Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Schreiber Engineering: Model No. 400 AC

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Schreiber

Schreiber Engineering
Engineering
Corporation since 1958
high-performance
water chillers
made in the U.S.A.
ISO 9001: 2000
capacity: 4 ton air cooled application: general recommended for all commercial applications

Model no. 400 AC

GENERAL DATA

Energy Saving Design CAPACITIES


Chiller Capacity: 4 Tons
Does not use hot gas bypass @ 44 F Water 48,000 BTU/hr
95 F Ambient 14.06 kW
Chiller Compressor cycles on and off Reservoir Capacity 45 U.S. Gallons
based on supply/discharge temperature
DIMENSIONS
requirements
Width 30.25 in.
Height 42.25 in.
Digital Temperature Control
Depth 46 in.
Displays discharge and return
WEIGHT
temperature readings Dry Weight 800 lbs

Pump and compressor shut-off switches ELECTRICAL


Volts/Phase 230/3 --- 460/3 -- 230/1
High-Temperature Alarm and contact FLA (Amps) 23.7 --- 11.8 A
Min Amps 27.7 --- 13.8 V
All Non-Ferrous plumbing components Max Fuse (Amps) 30 --- 15 A
I
Trust the Leader Insulated, double-wall reservoir MISCELLANEOUS SPECIFICATIONS L
(non-pressurized) Charge 14 lbs A
Ensure your investment with reliable chilled Refrigerant R-22 B
water. TrueTon engineers design water chillers Stainless steel centrifugal pump Compressor FLA (Amps) 16 --- 8 L
to be accurately compatible with your specic Compressor LRA (Amps) 110 --- 55 E
equipment requirements. We use only the All-copper evaporator / Brazed plate Compressor HP 4 HP
nest, most reliable components to assure Compressor Type Reciprocating U
reliability and high-performance results. Powder coated cabinet Water Pump FLA (Amps) 5.4 --- 2.7 P
Water Pump HP 2 HP O
Ranging from 1/3rd ton to 60 ton capacities 1 Year parts and labor Water Pump GPM 40 N
we offer a chiller for most applications. Water Pump Pressure 44.8 P.S.I.
Clearance Fan FLA (Amps) 2.3 --- 1.1 R
Fan HP 1/2 HP E
Top fan discharge 12 ft Fan Blade Width 18 in. Q
Fans Installed 1 qty. U
Condenser (left) 4 ft Total Air Flow 3200 CFM E
Access panel(right) 4 ft Fan Speed 1140 RPM S
Make-up Connection 1/2 in. N.P.T. T
Overow(rear) 2 ft CHW Connections 1 in. N.P.T.

Control panel 3 ft
(check code)
PUMP PERFORMANCE CHART (GPM vs. FT)
Install Controls Indoors


250

If you choose to locate the chiller units

outdoors, the optional remote control panel
enclosure may be installed indoors for 200
easy access, monitoring and convenience.

To tal Dyn amic Hea d (FT .)


150
Options


Micro Processor Controls

100
Outdoor Installation

Pump upgrades

High ambient package 50

Tank less Chiller

Call factory for pricing and additional 0


0 10 20 30 40 50
options Capacity U.S. GPM
Please contact our engineering department for assistance
in the selection of the appropriate chiller equipment for Most all Schreiber Chillers have been
your specic application. ETL and CSA Tested and Approved.

Medical Systems l Manufacturing l Process Cooling l Welding l Aerojet l Heavy Equipment l Automotive l HVAC l More

trueton.com 12111 E. Park Street Cerritos, CA 90703 TEL 562 926 3855 FA X 5 6 2 9 2 6 0 9 6 9
2004 Schreiber Engineering Corp. 400 AC-04 Specications subject to change
REV. DESCRIPTIONS DATE BY
WATER FILL LOCATION
SEE SHEET 2 OF 2 FOR
COMPONENTS DETAIL. 26.250 30.500
46.250 11.000

6.375

29.000
OVER FLOW
42.000

Minimum Clearances:
Rear: 3 ft (Water Over Flow) 43.000
Front : 4 ft (Control Box)
30.000 Right: 4 ft (Condenser Side)
Top: 12 ft (Fan Exhaust)
2.000
Water drain located inside the chiller
Remove door to drain the water from tank

Note: No clearance requirements


for top and right side for remote 2 - 3 - 4 - 5 CABINET.
air cooled and water cooled models.
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
Schreiber 12111 EAST PARK
Refrigration piping connections TOLERANCE ARE:
FRACTION
+
DECIMALS
.XX +.03
ANGLES
+.5
Engineering STREET
CERRITOS, CA 90703
for remote condensers are from .XXX + .015
TITLE COMPLETE CABINET ASSEMBLY
MATERIAL
the front panel of the chiller. 2-3-4-5 TON
FINISH BIRCH WHITE SIZE SHT1 SHT2 DRAWING NO.
B B B 500 - 001- ASY REV
A
DO NOT SCALE DRAWING SCALE: DRAWN BY: STEVEN Q. LY DATE: 06.10.02 SHT 1 OF 2
REV. DESCRIPTIONS DATE BY
Minimum Clearances:
Rear: 3 ft (Water Over Flow)
50.368
Front : 4 ft (Control Box) 46.289
Right: 4 ft (Condenser Side) 6.364 26.097
Top: 12 ft (Fan Exhaust)

Water drain located inside the chiller

30.249
Remove door to drain the water from tank

19.119
Note: No clearance requirements
for top and right side for remote
air cooled and water cooled models.

Refrigration piping connections RESERVOIR FILL


for remote condensers are from (MANUAL, O 3")) ELECTRICAL
the front panel of the chiller. QUICK 2.844 CONTROL BOX
DISCONNECT
15.125 OVER FLOW WATER PRESSURE WATER RETURN
7.027 1" NPT GAUGE 1" NPT
2.936
SIGHT GLASS
(WATER LEVEL)
WATER DISCHARGE
1" NPT
45.335

42.060
43.402

38.000
38.000
35.125

30.868

27.750
24.861

23.250
20.250
20.213 7.563
2.000 40.277 RESERVOIR FILL 5.560
(AUTOMATIC 10.875
43.231 1/2" NPT) UNLESS OTHERWISE SPECIFIED Schreiber 12111 EAST PARK
DIMENSIONS ARE IN INCHES

46.109 PUMP ROTATION


TOLERANCE ARE:
FRACTION
+
DECIMALS
.XX +.03
.XXX + .015
ANGLES
+.5
Engineering STREET
CERRITOS, CA 90703

CHECK HOLE MATERIAL


TITLE COMPLETE CABINET ASSEMBLY
2-3-4-5 TON
FINISH BIRCH WHITE SIZE SHT1 SHT2 DRAWING NO.
B B B 500 - 001- ASY REV
A
DO NOT SCALE DRAWING SCALE: DRAWN BY: STEVEN Q. LY DATE: 06.10.02 SHT OF
Model Number 400AC
Chiller Capacity 4 [Tons]
o
250
@ 44 F Water & 48000 [BTU/hr]
o
95 F Ambient 14.1 [KW]
Width 30.25 [in]
Height 46.00 [in]
200
Depth 42.25 [in]
Volts/Phase 220/3 440/3 [Volts]
FLA 20.6 11.8 [Amps]
Min Amps 23.6 13.8 [Amps]
150
Max Fuse 35 20 [Amps]
Charge 13.0 [lbs]
Refrigerant R-22
Compressor FLA 12.0 8.0 [Amps]
100
Compressor LRA 110 55 [Amps]
Compressor HP 4 [HP]
Compressor Type Scroll
Water Pump FLA 3.2 1.6 [Amps] 50
Water Pump HP 1 [HP]
Water Pump GPM 40 [GPM]
Water Pump Pressure 45 [psi]
Fan FLA 3.4 1.7 [Amps] 0
Fan HP 0.5 [HP] 0 PUMP
10 PERFORMANCE
20 30 40 50
Fan Blade 18 [in] GPM vs. FT
Fan Quanitity 1
Total Air Flow 2900 [CFM]
Fan RPM 1140 [RPM]
NoiseLevel 60dba@5ft
Make-up Connection1/2 N.P.T. [in]
CHW Connections1 N.P.T. [in]
Reservoir Capacity 45 [Gal]
Dry Weight 800 [lbs]

You might also like