DM-10 IECO Diode Monitor User's Manual
DM-10 IECO Diode Monitor User's Manual
DM-10 IECO Diode Monitor User's Manual
21.10.1997
GENERAL
OPERATING PRINCIPLE
There are few failure frequencies and related switch positions used
by general generators calculated in a table.
INSTALLATION
COMMISSIONING
Power input
Input voltage range for DC is from 24V to 300V and for AC range is
from 50V to 250V.
Excitation current
Excitation current is fed via diode monitor. There are two terminals
for input (9 and 10 in parallel) and for output (7 and 8 in parallel).
When using 2,5 mm2 cable one terminal is sufficient to couple with
20 A continuous.
Relay outputs
For both diode open and shorted failure there is a relay output. Both
relays have three terminals; common, normal close and normal
open.
Level setting
Frequency setting
Test connections
Eg. If wanted frequency is 132 Hz, the test out frequency should be
50 x 132 Hz = 6600 Hz. Now you can verify the frequency of the
filter.
SPECIFICATIONS
Inputs
Outputs
Functions
Generator selection 3 pcs 16 position switches (to be set according to separate table)