26 00 00 - Electrical General: Design & Construction Standards, Revised January 2013 26.00.00-1
26 00 00 - Electrical General: Design & Construction Standards, Revised January 2013 26.00.00-1
26 00 00 - Electrical General: Design & Construction Standards, Revised January 2013 26.00.00-1
A. This section of the design and construction standard outlines general requirements for
electrical and telecommunications designs to be performed for the University of Texas at
Austin. This standard is intended to provide useful information to the Professional
Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
to apply the principles of this section and the ones that follow such that the University
may achieve a level of quality and consistency in the design and construction of their
facilities.
A. The following requirements are to be used by architects for electrical space planning
considerations at the conceptual design level. Refinements and modifications will be
considered upon evaluation of the specific requirements in the building, but as a
minimum, allow space according the following guidelines:
1. Main Service Entrance room shall provide for adequate equipment and maintenance
clearance. Provide outside equipment access to this room.
2. Electrical rooms shall be centrally located and “stacked” so that feeder conduits and
bus duct are run as straight and short as possible.
3. Doors shall swing out where possible and as required by the National Electrical Code
(NEC).
4. Electrical rooms shall not share space with storage, telecommunications, janitor’s
sink, and piping.
5. If possible locate electric rooms away from outside walls, elevator shafts, stairwells,
HVAC duct chases, trunk runs, and other Utility Avenues so that branch circuits can
fan out in all directions.
6. Locate electrical room where it is not susceptible to flood from heavy rains, broken
pipes, stopped drains, or fire hose deluge.
7. Provide a separate space in the building for storage of spare lamps.
A. This section provides general guidance concerning the specific preferences of The
University for abatement or removal of polychlorinated biphenyl (PCB) within buildings.
B. Reference Standards: Texas Hazard Communication Act chapter 502 of the Texas Health
and Safety Code. Volume 40-Code of Federal Regulations, Chapter 761.
C. General Requirements:
PART 2: PRODUCTS
A. All products used and specified in Division 26 and 27 must be UL approved and must
meet all applicable ANSI, NFPA, IEEE, EIA/TIA standards as indicated in the
appropriate sections of this design standard.
PART 3: EXECUTION
A. In addition to the specific requirements of the sections of the standard that follow, use the
following as baseline programming guidelines.
B. A typical Division 26 design project for the University shall include, but not be limited to
the design and specifications for the following items:
1. As a part of the project cost, the Owner will provide and terminate the necessary (15kV rated)
cables from the designated manhole to the main service entrance equipment.
2. The main service entrance equipment shall be a double-ended unit substation configured according
to the attached one-line diagram.
1. The low voltage distribution system shall be separately derived 3 phase, 4 wire 277/480 volt
system supplying power to all fluorescent and HID lighting, all 480 volt utilization equipment and all
2. Provide at least one circuit for each classroom and do not connect more than one classroom on a
circuit.
3. All large electrical equipment, e.g. transformers and main switchgear shall be located at or near
ground level in the building near the power service entrance such that it may be removed if necessary
without dismantling
4. There shall be a complete grounding system with ground bars in each electrical room with
distribution equipment or transformers and ground wires with each circuit.
E. Coordination Issues
1. It is the responsibility of the engineering team to prepare Reflected Ceiling Plans that accurately
locate and coordinate ceiling panels, lighting fixtures, A/C supply and return grilles, sound system
speakers, automatic sprinkler heads, fire and smoke detectors, access doors, and any other ceiling
located items.
a. Physical space above ceiling for duct work, lighting fixtures, piping, etc.
b. That no piping of any type encroaches on electrical switchgear.
c. That electric closets are “stacked” so that feeder conduits and bus duct are in as straight a line and
as short a route as possible.
d. That electric closets are not next to elevator shafts or stair wells, vertical HVAC duct chases and
horizontal trunk runs or other Utility Avenues, etc., so that branch circuit conduits can “fan out” in
all directions. Do not locate on exterior walls.
e. That electric panels or terminal boards are not in Janitor’s closets or public areas.
a. The location of all electric utilization, power distribution and special systems
equipment.
b. All branch circuit and feeder wiring including circuit numbers and circuit
schedule.
c. An overall electrical one-line diagram.
d. Complete riser diagrams for power and special systems.
a. Typical Rooms.
b. Electrical vaults and main power distribution areas.
c. Kitchens and other areas with high density of utilization equipment.
3. Separate drawings should be provided for lighting, power, special systems, and
telecommunications of each floor and roof.
4. Room names and numbers shall appear on all Electrical Floor Plans. Special systems
floor plans will require door numbers as well.
5. Column lines and designations, plan North, and graphic scale shall appear on all
sheets as they shall appear on all Architectural Sheets. All drawings shall be dated
and signed for each Review Submittal.
G. Specification Requirements
2. Electrical Specifications should not instruct the contractor or installer to size a piece
of electrical equipment according to the National Electrical Code. All electrical
designs should be complete and appear as such on the Drawings and Specifications.
3. A clear statement shall be made concerning construction power; where available, and
at what voltage and phase, who makes and removes the installation, and who pays for
the energy.
5. Utility Specifications
K. Design Review
1. Schematic design review (3% overall) shall include:
END OF STANDARD