Basi Calculation For Pump Tank Selection
Basi Calculation For Pump Tank Selection
Basi Calculation For Pump Tank Selection
Fire hose reel TANK STORAGE CAPACITY (for Ordinary Hazard Area)
Pressure loss in pipe/fittings etc = 0.5 bar (assumed, larger length of pipe needs more pressure)
Safety = 0.5 bar
Pressure loss in pipe/fittings etc = 1.5 bar (assumed, larger length of pipe needs more pressure)
Safety = 0.5 bar
3) SPRINKLER SYSETM
4) WET RISER
Pressure loss in pipe/fittings etc = 1.5 bar (assumed, larger length of pipe needs more pressure)
Safety = 0.5 bar
NOTE:-
1) ESFR - Early Suppression Fast Response Sprinkler (or) combination of standard sprinklers for overhead and in-racks
2) If rack sprinklers are provided, then the flow rate and number of sprinklers will vary
The following are the design considered based on ROP standard Part-IV
Pressure loss in pipe/fittings etc = 0.5 bar (assumed, larger length of pipe needs more pressure)
Safety = 0.5 bar
Pressure loss in pipe/fittings etc = 1.5 bar (assumed, larger length of pipe needs more pressure)
Safety = 0.5 bar
NOTE:-
1) ESFR - Early Suppression Fast Response Sprinkler (or) combination of standard sprinklers for overhead and in-ra
2) If rack sprinklers are provided, then the flow rate and number of sprinklers will vary
d) WET RISER
Accordance with NFPA 13.
Wet Riser(Landing Valve) Flow rate = 250 gpm
Max No of WR in operation at any time = 1 No
Pump flow rate required = 1 x 250 gpm = 250 gpm
Fire hose reel pump Head calculation
Residual Pressure required at WR = 4.5 Bar
Pressure loss in pipe/fittings etc = 1.5 bar (assumed, larger length of pipe needs more pressure)
Safety = 0.5 bar
The system is designed as NFPA standard 750, in ordinary Hazard -II(area of operation - 144Sq.meter)
Number of nozzles to protect the area of 144 sq.mtr: 12nos of Nozzle will be operate.
Nozzle Flow rate = 28.8 Lpm
Max No of Nozzle in operation at any time = 12 Nos
pump capacity = 3x120L/min at 120 bar pressure +standby 1x120 L.min at 120bar
Fire hose reel TANK STORAGE CAPACITY (for Ordinary Hazard Area)
c) SPRINKLER SYSETM
d) WET RISER
Water Tank for 316 lpm with 90 minutes operation = 360 x 90 minute = 28000 litre effective
e) Table
FHR 34 M3
FH 170 M3
SPRINKLER 77 M3
LANDING VALVE 85 M3
WATER MIST SYSTEM 28 M3
TOTAL 394 M3
34 m3
170 m3
20250 gallons
76646 litres
77 m3
85163 litres
85 m3
28 m3
PUMP POWER
= 69750
2772
= 25.16
= 140800
2772
= 50.79
= 38
95.11
95 GPM * 192 * 1
3960 * 0.7
= 18240
2772
= 6.58
= 4935
= 5
3) SUMP PUMP
15 GPM * 200 * 1
3960 * 0.7
= 3000
2772
= 1.08
= 812
= 0.812
D (Feet) * SP GRAVITY SP GRAVITY = SPECIFIC GRAVITY OF LIQUI
P EFFICIENCY NORMAL WATER = 1
hp
Watts
kW
110 meter
352 feet
hp
Watts
kW
6 l/s
gallons / min
60 meter
192 feet
hp
Watts
kW
200 feet
hp
Watts
kW
PECIFIC GRAVITY OF LIQUID
ORMAL WATER = 1
Each pump can discharge 120 lpm @ 120 bar pressure
Hence no. of pump required = 316.8/120 = 2.6 ~ 3 nos.
Each Motor Drive 1 pump, hence we choose main 3x120 L/min + stand by 1x120 L/min. Total
pump capacity on duty of 360 lpm @ 120 bar + 120 lpm @ 120 bar stand by, utilizing 4 nos. Of
30 kW electric driven motor.
Water Tank for 360 lpm with 30 minutes operation = 360 x 30 minute = 10800 litre effective
water capacity, therefore water tank capacity with 20% allowance which is of 12960 litre shall
be the minimum water capacity.
ng 4 nos. Of
WET RISER
PUMP POWER
= 69750
2772
= 25.16 hp
85163 litres
85 m3
170325 litres
170 m3
255 m3
BASIC CALCULATION FOR PUMP & TANK SELECTION
Fire hose reel TANK STORAGE CAPACITY (for Ordinary Hazard Area)
Pressure loss in pipe/fittings etc = 0.5 bar (assumed, larger length of pipe needs more pressure)
Safety = 0.5 bar
Pressure loss in pipe/fittings etc = 1.5 bar (assumed, larger length of pipe needs more pressure)
Safety = 0.5 bar
4) WET RISER
Pressure loss in pipe/fittings etc = 1.5 bar (assumed, larger length of pipe needs more pressure)
Safety = 0.5 bar
NOTE:-
1) ESFR - Early Suppression Fast Response Sprinkler (or) combination of standard sprinklers for overhead and in-racks
2) If rack sprinklers are provided, then the flow rate and number of sprinklers will vary
The following are the design considered based on ROP standard Part-IV
Pressure loss in pipe/fittings etc = 0.5 bar (assumed, larger length of pipe needs more pressure)
Safety = 0.5 bar
Pressure loss in pipe/fittings etc = 1.5 bar (assumed, larger length of pipe needs more pressure)
Safety = 0.5 bar
e) Table
ore pressure)
3960 * 0.7
= 60450
2772
= 25.16 hp