FX3G HardwareManual JY997D46001-D
FX3G HardwareManual JY997D46001-D
FX3G HardwareManual JY997D46001-D
B Side
A JAPANESE
Side
B ENGLISH
Turn off the power before attaching or detaching the following altitude
devices.
Failure to do so may cause device failures or malfunctions. (*1) The criterion is shown in IEC61131-2.
- Peripheral devices, display modules, expansion boards and
special adapters (*2) Dielectric withstand voltage and insulation resistance are
8(0.32") - Extension units/blocks and the FX Series terminal block shown in the following table.
W1
- Battery and memory cassette
W 86(3.39") Dielectric Insulation
Terminal
strength resistance
Notes
Mounting hole pitches Main units, Input/output extension units/blocks
When a dust proof sheet is supplied with an extension unit/
Between power supply
block, keep the sheet applied to the ventilation slits during 1.5 kV AC for
W1: terminal (AC power) and
installation and wiring work. one minute
W: mm (inches) MASS (Weight): ground terminal
Model name To prevent temperature rise, do not install the PLC on a floor, a
mm (inches) Direct mounting kg (lbs) Between power supply
ceiling or a vertical surface. 5M or more by
hole pitches terminal (DC power) and
Install it horizontally on a wall as shown in section 2.2. 500V DC megger
Approx. 0.50 Keep a space of 50mm (1.97”) or more between the unit main ground terminal 500V AC for
FX3G-14M 90 (3.55”) 82 (3.23”)
(1.10lbs) body and another device or structure (part A). Install the unit as one minute
Between input terminal
far away as possible from high-voltage lines, high-voltage (24V DC) and ground
Approx. 0.55
FX3G-24M 90 (3.55”) 82 (3.23”) devices and power equipment. terminal
(1.21lbs)
2.2 Installation location 2.3 Procedures for installing to and detaching from 2.4.2 Installation Notes
DIN rail
Install the PLC in an environment conforming to the generic 1) Make mounting holes in the Simultaneously turn on and off the power supplies of the main
specifications (section 2.1), installation precautions and notes. The products can be installed on a DIN46277 rail [35 mm (1.38”) mounting surface referring to unit and extension devices.
For more details, refer to FX3G Series User's Manual - Hardware wide]. the external dimensions Even if the AC power supply causes an instantaneous power
Edition. This section explains the installations of the main units. diagram. B failure for less than 10 ms, the PLC can continue to operate.
For the input/output extension units/blocks and special adapters, 2) Fit the main unit (A in the right Even if the DC power supply causes an instantaneous power
Installation location in enclosure
refer to the following manual. figure) based on the holes, and failure for less than 5 ms, the PLC can continue to operate.
Refer to FX3G Series User's Manual - Hardware Edition. secure it with M4 screws (B in If a long-time power failure or an abnormal voltage drop occurs,
the right figure). the PLC stops, and output is turned off. When the power
2.3.1 Installation
The mounting hole pitches and supply is restored, it will automatically restart (when the RUN
number of screws depend on input is on).
1) Push out all DIN rail mounting hooks (below fig.A).
the product. Refer to the A
external dimensions diagram WIRING
(Section 1.2). B PRECAUTIONS
Cut off all phases of the power supply externally before
1) 1)
installation or wiring work in order to avoid damage to the
product or electric shock.
3. Power supply/input/output specifications
1) 1) and examples of external wiring WIRING
A A
PRECAUTIONS
As for the details of the power supply wiring and input/output wiring,
refer to the following manual. Connect the AC power supply to the dedicated terminals
Space in enclosure 2) Fit the upper edge of the DIN rail specified in this manual.
Extension devices can be connected on the left and right sides of the mounting groove (right fig.C) Refer to FX3G Series User's Manual - Hardware Edition.
If an AC power supply is connected to a DC input/output
main unit of the PLC. onto the DIN rail. DESIGN terminal or DC power supply terminal, the PLC will burn out.
If you intend to add extension devices in the future, keep necessary C PRECAUTIONS Do not wire vacant terminals externally.
spaces on the left and right sides. Doing so may damage the product.
Make sure to have the following safety circuits outside of the
Configuration without extension cable Perform class D grounding (grounding resistance: 100 or
PLC to ensure safe system operation even during external
less) to the grounding terminal on the FX3G Series main unit
A 3) Lock the DIN rail mounting hooks power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents. with a wire 2 mm2 or thicker.
(below fig.D) while pressing the PLC against the DIN rail. Do not use common grounding with heavy electrical systems
FX2N-16EYT
FX2N-16EX
A The product can be installed directly on the panel (with screws). output device, the output could be held either on or off.
FX3G-CNV-
FX3U-4AD-
manual.
FX3G Series This section explains the installation of the main units. For output signals that may lead to serious accidents,
- Tighten the screws using a Phillips-head screwdriver No.2
main unit As for the details of the installation/detaching for input/output external circuits and mechanisms should be designed to
(shaft diameter 6mm (0.24”) or less). Make sure that the
ADP
ADP
extension units/blocks and special adapters, refer to the following ensure safe machinery operation in such a case.
screwdriver does not touch the partition part of the terminal
manual. block.
Refer to FX3G Series User's Manual - Hardware Edition. DESIGN
A Extension
cable PRECAUTIONS Notes
2.4.1 Mounting hole pitches
·FX0N-65EC
FX3U-64CCL
Do not bundle the control line together with or lay it close to the Input/output wiring 50 to 100m (164’1” to 328’1”) long will cause
FX2N-16EX
FX2N-CNV-
Input/output ·FX0N-30EC Refer to the External Dimensions (section 1.2) for the product's
powered main circuit or power line. As a guideline, lay the control line at almost no problems of noise, but, generally, the wiring length
mounting hole pitch information. least 100mm (3.94") or more away from the main circuit or
extension Other should be less than 20m (65’7”) to ensure the safety.
A A As for the details of the mounting hole pitches for extension unit/ power line.
unit Extension cables are easily affected by noise. Lay the cables
BC
equipment block and special adapters, refer to the following manual. Noise may cause malfunctions.
at a distance of at least 30 to 50mm (1.19” to 1.97”) away from
Refer to FX3G Series User's Manual - Hardware Edition. Install module so that excessive force will not be applied to the
A the PLC output and other power lines.
built-in programming connectors, power connectors or I/O
Other equipment A ≥ 50mm (1.97") connectors.
Failure to do so may result in wire damage/breakage or PLC
failure.
2.2.1 Affixing The Dust Proof Sheet
The dust proof sheet should be affixed to the ventilation port before
beginning the installation and wiring work.
For the affixing procedure, refer to the instructions on the
dust proof sheet.
Be sure to remove the dust proof sheet when the installation and
wiring work is completed.
3.1 Wiring 3.2 Power supply specifications and example of 3.2.2 Example of external wiring (AC power type) 3.3 Grounding
external wiring
This section explains the wiring of the terminal type. 100 to 240V AC power is supplied to the main unit and input/output Ground the PLC as stated below.
For the connectors types, refer to the following manual. As for the details of the power supply specifications and example of extension unit.
Perform class D grounding. (Grounding resistance: 100 or less)
Refer to FX3G Series User's Manual - Hardware Edition. external wiring, refer to the following manual. For the details of wiring work, refer to section 3.1.
Ground the PLC independently if possible.
Refer to FX3G Series User's Manual - Hardware Edition. PLC
3.1.1 Cable end treatment and tightening torque 100 to 240V AC If it cannot be grounded independently, ground it jointly as shown
3.2.1 Power supply specifications Main unit below.
For the terminals of FX3G series PLC, M3 screws are used. [Main unit, Input/output extension units]
The electric wire ends should be treated as shown below. PLC Other PLC Other PLC Other
L Breaker equipment equipment equipment
Tighten the screws to a torque of 0.5 to 0.8 Nm. Specification
Item (* )
Do not tighten terminal screws with a torque outside the above- AC power type DC power type Power on
mentioned range. Failure to do so may cause equipment failures or N Emer- Independent grounding Shared grounding Common grounding
malfunctions. Supply voltage 100 to 240V AC 24V DC (Best condition) (Good condition) (Not allowed)
gency
Allowable supply voltage PL
When one wire is connected to one terminal 85 to 264V AC 20.4 to 28.8V DC MC Use ground wires thicker than AWG14 (2 mm2).
range
φ3.2 (0.13") Terminal Solderless Input/output MC Position the grounding point as close to the PLC as possible to
6.2 mm (0.24") screw terminal Rated frequency 50/60Hz - extension decrease the length of the ground wire.
or less Fuse
Operation can Operation can be unit L
be continued continued upon 3.4 Input specifications and external wiring
φ3.2 (0.13")
Allowable instantaneous upon occurrence occurrence of
6.2 mm (0.24") Terminal N As for the details of the Input specifications and external wiring, refer
power failure time of instantaneous instantaneous
or less power failure for power failure for MC MC to the following manual.
10 ms or less. 5 ms or less. Refer to FX3G Series User's Manual - Hardware Edition.
<Reference>
FX3G-14M, 3.4.1 Input specifications (24V DC input type)
Terminal Pressure 250V 1A 125V 2.5A
Type No. Certification FX3G-24M
Manufacturer Bonding Tool Item Specification
FX3G-40M, DC
JAPAN FV1.25-B3A Power fuse 250V 3.15A 125V 3.15A
FX3G-60M power FX2N-8ER 4 points (8 points)(*1)
SOLDERLESS supply
UL Listed YA-1(JST) FX2N-32E 250V 3.15A -
TERMINAL MFG FV2-MS3
FX3G-14M,
CO LTD (JST) FX2N-48E 250V 5A 250V 5A 8 points
FX2N-8EX
When two wires are connected to one terminal 30A max. 5ms or (*) Class D grounding DC AC 14 points(16 points)(*1)
less/100 V AC 30A max. 1ms or See section 3.3 for Number of FX3G-24M
Main unit Power supply for loads connected
φ3.2 (0.13") 50A max. 5ms or less/24 V DC details. input
Terminal Solderless to PLC output terminals FX2N-16EX,
6.2 mm (0.24") less/200 V AC points 16 points
screw terminal Rush current FX2N-32E
or less 40A max. 5ms or 3.2.3 Example of external wiring (DC power type) FX3G-40M,
6.3 mm(0.25") FX2N-32E, less/100 V AC 24 points
or more - FX2N-48E
FX2N-48E 60A max. 5ms or 24V DC power is supplied to the main unit and input/output
φ3.2 (0.13") less/200 V AC extension unit. FX3G-60M 36 points(40 points)(*1)
6.2 mm (0.24") Terminal
or less FX3G-14M 31W 19W For the details of wiring work, refer to section 3.1.
6.3 mm(0.25") PLC Input connecting type Refer to FX3G Series
FX3G-24M 32W 21W 24V DC
or more User's Manual -
Power Main unit Input form
FX3G-40M 37W 25W Hardware Edition
<Reference> consumption
(*1) FX3G-60M 40W 29W Circuit protector AC power type 24V DC +10%, -10%
Terminal Pressure Main unit
Type No. Certification FX2N-32E 30W - (* )
Manufacturer Bonding Tool DC power type 20.4 to 28.8V DC
Power on Input
JAPAN FX2N-48E 35W 30W signal Input/ AC power type 24V DC +10%, -10%
Emer-
SOLDERLESS Main unit 400mA - voltage output
FV1.25-B3A UL Listed YA-1(JST) 24V DC PL gency
TERMINAL MFG MC extension
service FX2N-32E 250mA - DC power type 24V DC +20%, -30%
CO LTD (JST) unit
power supply Input/output
FX2N-48E 460mA - MC
extension X000 to X007 3.3k
5V DC built- FX2N-32E Fuse Main unit
3.1.2 Removal and installation of quick-release terminal unit Input X010 or more 4.3k
in power 690mA or less 690mA or less
block supply FX2N-48E impedance
Input/output
4.3k
Removal Unscrew the terminal block mounting screw [both right (*1) This item shows values when all 24V DC service power extension unit/block
and left screws] evenly, and remove the terminal block. MC MC
supplies are used in the maximum configuration connectable X000 to X007 7mA/24V DC
Installation Place the terminal block in the specified position, and Main unit
to the main unit or input/output extension units, Input
tighten the terminal block mounting screw evenly [both X010 or more 5mA/24V DC
For the power (current) consumed by the input/output signal
right and left screws]. extension units/blocks, refer to FX3G Series User's Manual - current Input/output
Tightening torque 0.4 to 0.5 Nm Hardware Edition. (The DC power type main unit does not 5mA/24V DC
Do not tighten the terminal block mounting screws (*) Class D grounding extension unit/block
have a 24V DC service power supply.) See section 3.3 for
exceeding the specified torque. For the power consumed by the special extension blocks, Power supply for loads connected X000 to X007 4.5mA or more
details. to PLC output terminals Main unit
Failure to do so may cause equipment failures or refer to the respective manual. ON input
malfunctions. Refer to FX3G Series User’s Manual - Hardware Edition. X010 or more 3.5mA or more
sensitivity
(*) Pay attention so that the center of the terminal block current Input/output
3.5mA/24V DC
is not lifted. extension unit/block
OFF input sensitivity current 1.5mA or less
Input response time Approx. 10ms
Item Specification 3.4.3 Examples of input wiring [DC power type] 3.4.5 Input specifications (100V AC input type) 3.5 Relay output specifications and example of
external wiring
Sink input: 1.Sink input type 2.Source input type Item Specification
No-voltage contact As for the details of the relay output specifications and external
input [1] [1] Number FX2N-8EX-UA1/UL 8 points wiring, refer to the following manual.
NPN open collector Fuse Fuse of input Refer to FX3G Series User's Manual - Hardware Edition.
transistor points FX2N-48ER-UA1/UL 24 points
Input signal form (*1) (*1) 3.5.1 Relay output specifications
Source input: Input connecting type
No-voltage contact Refer to FX3G Series
input Input form User's Manual - Hardware Edition Item Specification
PNP open collector 24V DC 24V DC 4 points(8 points)(*1)
Input signal voltage 100V AC to 120V FX2N-8ER
transistor S/S S/S
Approx. 21k/50Hz FX3G-14MR 6 points(8 points)(*1)
Input circuit insulation Photocoupler insulation (*2) (*2) Input impedance
Approx. 18k/60Hz
FX2N-8EYR 8 points
LED on panel lights
4.7mA/100V AC 50Hz Number
Input operation display when photocoupler is X000 X000 Input signal current FX3G-24MR 10 points(16 points)(*1)
6.2mA/110V AC 60Hz of output
driven.
X001 X001 points FX3G-40MR,
3-wire type 3-wire type ON input sensitivity current 3.8mA/80V AC
(*1) Each value inside ( ) indicates the number of occupied points. X002 X002 FX2N-32ER, 16 points
sensor sensor OFF input sensitivity current 1.7mA/30V AC FX2N-16EYR
X003 X003
Input response time Approx. 25ms to 30ms FX3G-60MR,
3.4.2 Examples of input wiring [AC power type] [2] [2] 24 points
FX2N-48ER
Input signal form Contact input
S/S S/S Refer to FX3G Series User's
1. Sink input type 2. Source input type Input circuit insulation Photocoupler insulation Output connecting type
X000 X000 Manual - Hardware Edition
[1] [1]
LED on panel lights when Output form Relay
Fuse Fuse Input operation display
(*1) Class D grounding photocoupler is driven.
L L 30V DC or less
(* ) (*) See section 3.3 for details. External power supply 240V AC or less(*2)
(*2) Do not connect the [ ] terminals with others,
N N
since they are not available.
3.4.6 Examples of 100V AC input wiring Resistance load 2A/point(*3)
100 to 240V AC 100 to 240V AC Max. load
[1]:Main unit, Input/output extension unit Inductive load 80VA
S/S S/S (Common to both sink and source inputs) Input/ Fuse
L Min. load 5V DC, 2mA (reference value)
0V 0V output
[2]:Input/output extension block (*1)
24V 24V (Common to both sink and source inputs) extension Open circuit leakage current -
unit N
Response OFFON
X000 X000 3.4.4 Instructions for connecting input devices Approx. 10ms
COM time ONOFF
X001 X001
3-wire type 3-wire type As for the details of Instructions for connecting input devices, refer to X000 Circuit insulation Mechanical insulation
X002 sensor X002 sensor the following manual. X001
X003 X003 Refer to FX3G Series User's Manual - Hardware Edition. LED lights when power is applied
X002 Display of output operation
to relay coil.
[2] [2] 1) In the case of no-voltage contact:
The input current of this PLC is 5 to 7mA/24V DC. (*1) Each value inside ( ) indicates the number of occupied points.
S/S S/S Use input devices applicable to this minute current. Input/
X000 X000 If no-voltage contacts (switches) for large current are used, output COM (*2) Between 250V and 240V CE, UL, and cUL are not compliant.
contact failure may occur. extension X000
block (*3) The total load current of resistance loads per common
X001
(*) Class D grounding MC(*2) terminal should be the following value or less.
2) In the case of input device with built-in series diode:
See section 3.3 for details. - 1 output point/common terminal : 2A
The voltage drop of the series diode should be approx. 4V or
[1]:Main unit, Input/output extension unit less. - 4 output points/common terminal : 8A
(*1) Class D grounding
(Common to both sink and source inputs) When lead switches with a series LED are used, up to two See section 3.3 for details. - 8 output points/common terminal : 8A
[2]:Input/output extension block switches can be connected in series. As for the number of outputs per common terminal, refer to
Also make sure that the input current is over the input-sensing (*2) Do not take input signals from loads generating surge. “Chapter 4 interpretation of partition” and the following manual.
(Common to both sink and source inputs)
level while the switches are ON. Refer to FX3G Series User's Manual - Hardware Edition.
3) In the case of input device with built-in parallel resistance:
Use a device with a parallel resistance of 15kor more.
When the resistance is less than 15k, connect a bleeder
resistance.
4) In the case of 2-wire proximity switch:
Use a two-wire proximity switch whose leakage current is 1.5mA
or less when the switch is off.
When the current is 1.5mA or more, connect a bleeder
resistance.
3.5.2 Life of relay output contact 3.5.4 Cautions in external wiring Item Specification (*2) The total load current of resistance loads per common