim along with the test and alarm trim
additionally, which bells on actuation of the Deluge
as well as the drip and drain trim. A solenoid valve
valve.
for electric remote actuation and pressure
e) DRAIN AND DRIP TRIM switch for sensing & announciation are optional.
This consists of main and system drain valve in

TRIM TRIM DESCRIPTION MOUNTING SCHEMATIC


MODEL NO.
NO.
ETW Basic Wet Pilot Trim Vertical Schematic 1
ETD Basic Dry Pilot Trim Vertical Schematic 2
ETW-T Basic Wet Pilot Trim with Test & Alarm Trim Vertical Schematic 3
ETD-T Basic Dry Pilot Trim with Test & Alarm Trim Vertical Schematic 4
ETW-D Basic Wet Pilot Trim with Drip & Drain Trim Vertical Schematic 5
ETD-D Basic Dry Pilot Trim with Drip & Drain Trim Vertical Schematic 6
NTW Basic Wet Pilot Trim with Test & Alarm Trim and Drip & Drain Trim Vertical Schematic 7
NTD Basic Dry Pilot Trim with Test & Alarm Trim and Drip & Drain Trim Vertical Schematic 8
ETW Basic Wet Pilot Trim Horizontal Schematic 9
ETD Basic Dry Pilot Trim Horizontal Schematic 10
ETW-T Basic Wet Pilot Trim with Test & Alarm Trim Horizontal Schematic 11
ETD-T Basic Dry Pilot Trim with Test & Alarm Trim Horizontal Schematic 12
ETW-D Basic Wet Pilot Trim with Drip & Drain Trim Horizontal Schematic 13
ETD-D Basic Dry Pilot Trim with Drip & Drain Trim Horizontal Schematic 14
NTW Basic Wet Pilot Trim with Test & Alarm Trim and Drip & Drain Trim Horizontal Schematic 15
NTD Basic Dry Pilot Trim with Test & Alarm Trim and Drip & Drain Trim Horizontal Schematic 16

Company Registration No. 5717368 V.A.T No. 883908672 www.fireguard-uk.com


Tel: 00-44-8450751042 Fax: 00-44-8450751043 Email: info@fireguard-uk.com
2nd FLOOR | 145-157 ST.JOHNS STREET | LONDON | EC1V 4P Y | UNITED KINGDOM

RESETTING PROCEDURE FOR THE open the deluge valve. Close the upstream side
DELUGE VALVE stop valve immediately
(i) Close the upstream side stop valve provided (iii) Reset the valve as per the procedure given
below the deluge valve under heading "RESETTING PROCEDURE FOR
ii) Open both the drain valves/ drain plugs and close THE DELUGE VALVE"
when the flow of water has ceased INSPECTION AND MAINTENANCE
(iii) Close the release device/replace the Sprinkler Installed system piping network must be flushed
if release was through Sprinkler/QB Detector properly before placing the Deluge valve in service.
iv) Inspect and release if required, or close the A qualified and trained person must commission the
section of the detection system subjected to system. After few initial successful tests, an
"Fire condition" authorized person must be trained to perform
(v) In case of dry pilot detection system, open the inspection and testing of the system. It is
air supply valve to build-up air pressure. Open recommended to have regular inspection and test
the priming valve fully. Open the upstream side run of the system as per NFPA guideline or in
of the stop valve provided below the Deluge accordance to the organisation having local
valve. No water should flow into the system jurisdiction.

vi) Where priming shut off valve is provided for (i) WARNING
resetting, in addition to above steps press the Inspection and testing is to be carried out only
knob on actuator while resetting by authorised and trained personnel. DO NOT
TURN OFF the water supply or close any valve
CAUTION to make repair(s) or test the valve, without
(a) Do not close the priming valve, downstream placing a roving fire patrol in the area covered
and upstream stop valves, while the system is by the system. Also inform the local security
in service personnel and central alarm station, so that
(b) The releasing device must be maintained in the there is no false alarm signal.
open position, when actuated, to prevent the
deluge valve from closure if anti shut off valve It is recommended to carry out physical
is not provided inspection of the system at least twice in a
week. The inspection should verify that all the
(c) While using a Deluge valve in the wet pilot control valves are in proper position as per the
system the height and the length of the wet system requirement and that there are no
pilot detection line is to be limited as shown in damages to any component.
the wet pilot sprinkler height limitation graph
The frequency of inspections must be increased
(d) Do not connect the Sprinkler Alarm outlet drain in the presence of contaminated water supplies,
line to close a common drain as it may create corrosive/ scaling water supplies, and corrosive
back pressure and Sprinkler Alarm may not atmospheres.
function
(e) Deluge valve must have support to absorb (ii) NORMAL CONDITION
sudden opening or closing vibration shock to (a) All main valves are open and are sealed
the piping with tamper proof seal
(f) To avoid water damage, take precautions when (b) Drain valves must be kept closed
opening the water supply main control valve, (c) No leak or drip is detected from the drip
since water will flow from all open system valves valve
(g) The responsibility of maintenance of the (d) All the gauges except the system side
protection system and devices in proper water pressure gauge, should show the
operating condition lies with the owner of the required pressure
system
(e) There should be no leakage in the system
SYSTEM TESTING PROCEDURE
(i) Keep the upstream side of the stop valve (iii) NORMAL CONDITION TEST
partially open. To avoid water flow to system (a) The system should be checked for normal
side close the system side stop valve. This valve condition at least once in a week
is to be kept in open position after the testing
(b) Test the sprinkler alarm bell or electric
is completed
alarm by turning the alarm test valve to
(ii) Let any of the release devices to trip. This will the test position. The alarm should sound.
result in a sudden drop of water pressure in This test should be carried out at least
the deluge valve top chamber which in turn will once in a week

Company Registration No. 5717368 V.A.T No. 883908672 www.fireguard-uk.com


Tel: 00-44-8450751042 Fax: 00-44-8450751043 Email: info@fireguard-uk.com
2nd FLOOR | 145-157 ST.JOHNS STREET | LONDON | EC1V 4P Y | UNITED KINGDOM

(c) Depress the drip valve knob. Significant


accumulation indicates a possible seat
leakage
(d) Conduct the water flow test as per the
procedure of system testing at least once
a month.
(iv) PERIODIC CHECK
Conduct the water flow test by actuating few of
the release devices provided in the system. Clean
all strainer(s) and priming line restriction. This
test is to be carried out at least once in three
months.

ABNORMAL CONDITION
(i) ALARM FAILS TO SOUND
(a) Check for any obstruction in the alarm
test line, make certain that the sprinkler
alarm is free to operate
(b) If an electric alarm is provided, check the
electrical circuitry to the alarm

(ii) FALSE TRIPS


(a) Check for clogging in priming line,
restriction orifice check valve, priming
valve & strainer
(b) Leakage in the release system
(c) The deluge air panel orifice clogged or low
supply pressure

(iii) LEAKAGE THROUGH THE DELUGE VALVE


(a) Damaged deluge valve seat or obstruction
on the seat face by foreign object
(b) Leakage in release system
(c) Partly clogged priming line restriction
orifice check valve
(d) Low air pressure on release system line
or leakage in release system

Company Registration No. 5717368 V.A.T No. 883908672 www.fireguard-uk.com


Tel: 00-44-8450751042 Fax: 00-44-8450751043 Email: info@fireguard-uk.com
2nd FLOOR | 145-157 ST.JOHNS STREET | LONDON | EC1V 4P Y | UNITED KINGDOM

DELUGE VALVE MODEL - C1 SIZE 200 / 150 / 100 / 80/ 50 NB

20
19
18

17

16

15

14

13
12

11

10

6
21
5

Company Registration No. 5717368 V.A.T No. 883908672 www.fireguard-uk.com


Tel: 00-44-8450751042 Fax: 00-44-8450751043 Email: info@fireguard-uk.com
2nd FLOOR | 145-157 ST.JOHNS STREET | LONDON | EC1V 4P Y | UNITED KINGDOM

DELUGE VALVE MODEL - C1 SIZE 200 / 150 / 100 / 80 / 50 NB

DIMENSION in millimeter (Approximate)


VALVE
NOMINAL A B
SIZE
200 NB 552 332
150 NB 462 282
100 NB 412 245
80 NB 372 232
50 NB 320 232

PART LIST
PART NO. QTY.
ITEM 200 150 100 80 50 DESCRIPTION 200 150 100 80/50 MATERIAL
NO. NB NB NB NB NB NB NB NB NB SPECIFICATION
1 2529 2527 2525 2523 2522 HOUSING 1 1 1 1 CAST STEEL
2 8561 9783 9784 9791 9791 ORING 1 1 1 1 NEOPRENE
RUBBER
3 4025 3993 4003 4017 4017 SEAT 1 1 1 1 BRONZE
4 9151 9112 9112 - - BOLT 8 4 4 - STAINLESS STEEL
5 4026 3994 4004 4018 4018 RUBBER CLAMP 1 1 1 1 BRONZE
6 4027 4000 4005 4023 4023 RUBBER SEAT 1 1 1 1 NEOPRENE
RUBBER
7 4034 3990 4011 4041 4041 CLAPPER 1 1 1 1 DUCTILE IRON /*
8 4035 2427 2786 2786 2786 DIAPHRGM 1 1 1 1 NEOPRENE
RUBBER
9 4030 2424 2504 2788 2788 CLAMP RING 1 1 1 1 BRONZE
10 8806 9151 9151 9187 9187 BOLT 12 8 8 8 STAINLESS STEEL

11 9986 9986 9986 9986 9986 ORING 1 1 1 1 NEOPRENE


RUBBER
12 4029 3996 4007 4020 4020 SPINDLE 1 1 1 1 STAINLESS STEEL

13 9185 8838 8838 9185 9185 NUT 1 1 1 1 STAINLESS STEEL

14 9186 9184 9184 9186 9186 LOCK NUT 1 1 1 1 STAINLESS STEEL


15 2980 2979 2978 2977 2977 SPRING 1 1 1 1 STAINLESS STEEL
16 4033 3998 4010 3983 3983 ADAPTOR 1 1 1 1 BRONZE
17 2530 2528 2526 2524 2524 COVER 1 1 1 1 CAST STEEL
18 9008 9049 9051 8692 8692 BOLT 16 12 12 12 CARBON STEE
19 9982 9982 9982 9982 9982 ORING 1 1 1 1 NEOPRENE
RUBBER
20 2514 2514 2514 2514 2514 PLUG 1 1 1 1 STEEL PLATED
21 8843 - - - - ALLEN BOLT 6 - - - STAINLESS STEEL
* Optional Bronze

Company Registration No. 5717368 V.A.T No. 883908672 www.fireguard-uk.com


Tel: 00-44-8450751042 Fax: 00-44-8450751043 Email: info@fireguard-uk.com
2nd FLOOR | 145-157 ST.JOHNS STREET | LONDON | EC1V 4P Y | UNITED KINGDOM

SCHEMATIC FOR WET PILOT BASIC TRIM FOR DELUGE VALVE


MODEL - C1 FOR VERTICAL MOUNTING

ETW

OUTLET
TO DETECTION
LINE

**
PS2

PG

PG

SCV DV
RN
**
SV
OD

~
M
~
INLET

OD

SCHEMATIC 1

SCHEMATIC FOR DRY PILOT BASIC TRIM FOR DELUGE VALVE


MODEL - C1 FOR VERTICAL MOUNTING

ETD TO DETECTION
LINE
PG
**
PS1
AIR SUPPLY
SCV RN-A
OUTLET

**
PS2
PG DPA
PG
OD

SCV DV
RN
**
SV
OD
~

M
~
OD
INLET

SCHEMATIC 2

DV DELUGE VALVE G SPRINKLER ALARM (WMG) SWING CHECK VALVE M EMERGENCY RELEASE STATION
OD OPEN DRAIN VALVE RN RESTRICTION NOZZLE (PRIMING LINE) DPA DRY PILOT ACTUATOR
STRAINER SV SOLENOID VALVE ANGLE VALVE PG PRESSURE GAUGE
DR.V DRIP VALVE
PS2
BY USER
WATER FLOW PRESSURE ALARM SWITCH
PS1 LOW AIR ALARM PRESSURE SWITCH
RN-A RESTRICTION NOZZLE (AIR LINE)
** OPTIONAL

Company Registration No. 5717368 V.A.T No. 883908672 www.fireguard-uk.com


Tel: 00-44-8450751042 Fax: 00-44-8450751043 Email: info@fireguard-uk.com
2nd FLOOR | 145-157 ST.JOHNS STREET | LONDON | EC1V 4P Y | UNITED KINGDOM

SCHEMATIC FOR WET PILOT BASIC TRIM FOR DELUGE VALVE


MODEL - C1 FOR VERTICAL MOUNTING

ETWT

**

OUTLET
PS2 TO DETECTION
**
G LINE

SCV
OD
PG
PG

SCV DV
RN
**
SV
OD

~
M
~
OD
INLET

SCHEMATIC 3

SCHEMATIC FOR DRY PILOT BASIC TRIM FOR DELUGE VALVE


MODEL - C1 FOR VERTICAL MOUNTING

ETDT TO DETECTION
LINE
PG
**
PS1
AIR SUPPLY
SCV RN-A
**
OUTLET

PS2
**
G

SCV
OD PG DPA

PG OD

SCV DV
RN
**
SV
OD
~

M
~
OD
INLET

SCHEMATIC 4

DV DELUGE VALVE G SPRINKLER ALARM (WMG) SWING CHECK VALVE M EMERGENCY RELEASE STATION
OD OPEN DRAIN VALVE RN RESTRICTION NOZZLE (PRIMING LINE) DPA DRY PILOT ACTUATOR
STRAINER SV SOLENOID VALVE ANGLE VALVE PG PRESSURE GAUGE
DR.V DRIP VALVE
PS2
BY USER
WATER FLOW PRESSURE ALARM SWITCH
PS1 LOW AIR ALARM PRESSURE SWITCH
RN-A RESTRICTION NOZZLE (AIR LINE)
** OPTIONAL

Company Registration No. 5717368 V.A.T No. 883908672 www.fireguard-uk.com


Tel: 00-44-8450751042 Fax: 00-44-8450751043 Email: info@fireguard-uk.com
2nd FLOOR | 145-157 ST.JOHNS STREET | LONDON | EC1V 4P Y | UNITED KINGDOM

SCHEMATIC FOR WET PILOT BASIC TRIM FOR DELUGE VALVE


MODEL - C1 FOR VERTICAL MOUNTING
ETWD

OUTLET
TO DETECTION
LINE

**
PS2 DR.V

~
PG OD
PG
OD

DV OD
SCV RN
**
SV
OD

~
M
~
OD
INLET

SCHEMATIC 5

SCHEMATIC FOR DRY PILOT BASIC TRIM FOR DELUGE VALVE


MODEL - C1 FOR VERTICAL MOUNTING

ETDD TO DETECTION
LINE
PG
**
PS1
AIR SUPPLY
RN-A
OUTLET

SCV

**
PS2 DR.V
~
PG OD
PG
OD DPA

OD OD
SCV DV
RN
**
SV
OD
~

M
~
OD
INLET

SCHEMATIC 6

DV DELUGE VALVE G SPRINKLER ALARM (WMG) SWING CHECK VALVE M EMERGENCY RELEASE STATION
OD OPEN DRAIN VALVE RN RESTRICTION NOZZLE (PRIMING LINE) DPA DRY PILOT ACTUATOR
STRAINER SV SOLENOID VALVE ANGLE VALVE PG PRESSURE GAUGE
DR.V DRIP VALVE
PS2
BY USER
WATER FLOW PRESSURE ALARM SWITCH
PS1 LOW AIR ALARM PRESSURE SWITCH
RN-A RESTRICTION NOZZLE (AIR LINE)
** OPTIONAL

Company Registration No. 5717368 V.A.T No. 883908672 www.fireguard-uk.com


Tel: 00-44-8450751042 Fax: 00-44-8450751043 Email: info@fireguard-uk.com
2nd FLOOR | 145-157 ST.JOHNS STREET | LONDON | EC1V 4P Y | UNITED KINGDOM

SCHEMATIC FOR WET PILOT BASIC TRIM FOR DELUGE VALVE


MODEL - C1 FOR VERTICAL MOUNTING

NTW TO DETECTION
LINE

**

OUTLET
PS2
**
G

DR.V
SCV
OD ~
PG OD
PG
OD

DV
OD
SCV RN
**
SV
OD

~
M
~
INLET

OD

SCHEMATIC 7

SCHEMATIC FOR DRY PILOT BASIC TRIM FOR DELUGE VALVE


MODEL - C1 FOR VERTICAL MOUNTING

TO DETECTION
NTD LINE
PG
**
PS1
AIR SUPPLY
SCV RN-A
**
OUTLET

PS2
**
G

DR.V
SCV
OD ~
PG OD
PG
OD DPA

DV OD OD
SCV RN
**
SV
OD
~

M
~
OD
INLET

SCHEMATIC 8

DV DELUGE VALVE G SPRINKLER ALARM (WMG) SWING CHECK VALVE M EMERGENCY RELEASE STATION
OD OPEN DRAIN VALVE RN RESTRICTION NOZZLE (PRIMING LINE) DPA DRY PILOT ACTUATOR
STRAINER SV SOLENOID VALVE ANGLE VALVE PG PRESSURE GAUGE
DR.V DRIP VALVE
PS2
BY USER
WATER FLOW PRESSURE ALARM SWITCH
PS1 LOW AIR ALARM PRESSURE SWITCH
RN-A RESTRICTION NOZZLE (AIR LINE)
** OPTIONAL

Company Registration No. 5717368 V.A.T No. 883908672 www.fireguard-uk.com


Tel: 00-44-8450751042 Fax: 00-44-8450751043 Email: info@fireguard-uk.com
2nd FLOOR | 145-157 ST.JOHNS STREET | LONDON | EC1V 4P Y | UNITED KINGDOM

SCHEMATIC FOR WET PILOT BASIC TRIM FOR DELUGE VALVE


MODEL - C1 FOR HORIZONTAL MOUNTING

TO DETECTION
ETW LINE

**
OD

~
SCV RN SV
M
~
PG OD

PS2 **

DV
INLET OUTLET

PG

SCHEMATIC 9

SCHEMATIC FOR DRY PILOT BASIC TRIM FOR DELUGE VALVE


MODEL - C1 FOR HORIZONTAL MOUNTING

ETD TO DETECTION
LINE
PG
PS1 **
AIR SUPPLY
RN-A SCV
DPA

OD
** OD
~

RN M SV
~
PG OD

PS2 **

INLET DV OUTLET

PG

SCHEMATIC 10

DV DELUGE VALVE G SPRINKLER ALARM (WMG) SWING CHECK VALVE M EMERGENCY RELEASE STATION
OD OPEN DRAIN VALVE RN RESTRICTION NOZZLE (PRIMING LINE) DPA DRY PILOT ACTUATOR
STRAINER SV SOLENOID VALVE ANGLE VALVE PG PRESSURE GAUGE
DR.V DRIP VALVE
PS2
BY USER
WATER FLOW PRESSURE ALARM SWITCH
PS1 LOW AIR ALARM PRESSURE SWITCH
RN-A RESTRICTION NOZZLE (AIR LINE)
** OPTIONAL

Company Registration No. 5717368 V.A.T No. 883908672 www.fireguard-uk.com


Tel: 00-44-8450751042 Fax: 00-44-8450751043 Email: info@fireguard-uk.com
2nd FLOOR | 145-157 ST.JOHNS STREET | LONDON | EC1V 4P Y | UNITED KINGDOM

SCHEMATIC FOR WET PILOT BASIC TRIM FOR DELUGE VALVE


MODEL - C1 FOR HORIZONTAL MOUNTING
ETWT
TO DETECTION
LINE

**
OD

~
SCV RN SV
M
~
OD
PG
**
PS2
** G

~
OD
SCV

DV
INLET OUTLET

PG

SCHEMATIC 11

SCHEMATIC FOR DRY PILOT BASIC TRIM FOR DELUGE VALVE


MODEL - C1 FOR HORIZONTAL MOUNTING

ETDT TO DETECTION
LINE

PG
**
PS1
AIR SUPPLY
RN-A SCV
DPA

OD ** OD
~

RN M SV
~
PG
**
PS2
OD
** G

~
OD
DV
INLET OUTLET
PG

SCHEMATIC 12

DV DELUGE VALVE G SPRINKLER ALARM (WMG) SWING CHECK VALVE M EMERGENCY RELEASE STATION
OD OPEN DRAIN VALVE RN RESTRICTION NOZZLE (PRIMING LINE) DPA DRY PILOT ACTUATOR
STRAINER SV SOLENOID VALVE ANGLE VALVE PG PRESSURE GAUGE
DR.V DRIP VALVE
PS2
BY USER
WATER FLOW PRESSURE ALARM SWITCH
PS1 LOW AIR ALARM PRESSURE SWITCH
RN-A RESTRICTION NOZZLE (AIR LINE)
** OPTIONAL

Company Registration No. 5717368 V.A.T No. 883908672 www.fireguard-uk.com


Tel: 00-44-8450751042 Fax: 00-44-8450751043 Email: info@fireguard-uk.com
2nd FLOOR | 145-157 ST.JOHNS STREET | LONDON | EC1V 4P Y | UNITED KINGDOM

SCHEMATIC FOR WET PILOT BASIC TRIM FOR DELUGE VALVE


MODEL - C1 FOR HORIZONTAL MOUNTING

ETWD TO DETECTION
LINE

**
OD

~
SCV RN SV
M
~
PG OD

PS2 **

DV
INLET OUTLET

PG

DR.V ~
OD
~
OD
OD

SCHEMATIC 13

SCHEMATIC FOR DRY PILOT BASIC TRIM FOR DELUGE VALVE


MODEL - C1 FOR HORIZONTAL MOUNTING

TO DETECTION
ETDD LINE
PG
PS1 **
AIR SUPPLY
RN-A SCV
DPA

OD
** OD
~

RN M SV
~
PG OD

**
PS2

DV
INLET OUTLET
PG

DR.V
~
OD
~
OD
OD

SCHEMATIC 14

DV DELUGE VALVE G SPRINKLER ALARM (WMG) SWING CHECK VALVE M EMERGENCY RELEASE STATION
OD OPEN DRAIN VALVE RN RESTRICTION NOZZLE (PRIMING LINE) DPA DRY PILOT ACTUATOR
STRAINER SV SOLENOID VALVE ANGLE VALVE PG PRESSURE GAUGE
DR.V DRIP VALVE
PS2
BY USER
WATER FLOW PRESSURE ALARM SWITCH
PS1 LOW AIR ALARM PRESSURE SWITCH
RN-A RESTRICTION NOZZLE (AIR LINE)
** OPTIONAL

Company Registration No. 5717368 V.A.T No. 883908672 www.fireguard-uk.com


Tel: 00-44-8450751042 Fax: 00-44-8450751043 Email: info@fireguard-uk.com
2nd FLOOR | 145-157 ST.JOHNS STREET | LONDON | EC1V 4P Y | UNITED KINGDOM

SCHEMATIC FOR WET PILOT BASIC TRIM FOR DELUGE VALVE


MODEL - C1 FOR HORIZONTAL MOUNTING
NTW TO DETECTION
LINE

**
OD

~
SCV RN SV
M
~
PG
PS2 ** OD
** G

~
OD
SCV

DV
INLET OUTLET

PG

DR.V ~
OD
~
OD
OD

SCHEMATIC 15

SCHEMATIC FOR DRY PILOT BASIC TRIM FOR DELUGE VALVE


MODEL - C1 FOR HORIZONTAL MOUNTING

NTD TO DETECTION
LINE
PG
**
PS1
AIR SUPPLY
RN-A SCV
DPA

OD **
SV
OD
~

RN M
~
PG
**
PS2
OD
** G
~
OD
DV
INLET OUTLET
PG

DR.V
~
OD
~
~ OD

SCHEMATIC 16

DV DELUGE VALVE G SPRINKLER ALARM (WMG) SWING CHECK VALVE M EMERGENCY RELEASE STATION
OD OPEN DRAIN VALVE RN RESTRICTION NOZZLE (PRIMING LINE) DPA DRY PILOT ACTUATOR
STRAINER SV SOLENOID VALVE ANGLE VALVE PG PRESSURE GAUGE
DR.V DRIP VALVE
PS2
BY USER
WATER FLOW PRESSURE ALARM SWITCH
PS1 LOW AIR ALARM PRESSURE SWITCH
RN-A RESTRICTION NOZZLE (AIR LINE)
** OPTIONAL

Company Registration No. 5717368 V.A.T No. 883908672 www.fireguard-uk.com


Tel: 00-44-8450751042 Fax: 00-44-8450751043 Email: info@fireguard-uk.com
2nd FLOOR | 145-157 ST.JOHNS STREET | LONDON | EC1V 4P Y | UNITED KINGDOM

SPRINKLER HEIGHT LIMITATION

DV 200NB DV 150NB
KG/SQCM KG/SQCM
2 4 6 8 10 12 14 16 18 2 4 6 8 10 12 14 16 18
220. 240
65 70
220. ET
200 FE

MAXIMUM PILOT LINE HEIGHT - FEET


60 65
ET 25
MAXIMUM PILOT LINE HEIGHT - FEET

T
180 FE 55 200
FE
E 60
25 T 0
E 50 25 55
160 FE
180
ET
0 FE
25 45 160 5 00 50
140
E ET 45
0F 40

METERS
140

METERS
120 50 40
35
120
100 35
30
100 30
80 25
80 25
20
60 20
15 60
40 15
10 40
10
20 5 20 5
0
20 50 100 150 200 250 0
20 50 100 150 200 250
SYSTEM SUPPLY PRESSURE - PSI SYSTEM SUPPLY PRESSURE - PSI
EQUIVALENT LENGTH BASED ON 1/2" SCHEDULE 40 PIPE WITH C = 120 EQUIVALENT LENGTH BASED ON 1/2" SCHEDULE 40 PIPE WITH C = 120

DV 200NB DV 150NB

DV 100NB DV 80NB

KG/SQCM KG/SQCM
2 4 6 8 10 12 14 16 18 2 4 6 8 10 12 14 16 18
240 220.
70 65
220. 200
MAXIMUM PILOT LINE HEIGHT - FEET

65 60
MAXIMUM PILOT LINE HEIGHT - FEET

ET
200 ET 60 180 FE 55
FE 25
25 55 50
180 160 ET
E T FE
FE 50 25
0 45
160 25
0 140
45 T 40
METERS

140 ET EE
FE 120 0F
METERS

0 40 50 35
50
120 35 100 30
100 30 80 25

80 25 20
60
20 15
60 40
15 10
40 20
10 5
20 5 0
20 50 100 150 200 250
0
20 50 100 150 200 250 SYSTEM SUPPLY PRESSURE - PSI
SYSTEM SUPPLY PRESSURE - PSI EQUIVALENT LENGTH BASED ON 1/2" SCHEDULE 40 PIPE WITH C = 120
EQUIVALENT LENGTH BASED ON 1/2" SCHEDULE 40 PIPE WITH C = 120
DV 80NB
DV 100NB

Company Registration No. 5717368 V.A.T No. 883908672 www.fireguard-uk.com


Tel: 00-44-8450751042 Fax: 00-44-8450751043 Email: info@fireguard-uk.com
2nd FLOOR | 145-157 ST.JOHNS STREET | LONDON | EC1V 4P Y | UNITED KINGDOM

SPRINKLER HEIGHT LIMITATION

DV - 50NB
KG/SQCM
2 4 6 8 10 12 14 16 18
220.
65
200
MAXIMUM PILOT LINE HEIGHT - FEET

60
T 55
180 EE
F
25 50
160 ET
0 FE 45
140 25
40
ET

METERS
120 E
0F 35
50
100 30
80 25
20
60
15
40
10
20 5
0
20 50 100 150 200 250
SYSTEM SUPPLY PRESSURE - PSI
EQUIVALENT LENGTH BASED ON 1/2" SCHEDULE 40 PIPE WITH C = 120

DV 50NB
DELUGE VALVE MODEL C1

Company Registration No. 5717368 V.A.T No. 883908672 www.fireguard-uk.com

You might also like