1. SCOPE
1.1. This specification covers design, manufacture, testing of Three Phase, Four
wire 3 x 240 volts, 100/5 Amps, Class 1 direct connected static Trivector
energy meter.
1.2. The scope of supply comprises of following:
1.2.1. LT Three Phase Four wire ,3 x 240 volts, 100/5 Amps CT
Operated Trivector static energy meters with optically isolated
RS 232 front Communication Port
1.2.2. Memory resident software for Common Meter Reading
Instruments (preferably with DOS and/or Windows Latest
Operating System) and Laptops to download the data from
energy meter through optically isolated RS 232
communication port
1.2.3. Base Computer Software for analysis of meter data
1.2.4. Operational manuals of energy meter and software including
drawings
1.2.5. Routine test certificates.
1.3. It is not the intent to specify completely herein all the details of the design
and construction of material. However the product shall conform in all
respects to high standards of engineering, design and workmanship and shall
be performing in continuous commercial operation in manner acceptable to
the Customer. The material shall be complete with all components necessary
for their intended purpose. The design, manufacture and performance of
equipment shall comply with all currently applicable standards, regulations
and safety codes in the locality where the equipment will be installed.
2. APPLICABLE CODES AND STANDARDS
2.1. The meter shall conform (for performance and testing thereof) in all respects
to the relevant Indian/International Standard Specifications with latest
amendments there to unless otherwise specifically mentioned in this
specification.
2.2. The meter shall conform to the following standards
Page 2 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
2.3. Unless otherwise specified elsewhere in this specification the meter shall
conform to the latest version available of the standards/codes as specified
above.
2.4. This meter shall have Type Test certificates of laboratories approved by
NABL such as ERDA, NPL, and CPRI etc.
2.5. The meter shall conform shock test as per IS 9000 Part 8 and IS 13010
Clause # 12.3.2 to their latest amendments.
3. SERVICE CONDITIONS
3.1. The meter shall be required to operate satisfactorily and continuously under
the following tropical conditions.
3.2. The overall climatic condition is moderately hot and humid tropical climate,
conducive to rust and fungus growth.
Page 3 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
4. ACCURACY
The meter shall be of class 0.5s or better accuracy as per IS: 14697.
5. GENERAL TECHNICAL PARAMETERS
5.1. The meter shall comply all the provisions of IS/ CBIP recommendations and
CEA Regulations-2006 (together with amendments 2010 and 2014) at all
power factor angles from 0 to 360 degrees.
5.6. Meter shall be suitable for measurement of active energy (kWh), reactive
energy (kVArh) and apparent energy (kVAh) and power demands (kW, kVAr,
kVA) with balanced and unbalanced loads over a power factor range from
zero (lagging) through unity to zero (leading).
5.7. The meter shall be suitable to carry continuously and work accurately at 12
amperes(120% of Imax).
5.8. Power Supply Variation
The meter should be suitable for working with following supply system
variations without damage and without degradation of its metrological
characteristics.
Page 4 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
Page 5 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
6.6. The meter cover shall be fully transparent made of transparent polycarbonate
material for easy reading of all the displayed values / parameters, nameplate
details and observation of operation indicator. The transparency of the plastic
shall not degrade over a period of time.
6.7. Display portion/area of top cover shall preferably be 1mm or 2 mm lower
compared to whole top cover, to avoid scratches on visible display portion.
6.8. The meter base and meter cover shall be ultrasonically welded fully in a
seamless manner. In addition, providing self lockable feature for top cover
like press-fit mechanism or unidirectional screws is desirable.
6.9. Arrangement shall be provided to record the opening of meter cover with
date and time of opening with snap shot for KWh reading. Once the meter
cover is opened, the LCD shall display only “C-OPEN” or “TAMPER”, on
display and stop the display sequence in Auto display mode. However, the
meter shall continue to register the energy consumption and it shall be
possible to view the data in push button mode as well as data download to
CMRI/Laptop through optical communication port.
6.10. The meter shall be wall mounted projected type, fitted with the help of
screws, and shall have a handle at its top to facilitate carrying around.
6.11. The meter case shall have at least three mounting holes. Two holes for
mounting screws on the terminal block sealed beneath the terminal over and
one for hanging screw on the top.
6.12. All parts, which are subject to corrosion under normal working conditions,
shall be protected effectively. Any protective coating shall not be liable to
damage by ordinary handling or damage due to exposure to air, under normal
working conditions. Meter shall withstand solar radiation.
6.13. All insulating material used in the construction of the meter shall be non
hygroscopic, non-aging and of tested quality.
6.14. The terminal block, terminal cover, meter cover and meter case shall ensure
reasonable safety against the spread of fire. They shall not be ignited by
thermal overload of live parts in contact with them.
6.15. Meter shall be designed and constructed in such a way as to avoid
introducing any danger in use and under normal conditions so as to ensure
specially
6.15.1. Personnel safety against electric shock
6.15.2. Personnel safety against effects of excessive temperature.
6.15.3. Protection against spread of fire
Page 6 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
Page 7 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
8.2.2. Du Pont
8.2.3. Buyer
8.2.4. Dow Plastics
8.3. The manufacturer shall use ASICs, PCBs and other meter components
manufactured by highly repute firms across the world. Following are the list
of approved makes of components.
Page 8 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
Page 9 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
Page 10 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
8.4. A detailed list of bought out items that are used in the manufacture of the
meter should be furnished indicating the name of firm from whom these are
procured.
8.5. Detailed specification and datasheets for the above items shall be provided
along with the meter.
9. DISPLAY
9.1. The meter shall have a minimum 7+0 (total 7) digits pin type built-in Liquid
Crystal Display (LCD) with few more digits for legends. It is preferable to
have decimal digit slightly smaller than the integer digits.
9.2. The energy (except in high resolution mode) shall be displayed with one
decimal digit.
9.3. The minimum size of each digit shall be 10 mm (Height) x 5 mm (Width).
9.4. The LCD shall be STN/ transflective type industrial grade with extended
temperature range. The LCD may be subjected to 65˚C temperature for at
least 72 Hours. The display shall be visible and readable after the test.
9.5. The LCD shall have STN type with horizontal viewing angle of ±50º and
vertical viewing angle of +60º/-35º.
9.6. The display module shall be well protected from the external ultraviolet
radiations.
Page 11 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
9.7. The LCD shall be with backplane with LED illumination. The LCD shall be
bright and with uniform backlit.
9.8. It shall be possible to display contents of relevant parameters/tamper events
with another digit displaying legend for identification.
9.9. The meter should have facility for a manual mode where the parameters can
be read by push button operation. The manual display shall switch over to
auto-display mode automatically after 30 idle minutes.
9.10. The electronic display of parameter need not be visible, when meter is not
energized.
10. BATTERY
10.1. The battery provided shall be of Lithium Thyonil Sulphide (LiSOCl2) with
15 years of useful life and a minimum of 3 years shelf life.
10.2. It is preferable that the battery is of cylindrical type with more than 800 mAh
capacity and rated output voltage of 3.6 volts.
10.3. The battery shall support powering up the meter in the event of mains power
failure. This battery shall support meter reading through meter display as
well as complete meter data download through CMRI.
10.4. Meter reading through battery shall be restricted to 5 times only for a
maximum duration of 30 minutes in a month
10.5. The datasheet or/and the test certificates shall be provided for the same along
with the meter.
11. OUTPUT DEVICES
11.1. The meter shall have a suitable test output device for testing of meter. The
blinking LED or other similar device shall be provided. Test output should
also work as operating indicator for meter.
11.2. The device shall be suitable for use with sensing probe used with test
benches or reference standards.
11.3. The test output device shall have constant pulse rate i.e. number of impulses
per kWh and impulses per kVARh and their values should be indelibly
printed on the name plate.
11.4. It is preferable that two separate output devices, one for active energy and
second for reactive energy are provided.
Page 12 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
Page 13 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
Page 14 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
16.6. The potential link shall not be provided outside on meter terminal block.
Internal solid link having adequate capacity shall be provided.
16.7. All parts of each terminal shall be such that the risk of corrosion resulting
from contact with any other metal part is minimized.
16.8. The terminals shall be marked properly on the terminal block for giving
external connections.
16.9. Detailed drawings of the terminal block shall be provided along with Meter.
17. TERMINAL COVER
17.1. The terminal cover shall be made of transparent engineering polycarbonate.
17.2. The terminal cover and meter base shall be extended such that when the
terminal cover is placed in position, it is not possible to approach the
connections or connecting wires.
17.3. Suitable cut-outs to be provided for cable entry.
17.4. The following shall be marked on the terminal cover
17.4.1. Manufacturer’s name or Logo
17.4.2. Connection diagram
17.5. The marking shall be indelible, distinct & readable from outside the meter.
17.6. Detailed drawings of the terminal cover and sealing arrangement on the
meter shall be provided.
17.7. The terminal cover shall be separate from the meter body and shall be of
removable type for ease of installation/maintenance.
18. SEALING ARRANGEMENT
18.1. The meter cover shall not be removable without breaking the same& leaving
the significant evidence. In case of opening of the cover, necessary indication
is required to be appeared on the display. The meter cover shall have at least
two sealing arrangements on either side, each having two sealing holes for
applying polycarbonate seals. If sealing screws are provided, the same shall
be made of brass and capable of being tightened from the rear.
18.2. Separate sealing arrangements shall be provided for terminal cover and
communication port.
18.3. The sealing arrangement on meter shall be suitable for application of
polycarbonate seals as well as hologram seals. Adequate plain surface shall
be made available on the sides of the meter to facilitate application of
hologram seals.
Page 15 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
18.4. The manufacturer shall provide one polycarbonate seal on Meter. The seal
shall be applied on the left side of the meter.
18.5. The manufacture shall provide one hologram / stick seal on meter. The seal
shall be applied on the right side of the meter.
19. NAMEPLATE AND MARKING
19.1. Meter shall have a nameplate clearly visible and effectively secured against
removal, indelibly and distinctly marked with all essential particulars as per
relevant standards.
19.2. The rating plate of the meter shall have distinct background color.
19.3. The marking on every meter shall be in accordance with IS: 14697:1999. In
addition to the standard, following shall be marked on the nameplate.
19.3.1. Manufacturer's name and place of manufacture
19.3.2. Meter type
19.3.3. Number of phases and wires
19.3.4. Alphanumeric serial number ( It shall have letter height of
minimum 5mm)
19.3.5. Bar code (Code 128/ Type 3 of 9) of the serial number
19.3.6. BIS mark
19.3.7. Month and Year of manufacture
19.3.8. Reference voltage & frequency
19.3.9. Principal unit in which the meter reads (kWh, kVArh, kVAh)
19.3.10. Rated Current (Basic current & Maximum current)
19.3.11. Meter constant (Imp/kWh, Imp/kVArh & Imp/kVAh)
19.3.12. Accuracy Class of the meter
19.3.13. Symbol of Ultrasonic Welding
19.3.14. Sign of Double square for Insulation encased meter
19.4. The marking shall be indelible, distinct & readable from outside the meter.
20. CONNECTION DIAGRAM
20.1. Meter shall be indelibly marked with connection diagram showing the
phase/neutral sequence for which it is intended and shall be attached to the
inner side of the extended terminal block cover.
20.2. In case of any special precautions need to be taken at the time of testing the
meter, the same may be indicated along with the circuit diagram.
Page 16 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
20.3. Drawings of the connection diagram shall be furnished along with the meter.
21. MEASUREMENT OF ENERGY
21.1. The meter shall be capable of measuring total energy consisting of
fundamental energy and harmonic energy. Total displayed energy shall be
including of harmonic energy i.e. Total Energy (Active, reactive or Apparent)
= Fundamental Energy + Harmonic Energy
21.2. The details as to how harmonic energy is to be measured shall be provided.
21.3. KVAh calculation should be the vector sum of kWh, kVArh (Lag) and kVArh
(Lead)
22. MAXIMUM DEMAND REGISTRATION
22.1. The metering module shall continuously monitor and calculate the average
demand in kW and kVA during the integration period set and the maximum,
out of these shall be stored along with date and time of occurrence in the
meter memory.
22.2. The rising demand under the current integration period shall be displayed
along with the elapsed time.
22.3. The meter shall memorize maximum demand data (together with date and
time of occurrence) for last 12 months on FIFO basis.
22.4. The integration period shall be 30 minutes.
22.5. MD Reset:
The meter shall have any and combinations of the following MD resetting
options. It shall not be possible, in any case, to reset MD through push button.
However if required specifically, it should enable MD reset through Auto and
Manual both. Auto MD reset should be programmable for flexible date and time
and Default reset mode should be manual.
Page 18 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
In addition, the BCS shall also display the following parameters in load survey
• Active Demand (kW)
• Apparent Demand (kVA)
• Reactive Demand – Lag (kVAr)
• Reactive Demand – Lead (kVAr)
• Power Factor
c) Following Daily energy/ data at midnight cross-over shall be recorded (cumulative
values) for 90 days
• C-kWh
• C-kVAh
• C-kVArh-Lag
• C-kVArh-Lead
d) Data logging should be on first in first out basis.
e) It should be possible to transfer this data on computer and to a hand held Meter
Reading Instrument / Data Collection Device.
25. QUANTITIES TO BE DISPLAYED
25.1. The meter shall be capable of measuring and displaying the electrical
quantities mentioned in Annexure – A within specified accuracy limits for all
loads and power factors.
25.2. It shall be possible to configure the display sequence either in auto-scroll
mode or manual push button mode.
25.3. The meter shall have facility for a manual mode where the parameters can be
read by push button operation. The manual display shall switch over to auto-
display mode automatically after 30 idle minutes.
25.4. It shall be possible to lock / freeze the display of any parameter by long
pressing of the pushbutton for monitoring the parameter.
25.5. It shall be possible to unlock the parameter by long pressing of the
pushbutton.
26. TAMPER AND FRAUD PROTECTION
The meter shall have the following special features to prevent / to detect tampering
of metering system:
26.1. The meter shall not get affected by the action of any remote control devices
including injection of high frequency voltage surges / spikes. Meter shall log
event with snap shot of parameters when meter accuracy or component’s
function get affected by such tampering attempts.
Page 19 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
26.2. The meter shall record at rated voltage, unity power factor and Imax under the
influence of external AC/DC/ permanent magnetic field irrespective of actual
load. The meter shall run as per actual load once the external magnet is
removed. Persistence time for magnetic tamper logging shall be 10 seconds.
Event shall be logged with snap shot. Meter shall record energy in main
register as well as in defraud register. Defraud resister shall be available in
BCS and meter display.
26.3. The meter shall record an event when average kW or kVA drawn by the
consumer during an Integration period is more than the specified threshold
value of kW and kVA. The event shall be supported by date & time and
average load for that integration period.
26.4. The meter shall be capable of recording & displaying tamper information
along with the date and time of all tamper occurrence and restoration
including initial & final tamper for the following:
26.4.1. Phase wise voltage failure
26.4.2. Voltage unbalance
26.4.3. CT Short/ Bypass
26.4.4. Phase wise CT Open
26.4.5. Current Unbalance
26.4.6. Phase wise Current reversal
26.4.7. Over load
26.4.8. Magnet tamper
26.4.9. Neutral Disturbance
26.4.10. HV / HF (ESD)
26.4.11. Power-Off
26.5. The meter shall work accurately irrespective of phase sequence of the mains
supply.
26.6. The meter shall remain powered up and functional in presence of any two
wires.
26.7. The meter shall continue to record accurately even if the neutral of supply
gets disconnected.
26.8. The meter shall record correct energy in forward direction in case of current
reversal of one or more phases.
Page 20 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
Page 21 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
27.2. The meter shall be capable to protect against the action of any remote control
devices including injection of high frequency, high voltage surges / spikes,
Electro Static Discharge more than 35 KV & HF up to 10 GHz
27.3. The meter shall be capable of protecting and archiving all the data in case of
any tamper which affects the memory, power supply units, microcontroller,
RTC etc.
27.4. The meter shall be designed in such a way that conducted or radiated
electromagnetic disturbance as well as electrostatic discharge do not damage
or substantially influence the meter and its performance. The disturbance to
be considered are:-
27.4.1. Harmonics
27.4.2. Voltage dips and short interruptions
27.4.3. Conducted transients
27.4.4. DC and AC magnetic fields
27.4.5. Electromagnetic fields
27.4.6. Electrostatic discharges
27.4.7. High voltage/ High Frequency sparks
27.5. The performance of meter should be as per IS: 14697, IEC: 62053-21 and
CBIP technical report No. 325 and latest version thereof.
27.6. The meter shall not generate noise, which could interfere with other
equipment.
28. SELF-DIAGNOSTIC FEATURES
28.1. Indications to show the satisfactory performance of the meter shall be
provided in the meter. The meter shall have capability to check its circuits for
any malfunctioning. There should be a defined diagnostic cycle, for instance
every one hour, and if some malfunctioning occurs, the meter may display
the malfunctioning of the meter.
28.2. The meter shall have internal diagnosis feature to monitor micro control
functions to ensure correct operation of demand interval time by quartz
crystal timer.
28.3. Minimum features of internal diagnosis to be provided are Time, calendar,
RTC, RTC battery and NVM.
28.4. The meter shall also have self diagnostic feature to detect any increment in
energy registers on no-load.
Page 22 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
29. SOFTWARE
29.1. The following software shall be supplied along with the Meter
29.1.1. Software for downloading data from meter through meter
reading instrument / computer/ AMR (PSTN/ GSM / GPRS/
CDMA).
29.1.2. Exclusive software for changing date of monthly MD reset
29.1.3. Exclusive software for changing the display sequence
29.1.4. Exclusive software for changing Integration period for max
demand
29.1.5. Exclusive Software module for changing TOD / seasonal tariff
timings.
29.1.6. Exclusive Software module for resetting tamper data and
tamper counts
29.1.7. Software module for adjustment of real time of the meter
through meter reading instrument with proper password
protection.
29.1.8. Base Computer Software for accepting data from MRI and
uploading instructions from base computer to MRI.
29.1.8.1. The BCS shall give complete details of the Energy and
demand pattern both in numeric data form and in
graphic form.
29.1.8.2. Energy and Demand data shall be displayed starting
from 0000 to 2400 hours on daily basis in graphic
form. Graphic software shall be capable of displaying
different quantities in cumulative form and in any
combination as per requirement. Graphic software shall
be capable of displaying data in monthly, weekly and
daily combinations.
29.1.8.3. BCS shall have facility to export data to ASCII and
Spreadsheet compatible format.
29.1.9. Necessary software for loading application program via serial
port/ Universal serial port.
29.1.10. Analysis software for data downloaded from meter. The
software should provide necessary facility to export data to
Microsoft Excel.
Page 23 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
Page 24 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
31.1.2.4. Test of no load condition
Page 25 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
Page 26 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
Page 27 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
32.2. The supplier should have the necessary minimum testing facilities for
carrying out the following tests
32.2.1. A.C. High Voltage test
32.2.2. Insulation Resistance
32.2.3. Test on limits of errors
32.2.4. Test on meter constant
32.2.5. Test of starting condition
32.2.6. Test of no-load condition
32.2.7. Repeatability of error test
32.2.8. Test of power consumption
32.2.9. Vibration test
32.2.10. Shock test
32.2.11. Tamper conditions as per the specification.
32.3. The manufacturer should have duly calibrated Standard meter of Class 0.05
or better accuracy.
33. TEST CERTIFICATES:
33.1. The meter shall be fully type tested as per relevant standards IS: 14697 and
CBIP report No. 325. The type test reports (not older than 2 years) of the
meter shall be submitted along with the meter.
33.2. The type test report for 10kV surge immunity test 1.2 / 50 micro second in
case of open circuit voltage and 8/20 micro second in case of short circuit
current as per IEC: 1000-4-5 Standard ,shall be submitted.
33.3. The test reports for tamper resistance features as stated in the specification.
33.4. The test report for immunity of meter against external AC/DC/ permanent
magnet, EMF of minimum 0.5 Tesla and High Voltage Spark discharge to be
provided.
33.5. Routine test reports in hard and soft copy shall be submitted along with the
meter.
34. INFORMATION TO BE SUBMITTED WITH THE METER
The following shall be furnished with the meter:
34.1. Catalogues describing the equipment and indicating the type and model
number
34.2. Constructional features, materials used and relevant technical literature
Page 28 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
Page 29 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
Page 30 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
b. Manual Display
xxxiv. Segment check
xxxv. Meter serial no.
xxxvi. Real Date
xxxvii. Real Time
xxxviii. Rising Demand with Elapsed Time (Apparent) in kVA (4+2 digits)
xxxix. Reset MD count
xl. Cumulative fundamental active Energy (kWh) (7+0 digits)
xli. Cumulative reactive Energy (kVArh) Lead while Active Import (7+0
digits)
xlii. Cumulative reactive Energy (kVArh) Lag while Active Import (7+0
digits)
Page 31 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
Page 32 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
Page 33 of 31
Technical Specification for Three Phase 4 Wire 100/5 A Class 0.5s LT CT Operated Static Energy Meter
TOU Zone-3 18:00 Hrs to 22:00 Hrs 18:00 Hrs to 22:00 Hrs
TOU Zone April to October November to March
TOU Zone-4 22:00 Hrs to 06:00 Hrs 22:00 Hrs to 06:00 Hrs
TOU Zone-5 06:00 Hrs to 07:00 Hrs 06:00 Hrs to 07:00 Hrs
TOU Zone-6 - -
TOU Zone-7 - -
TOU Zone-8 - -
d. Tariff: Lag only