Surge Arrester: Technical Data
Surge Arrester: Technical Data
Surge Arrester: Technical Data
Surge arrester
MWD
Technical data
--
t = 10 s U TOV = 1.256 × Uc
Overvoltage protection of
Transformers
--
Mechanical loads
Motors Torque moment 50 Nm
Cables
-
Tensile strength axial 1200 N
Cable sheath Short term load SSL horizontal to axis 153 Nm
Medium voltage equipment Long term load SLL horizontal to axis 88 Nm
--
Application
Alternating current (AC)
Indoor
General data
Ambient air temperature
Altitude
−60 to +40 °C (for higher values
contact manufacturer)
up to 1800 m (for higher values
contact manufacturer)
Frequency of system voltage 50/60 Hz
Electrical data
2 MWD | Surge arrester
Housing
Uc Creepage Flashover Minimum clearances Height H Weight Insulation withstand voltage on empty housing
Continuous distance distance
operating
voltage 1.2/50 μs 50 Hz, 60 s dry
E min Fmin req. values tested req. values tested
acc. to IEC acc. to IEC
kV rms mm mm mm mm mm kg kV pv kV pv kV rms kV rms
4 170 165 50 90 187 1.3 16 66 8 42
5 170 165 60 90 187 1.3 21 66 10 42
6 170 165 70 90 187 1.4 25 66 12 42
7 170 165 80 90 187 1.4 28 66 13 42
8 170 165 90 100 187 1.5 32 66 15 42
9 210 205 100 110 227 1.8 37 81 17 52
10 210 205 110 120 227 1.8 40 81 19 52
11 250 245 120 130 267 2.1 44 97 21 62
12 250 245 130 140 267 2.1 48 97 23 62
13 250 245 140 150 267 2.2 52 97 24 62
14 250 245 150 160 267 2.2 56 97 26 62
15 250 245 160 170 267 2.3 60 97 28 62
16 290 285 170 180 307 2.5 64 113 30 72
17 290 285 180 190 307 2.5 68 113 32 72
18 290 285 190 200 307 2.6 72 113 34 72
19 290 285 200 210 307 2.6 76 113 36 72
20 290 285 209 220 307 2.7 80 113 37 72
21 330 325 220 230 347 3.0 84 129 39 82
22 330 325 229 240 347 3.0 88 129 41 82
23 330 325 239 250 347 3.1 92 129 43 82
24 330 325 249 260 347 3.1 96 129 45 82
25 370 365 259 270 387 3.4 100 145 47 92
26 370 365 269 280 387 3.4 104 145 48 92
27 370 365 279 290 387 3.5 108 145 50 92
28 370 365 289 300 387 3.5 112 145 52 92
29 370 365 299 310 387 3.6 116 145 54 92
30 370 365 309 320 387 3.6 120 145 56 92
31 490 485 319 330 507 4.4 124 192 58 122
32 490 485 329 340 507 4.4 128 192 59 122
33 490 485 339 350 507 4.5 132 192 61 122
34 490 485 349 360 507 4.5 136 192 63 122
35 490 485 359 370 507 4.6 140 192 65 122
36 490 485 369 380 507 4.6 144 192 67 122
37 490 485 379 390 507 4.7 148 192 69 122
38 490 485 389 400 507 4.7 152 192 71 122
39 490 485 398 409 507 4.8 156 192 72 122
40 490 485 408 419 507 4.8 160 192 74 122
41 490 485 418 429 507 4.9 164 192 76 122
42 530 525 428 439 547 5.1 168 208 78 132
43 530 525 438 449 547 5.3 172 208 80 132
44 530 525 448 459 547 5.3 176 208 82 132
Surge arrester | MWD 3
Housing
4 MWD | Surge arrester
For further information please contact: Note
1HC0075864 E01 AA
We reserve the right to make technical changes or modify the contents of
ABB Switzerland Ltd this document without prior notice. With regard to purchase orders the
High Voltage Products a greed particulars shall prevail. ABB AG does not accept any responsibility
whatsoever for potential errors or possible lack of information in this docu-
Surge Arresters
ment. We reserve all rights in this document and in the subject matter and
Jurastrasse 45 illustrations contained therein. Any reproduction, disclosure to third parties
CH-5430 Wettingen/Switzerland or utilization of its contents – in whole or in parts – is forbidden without prior
Tel. +41 58 585 29 11 written consent of ABB AG.
www.abb.com/arrestersonline
Our products are certified according ISO 9001, 14001, 18001 and IRIS