3tf Contactor
3tf Contactor
3tf Contactor
Description
3TF Series AC Contactors are latest products of Siemens AG in 1990’s. The series products are suitable for frequency of 50/60Hz, rated
insulation voltage up to 690 ~ 1000V, rated operational current up to 9A ~ 400A at rated operational voltage up to 380V under the utilization
category AC - 3. 3TF Series AC Contactors are mainly used for making/breaking electric circuits at a long distance and for frequent starting/
stopping and reversing control of AC motors.They comply with IEC947, VDE0660, GB14048.
Operating Conditions
The altitude of the site of installation does not exceed 2000 meters above sea levels.
The ambient air temperature: -25 ~ +55°C
2
Relative humidity does not exceed 50% at +40¼C and 90% at +25°C
Atmospheric conditions: the air does not contain any explosive medium, corrosive gases and conductive dust.
Never be shocked and vibrated obviously.
Never be wetted by rain and snow.
Features
For better safety, conductive part are enclosed.
Small sizes, light weight, material of arc chute adopts unsaturated resin, with good arc resistance, never splitting.
The arc chute is enclosed , arc-over distance is small, with a compact electric cabinet.
Construction of main contacts system is unique, abrasion of the contacts is small, with a long electric endurance.
The operation of the magnet has many advantages such as good reliability, little consumption, low noise and high mechanical strength.
The contactors have higher operation frequency and control capacity.
Auxiliary contact block may be attached to 3TF30 ~ 50 Series AC Contactors.
SIGUT - Siemens patent terminal, ensures easy and reliable connection, strog shock resistance and perfect safety protection.
2/1
3TF AC Contactors
AC operation
Auxiliary contacts
NO NC
NO - NC NO - NC NO - NC NO - NC
3TF40 10 - 0X 1 - 3TF41 10 - 0X 1 -
Order No. 3TF30 00 - 0X - - 3TF40 01 - 0X - 1 3TF31 00 - 0X - - 3TF41 01 - 0X - 1
3TF30 10 - 0X 1 - 3TF40 11 - 0X 1 1 3TF31 10 - 0X 1 - 3TF41 11 - 0X 1 1
3TF30 01 - 0X - 1 3TF40 22 - 0X 2 2 3TF31 01 - 0X - 1 3TF41 22 - 0X 2 2
3TF40 20 - 0X 2 - 3TF41 20 - 0X 2 -
3TF40 31 - 0X 3 1 3TF41 31 - 0X 3 1
Rated insulation voltage (V) 690 690 690 690
Rated operational current (380V) AC - 3 9 9 12 12
AC - 4 3.3 3.3 4.3 4.3
230/220V 2.4 2.4 3.3 3.3
Rated outputs of
400/380V 4 4 5.5 5.5
three-phase motors
AC - 3 500 V 5.5 5.5 7.5 7.5
at 50Hz (KW)
690/660V 5.5 5.5 7.5 7.5
1000 V -- -- -- --
400/380V 1.48/1.4 1.48/1.4 2/1.9 2/1.9
AC - 4
690/660V 2.54/2.4 2.54/2.4 3.45/3.3 3.45/3.3
Mechanical endurance (x106) 15 15 15 15
Electrical endurance (x106) AC - 3 1.2 1.2 1.2 1.2
AC - 4 0.2 0.2 0.2 0.2
Switching frequency (1/h) AC - 3 1000 1000 1000 1000
AC - 4 250 250 250 250
Coil voltage tolerance (AC) (0.8~1.1)Us
Order No. suffixes for rated Coils for 50Hz Coils for 60Hz Coils for 50/60Hz
control voltages for coils 50Hz 60Hz 60Hz 50Hz
24V 29V B0 24V 20V C1 24V C2
32V 38V C0 110V 92V G1 42V D2
36V 42V G0 115V 96V J1 110V G2
3TF3 -0X 42V 50V D0 120V 100V K1 115V J2
3TF4 -0X 48V 58V H0 208V 173V M1 120V K2
60V 72V E0 220V 183V N1 208V M2
110V 132V F0 230V 192V L1 220V N2
125/127V 150/152V L0 240V 200V P1 230V L2
220V 264V M0 440V 367V R1 240V P2
230V 277V P0 575V 480V S1 440V R2
240V 288V U0 575V S2
380V 460V Q0
400V 480V V0
415V 500V R0
500V 600V S0
Closed (VA) 10 10 10 10
p.f. 0.29 0.29 0.29 0.29
Power consumption
of coil (50Hz) Closed (VA) 68 68 68 68
p.f. 0.82 0.82 0.82 0.82
Conventional thermal current (A) 20 20 20 20
Conventional thermal current of auxiliary contacts 10 10 10 10
Rated insulation voltage of auxiliary contacts 690 690 690 690
Rated operational current of AC - 15
6/10 6/10 6/10 6/10
auxiliary contacts (A) 380/220V
DC - 13 0.9/0.45 0.9/0.45 0.9/0.45 0.9/0.45
110/220V
Weight (kg) 0.37 0.43 0.37 0.43
Note: 3TX4 auxiliary contact blocks for 3TF3 series, see P2/16.
2/2
3TF AC Contactors
AC operation
Auxiliary contacts
2
NO NC
NO - NC NO - NC NO - NC NO - NC
3TF42 10 - 0X 1 - 3TF43 10 - 0X 1 -
Order No. 3TF32 00 - 0X - - 3TF42 11 - 0X 1 1 3TF33 00 - 0X - - 3TF43 11 - 0X 1 1
3TF32 11 - 0X 1 1 3TF42 20 - 0X 2 - 3TF33 11 - 0X 1 1 3TF43 20 - 0X 2 -
3TF42 22 - 0X 2 2 3TF43 22 - 0X 2 2
Note: 3TX4 auxiliary contact blocks for 3TF3 series, see P2/16
2/3
3TF AC Contactors
AC operation
Auxiliary contacts
NO NC
NO - NC NO - NC NO - NC NO - NC
Note: 3TX4 auxiliary contact blocks for 3TF3 series, see P2/16.
2/4
3TF AC Contactors
AC operation
Auxiliary contacts
2
NO NC
NO - NC NO - NC NO - NC NO - NC
2/5
3TF AC Contactors
AC operation
Auxiliary contacts
NO NC
NO - NC NO - NC NO - NC NO - NC
2/6
3TF AC Contactors
AC operation
Auxiliary contacts
2
NO NC
NO - NC NO - NC NO - NC
2/7
3TF AC Contactors
DC operation
Auxiliary contacts
NO NC
NO - NC NO - NC NO - NC NO - NC
3TF40 10 - 1X 1 - 3TF41 10 - 1X 1 -
Order No. 3TF30 00 - 1X - - 3TF40 01 - 1X - 1 3TF31 00 - 1X - - 3TF41 01 - 1X - 1
3TF30 10 - 1X 1 - 3TF40 11 - 1X 1 1 3TF31 10 - 1X 1 - 3TF41 11 - 1X 1 1
3TF30 01 - 1X - 1 3TF40 20 - 1X 2 - 3TF31 01 - 1X - 1 3TF41 20 - 1X 2 -
3TF40 22 - 1X 2 2 3TF41 22 - 1X 2 2
3TF40 31 - 1X 3 1 3TF41 31 - 1X 3 1
Rated insulation voltage (V) 690 690 690 690
3TF3 -1X
3TF4 -1X Order No. suffix A4 U4 B4 C4 V4 D4 W4 E4 F4 G4 K4 M4 P4 Q4 N4
Note: 3TX4 auxiliary contact blocks for 3TF3 series, see P2/16.
2/8
3TF AC Contactors
DC operation
Auxiliary contacts
2
NO NC
NO - NC NO - NC NO - NC NO - NC
3TF42 10 - 1X 1 - 3TF43 10 - 1X 1 -
Order No. 3TF32 00 - 1X - - 3TF42 11 - 1X 1 1 3TF33 00 - 1X - - 3TF43 11 - 1X 1 1
3TF32 11 - 1X 1 1 3TF42 20 - 1X 2 - 3TF33 11 - 1X 1 1 3TF43 20 - 1X 2 -
3TF42 22 - 1X 2 2 3TF43 22 - 1X 2 2
Note: 3TX4 auxiliary contact blocks for 3TF3 series, see P2/16.
2/9
3TF AC Contactors
DC operation
Auxiliary contacts
NO NC
NO - NC NO - NC NO - NC NO - NC
Note: 3TX4 auxiliary contact blocks for 3TF3 series, see P2/16.
2/10
3TF AC Contactors
DC operation
Auxiliary contacts
2
NO NC
NO - NC NO - NC NO - NC NO - NC
2/11
3TF AC Contactors
DC operation
Auxiliary contacts
NO NC
NO - NC NO - NC NO - NC NO - NC
Note: The changeover contactor of 3TF52 3TF56 DC operation contactors is included in the delivery and contained in the contactor package.
2/12
3TF AC Contactors
DC operation
Auxiliary contacts
2
NO NC
NO - NC NO - NC NO - NC
Note: The changeover contactor of 3TF52 3TF56 DC operation contactors is included in the delivery and contained in the contactor package.
2/13
3TB AC Contactors
AC operation
Auxiliary contacts
NO NC
NO - NC NO - NC NO - NC NO - NC NO - NC
3TB40 10 - 0X 1 - 3TB41 10 - 0X 1 -
Order No. 3TB40 01 - 0X - 1 3TB41 01 - 0X - 1
3TB40 22 - 0X 2 2 3TB41 22 - 0X 2 2 3TB42 22 - 0X 2 2 3TB43 22 - 0X 2 2 3TB44 22 - 0X 2 2
Rated insulation voltage (V) 660 660 660 660 660
110 F0 110 G2
3TB44 -0X 220 M0 220 N2
240 U0 240 P2
380 Q0
Closed (VA) 10 10 10 10 10
Power consumption
of coil (50Hz) p.f. 0.29 0.29 0.29 0.29 0.29
Closing (VA) 68 68 68 68 69
p.f. 0.82 0.82 0.82 0.82 0.86
2/14
3TF AC Contactors
Spare Parts
Type Contactor size Contacts No Order No Illustration Weight
NO NC kg
3TF44 - 3TF56 1
1
1
1
3TY7 561 - 1AA00
3TF30 - 3TF33 3TY7 403 - 0X.. Double coil from 3TF48 0.07
3TF40 - 3TF43
3TH3 - 3TH4
3TF30 - 3TF35
3TH3
3TX40.. - ..
3TF44 3TY74 40 - 0X Three pieces of contact bridge 0.1
3TF45 3TY74 50 - 0X and six pieces of contacts
consists of one sets
3TF46 3TY74 60 - 0X 0.1
3TF47 3TY74 70 - 0X
2/15
3TF AC Contactors
Technical data
Contactor type
2/16
3TF AC Contactors
Technical data
Contactor type
2
230V
500V
400V
690V
4 7.5 15 22 37 PN(KW)
5.5 11 18.5 30 45
Contactor type
3TF56
3TF57
a
Breaking current PN Rated output of three-phase motors
e
Rated operational current with squirrel-cage (at 400V)
2/17
3TF/3TB AC Contactors
DC circuit diagrams
3TF46-3TF51 3TF52-3TF56
DC economy circuit DC economy circuit
with changeover contactor:
3TF52 3TF55 : 3TF40
3TF56 : 3TF42
Technical data
Contact endurance of the main contacts (AC-3):
Contactor type
Make - break operations
Dimension drawings
Type a b c d e f g
3TB40, 3TB41 79 60 46 35 *90 7.5 ∅5
106
3TB42, 3TB43 89 75 46 35 116 8 ∅5
3TB44 90 75 74 50 109 8 ∅5
3TB40-3TB43 3TB44
2/18
3TF AC Contactors
Dimension drawings
(143)1 (155)1
(112)1 (124)1
1)
2)
1)
2) 2
3TF30 and 3TF31, size 0 3TF32 and 3TF33, size 1
Auxiliary contact block with position indicator Without and with overload relay (3UA52 or 3UW13)
Labelling plate
(173)1
(149)1 3TF34 and 3TF35, size 2
1)
1) (149)1
2)
(140)1
2) 2)
1) 1)
3TF40 and 3TF41, size 0 3TF42 and 3TF43, size 1 3TF44 and 3TF45, size 2
With and without 3UA50 or 3UW10 With and without 3UA52 or 3UW13 With and without 3UA55
overload relay overload relay overload relay
2/19
3TF AC Contactors
Dimension drawings
(185)1
1)
2)
Without and with 3UA62 overload relay With and without 3UA58 overload relay
3 3TF46, 3TF47 90 113 70 117 175 100 123 123 8 26.5 25 94 34 80 63 122 28 4.8 6.1(M6)
4 3TF48 100 123 80 133 194 110 140 140 8 26.5 25 107 36 89 63 122 39 5.5 6.1(M6)
4 3TF49 100 123 80 133 194 110 140 140 10.5 26.5 25 116 31.5 89 63 122 39 5.5 6.1(M6)
1)
*
With and without overload relay
3UA60 (with box terminals) for 3TF50
3UA61 (with box terminals) for 3TF51
Type h j
3UA60 37 M6
3UA61 42 M8
2)
,
3TF50 and 3TF51, size 6 (box terminal with 3TF50) * 3TF51 hasn t box terminals, Accessories
3TF50 120 143 100 150 232 130 150 150 15 37 37 130 213 40 93 80 146 45 6.3 6.1(M6)
3TF51 120 143 100 150 232 130 150 150 20 42 37 139 215.5 40.5 93 80 146 45 6.3 9(M8)
( )1 DC operation
2/20
3TF AC Contactors
Dimension drawings
++++
++++
2/21
3TD Reversing Contactor Combinations
Description
3TD Reversing Contactor Combinations are suitable for frequency of 50/60Hz, rated insulation voltage up to 690 ~ 1000V, rated operational
current 9A ~ 400A at rated operational voltage 380V under AC - 3. They are mainly used for controlling the forward and reverse rotation. They
comply with IEC947, VDE0660, GB14048.
Operating Conditions
The altitude of the site of installation does not exceed 2000 meters above sea levels.
The ambient air temperature: -25 ~ +55°C
Relative humidity does not exceed 50% at +40°C and 90% at +25°C
Atmospheric conditions: the air does not contain any explosive medium, corrosive gases and conductive dust.
Never be shocked and vibrated obviously.
Never be wetted by rain and snow.
Features
It is a Combinations consisting of two same type sets of 3TF AC contactors, between which one is interlocked by another through a
mechanical device.
The mechanical interlocking device does not affect the acting time of a single set of AC contactors.
The conducting wires of the main circuit and auxiliary circuit have been connected. (The products without connection can also be suplied.)
Compact in size, reliable in interlocking.
The overload relays 3UA can be mounting directly on the 3TD (up to 3TD42).
3TD 0 -0X
Code of specification
2/22
3TD Reversing Contactor Combinations
Order No.
Auxi.
contact
no. per
Rated
operational
current e
Rated outputs of three-phase motors
AC-3
Overload
Relay
Type
Fuses
Condination
type
2
contactor
at AC-3, 230/ 400/ 500V 690/ 1000V
400/380V 220V 380V 660V “1” “2”
NO NC A KW KW KW KW KW A A
3TD40 02 - 0X .. 2 2
3TD40 02 - 0X .. - Z1 2 2
9 2.4 4 5.5 5.5 - 35 25
3TD40 01 - 0X .. - Z1 1 1
3TD40 00 - 0X .. - Z1 - 1
3UA50
3TD41 02 - 0X .. 2 2
3TD41 02 - 0X .. - Z1 2 2
12 3.3 5.5 7.5 7.5 - 35 25
3TD41 01 - 0X .. - Z1 1 1
3TD41 00 - 0X .. - Z1 - 1
3TD42 02 - 0X .. 2 2
16 4 7.5 9 11 - 65 35
3TD42 02 - 0X .. - Z1 2 2
3UA52
3TD43 02 - 0X .. 2 2
22 5.5 11 11 11 - 65 35
3TD43 02 - 0X .. - Z1 2 2
3TD44 02 - 0X .. 2 2
3TD44 02 - 0X .. - Z1 2 2 32 8.5 15 21 23 - 80 63
3UA55
3TD45 02 - 0X .. 2 2
38 11 18.5 25 23 - 80 63
3TD45 02 - 0X .. - Z1 2 2
3TD46 02 - 0X .. 2 2 45 15 22 30 39 - 160 100
3TD47 02 - 0X .. 2 2 63 18.5 30 41 55 - 3UA58 160 125
3TD48 02 - 0X .. 2 2 75 22 37 50 67 39 250 160
3TD50 02 - 0X .. 2 2 110 37 55 76 100 55 3UA60 315 250
3TD52 02 - 0X .. 2 2 170 55 90 118 156 90 3AU62 355 250
3TD54 02 - 0X .. 2 2 250 78 132 178 235 132 500 315
3UA66
3TD56 02 - 0X .. 2 2 400 125 200 284 375 150 800 500
1) The coil for AC 50/60 Hz for 3TD40 to 3TD50 contactor combinations should be used only if it is ensured that between the signal output
for both directions of rotation minimum dead interval on reversing of 50ms exists.
2) Selection of the fuses in the above table is in accordance with excerpt from IEC947 - 4.
Type of co-ordination “1”:
Destruction of contactor and overload relay is admissible. Contactor and/or overload relay must be replaced, if necessary.
Type of co-ordination “2”:
No damage can be tolerated on the overload relay, but contact welding on the contactor is permitted, if the contacts can easily be
separated.
2/23
3TD Reversing Contactor Combinations
1.a) 1.b) 1.c) 1.d) 1.e) 1.f) 1.g) 1.h) 1.i) 2.a) 2.b) 2.c) 2.d) 2.e)
mm2 mm2 mm2 mm2 mm2 mm Nm/Ib.in AWG mm2 mm2 Nm/Ibin AWG
3TD40 1~2.5
0.75~2.5 - - 10 M3.5 0.8~1, 4/7~12 18~12 0.5~2.5 0.75~2.5 M3.5 0.8~1, 4/7~12 18~14
3TD41 1 4
3TD42
2.5~6 1.5~4 - - - 12 M4 1~1.5/9~13 14~10 0.5~2.5 0.75~2.5 M3.5 0.8~1, 4/7~12 18~14
3TD43
3TD44
2.5~25 2.5~16 - - 10 M5 2.5~3/22~26.5 14~6
3TD45
3TD46
3TD47 6~35 4~25 - - - 16+3 - 3~4
3TD48
3TD50 25~70 25~50 - - - 22+3 - 4~5
3TD52 - - 35~95 50~120 20 3 - M8 10~14
3TD54 - - 50~240 70~240 25 5 - M10 14~16.5
3TD56 - - 50~240 70~240 2 (25 5) - M10 14~16.5
Circuit diagrams
L1
Power circuit Control circuit for momentary- Control circuit for maintained-
contact control contact control
2/24
3TD Reversing Contactor Combinations
2
Dimension drawings
1. 3TD40, 3TD41 c=97mm/81mm 2. 3TD42, 3TD43 c=107mm
a1 a2 b1 b2 b4 c1 c2 d1 e g1
2/25