Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Hilite XL 120kn SML Data

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

16 mm (5/8") Rod Diameter Suspension Insulators

Section Length Section Length


x
Mechanical Ratings
SML = 120 kN Type x mm (in.) y mm (in.)
A10.. 97 (3.8) 114 (4.5)
RTL = 60 kN D10.. 109 (4.3) 140 (5.5)
94 mm (3.7")
G10.. 130 (5.1) 160 (6.3)
y High Leak Design
Standard Design
(2)
IEC Wet (2)
IEC (2)
IEC Light-
Switching Power ning Impulse
Selection Guide Leakage Catalog Impulse Freq. Wet Withstand (ANSI
Typical Distance Number Section Dry Arc Withstand Withstand Critical Impulse
Line Voltage, kV (1) mm (in.) XX = with IEC Length No. Distance (ANSI 60 (ANSI 60 F.O.) kV
16 mm ball mm of mm Hz. Dry Hz. Wet
70 110 132 161 220 330 400 51 A1 D1 G1 - socket (in.) Sheds (in.) F.O.) kV F.O.) kV Pos-kV Neg-kV
1160 1340 1530 1760 731 470 260 135 275 255
(45) (53) (60) (69) XX00032A07 (28.8) 12 (18.5) (180) (180) (310) (285)
1550 1790 2040 2350 886 625 345 180 365 350
(61) (70) (80) (92) XX00042A07 (34.9) 16 (24.6) (245) (240 (410) (390)
1940 2230 2540 2920 1039 775 420 220 450 440
(76) (88) (100) (115) XX00052A07 (40.9) 20 (30.6) (310) (295) (505) (490)
2320 2680 3060 3520 1195 930 500 260 540 530
(91) (105) (120) (138) XX00062A07 (47.1) 24 (36.8) (370) (350) (605) (595)
2710 3130 3570 4110 1351 1090 570 305 630 620
(107) (122) (140) (162) XX00072A07 (53.2) 28 (42.9) (430) (405) (700) (695)
3100 3580 4080 4700 1507 1245 650 340 715 710
(122) (141) (160) (185) XX00082A07 (59.3) 32 (49.0) (490) (455) (795) (795)
3490 4020 4580 5280 1659 1395 720 380 800 800
(137) (158) (180) (207) XX00092A07 (65.3) 36 (55.0) (545) (505) (890) (890)
3880 4480 5100 5870 1815 1555 790 420 885 890
(152) (176) (200) (231) XX00102A07 (71.5) 40 (61.2) (600) (555) (985) (990)
4270 4930 5610 6460 1971 1710 860 455 970 975
(168) (194) (221) (254) XX00112A07 (77.6) 44 (67.3) (655) (605) (1080) (1090)
4660 5370 6120 7050 2127 1865 930 490 1050 1065
(183) (211) (241) (277) XX00122A07 (83.8) 48 (73.5) (710) (655) (1170) (1185)
5040 5820 6620 7630 2279 2015 995 525 1135 1145
(198) (229) (261) (300) XX00132A07 (89.8) 52 (79.5) (760) (700) (1260) (1280)
5430 6270 7140 8220 2435 2175 1060 560 1215 1230
(214) (247) (281) (323) XX00142A07 (95.9) 56 (85.6) (810) (750) (1350) (1370)
5820 6720 7650 8810 2591 2330 1120 595 1295 1315
(229) (264) (301) (347) XX00152A07 (102.1) 60 (91.7) (855) (790) (1440) (1465)
6210 7170 8160 9400 2747 2485 1185 625 1375 1400
(244) (282) (321) (370) XX00162A07 (108.2) 64 (97.9) (905) (835) (1530) (1560)
6600 7610 8670 9980 2900 2635 1240 655 1455 1480
(260) (299) (341) (393) XX00172A07 (114.2) 68 (103.9) (945) (880) (1615) (1650)
6990 8060 9180 10570 3056 2795 1300 690 1530 1565
(275) (317) (361) (416) XX00182A07 (120.3) 72 (110.0) (990) (920) (1705) (1740)
7380 8510 9700 11170 3212 2950 1355 720 1610 1645
(290) (335) (381) (439) XX00192A07 (126.5) 76 (116.2) (1030) (960) (1790) (1830)
7770 8960 10210 11760 3368 3105 1410 745 1685 1725
(306) (353) (402) (463) XX00202A07 (132.6) 80 (122.3) (1070) (1000) (1875) (1920)
8150 9400 10710 12330 3520 3260 1460 775 1760 1800
(321) (370) (421) (485) XX00212A07 (138.6) 84 (128.3) (1110) (1040) (1960) (2005)
8540 9860 11220 12930 3676 3415 1510 800 1835 1880
(336) (388) (442) (509) XX00222A07 (144.8) 88 (134.4) (1145) (1075) (2040) (2090)
8930 10310 11740 13520 3832 3570 1560 830 1910 1955
(351) (406) (462) (532) XX00232A07 (150.9) 92 (140.6) (1180) (1110) (2125) (2175)
Notes: (1) For voltages above 400 kV, and other section lengths, contact your Ohio Brass representative.
(2) Electrical values are without corona ring. For voltages above 161 kV refer to Page 3 for Corona Rings, and associated physical/electrical changes
to above data. Dimensions are within allowable tolerances as specified by IEC 1109 and ANSI C29.12.
Y-Clevis Tower Attachment Detail
for all Hi*Lite XL Insulators

Ground Line Suffix Length Change


Fitting Fitting Code mm Inches
“D” Max.
Eye Eye 2000 +59 +2.3
25 mm (1") Dia. Minimum
19 mm (3/4") Max.
Eye IEC 16 mm Ball 2007 +26 +1.0
3 mm (1/8") x 45° Chamfer
Rod Dia. mm (in.) “D” Max. mm (in.) Y-Clevis IEC 16 mm Ball 2207 +24 +0.9
16 (5/8") 13 (.53) Y-Clevis Eye 2200 +57 +2.2
22 (7/8") 25 (1.0)
To achieve insulator SML value, proper grade steel should be used
IEC 16C Clevis Eye 2800 +31 +1.2

JULY 2010 OHIO BRASS – AIKEN, SC, USA