L011199 - PRONET-E Series Users Manual - V2.11
L011199 - PRONET-E Series Users Manual - V2.11
L011199 - PRONET-E Series Users Manual - V2.11
(Version:V2.11)
Revision History
1 Addition: ProNet-02A/04A
○
All chapters
2 Addition: Pn139 and Pn140
○
2010-11 V1.09
Revision: Pn102、Pn107、Pn139、Pn14、
Appendix A
2011-09 V1.22 Pn413、Pn414、Pn511
1 Revision: ProNet-7.5kW~15kW
○
appearance
Chapter 1 and 3
2012-03 V1.25 2 Addition: Resolver description
○
Appendix
3 Addition: Reserved some parameters
○
4 Addition: Pn301 and Pn415
○
ProNet-02A~04A/ ProNet-E-02A~04A
3.1.2
Add and revise note
ProNet-02A~04A/ ProNet-E-02A~04A
2013-1 V2.02 3.5.1
Add and revise note
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or
by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of ESTUN.
No patent liability is assumed with respect to the use of the information contained herein.
ProNet Series AC Servo User's Manual
This manual describes the following information required for designing and maintaining ProNet series servo drives.
•Communication protocols.
Intended Audience:
-1-
ProNet Series AC Servo User's Manual
Safety Precautions
■ Do not plug or unplug connectors from servo drive when power is on.
Failure to observe this may result in damage to servo drive and servomotor.
■Please note that even after power is removed, residual voltage still remains in the capacitor inside the servo drive. If
inspection is to be performed after power is removed, please wait 5 minutes to avoid risk of electrical shock.
The servo drive generates heat. Install the servo drive so that it can radiate heat freely. When installing servo drives
with other devices in a control panel, provide at least 10mm space between them and 50mm space above and below
them. Please install servo drives in an environment free from condensation, vibration and shock.
Please comply with the following instructions to avoid noise generated by signal lines.
3. Single point grounding is required for the servomotor and servo drive (grounding resistance 100Ω or below).
4. Never use a line filter for the power supply in the circuit.
■ Conduct a voltage resistance test for the servo drive under the following conditions:
3. Frequency:50/60Hz
4. Voltage applied point: Between L1, L2,L3 terminals and frame ground.
For a ground-fault interrupter, always use a fast-response type or one designed for PWM inverters. Do not use a
time-delay type.
Failure to observe this caution may result in injury or damage to the product due to unstable operation.
Frequently turning the power ON and OFF causes the internal circuit elements to deteriorate, resulting in unexpected
-2-
ProNet Series AC Servo User's Manual
—Contents—
Chapter 1 ........................................................................................................................................................................ - 7 -
Chapter 2 ...................................................................................................................................................................... - 23 -
Installation ..................................................................................................................................................................... - 23 -
2.1 Servomotor ..................................................................................................................................................... - 23 -
2.1.1 Storage ................................................................................................................................................ - 23 -
2.1.2 Installation Sites .................................................................................................................................. - 23 -
2.1.3 Installation Alignment ........................................................................................................................... - 24 -
2.1.4 Installation Orientation ......................................................................................................................... - 24 -
2.1.5 Handling Oil and Water ........................................................................................................................ - 24 -
2.1.6 Cable Tension ...................................................................................................................................... - 25 -
2.1.7 Install to the Client ............................................................................................................................... - 25 -
2.2 Servo Drive ..................................................................................................................................................... - 25 -
2.2.1 Storage ................................................................................................................................................ - 25 -
2.2.2 Installation Sites .................................................................................................................................. - 25 -
2.2.3 Installation Orientation ......................................................................................................................... - 26 -
2.2.4 Installation Method .............................................................................................................................. - 26 -
Chapter 3 ...................................................................................................................................................................... - 28 -
Wiring ............................................................................................................................................................................ - 28 -
3.1 Main Circuit Wiring .......................................................................................................................................... - 28 -
3.1.1 Names and Functions of Main Circuit Terminals .................................................................................. - 28 -
3.1.2 Typical Main Circuit Wiring Examples .................................................................................................. - 29 -
3.2 I/O Signals ...................................................................................................................................................... - 33 -
3.2.1 Examples of I/O Signal Connections ................................................................................................... - 33 -
3.2.2 I/O Signal Names and Functions ......................................................................................................... - 34 -
3.2.3 I/O Signal Connector (CN1) Terminal Layout ...................................................................................... - 36 -
3.2.4 Interface Circuit ................................................................................................................................... - 37 -
3.3 Wiring Encoders.............................................................................................................................................. - 38 -
3.3.1 Connecting an Encoder(CN2).............................................................................................................. - 38 -
3.3.2 Encoder Connector(CN2) Terminal Layout ......................................................................................... - 40 -
3.4 Communication Connection ............................................................................................................................ - 40 -
3.4.1 Communication Connector(CN3) Terminal Layout .............................................................................. - 40 -
3.4.2 Communication Connector(CN4) Terminal Layout .............................................................................. - 41 -
3.5 Standard Wiring Examples .............................................................................................................................. - 42 -
3.5.1 Single-phase 200V ProNet-02A~04A/ProNet-E-02A~04A ............................................................... - 42 -
-3-
ProNet Series AC Servo User's Manual
Chapter 4 ...................................................................................................................................................................... - 60 -
Operation ...................................................................................................................................................................... - 60 -
4.1 Trial Operation ................................................................................................................................................ - 60 -
4.1.1 Trial Operation for Servomotor Without Load ...................................................................................... - 63 -
4.1.2 Trial Operation for Servomotor without Load from Host Reference ..................................................... - 65 -
4.1.3 Trial Operation with the Servomotor Connected to the Machine.......................................................... - 69 -
4.1.4 Trial Operation for Servomotor with Brakes ......................................................................................... - 70 -
4.1.5 Position Control by Host Controller ...................................................................................................... - 70 -
4.2 Control Mode Selection................................................................................................................................... - 70 -
4.3 Setting Common Basic Functions ................................................................................................................... - 72 -
4.3.1 Setting the Servo ON Signal ................................................................................................................ - 72 -
4.3.2 Switching the Servomotor Rotation Direction ...................................................................................... - 73 -
4.3.3 Setting the Overtravel Limit Function ................................................................................................... - 74 -
4.3.4 Setting for Holding Brakes ................................................................................................................... - 77 -
4.3.5 Instantaneous Power Loss Settings..................................................................................................... - 80 -
4.4 Absolute Encoders .......................................................................................................................................... - 81 -
4.4.1 Selecting an Absolute Encoder ............................................................................................................ - 81 -
4.4.2 Handling Battery .................................................................................................................................. - 82 -
4.4.3 Replacing Battery ................................................................................................................................ - 83 -
4.4.4 Absolute Encoder Setup(Fn010、Fn011) ............................................................................................ - 83 -
4.5 Operating Using Speed Control with Analog Reference.................................................................................. - 84 -
4.5.1 Setting Parameters .............................................................................................................................. - 84 -
4.5.2 Setting Input Signals ............................................................................................................................ - 85 -
4.5.3 Adjusting Reference Offset .................................................................................................................. - 86 -
4.5.4 Soft Start .............................................................................................................................................. - 89 -
4.5.5 Speed Reference Filter Time Constant ................................................................................................ - 89 -
4.5.6 S-curve Risetime ................................................................................................................................. - 90 -
4.5.7 Using the Zero Clamp Function ........................................................................................................... - 90 -
4.5.8 Encoder Signal Output ........................................................................................................................ - 92 -
4.5.9 Speed coincidence output ................................................................................................................... - 93 -
4.6 Operating Using Position Control .................................................................................................................... - 94 -
-4-
ProNet Series AC Servo User's Manual
-5-
ProNet Series AC Servo User's Manual
-6-
ProNet Series AC Servo User's Manual
Chapter 1
1.1.1 Servomotor
EMJ– 08 A P B 1 1 -WR
ESTUN Servomotor
【1+2】 【3】 【4】 【5】 【6】 【7】 【8+9】
EMJ Model
【1+2】
【4】Encoder 【7】Option
Rated Output
Code Spec. Code Spec. Code Spec.
A5 0.05 kW D Incremental encoder :131072P/R 1 None
01 0.1 kW Incremental Wire-saving Type: 2 With oil seal
P
02 0.2kW 2500P/R 3 With brake (DC24V)
04 0.4kW S Absolute encoder:131072P/R 4 With oil seal and brake(DC24V)
08 0.75kW 【5】Designing Sequence 【8+9】Connector
10 1.0kW Code Spec. Code Spec.
A Designing sequence A Standard connector
B Designing sequence B Water proof connector (Incremental
WR
【3】Voltage 【6】Shaft End Wire-saving Type )
-7-
ProNet Series AC Servo User's Manual
EMG– 10 A D A 1 1
ESTUN Servomotor
【1+2】 【3】 【4】 【5】 【6】 【7】
EMG Model
【1+2】
【4】Encoder 【7】Option
Rated Output
Code Spec. Code Spec. Code Spec.
50 5.0kW
【3】Voltage 【5】Designing Sequence 【6】Shaft End
Code Spec. Code Spec. Code Spec.
A 200VAC A Designing sequence A 1 Straigt without key (Standard)
D 400VAC 2 Straigt with key and tap
Note:1. The EMG-30A□A□□, EMG-50A□A□□ servomotors are not mounted with an incremental encoder.
2. There is no brake mounted on the EMG-□□□DA□□ servomotor.
EML– 10 A D A 1 1
ESTUN Servomotor
【1+2】 【3】 【4】 【5】 【6】 【7】
EML Model
【1+2】
【4】Encoder 【7】Option
Rated Output
Code Spec. Code Spec. Code Spec.
-8-
ProNet Series AC Servo User's Manual
EMB– 1E D S A 1 1
ESTUN Servomotor
【1+2】 【3】 【4】 【5】 【6】 【7】
EMB Model
【1+2】
【4】Encoder 【7】Option
Rated Output
Code Spec. Code Spec. Code Spec.
-9-
ProNet Series AC Servo User's Manual
PRONET – 10 A E A -P
ProNet Model
Extended module type
Rated Output
-D DP100
02 0.2kW
-E EC100
04 0.4 kW
-P PL100
08 0.75 kW
10 1.0 kW
15 1.5 kW
20 2.0 kW
30 3.0 kW
50 5.0 Kw
70 7.0kW
75 7.5 kW Encoder Interface
1A 11 kW A 17-bit serial encoder
1E 15 Kw Absolute Encoder
2B 22kW B Resolver○ 1
Voltage
A 200VAC
B:100VAC
D 400VAC
Control Mode
M Speed control, torque control, position control
E Speed control, torque control, position control (support extended module)
Note:
○
1 Resolver, with the feature of high reliability and long service life, is suitable for harsh environments and a wide range
of temperatures and humidity levels. The factory setting for the resolver precision used in the ESTUN servo drive is
4096.
2 ProNet-□□□E□ Supports AE100 model. ProNet-□□□M□ does not support extended module.
○
ProNet-E Servo drive Model Designation
PRONET–E – 10 A
Voltage
ProNet-E Model
A:200VAC
B:100VAC
D:400VAC
Rated Output
02 0.2kW
04 0.4 kW
08 0.75 kW
10 1.0 kW
15 1.5 kW
20 2.0 kW
30 3.0 kW
50 5.0 kW
- 10 -
ProNet Series AC Servo User's Manual
Note:
○
1 ProNet-E is only available with the wire-saving incremental encoder (2500 P/R)
ProNet-02A/04A ProNet-08A/10A
CHARGE POWER
CN3
L1
L2
CN4
L3
+1
+2
L1C
CN1
L2C
B1
B2
B3
V
CN2
ProNet-15A/20A ProNet-10D/15D/20D
L1 L1
L2 L2
CN4
CN4
L3 L3
+1 +1
+2 +2
- -
L1C
CN1
24V
CN1
L2C GND
B1 B1
B2 B2
B3 B3
U U
V V
CN2
CN2
W W
- 11 -
ProNet Series AC Servo User's Manual
ProNet-30A/50A ProNet-30D/50D/70D/75D
CHARGE
CHARGE POWER
POWER
CN3
CN3
L1
CN4
L1
L2
CN4
L2
L3
L3
+1
+1
+2
CN1
+2
CN1
-
24V
L1C GND
L2C B1
CN2
B1
CN2
B2
B2 B3
B3 U
U V
V W
ProNet-1AD/1ED/2BD ProNet-02B
- 12 -
ProNet Series AC Servo User's Manual
ProNet-04B ProNet-08B
ProNet-E-02A/04A ProNet-E-08A/10A
CHARGE POWER
CN3
L1
L2
CN4
CN3
L3
CHARGE
+1
L1
CN4
L2 +2
FG
-
+1
+2 L1C
CN1
- L2C
B1
CN1
L1C
B2
L2C B3
B1
B2
U
B3
V
W
CN2
V
W
CN2
- 13 -
ProNet Series AC Servo User's Manual
ProNet-E-15A/20A ProNet-E-10D/15D/20D
CHARGE POWER
CN3
CHARGE POWER
L1
CN3
L2
CN4
L1 L3
L2 +1
CN4
L3
+2
+1
-
+2
24V
CN1
-
GND
L1C B1
CN1
L2C B2
B1 B3
B2
U
B3
V
U
CN2
W
V
CN2
ProNet-E-30A/50A ProNet-E-30D/50D
CHARGE CHARGE
POWER POWER
CN3
CN3
L1 L1
CN4
CN4
L2 L2
L3 L3
+1 +1
+2
CN1
+2
CN1
-
-
L1C
24V
L2C
GND
B1
CN2
B1
CN2
B2
B2
B3
B3
U
U
V
V
W
W
- 14 -
ProNet Series AC Servo User's Manual
ProNet-E-02B ProNet-E-04B
ProNet-E-08B
- 15 -
ProNet Series AC Servo User's Manual
Servodrive model
Applicable power Applicable servomotor
supply capacity
Serial number
- 16 -
ProNet Series AC Servo User's Manual
1.2.1 Servomotor
Encoder
Mounting hole
Shell
Output shaft
Flange
ProNet-02A/04A/ProNet-E-02A/04A
Charge indicator
Lights when the main circuit power supply is
ON and stays lit as long as the main circuit
power supply capacitor remains charged.
Connector for communication
Main circuit power supply terminals
Used to communicate with other devices.
Used for main circuit power supply input.
Servomotor terminals
Connects to the servomotor power line. Encoder connector
Connects to the encoder in the
Ground terminal servomotor.
Be sure to connect to protect electric shock.
- 17 -
ProNet Series AC Servo User's Manual
ProNet-08A/10A /ProNet-E-08A/10A
CN3
CN4
CN1
CN2
ProNet-15A/20A/ ProNet-E-15A/20A
CHARGE POWER
CN3
L1
L2
CN4
L3
+1
+2
L1C
CN1
L2C
B1
B2
B3
V
CN2
- 18 -
ProNet Series AC Servo User's Manual
ProNet-10D/15D/20D/ProNet-E-10D/15D/20D
Charge indicator
Lights when the main circuit power supply is
ON and stays lit as long as the main circuit CHARGE POWER Power on indicator
power supply capacitor remains charged. Lights when the control power supply is on.
CN3
L1
Main circuit power supply terminals L2 Connector for communication
Used for main circuit power supply input. Used to communicate with other devices.
CN4
L3
+1
CN1
24V
GND
Servomotor terminals
U
ProNet-30A/50A/ ProNet-E-30A/50A
Charge indicator
Lights when the main circuit
power supply is ON and
stays lit as long as the main
circuit power supply
CHARGE
POWER Power on indicator
Lights when the control power supply is
CN3
- 19 -
ProNet Series AC Servo User's Manual
ProNet-30D/50D/70D/75D/ ProNet-E-30D/50D
Charge indicator
Lights when the main circuit
power supply is ON and
stays lit as long as the main
Power on indicator
circuit power supply
CHARGE
Lights when the control power supply is
capacitor remains charged. POWER
on.
CN3
Main circuit power Connector for communication
L1
supply terminals
CN4
L2 Used to communicate with other devices.
Used for main circuit
L3
power supply input.
+1
Connecting terminal
+2
I/O signal connector
of DC reactor
CN1
Used for reference input
-
Control power supply signals and sequence I/O
terminals 24V signals.
Used for control power GND
supply input. B1
Encoder connector
CN2
Regenerative resistor Connects to the encoder
B2
connecting terminals in the servomotor.
B3
Used to connect external
regenerative resistors. U
Servomotor terminals V
Ground terminal
Be sure to connect to protect
electric shock.
ProNet-1AD/1ED/2BD
- 20 -
ProNet Series AC Servo User's Manual
ProNet-02B/ProNet-E-02B
Charge indicator
Lights when the main circuit power supply is
ON and stays lit as long as the main circuit
power supply capacitor remains charged.
Connector for communication
Main circuit power supply terminals
Used to communicate with other devices.
Used for main circuit power supply input.
Servomotor terminals
Connects to the servomotor power line. Encoder connector
Connects to the encoder in the
Ground terminal servomotor.
Be sure to connect to protect electric shock.
ProNet-04B/ProNet-E-04B
Charge indicator
Lights when the main circuit
power supply is ON and
stays lit as long as the main Power on indicator
circuit power supply Lights when the control power supply is
capacitor remains charged. on.
Main circuit power
supply terminals
Used for main circuit Connector for communication
power supply input. Used to communicate with other devices.
Connecting terminal
of DC reactor
Control power supply
terminals
Used for control power
supply input.
Regenerative resistor I/O signal connector
connecting terminals Used for reference input
Used to connect external signals and sequence I/O
regenerative resistors. signals.
Servomotor terminals
Connects to the servomotor
Encoder connector
power line.
Connects to the encoder
Ground terminal
in the servomotor.
Be sure to connect to protect
electric shock.
- 21 -
ProNet Series AC Servo User's Manual
ProNet-08B /ProNet-E-08B
Charge indicator
Lights when the main circuit
power supply is ON and
stays lit as long as the main
circuit power supply
capacitor remains charged. Power on indicator
Main circuit power Lights when the control power supply is
supply terminals on.
Used for main circuit Connector for communication
power supply input. Used to communicate with other devices.
Connecting terminal
of DC reactor
Control power supply
terminals
I/O signal connector
Used for control power
Used for reference input
supply input.
Regenerative resistor signals and sequence I/O
connecting terminals signals.
Used to connect external
regenerative resistors.
Servomotor terminals
Connects to the servomotor Encoder connector
power line. Connects to the encoder
Ground terminal in the servomotor.
Be sure to connect to protect
electric shock.
- 22 -
ProNet Series AC Servo User's Manual
Chapter 2
Installation
2.1 Servomotor
Servomotor can be installed either horizontally or vertically. However, if the servomotor is installed incorrectly, the
service life of the servomotor will be shortened or unexpected problems may occur.
Please observe the installation instructions described below to install the servomotor correctly.
Before installation:
Anticorrosive paint is coated on the edge of the servomotor shaft. Clean off the anticorrosive paint thoroughly using
a cloth moistened with thinner.
Avoid getting thinner on other parts of the servomotor when cleaning the shaft.
2.1.1 Storage
When the servomotor is not being used, store it in an area with a temperature between -25℃ and 60℃ with the power
cable disconnected.
The servomotor is designed for indoor use. Install the servomotor in an environment which meets the following
conditions.
Free from corrosive and explosive gases.
Well-ventilated and free from dust and moisture.
Ambient temperature from 0 to 40℃.
Relative humidity from 26% to 80%( non-condensing).
Facilitates inspection and cleaning.
- 23 -
ProNet Series AC Servo User's Manual
Align the shaft of the servomotor with that of the machinery shaft to be controlled. Then connect the two shafts with an
elastic coupling.
Install the servomotor so that alignment accurancy falls within the range shown below.
Measure this distance at four different positions in the circumference. The difference between the maximum and
minimum measurements must be 0.03mm or less.(Turn together with couplings.)
Note:
·If the alignment accurancy is incorrect , vibration will occur, resulting in damage to the bearings.
·Mechanical shock to the shaft end is forbidden, otherwise it may result in damage to the encoder of the servomotor.
If the servomotor is used in a location that is subject to water or oil drops, make sure of the servomotor protective
specification. If the servomotor is required to meet the protective specification to the through shaft section by default,
use a servomotor with an oil seal.
- 24 -
ProNet Series AC Servo User's Manual
When connecting the cables, the bending radius should not be too small, do not bend or apply tension to cables.
Since the conductor of a signal cable is very thin (0.2 mm or 0.3 mm), handle it with adequate care.
When the servo motor is mounted to the client, please firmly secure the servo motor by the screws with backing ring
as shown in the figure.
In
or stall
i en at
tat ion
io
n
ProNet series servo drive is a base-mounted type. Incorrect installation will cause problems. Always observe the
installation instructions described below.
2.2.1 Storage
When the servomotor is not being used, store it in an area with a temperature between -25℃ and 55℃ with the
power cable disconnected.
- 25 -
ProNet Series AC Servo User's Manual
Install the servo drive perpendicular to the wall as shown in the figure. The servo drive must be oriented this way
because it is designed to be cooled by natural convection or a cooling fan if required. Firmly secure the servo drive
through two mounting holes.
When installing multiple servo drives side by side in a control panel, observe the following installation method.
■Installation Orientation
Install servo drive perpendicular to the wall so that the front panel (containing connectors) faces outward.
■Cooling
Provide sufficient space around each servo drive to allow cooling by natural convection or fans.
When installing servo drives side by side, provide at least 10mm space between each individual servo drive and at
least 50mm space above and below each one as well as shown in the figure above. Ensure the temperature inside the
control panel is evenly distributed, and prevent the temperature around each servo drive from increasing excessively.
- 26 -
ProNet Series AC Servo User's Manual
■Working conditions
1.Temperature:-20~ 55℃
2.Humidity:5%~95%RH
2
3.Vibration:4.9m/s or less
4.Ambient temperature to ensure long-term reliability: 45℃ or less
- 27 -
ProNet Series AC Servo User's Manual
Chapter 3
Wiring
Please observe the following instructions while wiring the main circuit.
· Do not bundle or run power and signal lines together in the same duct. Keep power and signal lines
separated by at least 300 mm.
· Use twisted-pair shielded wires or multi-core twisted-pair shielded wires for signal and encoder feedback
lines.
· The maximum length is 3 m for reference input lines and 20 m for encoder feedback lines.
· Do not touch the power terminals for 5 minutes after turning power OFF because high voltage may still
remain in the servo drive.
Servo Servo
Main
Terminal Drive Drive
Name Circuit Functions
Symbol Model Model
Voltage(V)
ProNet- Pronet-E-
100 02B-08B 02B-08B Single-phase 100~120VAC +10%~-15% (50/60Hz)
- 28 -
ProNet Series AC Servo User's Manual
Servo Servo
Main
Terminal Drive Drive
Name Circuit Functions
Symbol Model Model
Voltage(V)
ProNet- Pronet-E-
resistor 100 04B-08B 04B-08B If using an internal regenerative resistor, please short
connection 200 08A-50A 08A-50A B2 and B3. Remove the wire between B2 and B3 and
terminal connect an external regenerative resistor(provided
10D-75D 10D-50D by customer) between B1 and B2, if the capacity of
400 the internal regenerative resistor is insufficient.
Connect an external regenerative resistor between
B1,B2 1AD-2BD -
B1 and B2.
DC reactor for Normally short ○
+ 1and ○+ 2.
200 02A-50A 02A-50A
harmonic If a countermeasure against power supply harmonic
+ 1,○
○ +2
suppression waves is needed, connect a DC reactor between ○
+
400 10D-75D 10D-50D
terminal 1and ○
+ 2.
Main circuit 200 02A-50A 02A-50A Normally not connected.
○
-
minus terminal 400 10D-75D 10D-50D
Surge Protector
1Ry 1PL (Servo Alarm Display)
Noise Filter
Power OFF Power ON
1KM
Magnetic Contactor
L1
A(1) Servodrive
L2 ProNet U
Series Servodrive V
B(2)
M
C(3)
1 W
D(4)
2
L1C
L2C
Encoder
CN2 PG
External regenerator resistor
B1
B1
B2
B2
B3
B3
1Ry +24V
7 ALM+
8 ALM-
1D
Ground Terminal 0V
Note
1.The L1,L2,L3 and L1C,L2C terminals wiring method of ProNet-02A~04A/ProNet-E-02A~04A servo drives is different
from other ProNet series servo drives. Please note the specific terminal definition while wiring.
2.The main circuit power supply of ProNet-02A~04A/ProNet-E-02A~04A is Single-phase 200V
- 29 -
ProNet Series AC Servo User's Manual
3. External regenerative resistor for ProNet-02A~04A/ProNet-E-02A~04A is provided by customer, the model of 60W,
50Ωresistor is recommended.
4.Change Pn521.0 from “1” to “0” when using the external regenerative resistor in ProNet-02A~04A/ProNet-E-02A~04A
servo drives.
Surge Protector
1Ry 1PL (Servo Alarm Display)
Noise Filter
Power OFF Power ON
1KM
Magnetic Contactor
L1
Servomotor
L2
ProNet U
A(1)
L1C
L2C
Encoder
CN2 PG
B1 B1
B2 B2
External Regenerator Resistor
B3 B3
+24V
1Ry
7 ALM+
8 ALM-
1D
Ground Terminal 0V
Surge Protector
1Ry 1PL (Servo Alarm Display)
Noise Filter
Power OFF Power ON
1KM
Magnetic Contactor
L1
Servomotor
L2
ProNet U
A(1)
24V
24VDC Power Supply
GND
Encoder
CN2 PG
B1 B1
B2 B2
External Regenerator Resistor
B3 B3
+24V
1Ry
7 ALM+
8 ALM-
1D
Ground Terminal 0V
- 30 -
ProNet Series AC Servo User's Manual
Surge Protector
1Ry 1PL (Servo Alarm Display)
Noise Filter
Power OFF Power ON
1KM
Magnetic Contactor
L1
A(1) Servodrive
L2 ProNet U
L3 Series Servodrive V
B(2)
M
C(3)
W
D(4)
L 1C
L2C
Encoder
CN2 PG
B2
1Ry +24V
7 ALM+
8 ALM-
1D
Ground Terminal 0V
Notes:
1. A resistor value of 1500W/20Ω is recommended for the external regenerative resistor of ProNet-1AD.
2. A resistor value of 1500W/15Ω is recommended for the external regenerative resistor of ProNet-1ED.
3. A resistor value of 1500W/20Ω is recommended for the external regenerative resistor of ProNet-2BD.
L1 L2 +10%
Single-phase 100~120V -15% (50/60Hz)
Molded-case Circuit Breaker
Surge Protector
1Ry 1PL (Servo Alarm Display)
Noise Filter
Power OFF Power ON
1KM
Magnetic Contactor
L1
A(1) Servodrive
U
L2
B(2)
V M
C(3)
1 W
D(4)
2
L1C
L2C
Encoder
CN2 PG
External regenerator resistor
B1
B1
B2
B2
B3
B3
1Ry +24V
7 ALM+
8 ALM-
1D
Ground Terminal 0V
- 31 -
ProNet Series AC Servo User's Manual
L1 L2 +10%
Single-phase 100~120V -15% (50/60Hz)
Molded-case Circuit Breaker
Surge Protector
1Ry 1PL (Servo Alarm Display)
Noise Filter
Power OFF Power ON
1KM
Magnetic Contactor
L1
A(1) Servodrive
U
L2
B(2)
V M
C(3)
1 W
D(4)
2
L1C
L2C
Encoder
CN2 PG
External regenerator resistor
B1
B1
B2
B2
B3
B3
1Ry +24V
7 ALM+
8 ALM-
1D
Ground Terminal 0V
L1 L2 +10%
Single-phase 100~120V -15% (50/60Hz)
Molded-case Circuit Breaker
Surge Protector
1Ry 1PL (Servo Alarm Display)
Noise Filter
Power OFF Power ON
1KM
Magnetic Contactor
L1
A(1) Servodrive
U
L2
B(2)
V M
C(3)
1 W
D(4)
2
L1C
L2C
Encoder
CN2 PG
External regenerator resistor
B1
B1
B2
B2
B3
B3
1Ry +24V
7 ALM+
8 ALM-
1D
Ground Terminal 0V
Notes:
When single-phase 100VAC is provided for main circuit on rated speed, instantaneous peak torque≤4.78 N.m.
When three-phase 100VAC is provided for main circuit on rated speed, instantaneous peak torque≤7.16 N.m.
- 32 -
ProNet Series AC Servo User's Manual
ProNet
Series Servodrive
10K
40K ref
VREF+ 1 +
Speed Reference(±0~10V/Rated Speed)
P
40K
VREF- 2 -
20 PAO+
10K
ref
A/D 21 PAO-
TREF+ 26 + 22 PBO+
Torque Reference(±0~10V/Rated Torque) PG Divided Ratio Output
P
TREF- 27 -
23 PBO- Applicable Line Output
24 PCO+ AM26LS32A Manufactured by TI or the Equivalent.
25 PCO-
50 DGND
150Ω
PULS+ 30
P
150Ω
SIGN+ 32
SIGN / CCW / B
P
SIGN- 33
1Ry +24V
7 ALM+
Shield 8 ALM-
Connect Shield to Connector Shell
1D
0V
ALM: Servo Alarm Output
Photocoupler Output:
Represents Twisted-pair Wires Maximum Operating Voltage:DC30V
P
- 33 -
ProNet Series AC Servo User's Manual
Input Signals
Control Signal Pin
Function
Mode Name No.
/S-ON 14 Servo ON: Turns the servomotor on.
Function selected by parameter.
Proportional Switches the speed control loop from PI to P control when
control reference ON.
Direction With the internally set speed selection: Switch the rotation
reference direction.
Internal speed With the internally set speed selection: Switches the internal
switching speed settings.
VREF+ 1
Speed Speed reference input: ±10V.
VREF- 2
PULS+ 30
Pulse reference input mode:
PULS- 31 Sign + pulse train
CCW + CW pulse
SIGN+ 32
Two-phase pulse (90º phase differential)
SIGN- 33
Power supply input for open collector reference (2KΩ/0.5W resistor is built into the
Position PPI 34
servo drive).
Positional error pulse clear input: Clear the positional error pulse during position
/CLR 40
control.
T-REF+ 26
Torque Torque reference input: ±10V.
T-REF- 27
- 34 -
ProNet Series AC Servo User's Manual
Output signals
Control
Signal
Mode Pin No. Function
Name
/TGON+ 5 Detects when the servomotor is rotating at a speed higher than the motor
/TGON- 6 speed seeting.
ALM+ 7 Servo alarm:
ALM- 8 Turns off when an error is detected.
/S-RDY+ 9 Servo ready:
ON if there is no servo alarm when the control/main circuit power supply
/S-RDY- 10
Speed is turned ON.
Position PAO+ 20
Phase-A signal
Torque PAO- 21 Converted two-phase pulse(phases A and B)
PBO+ 22 encoder output.
Phase-B signal
PBO- 23
PCO+ 24
Phase-C signal Zero-point pulse(Phase-C) signal
PCO- 25
Connect frame to ground if the shield wire of the
FG Shell
I/O signal cable is connected to the connector shell.
Reserved terminals:
The functions allocated to /TGON, /S-RDY, and /V-CMP (/COIN) can be
/CLT changed by using the parameters.
/CLT: Torque limit output
Turns on when it reaches the value set.
— /BK: Brake interlock output
Releases the brake when ON,
Reserved
/PGC:C pulse output
/BK OT:Over travel signal output
/RD:Servo enabled motor excitation output
/HOME: Home completion output
4,18,19,29,35
— 36,37,38,43 Not used.
44,45,47,49
- 35 -
ProNet Series AC Servo User's Manual
Terminal Terminal
Name Function Name Function
No. No.
1 VREF+ 26 T-REF+
Speed reference input:±10V Torque referenceinput:±10V
2 VREF- 27 T-REF-
3 DGND DGND 28 DGND DGND
4 — Reserved 29 — Reserved
5 /TGON+ 30 PULS+
Running signal output Reference pulse input
6 /TGON- 31 PULS-
7 ALM+ 32 SIGN+
Servo alarm Reference sign input
8 ALM- 33 SIGN-
Open collector reference
9 /S-RDY+ 34 PPI
Servo ready power supply
10 /S-RDY- 35 — Reserved
11 /COIN+ 36 — Reserved
Positioning completion
12 /COIN- 37 — Reserved
I/O signal power supply 24V
13 DICOM 38 — Reserved
DC
14 /S-ON Servo ON 39 /ALM-RST Alarm reset
15 /P-CON P/PI control input 40 /CLR Position error pulse clear input
16 P-OT Forward run prohibited 41 /PCL Forward torque limit input
17 N-OT Reverse run prohibited 42 /NCL Reverse torque limit input
18 — Reserved 43 — Reserved
19 — Reserved 44 — Reserved
20 PAO+ PG dividing 45 — Reserved
pulse output PG
21 PAO- 46 DGND DGND
phase A dividing
22 PBO+ PG dividing pulse 47 — Reserved
pulse output output
23 PBO- 48 DGND DGND
phase B
24 PCO+ PG dividing 49 — Reserved
Zero-point
pulse output
25 PCO- pulse 50 DGND DGND
phase C
Note: The functions allocated to the following input and output signals can be changed by using the parameters.
·Input signals: /S-ON,/P-CON,P-OT,N-OT,/ALM-RST,/CLR,/PCL,/NCL,SHOM,ORG
·Output signals: /TGON,/S-RDY,/COIN,/HOME
Please refer to A.3 Parameters in details for detailed information.
- 36 -
ProNet Series AC Servo User's Manual
This section shows examples of servo drive I/O signal connection to the host controller.
Analog signals are either speed or torque reference signals at about 40kΩ impedance, and the maximum allowable
470Ω(1/2W)min.
10V 2 V-REF
2KΩ
About 40KΩ
1
GND
0V
The sequence input circuit interface connects through a relay or open-collector transistor circuit. Select a low-current relay
The amount of two-phase (phase A and phase B) pulse output signals (PAO,/PAO,PBO,/PBO) and zero-point pulse
signals (PCO,/PCO) are output via line-driver output circuits. Normally, the servo drive uses this output circuit in speed
control to comprise the position control system at the host controller. Connect the line-driver output circuit through a line
Photocoupler output circuits are used for Servo Alarm (ALM), Servo Ready(S-RDY), and other sequence output signal
- 37 -
ProNet Series AC Servo User's Manual
7(H) 2-7、2-8、2-9
PG5V
8(G) 2-17、2-18、2-19
PG0V
1-18 SG
0V 0V
1-36
FG Connector shell
9(J)
Connector shell
(Shell)
shielded wires
7(H) 2-7、2-8、2-9
PG5V
8(G) 2-17、2-18、2-19
PG0V
1-18 SG
0V 0V
1-36
- 38 -
ProNet Series AC Servo User's Manual
Phase-C 24 PCO
25 /PCO P
PG
Output line driver
AM26LS31 manufactured
by TI or the equivalent. Applicable line-
receiver SN75175
manufactured by TI
or the equivalent.
H(5) PG5V 9
G(6) PG0V 19
50 DGND
0V 0V
* P
Represents multi-core twisted pair shielded wires.
Note: (1)BAT+ and BAT- signals are not used when using an incremental encoder .
(2)The pin numbers for the connector wiring differ depending on the servomotors .
Resolver
Phase-C 24 PCO
25 /PCO P
PG Output line-driver
AM26LS31
manufactured by TI Applicable line-
or equivalent. receiver SN75175
manufactured by
TI or equivalent.
H R1 9
G R2 19
50 DGND
0V 0V
FG Connect shell
J
shielded wires Connector shell
Shell
- 39 -
ProNet Series AC Servo User's Manual
Resolver
Terminal No. Name Function Terminal No. Name Function
7 SIN+ Differential Sine Signal 17 COS+ Differential Cosine Signal
8 SIN- Differential Sine Signal 18 COS- Differential Cosine Signal
9 R1 Excitation signal 19 R2 Excitation Signal
- 40 -
ProNet Series AC Servo User's Manual
- 41 -
ProNet Series AC Servo User's Manual
Surge Protector
1Ry 1PL (Servo Alarm Display )
Noise Filter
Power OFF Power ON
1KM
Magnetic Contactor
ProNet Servomotor
A(1)
L1 Series Servodrives U
B(2)
L2 V M
C(3)
1 W
D(4)
2
CN2
Option
L1 C
Incremental Wire-saving
L2C Encoder(2500P/R) Serial Encoder
1 A+ Encoder
2 A- 7 S+
External Regenerator Resistor 3 B+ 8 S-
B1 4 B- 17 BAT+ PG
B1 5 C+ 18 BAT-
B2 6 C- 9 PG5V
B2 PG5V
7,8,9
19 PG0V
B3 17,18,19 PG0V
B3 Shell Shield
Shell Shield
CN3
40K
Speed Reference(±0~10V/Rated Speed) VREF- 2 -
10K A/D
8 CANL Note: Do not short terminal 1 and 2 of CN3.
ref
TREF+ 26 + Shell Shield
P
CN4
1 N.C.
2 N.C.
Open-collector Reference Use
PPI 34 3 485+
2KΩ
4 ISO_GND
150Ω
PULS+ 30 5 ISO_GND
PULS / CW / A
P
SIGN- 33
Shell Shield
+24V
Signal allocatons can be modified: DICOM 13 20 PAO+
3.3KΩ
S-ON: Servo ON S-ON 14 21 PAO-
P-CON: P Control P-CON 15 22 PBO+ PG Divided Ratio Output:
P-OT: Forward Run Prohibited P-OT 16 23 PBO- Applicable Line Receiver
AM26LS32A Manufactured by TI or the Equivalent.
N-OT: Reverse Run Prohibited N-OT 17 24 PCO+
ALM-RST: Alarm Reset ALM-RST 39 25 PCO-
CLR: Clear Error Pulse CLR 40 50 DGND
P-CL: Forward Torque Limit P-CL 41
N-CL: Reverse Torque Limit N-CL 42 Signal Allocations can be Modified:
V-CMP: Speed Coincidence
SHOM: Home 5 TGON+ COIN: Positioning Completion
ORG: Zero Position 6 TGON- TGON:Rotation Detection
S-RDY:Servo Ready
9 S-RDY+ CLT:Torque Limit Detection
10 S-RDY- BK:Brake Interlock
11 V-CMP+ PGC: Encoder C-Pulse Output
OT:Over Travel
12 V-CMP- RD: Servo Enabled Motor Excitation Output
HOME: Home Completion Output
1Ry +24V
7 ALM+
Connect Shield to Connector Shell. Shield Shell
8 ALM-
1D
0V
ALM: Servo Alarm Output
Photocoupler Output:
Maximum Operating Voltage:DC30V
Maximum Output Current:DC50mA
Note 1.The L1,L2,L3 and L1C,L2C terminals wiring method of ProNet-02A~04A/ProNet-E-02A~04A servo drives is
different from other ProNet series servo drives. Please note the specific terminal definition while wiring.
2.The main circuit power supply of ProNet-02A~04A/ProNet-E-02A~04A is Single-phase 200V
3. External regenerative resistor for ProNet-02A~04A/ProNet-E-02A~04A is provided by customer, the model of
60W,50Ωresistor is recommended.
4.Change Pn521.0 from “1” to “0” when using the external regenerative resistor in ProNet-02~04/ProNet-E-02A~
04A servo drives.
- 42 -
ProNet Series AC Servo User's Manual
Surge Protector
1Ry 1PL (Servo Alarm Display )
Noise Filter
Power OFF Power ON
1KM
Magnetic Contactor
L1
ProNet Servomotor
A(1)
L2 Series Servodrives U
B(2)
L3 V M
C(3)
1 W
D(4)
2
CN2
Option
L1C
40K
Speed Reference(±0~10V/Rated Speed) VREF- 2 -
10K A/D
8 CANL Note: Do not short terminal 1 and 2 of CN3.
ref
TREF+ 26 + Shell Shield
P
CN4
1 N.C.
2 N.C.
PPI 34 3 485+
Open-collector Reference Use 2KΩ
4 ISO_GND
150Ω
PULS+ 30 5 ISO_GND
PULS / CW / A
P
SIGN- 33
Shell Shield
+24V
Signal allocatons can be modified: DICOM 13 20 PAO+
3.3KΩ
S-ON: Servo ON S-ON 14 21 PAO-
P-CON: P Control P-CON 15 22 PBO+ PG Divided Ratio Output:
P-OT: Forward Run Prohibited P-OT 16 23 PBO- Applicable Line Receiver
AM26LS32A Manufactured by TI or the Equivalent.
N-OT: Reverse Run Prohibited N-OT 17 24 PCO+
ALM-RST: Alarm Reset ALM-RST 39 25 PCO-
CLR: Clear Error Pulse CLR 40 50 DGND
P-CL: Forward Torque Limit P-CL 41
N-CL: Reverse Torque Limit N-CL 42 Signal Allocations can be Modified:
V-CMP: Speed Coincidence
SHOM: Home 5 TGON+ COIN: Positioning Completion
ORG: Zero Position 6 TGON- TGON:Rotation Detection
S-RDY:Servo Ready
9 S-RDY+ CLT:Torque Limit Detection
10 S-RDY- BK:Brake Interlock
11 V-CMP+ PGC: Encoder C-Pulse Output
OT:Over Travel
12 V-CMP- RD: Servo Enabled Motor Excitation Output
HOME: Home Completion Output
1Ry +24V
7 ALM+
Connect Shield to Connector Shell. Shield Shell
8 ALM-
1D
0V
ALM: Servo Alarm Output
Photocoupler Output:
Maximum Operating Voltage:DC30V
Maximum Output Current:DC50mA
- 43 -
ProNet Series AC Servo User's Manual
Surge Protector
1Ry 1PL (Servo Alarm Display )
Noise Filter
Power OFF Power ON
1KM
Magnetic Contactor
L1
ProNet Servomotor
A(1)
L2 Series Servodrives U
B(2)
L3 V M
C(3)
1 W
D(4)
2
CN2
Option
24V
24VDC Power Supply
Incremental Wire-saving
GND Encoder(2500P/R)
Serial Encoder
Encoder
1 A+ Resolver 7 S+
B1 B1
2 A- 8 S-
7 SIN+
3 B+ 17 BAT+ PG
B2 B2 8 SIN-
4 B- 18 BAT-
External Regenerator Resisotr 17 COS+
5 C+ 9 PG5V
B3 B3 18 COS-
6 C-
9 R1 19 PG0V
7,8,9 PG5V 19 R2
17,18,19 PG0V Shell Shield
Shell Shield
Shell Shield
Be sure to ground CN3
40K
Speed Reference(±0~10V/Rated Speed) VREF- 2 -
10K A/D
8 CANL Note: Do not short terminal 1 and 2 of CN3.
ref
TREF+ 26 + Shell Shield
P
CN4
1 N.C.
2 N.C.
Open-collector Reference Use
PPI 34 3 485+
2KΩ
4 ISO_GND
150Ω
PULS+ 30 5 ISO_GND
PULS / CW / A
P
SIGN- 33
Shell Shield
+24V
Signal allocatons can be modified: DICOM 13 20 PAO+
3.3KΩ
S-ON: Servo ON S-ON 14 21 PAO-
P-CON: P Control P-CON 15 22 PBO+ PG Divided Ratio Output:
P-OT: Forward Run Prohibited P-OT 16 23 PBO- Applicable Line Receiver
AM26LS32A Manufactured by TI or the Equivalent.
N-OT: Reverse Run Prohibited N-OT 17 24 PCO+
ALM-RST: Alarm Reset ALM-RST 39 25 PCO-
CLR: Clear Error Pulse CLR 40 50 DGND
P-CL: Forward Torque Limit P-CL 41
N-CL: Reverse Torque Limit N-CL 42 Signal Allocations can be Modified:
V-CMP: Speed Coincidence
SHOM: Home 5 TGON+ COIN: Positioning Completion
ORG: Zero Position 6 TGON- TGON:Rotation Detection
S-RDY:Servo Ready
9 S-RDY+ CLT:Torque Limit Detection
10 S-RDY- BK:Brake Interlock
11 V-CMP+ PGC: Encoder C-Pulse Output
OT:Over Travel
12 V-CMP- RD: Servo Enabled Motor Excitation Output
HOME: Home Completion Output
1Ry +24V
7 ALM+
Connect Shield to Connector Shell. Shield Shell
8 ALM-
1D
0V
ALM: Servo Alarm Output
Photocoupler Output:
Maximum Operating Voltage:DC30V
Maximum Output Current:DC50mA
- 44 -
ProNet Series AC Servo User's Manual
Surge Protector
1Ry 1PL (Servo Alarm Display )
Noise Filter
Power OFF Power ON
1KM
Magnetic Contactor
L1
ProNet Servomotor
A(1)
L2 Series Servodrives U
B(2)
L3 V M
C(3)
W
D(4)
CN2
L1C
Option
Resolver
L2C Serial Encoder
1 Sensor 1 Encoder
3 Sensor 2 7 S+
B1 7 SIN+ 8 S-
8 SIN- 17 BAT+ PG
B2 17 COS+
External Regenerator Resisotr 18 BAT-
18 COS-
9 R1
9 PG5V
19 R2 19 PG0V
Shell Shield Shell Shield
40K
Speed Reference(±0~10V/Rated Speed) VREF- 2 -
8 CANL
10K
ref
A/D Note: Do not short terminal 1 and 2 of CN3.
TREF+ 26 + Shell Shield
P
CN4
1 N.C.
2 N.C.
Open-collector Reference Use
PPI 34 3 485+
2KΩ
4 ISO_GND
150Ω
PULS+ 30 5 ISO_GND
PULS / CW / A
P
SIGN- 33
Shell Shield
0V
ALM: Servo Alarm Output
Photocoupler Output:
Maximum Operating Voltage:DC30V
Maximum Output Current:DC50mA
Notes:
1. The resistor of 1500W/20Ω is recommended for the external regenerative resistor of ProNet-1AD.
2. The resistor of 1500W/15Ω is recommended for the external regenerative resistor of ProNet-1ED.
3. The resistor of 1500W/20Ω is recommended for the external regenerative resistor of ProNet-2BD.
- 45 -
ProNet Series AC Servo User's Manual
Surge Protector
1Ry 1PL (Servo Alarm Display )
Noise Filter
Power OFF Power ON
1KM
Servomotor
A(1)
L1 U
B(2)
L2 V M
C(3)
1 W
D(4)
2
CN2
Option
Incremental Wire-saving
L1C Serial Encoder Encoder(2500P/R)
7 S+ 1 A+
L2C
8 S- 2 A- Encoder
17 BAT+ 3 B+
External Regenerator Resistor 18 BAT- 4 B-
B1 9 PG5V 5 C+ PG
B1
19 PG0V 6 C-
B2 7,8,9 PG5V
B2 Shell Shield 17,18,19 PG0V
B3 Shell Shield
B3
CN3
40K
Speed Reference(±0~10V/Rated Speed) VREF- 2 -
8 CANL
10K A/D Note: Do not short terminal 1 and 2 of CN3.
ref
TREF+ 26 + Shell Shield
P
CN4
1 N.C.
2 N.C.
Open-collector Reference Use
PPI 34 3 485+
2KΩ
4 ISO_GND
150Ω
PULS+ 30 5 ISO_GND
PULS / CW / A
P
SIGN- 33
Shell Shield
+24V
Signal allocatons can be modified: DICOM 13 20 PAO+
3.3KΩ
S-ON: Servo ON S-ON 14 21 PAO-
P-CON: P Control P-CON 15 22 PBO+ PG Divided Ratio Output:
P-OT: Forward Run Prohibited P-OT 16 23 PBO- Applicable Line Receiver
AM26LS32A Manufactured by TI or the Equivalent.
N-OT: Reverse Run Prohibited N-OT 17 24 PCO+
ALM-RST: Alarm Reset ALM-RST 39 25 PCO-
CLR: Clear Error Pulse CLR 40 50 DGND
P-CL: Forward Torque Limit P-CL 41
N-CL: Reverse Torque Limit N-CL 42 Signal Allocations can be Modified:
V-CMP: Speed Coincidence
SHOM: Home 5 TGON+ COIN: Positioning Completion
ORG: Zero Position 6 TGON- TGON:Rotation Detection
S-RDY:Servo Ready
9 S-RDY+ CLT:Torque Limit Detection
10 S-RDY- BK:Brake Interlock
11 V-CMP+ PGC: Encoder C-Pulse Output
OT:Over Travel
12 V-CMP- RD: Servo Enabled Motor Excitation Output
HOME: Home Completion Output
1Ry +24V
7 ALM+
Connect Shield to Connector Shell. Shield Shell
8 ALM-
1D
0V
ALM: Servo Alarm Output
Photocoupler Output:
Maximum Operating Voltage:DC30V
Maximum Output Current:DC50mA
- 46 -
ProNet Series AC Servo User's Manual
Surge Protector
1Ry 1PL (Servo Alarm Display )
Noise Filter
Power OFF Power ON
1KM
Servomotor
A(1)
L1 U
B(2)
L2 V M
C(3)
1 W
D(4)
2
CN2
Incremental Wire-saving
L1C Option Encoder(2500P/R)
Serial Encoder 1 A+
L2C
2 A- Encoder
7 S+
3 B+
8 S-
4 B-
17 BAT+
5 C+ PG
B1 B1 18 BAT-
6 C-
9 PG5V
19 PG0V 7,8,9 PG5V
B2 B2
17,18,19 PG0V
External Regenerator Resisotr
Shell Shield Shell Shield
B3 B3
CN3
40K
Speed Reference(±0~10V/Rated Speed) VREF- 2 -
10K A/D
8 CANL Note: Do not short terminal 1 and 2 of CN3.
ref
TREF+ 26 + Shell Shield
P
CN4
1 N.C.
2 N.C.
Open-collector Reference Use
PPI 34 3 485+
2KΩ
4 ISO_GND
150Ω
PULS+ 30 5 ISO_GND
PULS / CW / A
P
SIGN- 33
Shell Shield
+24V
Signal allocatons can be modified: DICOM 13 20 PAO+
3.3KΩ
S-ON: Servo ON S-ON 14 21 PAO-
P-CON: P Control P-CON 15 22 PBO+ PG Divided Ratio Output:
P-OT: Forward Run Prohibited P-OT 16 23 PBO- Applicable Line Receiver
AM26LS32A Manufactured by TI or the Equivalent.
N-OT: Reverse Run Prohibited N-OT 17 24 PCO+
ALM-RST: Alarm Reset ALM-RST 39 25 PCO-
CLR: Clear Error Pulse CLR 40 50 DGND
P-CL: Forward Torque Limit P-CL 41
N-CL: Reverse Torque Limit N-CL 42 Signal Allocations can be Modified:
V-CMP: Speed Coincidence
SHOM: Home 5 TGON+ COIN: Positioning Completion
ORG: Zero Position 6 TGON- TGON:Rotation Detection
S-RDY:Servo Ready
9 S-RDY+ CLT:Torque Limit Detection
10 S-RDY- BK:Brake Interlock
11 V-CMP+ PGC: Encoder C-Pulse Output
OT:Over Travel
12 V-CMP- RD: Servo Enabled Motor Excitation Output
HOME: Home Completion Output
1Ry +24V
7 ALM+
Connect Shield to Connector Shell. Shield Shell
8 ALM-
1D
0V
ALM: Servo Alarm Output
Photocoupler Output:
Maximum Operating Voltage:DC30V
Maximum Output Current:DC50mA
- 47 -
ProNet Series AC Servo User's Manual
Surge Protector
1Ry 1PL (Servo Alarm Display )
Noise Filter
Power OFF Power ON
1KM
Servomotor
A(1)
L1 U
B(2)
L2 V M
C(3)
1 W
D(4)
2
CN2
Incremental Wire-saving
L1C Option Encoder(2500P/R)
Serial Encoder 1 A+
L2C
2 A- Encoder
7 S+
3 B+
8 S-
4 B-
17 BAT+
5 C+ PG
B1 B1 18 BAT-
6 C-
9 PG5V
19 PG0V 7,8,9 PG5V
B2 B2
17,18,19 PG0V
External Regenerator Resisotr
Shell Shield Shell Shield
B3 B3
CN3
40K
Speed Reference(±0~10V/Rated Speed) VREF- 2 -
10K A/D
8 CANL Note: Do not short terminal 1 and 2 of CN3.
ref
TREF+ 26 + Shell Shield
P
CN4
1 N.C.
2 N.C.
Open-collector Reference Use
PPI 34 3 485+
2KΩ
4 ISO_GND
150Ω
PULS+ 30 5 ISO_GND
PULS / CW / A
P
SIGN- 33
Shell Shield
+24V
Signal allocatons can be modified: DICOM 13 20 PAO+
3.3KΩ
S-ON: Servo ON S-ON 14 21 PAO-
P-CON: P Control P-CON 15 22 PBO+ PG Divided Ratio Output:
P-OT: Forward Run Prohibited P-OT 16 23 PBO- Applicable Line Receiver
AM26LS32A Manufactured by TI or the Equivalent.
N-OT: Reverse Run Prohibited N-OT 17 24 PCO+
ALM-RST: Alarm Reset ALM-RST 39 25 PCO-
CLR: Clear Error Pulse CLR 40 50 DGND
P-CL: Forward Torque Limit P-CL 41
N-CL: Reverse Torque Limit N-CL 42 Signal Allocations can be Modified:
V-CMP: Speed Coincidence
SHOM: Home 5 TGON+ COIN: Positioning Completion
ORG: Zero Position 6 TGON- TGON:Rotation Detection
S-RDY:Servo Ready
9 S-RDY+ CLT:Torque Limit Detection
10 S-RDY- BK:Brake Interlock
11 V-CMP+ PGC: Encoder C-Pulse Output
OT:Over Travel
12 V-CMP- RD: Servo Enabled Motor Excitation Output
HOME: Home Completion Output
1Ry +24V
7 ALM+
Connect Shield to Connector Shell. Shield Shell
8 ALM-
1D
0V
ALM: Servo Alarm Output
Photocoupler Output:
Maximum Operating Voltage:DC30V
Maximum Output Current:DC50mA
Notes:
When single-phase 100VAC is provided for main circuit on rated speed, instantaneous peak torque≤4.78 N.m.
When three-phase 100VAC is provided for main circuit on rated speed, instantaneous peak torque≤7.16 N.m.
- 48 -
ProNet Series AC Servo User's Manual
ProNet
Series Servodrives
20 PAO+
21 PAO-
22 PBO+ PG Divided Ratio Output:
Applicable Line Receiver
23 PBO- AM26LS32A Manufactured by TI or the Equivalent.
24 PCO+
25 PCO-
50 DGND
150Ω
PULS / CW / A
PULS+ 30
Position Reference
P
PULS- 31
2KΩ
150Ω
SIGN / CCW / B
SIGN+ 32
P
SIGN- 33
+24V
Signal allocatons can be modified: DICOM 13 3.3KΩ
S-ON: Servo ON S-ON 14
P-CON: P Control P-CON 15
P-OT: Forward Run Prohibited P-OT 16
N-OT: Reverse Run Prohibited N-OT 17
ALM-RST: Alarm Reset ALM-RST 39
CLR: Clear Error Pulse CLR 40
P-CL: Forward Torque Limit P-CL 41
N-CL: Reverse Torque Limit N-CL 42
SHOM: Home
ORG: Zero Position
1Ry +24V
7 ALM+
Connect Shield to Connector Shell. Shield Shell
8 ALM-
1D
0V
Photocoupler Output:
Maximum Operating Voltage:DC30V
Maximum Output Current:DC50mA
- 49 -
ProNet Series AC Servo User's Manual
ProNet
Series Servodrives
10K
ref
20 PAO+
40K
Speed Reference(±0~10V/Rated Speed) VREF+ 1 + 21 PAO-
P
40K
VREF- 2 -
22 PBO+ PG Divided Ratio Output:
Applicable Line Receiver
10K A/D 23 PBO- AM26LS32A Manufactured by TI or the Equivalent.
24 PCO+
25 PCO-
50 DGND
1Ry +24V
7 ALM+
8 ALM-
1D
Connect Shield to Connector Shell. Shield Shell
0V
ALM: Servo Alarm Output
Photocoupler Output:
Maximum Operating Voltage:DC30V
Maximum Output Current:DC50mA
Represents Twisted-pair Wires
P
- 50 -
ProNet Series AC Servo User's Manual
ProNet
Series Servodrives
20 PAO+
21 PAO-
22 PBO+ PG Divided Ratio Output:
Applicable Line Receiver
23 PBO- AM26LS32A Manufactured by TI or the Equivalent.
A/D 24 PCO+
ref
TREF+ 26 + 25 PCO-
Torque Reference (±0~10V/Rated Torque)
P
TREF- 27 - 50 DGND
1Ry +24V
7 ALM+
Connect Shield to Connector Shell. 8 ALM-
Shield Shell 1D
0V
ALM: Servo Alarm Output
Photocoupler Output:
Maximum Operating Voltage:DC30V
Maximum Output Current:DC50mA
Represents Twisted-pair Wires
P
- 51 -
ProNet Series AC Servo User's Manual
The servo drive uses high-speed switching elements in the main circuit. It may receive "switching noise" from these
• Position the input reference device and noise filter as close to the servo drive as possible.
• Always install a surge absorber in the relay, solenoid and electromagnetic contactor coils.
• The distance between a power line (servomotor main circuit cable) and a signal line must be at least 30 cm. Do not put
the power and signal lines in the same duct or bundle them together.
• Do not share the power supply with an electric welder or electrical discharge machine. When the servo drive is placed
near a high-frequency generator, install a noise filter on the input side of the power supply line. As for the wiring of noise
3.5mm2 min. *1
CN2 PG
CN1
2
2mm min.
*3 *2
Noise DC
filter power
3.5mm2 min.
2
•For ground wires connected to the ground plate, use a thick wire with a thickness of at least 3.5 mm (preferably, plain
stitch cooper wire)
•When using a noise filter, follow the precautions in 3.6.2 Precautions on Connecting Noise Filter.
- 52 -
ProNet Series AC Servo User's Manual
If the servomotor is grounded via the machine, a switching noise current will flow from the servo drive main circuit through
the servomotor stray capacitance.
Always connect servomotor frame terminal FG to the servo drive ground terminal. Also be sure to ground the ground
terminal .
If the I/O signal line receives noise, ground the 0 V line (SG) of the reference input line. If the main circuit wiring for the
motor is accommodated in a metal conduit, ground the conduit and its junction box. For all grounding, ground at one point
only.
- 53 -
ProNet Series AC Servo User's Manual
Note:
1. A single-phase servomotor should apply a two-phase filter. A three-phase servo drive should apply a
three-phase filter.
2. Choose the right filter according the specifications of operating voltage, current, and manufacturer.
(2) Precautions on Using Noise Filters
Do not put the input and output lines in the same duct or bundle them together.
Noise Noise
Filter Filter
Noise Noise
Filter Filter
Separate the noise filter ground wire from the output lines.
Do not accommodate the noise filter ground wire, output lines and other signal lines in the same duct or bundle them
together.
Noise Noise
Filter Filter
Connect the noise filter ground wire directly to the ground plate. Do not connect the noise filter ground wire to other
ground wires.
- 54 -
ProNet Series AC Servo User's Manual
Noise Noise
Filter Filter
servodrive servodrive servodrive servodrive
stub
Shielded
ground wire
If a noise filter is located inside a control panel, connect the noise filter ground wire and the ground wires from other
devices inside the control panel to the ground plate for the control panel first, then ground these wires.
Control Panel
Servodrive
Noise
Filter
Servodrive
Ground
Ground plate
To adapt a combination of a servomotor and a servodrive to EMC Directives (EN61326-1:2006), the following conditions
must be satisfied.
(1) EMC Installation Conditions
This section describes the installation conditions that satisfy EMC guidelines for each servo drive model.
This section describes the EMC installation conditions satisfied in test conditions prepared by ESTUN. The actual EMC
level may differ depending on the actual system’s configuration, wiring, and other conditions.
- 55 -
ProNet Series AC Servo User's Manual
Ground/Shield Box
Brake power
supply
Servo Drive
Brake
Clamp
U,V,W
Core
Power Supply
Core
Noise
Clamp
Three-phase 200VAC L1,L2,L3
4 filter 2 Servo-
Three-phase 400VAC
L1C,L2C motor
Core
Core
Clamp
Core
CN2 Encoder
3
PE Aprox.2m CN1
Core Aprox.5m PE
1
Core
Host controller
Notes: The example above shows three-phase 200VAC servo drive connection.
(2) Cable Core and Cable Clamp
(a) Attaching the Ferrite Core
The diagram shows two turns in the cable.
The table shows the cable and the position where the ferrite core is attached.
- 56 -
ProNet Series AC Servo User's Manual
The following diagram is an example of the wiring when more than one Servodrive is used.
Connect the alarm output (ALM) terminals for the three Servodrives in series to enable alarm detection relay 1RY to
operate.
When the alarm occurs, the ALM output signal transistor is turned OFF.
Multiple servos can share a single molded-case circuit breaker (QF) or noise filter. Always select a QF or noise filter that
has enough capacity for the total power capacity (load conditions) of those servos.
- 57 -
ProNet Series AC Servo User's Manual
Power supply
R S T
Power
Power ON
QF
OFF 1RY 1KM
1KM
Noise
filter
SA
1KM
L1 Servo Motor
L2 Servo Drive
L3
L1C M
L2C
Notes:
1. Power supply phase-S should connect to ground terminals.
2. The example above shows three-phase 200VAC servo drive connection.
- 58 -
ProNet Series AC Servo User's Manual
Servo drive wiring includes standard wiring (standard wiring refers to 3.5 Standard Wiring Examples) and optional
wiring. Connecting DC bus together of the optional wiring conduces to bus voltage more stable. The following diagram is
an example of the wiring when connecting more than one servo drive DC bus.
Notes:
Connecting DC bus together is available only for 200V ProNet and ProNet-E series servo drives. Please use the
wiring on ProNet-08A/10A, ProNet-E-08A/10A directly, and inquire customer service before wiring on other
products.
- 59 -
ProNet Series AC Servo User's Manual
Chapter 4
Operation
Make sure that all wiring has been completed prior to trial operation.
Perform the following three types of trial operation in order. Instructions are given for speed control mode (standard setting)
and position control mode. Unless otherwise specified, the standard parameters for speed control mode (factory settings)
are used.
(1)Trial Operation for Servomotor Without Load (Refer to 4.1.1)
■ Purpose
The servomotor is operated without connecting the shaft to the
machine in order to confirm the following wiring is correct.
To power supply
(3) Trial operation for servomotor and machine combined. (Refer to 4.1.3)
- 60 -
ProNet Series AC Servo User's Manual
■Purpose
Perform the trial operation with the servomotor
connected to the machine. The servo drive is adjusted to match the
machine characteristics.
·Servomotor speed and machine travel distance.
·Set the necessary parameters.
- 61 -
ProNet Series AC Servo User's Manual
Connect the power supply circuit (L1, L2 and L3), servomotor wiring (U, V,
2 Wiring W), I/O signal wiring (CN1), and encoder wiring (CN2). But during (1) Trial -
Operation for Servomotor Without Load, disconnect the CN1 connector.
Turn the power ON. Using the panel operator to make sure that the servo
Turn the power
3 drive is running normally. If using a servomotor equipped with an absolute -
ON
encoder, please perform the setup for the absolute encoder.
Execute JOG Execute JOG operation with the servomotor alone under the no-load JOG
4
operation condition. Operation
Connect input Connect the input signals (CN1) necessary for trial operation to the
5 -
signals servo drive.
Input the
Host
7 Servo-ON Input the Servo-ON signal, and turn ON the servomotor.
Reference
signal
Input the reference necessary for control mode, and check the servomotor Host
8 Input reference
for correct operation. Reference
Turn the power OFF, and connect the servomotor to the machine.
Protective If using a servomotor equipped with an absolute encoder, set up the absolute
9 -
operation encoder and make the initial settings for the host controller to match the
machine’s zero position.
Using the same procedure as you did to input a reference in step 8,operate
Set necessary the servomotor via the host controller and set the parameter to make sure
10 Host
parameters. the machine’s travel direction, travel distance, and travel speed all
Reference
correspond to the reference.
Host
11 Operation The servomotor can now be operated. Adjust the servo gain if necessary.
Reference
- 62 -
ProNet Series AC Servo User's Manual
·Release the coupling between the servomotor and the machine, and secure only the servomotor without a load.
·To prevent accidents, initially perform the trial operation for servomotor under no-load conditions (with all couplings
and belts disconnected).
In this section, confirm the cable connections of the main circuit power supply, servomotor and encoder. Incorrect wiring is
generally the reason why servomotors fail to operate properly during the trial operation.
Confirm the wiring, and then conduct the trial operation for servomotor without load according to the following steps.
Check the power supply circuit, servomotor, and encoder With the I/O signal connector (CN1) disconnected,
2 wiring. check the power supply circuit and servomotor wiring.
Refer to 3.1 Main Circuit Wiring.
Turn ON the control power supply and main circuit power If the power is correctly supplied, the panel operator
display on the front panel of the servo drive will appear
supply.
as shown on the left. The display on the left indicates
Normal Display that forward run prohibited (P-OT) and reverse run
prohibited (N-OT).
3 If an alarm display appears, the power supply circuit,
servomotor wiring, or encoder wiring is incorrect. If an
Alternate Display
alarm is displayed, turn OFF the power, find the
Example of Alarm Display problem, and correct it.
When using a servomotor with a brake, release the brake Please refer to 4.3.4 Setting for Holding Brakes
Please refer to 4.5 Operating Using Speed Control
first before driving the servomotor.
4 with Analog Reference
When using a servomotor equipped with an absolute
encoder, the encoder setup is required before driving the
servomotor.
- 63 -
ProNet Series AC Servo User's Manual
Press the MODE key. This will turn OFF the power to
6 MODE key
the servomotor.
Press the ENTER key to return to the Fn002 display
7 ENTER key of the utility function mode. Now, the servo drive is
OFF.
Note:
The servomotor’s rotation direction depends on the setting of parameter Pn001.0 (Direction Selection).
The example above describes operation with Pn001.0 in the factory setting.
- 64 -
ProNet Series AC Servo User's Manual
JOG Speed
Speed Position Torque
Pn305
Setting Range Setting Unit Factory Setting Setting Validation
0~6000 rpm 500 Immediately
Set the utility function Fn002 (JOG Mode Operation) to the reference value of servomotor speed.
The servomotor can be operated using only the panel operator without reference from the host controller.
Please note that the Forward Run Prohibited (P-OT) and Reverse Run Prohibited (N-OT) signals are invalid during JOG
mode operation.
4.1.2 Trial Operation for Servomotor without Load from Host Reference
Check that the servomotor move reference or I/O signals are correctly set from the host controller to the servo drive.
Also check the wiring and polarity between the host controller and servo drive, and the servo drive operation settings are
correct. This is the final check before connecting the servomotor to the machine.
The following circuits are required: External input signal circuit or equivalent.
Speed Control
Position Control
(Standard Setting)
[Pn005=H.□□1□]
[Pn005=H.□□0□]
CN1 CN1
+24V +24V
13 13
/S-ON /S-ON
14 14
P-OT P-OT
16 16
N-OT N-OT
17 17
V-REF PULS
1 30
SIGN
32
0V
0V
- 65 -
ProNet Series AC Servo User's Manual
Servodrive
CN1
13
+24V
/S-ON 14
P-OT 16
N-OT 17
V-REF+ 0V
V-REF+ 1
V-REF-
V-REF- 2
GND 3
Max. Voltage (12V)
- 66 -
ProNet Series AC Servo User's Manual
When the servo drive conducts speed control and position control is conducted at the host controller, perform the
operation below,following the operation in Operation Procedure in Speed Control Mode (Pn005=H.□□0□).
- 67 -
ProNet Series AC Servo User's Manual
Pulse reference
/PULS 31
SIGN
Reference pulse 32
according to parameter /SIGN
Pn004.2 setting. 33
- 68 -
ProNet Series AC Servo User's Manual
- 69 -
ProNet Series AC Servo User's Manual
Holding brake operation of the servomotor can be controlled with the brake interlock output (/BK) signal of the servo drive.
When checking the brake operation,take advance measures to prevent vibration due to gravity acting on the machine or
external forces. Check the servomotor operation and holding brake operation with the servomotor separated from the
machine. If both operations are correct, connect the servomotor to the machine and perform trial operation.
Refer to 4.3.4 Setting for Holding Brakes for wiring on a servomotor with brakes and parameter settings.
As described above, be sure to separate the servomotor and machine before performing trial operation of the servomotor
without a load. Refer to the following table, and check the servomotor operation and specifications in advance.
The control modes supported by the ProNet series servo drives are described below.
- 70 -
ProNet Series AC Servo User's Manual
- 71 -
ProNet Series AC Servo User's Manual
This sets the servo ON signal (/S-ON) that determines whether the servomotor power is ON or OFF.
(1)Servo ON signal(/S-ON)
Connector Pin
Type Name Setting Meaning
Number
ON(low level) Servomotor power ON. Servomotor can be operated.
CN1-14
Input /S-ON Servomotor power OFF. Servomotor cannot be
(Factory setting) OFF(high level)
operated.
■Important
Always input the servo ON signal before inputting the input reference to start or stop the servomotor.
Do not input the input reference first and then use the /S-ON signal to start or stop. Doing so will degrade internal
elements and may cause the servo drive to malfunction.
A parameter can be used to re-allocate the input connector number for the /S-ON signal. Refer to 3.2.2 I/O Signal Names
and Functions.
- 72 -
ProNet Series AC Servo User's Manual
The rotation direction of the servomotor can be switched without changing the reference pulse to the servo drive or the
reference voltage polarity.
This causes the rotation the servo motor shaft is rotating to change. The output signal polarity, such as the encoder pulse
output and the analog monitor signal from the servo drive do not change.
The standard setting for “forward rotation” is counterclockwise as viewed from the servomotor load end.
Reference
Parameter Name
Forward reference Reverse reference
b.□□□0 Standard setting
(CCW=forward) CCW
PAO
PAO
PBO PBO
Pn001
b.□□□1 Reverse rotation
mode CCW
CW
(CW=forward) Encoder pulse divisionoutput
Encoder pulse division output
PAO
PAO
PBO
PBO
The direction of P-OT and N-OT change. For Pn001=b.□□□0(standard setting), counterclockwise is P-OT. For
Pn001=b.□□□1(reverse rotation mode), clockwise is P-OT.
- 73 -
ProNet Series AC Servo User's Manual
The overtravel limit function forces movable machine parts to stop if they exceed the allowable range of motion and turn
ON a limit switch.
(1)Connecting the overtravel signal
To use the overtravel function, connect the following overtravel limit switch to the corresponding pin number of servo drive
CN1 connector correctly.
overtravel. Servomotor
CN1
For example, reverse rotation is possible during forward Limit switch Limit switch
P-OT
16
overtravel. N-OT 17
■Important
When using overtravel to stop the servomotor during position control, the position error pulses are present. A clear signal
(CLR) input is required to clear the error pulses.
When using the servomotor on a vertical axis, the workpiece may fall in the overtravel condition.
To prevent this, always set the zero clamp after stopping with Pn004.0=5.
- 74 -
ProNet Series AC Servo User's Manual
signal.
Parameter Meaning
b.□□0□ Inputs the forward rotation prohibited (P-OT) signal from
CN1-16 (factory setting).
b.□□1□ Disables the forward rotation prohibited (P-OT) signal. (Allows constant
forward rotation.)
Pn000
b.□0□□ Inputs the reverse rotation prohibited (N-OT) signal from CN1-17.
(factory setting)
b.□1□□ Disables the reverse rotation prohibited (N-OT) signal. (Allows constant
reverse rotation.)
·Applicable control modes: Speed control, position control, and torque control.
·After changing these parameters, turn OFF the main circuit and control power supplies, and then turn them ON again to
enable the new settings.
·A parameter can be used to re-allocate input connector number for the P-OT and N-OT signals. Refer to 3.2.2 I/O Signal
Names and Functions.
- 75 -
ProNet Series AC Servo User's Manual
·After changing these parameters, turn OFF the main circuit and control power
supplies, and then turn them ON again to enable the new settings.
·Stop by dynamic brake: Stops by using the dynamic brake (short circuiting its
electrical circuit).
·Coast to a stop: Stops naturally, with no brake, by using the friction resistance
of the servomotor in operation.
·Plug braking: Stops by using plug braking limit torque.
·Zero Clamp Mode: A mode forms a position loop by using the position
reference zero.
·Dynamic brake is an emergency stop function, and one of the general methods to cause a servomotor sudden stop.
·Dynamic brake suddenly stops a servomotor by shorting its electrical circuit.
·If the servomotor is frequently started and stopped by turning the power ON/OFF or using the servo ON signal(/S-ON),
the DB circuit will also be repeatedly operated, degrading the servo drive’s internal elements.
·Use the speed input reference and position reference to control the starting and the stopping of the servomotor.
- 76 -
ProNet Series AC Servo User's Manual
The holding brake is used when the servo drive controls a vertical axis.
A servomotor with the brake option helps prevent movable parts from shifting due to gravity when power is removed from
the servo drive.
(Refer to 4.1.4 Trial Operation for Servomotor with Brakes.)
1. The servomotor with the built in brake, is a de-energization brake. It is used to hold the servomotor and cannot be used
as a braking purposes. Use the holding brake only to hold a stopped servomotor.
2. When operating using only a speed loop, turn OFF the servo and set the input reference to 0V when the brake is
applied.
3. When forming a position loop, do not use a mechanical brake while the servomotor is stopped because the servomotor
enters servolock status.
(1)Wiring Example
Use the servo drive sequence output signal /BK and the brake power supply to form a brake ON/OFF circuit.
The following diagram shows a standard wiring example.
Servodrive Servomotor with brake
Power supply
R L1 U
S L2 V
M
T L3 W
L1C
L2C
CN2 PG
CN1
BK-RY (/BK+) *1
+24V
(/BK-) *2
BK
- 77 -
ProNet Series AC Servo User's Manual
Brake interlock output (/BK) is not used with the factory setting.The output signal must be allocated.
Connector Pin Number
Parameter Meaning
+ Terminal - Terminal
The /BK signal is output from output
Pn511 H.□□□4 CN1-11 CN1-12
terminal CN1-11,12.
The /BK signal is output from output
Pn511 H.□□4□ CN1-5 CN1-6
terminal CN1-5,6.
The /BK signal is output from output
Pn511 H.□4□□ CN1-9 CN1-10
terminal CN1-9,10.
■Important
When set to the factory setting, the brake signal is invalid.
For the allocation of servo drive output signals other than /BK signal, refer to 3.2.2 I/O Signal Names and Functions.
0 /COIN(/V-CMP)output
Related parameter:
Parameter Setting
Name Unit Default
No. Range
Pn505 Servo ON waiting time ms -2000~2000 0
Pn506 Basic waiting flow 10ms 0~500 0
Pn507 Brake waiting speed rpm 10~100 100
Pn508 Brake waiting time 10ms 10~100 50
- 78 -
ProNet Series AC Servo User's Manual
Pn505
Setting Range Setting Unit Factory Setting Setting Validation
-2000~2000 ms 0 Immediately
Pn506
Setting Range Setting Unit Factory Setting Setting Validation
Pn506 Pn505
■Important
·The servomotor will turn OFF immediately when an alarm occurs, regardless of the setting of this parameter.
·The machine movable part may shift due to gravity or external force during the time until the brake operates.
- 79 -
ProNet Series AC Servo User's Manual
The following parameters can be used to change the /BK signal output conditions when a stop reference is output during
Pn508
Setting Range Setting Unit Factory Setting Setting Validation
The /BK signal goes to high level (brake ON) when either of the following conditions is satisfied:
· When the servomotor speed falls below the level set in Pn507 after servo OFF.
Servo OFF
/S-ON input Servo ON
or alarm or
power OFF
Servomotor stopped
by applying DB or
Servomotor Speed Pn507 coasting.
(Pn004.0)
Pn508
Determines whether to continue operation or turn the servo OFF when the power supply voltage to the servo drive main
circuit is instantaneously interrupted.
Parameter Signal Name and Meaning
b.0□□□ Continue operation when the power supply voltage to servo drive main circuit is
Pn000 instantaneously interrupted.
b.1□□□ An alarm occurs when the power supply voltage to servo drive main circuit is
instantaneously interrupted.
- 80 -
ProNet Series AC Servo User's Manual
Parameter Meaning
Pn002 b.□0□□ Use the absolute encoder as an absolute encoder. (Factory setting)
·The back-up battery is not required when using the absolute encoder as an incremental encoder.
·After changing these parameters, turn OFF the main circuit and control power supplies and then turn them ON
- 81 -
ProNet Series AC Servo User's Manual
In order for the absolute encoder to retain position data when the power is turned OFF, the data must be backed up by a
battery.
Please purchase the special cable and battery case mabe by Estun if an absolute encoder is used.
- 82 -
ProNet Series AC Servo User's Manual
The servo drive will generate an absolute encoder battery alarm (A.48) when the battery voltage drops below about 3.1V.
1. Replace the battery with only the servo drive control power supply turned ON.
2. After replacing the battery, using the panel operator with utility function Fn011 to cancel the absolute encoder battery
alarm (A.48).
3. Turn ON the servo drive power back again. If it operates without any problems, the battery replacement has been
completed.
Note:
·The servo drive will generate an absolute encoder battery alarm (A.48) when the battery voltage drops below about 3.1V.
·If an absolute encoder battery alarm (A.47) occurred, it means the battery voltage drops below about 2.5V, and the
multiturn data is lost. Please reset the absolute encoder after changing the battery.
Note:
1. Encoder setup operation is only possible when the servo is OFF.
2. If the absolute encoder alarms(A.45~A.48,A.51 ) are displayed, cancel the alarm by using the same method as the
setup. They cannot be cancelled with the servo drive alarm reset input signal(/ALM-RST).
3. Any other alarms that monitor the inside of the encoder should be cancelled by turning OFF the power.
- 83 -
ProNet Series AC Servo User's Manual
Parameter Meaning
Pn005 H.□□0□ Control mode selection:Speed control(analog reference)(factory setting)
- 84 -
ProNet Series AC Servo User's Manual
- 85 -
ProNet Series AC Servo User's Manual
When using the speed control, the servomotor may rotate slowly even if 0V is specified as the analog voltage reference.
This happens if the host controller or external circuit has a slight offset (in the unit of mV) in the reference voltage.
Adjustments can be done manually or automatically by using the panel operator. Refer to 5.2 Operation in Utility
Function Mode.
The servo drive automatically adjusts the offset when the host controller or external circuit has the offset in the reference
voltage.
After completion of the automatic adjustment, the amount of offset is stored in the servo drive. The amount of offset can be
checked in the speed reference offset manual adjustment mode (Fn004). Refer to 4.5.3 (2) Manual Adjustment of the
Note:The speed reference offset must be automatically adjusted with the servo OFF.
1.Turn OFF the servo drive and input the 0V reference voltage from the host controller or external circuit.
- 86 -
ProNet Series AC Servo User's Manual
4.Press the ENTER key to enter into the speed reference offset automatic adjustment mode.
5.Press the MODE key for more than one second, the reference offset will be automatically adjusted.
7.Press ENTER key to return to the Fn003 display of the utility function mode.
- 87 -
ProNet Series AC Servo User's Manual
Use the speed reference offset manual adjustment (Fn004) in the following situations:
·If a loop is formed with the host controller and the postion error pulse is set to be zero when servolock is stopped.
·To check the offset data set in the speed reference offset automatic adjustment mode.
This function operates in the same way as the reference offset automatic adjustment mode (Fn003), except that the
3. Press the ENTER key to enter into the speed reference offset manual adjustment mode.
4. Turn ON the servo ON (/S-ON) signal. The display will be shown as below.
5. Press the ENTER key for one second to display the speed reference offset amount.
- 88 -
ProNet Series AC Servo User's Manual
The soft start function converts the stepwise speed reference inside the servo drive to a consistent rate of acceleration
and deceleration.
Pn310 can be used to select the soft start form:
0: Slope; 1: S curve; 2: 1st-order filter; 3: 2nd-order filter
Soft Start Acceleration Time
Speed
Pn306
Setting Range Setting Unit Factory Setting Setting Validation
0~10000 1ms 0 Immediately
Soft Start Deceleration Time
Speed
Pn307
Setting Range Setting Unit Factory Setting Setting Validation
0~10000 1ms 0 Immediately
The soft start function enables smooth speed control when inputting a stepwise speed reference or when selecting
internally set speeds. Set both Pn306 and Pn307 to “0” for normal speed control.
Set these parameters as follows:
· Pn306:The time interval from the time the servomotor starts until the servomotor maximum speed is reached.
· Pn307:The time interval from the time the servomotor is operating at the servomotor maximum speed until it stops.
- 89 -
ProNet Series AC Servo User's Manual
S-curve Risetime
Speed
Pn309
Setting Range Setting Unit Factory Setting Setting Validation
0~10000 1ms 0 Immediately
The zero clamp function is used for systems where the host controller does not form a position loop for the speed
reference input. When the zero clamp signal(/P-CON)is ON, a position loop is formed inside the servo drive as soon as
the input voltage of the speed reference (V-REF) drops below the servomotor zero clamp speed. The servomotor ignores
the speed reference and quickly stops and locks the servomotor.
The servomotor is clamped within ±1 pulse when the zero clamp function is turned ON, and will still return to the zero
- 90 -
ProNet Series AC Servo User's Manual
(2)Parameter Setting
Parameter Meaning
Pn005 H.□□A□ Control mode: Speed control(analog voltage reference) Zero Clamp
Zero Clamp Conditions:
Zero clamp is performed with Pn005=H.□□A□ when the following two conditions are both satisfied:
·/P-CON is ON (low level)
·Speed reference (V-REF) drops below the setting in Pn502.
/P-CON and /ZCLAMP are the input signals to switch to the zero clamp function.
■Important
In speed control (analog voltage reference) mode,when /ZCLAMP is allocated to an output terminal,zero clamp
function is enabled.
- 91 -
ProNet Series AC Servo User's Manual
Encoder feedback pulses processed inside the servo drive can be output externally.
Type Signal Name Connector Pin Number Name
PAO CN1-20 Encoder output phase A
Output
/PAO CN1-21 Encoder output phase /A
PBO CN1-22 Encoder output phase B
Output
/PBO CN1-23 Encoder output phase /B
PCO CN1-24 Encoder output phase C(zero-point pulse)
Output
/PCO CN1-25 Encoder output phase /C(zero-point pulse)
Encoder CN1
*
CN2 Phase A(PAO)
Serial Data Frequency Phase B(PBO)
PG
dividing
Phase C(PCO)
circuit
* The dividing output phase form is the same as the standard setting (Pn001.0=0) even if in reverse rotation mode
(Pn001.0=1).
■Output phase form
If the servomotor is not equipped with an absolute encoder, the servomotor needs two full rotations before using the servo
drive's Phase-C pulse output as the zero point reference.
Dividing: Dividing means that the divider converts data into the pulse density (Pn200) based on the pulse data of the
encoder installed on the servomotor, and outputs it. The setting unit is number of pulses/revolution.
- 92 -
ProNet Series AC Servo User's Manual
The speed coincidence (/V-CMP) output signal is output when the actual servomotor speed during speed control is the
same as the speed reference input. The host controller uses the signal as an interlock.
Type Signal Name Connector Pin Number Setting Meaning
CN1-11,12 ON(low level) Speed coincides.
Output /V-CMP(/COIN)
(factory setting) OFF(high level) Speed does not coincide.
Coincidence Difference
Speed
Pn501
Setting Range Setting Unit Factory Setting Setting Validation
0~100 rpm 10 Immediately
The /V-CMP signal is output when the difference between the speed reference and actual servomotor speed is less than
Pn501.
■Example
The /V-CMP signal turns ON at 1900 to 2100rpm if the Pn501 parameter is set to 100 and the reference speed is
2000rpm.
■Note
This pin outputs the /COIN signal in position control mode, and the /V-CMP signal in speed control mode.
- 93 -
ProNet Series AC Servo User's Manual
Set the following parameters for position control using pulse trains.
Parameter Meaning
Pn005 H.□□1□ Control mode selection:position control (pulse train reference)
×4
PG
Pn200
PG signal output
dividing Encoder
Pn006 0□□□ when pulse is difference input, servo receiving pulse frequency ≤4M
1□□□ when pulse is difference input, servo receiving pulse frequency ≤650K
2□□□ when pulse is difference input, servo receiving pulse frequency ≤150K
- 94 -
ProNet Series AC Servo User's Manual
(factory setting)
PULS
(CN1-30)
L PULS
CW+CCW SIGN
(CN1-30)
H.□1□□ — (CN1-32)
Pn004 (positive logic)
SIGN
(CN1-32) L
PULS
(CN1-30)
SIGN
(CN1-32)
×1倍
×4倍
- 95 -
ProNet Series AC Servo User's Manual
200kpps)
×2 input pulse multiplier:400kpps Phase B leads A by 90º. Phase B lags B by 90º. multiplier mode.
×4 input pulse multiplier:
200kpps
(6)Connection Example
The pulse train output form from the host controller corresponds to the following:
• Line-driver Output
• +24V Open-collector output
• +12V/+5V Open-collector output
Line-driver CN1
* Photocoupler
PULS 30 150Ω
/PULS 31
SIGN 32 150Ω
/SIGN 33
*
Represents twisted-pair wires。
- 96 -
ProNet Series AC Servo User's Manual
Servodrive
Host controller
1CN-30 75Ω
PULS
R
NOTE:
75Ω VDC=12~24V
/PULS 1CN-31
R=(VDC-1.5Volt)/10mA-150
VDC VDC=12V,
1CN-34 2KΩ
R=1KΩ/0.25W
2KΩ
1CN-32
VDC=24V,
SIGN
75Ω R=2KΩ/0.25W
/SIGN 1CN-33
R 75Ω
GND
Servodrive
Host controller
1CN-30 75Ω
PULS
75Ω
NOTE:
/PULS 1CN-31
VDC=12~24V
R R=(VDC-1.5Volt)/10mA-150
VDC
1CN-34 2KΩ
VDC=12V,
2KΩ R=1KΩ/0.25W
SIGN 1CN-32
75Ω
VDC=24V,
R=2KΩ/0.25W
/SIGN 1CN-33
75Ω
R
GND
Note:When the host controller is applied by open-collector signal output, the input signal noise margin lowers. When a
position error caused by the noise occurs, set the parameter Pn006.3.
- 97 -
ProNet Series AC Servo User's Manual
□□0□ Clear the error pulse when S-OFF, do not when overtravel.
□□2□ Clear the error pulse when S-OFF or overtravel (excep for zero clamp)
(1)Electronic Gear
The electronic gear enables the workpiece travel distance per input reference pulse from the host controller to be set to
any value.
One reference pulse from the host controller, i.e., the minimum position data unit, is called a reference unit.
When the Electronic Gear is Not Used When the Electronic Gear is Used
workpiece workpiece
Reference unit:1µm
- 98 -
ProNet Series AC Servo User's Manual
(2)Related Parameters
Electronic Gear Ratio (Numerator)
Position
Pn201
Setting Range Setting Unit Factory Setting Setting Validation
1~65535 — 1 After restart
Electronic Gear Ratio (Denominator)
Position
Pn202
Setting Range Setting Unit Factory Setting Setting Validation
1~65535 — 1 After restart
The deceleration ratio of the servomotor and the load shaft is given as n/m where m is the
rotation of the servomotor and n is the rotation of the load shaft.
·If the ratio is outside the setting range, reduce the fraction (both numerator and denominator) until you obtain integers
within the range.
·Be careful not to change the electronic gear ratio (B/A).
■Important
·Electronic gear ratio setting range: 0.01≤electronic gear ratio(B/A)≤ 100
·If the electronic gear ratio is outside this range, the servo drive will not operate properly. In this case, modify the load
configuration or reference unit.
- 99 -
ProNet Series AC Servo User's Manual
The following examples show electronic gear ratio settings for different load configurations.
Load Configuration
Ball Screw Disc Table Belt and Pulley
Reference unit:0.01mm
Reference unit:0.001mm
Load shaft Load shaft
Step Operation
Deceleration ratio: Pulley diameter:
17-bit encoder Ball screw pitch:6mm F 100mm
2:1
17-bit encoder
Pulley diameter:100 mm
Check machine Ball screw pitch:mm Rotation angle per revolution
1 (pulley circumference:314 mm)
specifications. Deceleration ratio:1/1 :360° Deceleration ratio:3/1
·Deceleration ratio:2/1
2 Encoder 17-bit:32768P/R 17-bit:32768P/R 17-bit:32768P/R
Determine the
1 reference unit:
3 reference unit 1 reference unit:0.1° 1 reference unit:0.01mm
0.001mm(1μm)
used
Calculate the
travel distance
4 6mm/0.001mm=6000 360°/0.1°=3600 314mm/0.01mm=31400
per load shaft
revolution
Calculate the
B 32768 4 1 B 32768 4 3 B 32768 4 2
5 electronic gear
A 6000 1 A 3600 1 A 31400 1
ratio
Pn201 131072 Pn201 393216 Pn201 262144
6 Set parameters
Pn202 6000 Pn202 3600 Pn202 31400
Pn201 32768 Pn201 32768 Pn201 32768
7 Final Result
Pn202 1500 Pn202 300 Pn202 3925
·Reduce the fraction (both numerator and denominator) if the calculated result will not be within the setting range.
·For example, reduce the above numerators and denominators by four or other numbers to obtain the final results in step
7 and complete the settings.
(5)Electronic Gear Ratio Equation
Servomotor n
Pitch=P(mm/rev)
Reference pulse B +
Position Speed
A — loop loop m
(mm / P )
(mm / P ) : Reference unit ×4
PG(P/rev))
PG(P/rev)):Encoder pulses
P(mm/rev):Ball screw pitch
m
:Deceleration ratio
n
n p B
( ) 4 PG m
A
B 4 PG m 4 PG m
( ) Set A and B with the following parameters:
A n p P n
A :Pn202 B :Pn201
- 100 -
ProNet Series AC Servo User's Manual
4.6.4 Smoothing
Parameter Description
0:1st-order filter
Pn205
1:2nd-order filter
* After changing the parameter, turn OFF the power once and turn it ON again to enable the new setting.
(2)Filter-related Parameters
Position Reference Acceleration/Deceleration Time Constant
Position
Pn204
Setting Range Setting Unit Factory Setting Setting Validation
0~32767 0.1ms 0 Immediately
■Important
When the position reference acceleration/deceleration time constant (Pn204) is changed, a value with no reference
pulse input and a position error of 0 will be enabled. To ensure that the setting value is correctly reflected, stop the
reference pulse from the host controller and input the clear signal (CLR), or turn OFF to clear the error.
This function provides smooth servomotor operation in the following cases.
· When the host controller that outputs a reference that cannot perform acceleration/deceleration processing.
· When the reference pulse frequency is too low.
· When the reference electronic gear ratio is too high (i.e., 10× or more)
- 101 -
ProNet Series AC Servo User's Manual
(1)Note:
For the low rigidity load, low frequency vibration will occur continually at the front end of the load during fast acceleration
or fast deceleration. The vibration may delay positioning time and affect the productive efficiency.
The function of low frequency vibration suppression is embedded in ProNet series servo drives by calculating the load
(2)Application:
Low frequency vibration suppression function is enabled in both speed control mode and position control mode.
Low frequency vibration suppression function is disabled or can not reach the expected effect in the following conditions.
Write the frequency data measured (unit:0.1Hz) directly to Parameter Pn411, if the vibration frequency can be
- 102 -
ProNet Series AC Servo User's Manual
Related Parameters
Parameter Meaning
H.□0□□ 0:Low frequency vibration suppression function disabled
Pn006
H.□1□□ 1:Low frequency vibration suppression function enabled
- 103 -
ProNet Series AC Servo User's Manual
This signal indicates that servomotor movement has been completed during position control. Use the signal as an
interlock to confirm that positioning has been completed at the host controller.
Type Signal Name Connector Pin Number Setting Meaning
CN1-11,CN1-12 ON (low level) Positioning has been
(Factory setting) completed.
Output /COIN
OFF (high level) Positioning is not
completed.
·This output signal can be allocated to an output terminal with parameter Pn511. Refer to 3.2.2 I/O Signal Names and
Functions.
·The factory setting is allocated to CN1-11,12.
Positioning Error
Position
Pn500 Setting Range Setting Unit Factory Setting Setting Validation
0~5000 1Puls 10 Immediately
Position complete time
Position
Pn520
Setting Range Setting Unit Factory Setting Setting Validation
0~60000 0.1ms 500 Immediately
·The positioning completion (/COIN) signal is output when the difference (position error pulse) between the number of
reference pulses output by the host controller and the travel distance of the servomotor is less than the value set in this
parameter and the stabilization time is more than the value of Pn520.
·Set the number of error pulses in reference unit (the number of input pulses defined using the electronic gear).
·Too large a value at this parameter may output only a small error during low-speed operation that will cause the /COIN
signal to be output continuously.
·The positioning error setting has no effect on final positioning accuracy.
Reference
Speed Servomotor speed
Pn500
Error pulse
(Un011,Un012)
/COIN
(CN1-11,12)
■Note
·/COIN is a position control signal.
·This signal is used for the speed coincidence output /V-CMP for speed control, and it always OFF (high level) for torque
control.
- 104 -
ProNet Series AC Servo User's Manual
(1)Description
This function inhibits the servo drive from counting input pulses during position control.
Pn005.1
Pn005=H.□□1□
OFF +
Reference pulse
Pn005=H.□□B□ Error Counter
ON -
/P-CON
/P-CON
Feedback pulse
(2)Setting Parameters
Parameter Meaning
Pn005 H.□□B□ Control mode selection:position control(pulse train reference)⇔INHIBIT
■Inhibit(INHIBIT) switching condition
·/P-CON signal ON (low level)
- 105 -
ProNet Series AC Servo User's Manual
Position control under contact reference (parameter Pn005.1=C). In this mode, servo drive can position with a single
axes without a host controller.
There are 16 position control points with each being able to set move distance, running speed, constants for position
reference filter time, and the stop time when positioning completed. Two speeds (1. speed moving toward distance switch
“speed of looking for reference point”. 2. Speed moving away from distance switch “moving speed.”) of reference points
could be set as:
Two position modes: 1. Absolute position mode 2. Relative position mode
Two running modes: 1. Circling mode 2. Non-circling mode
Two step switching method: 1. Delay step switching 2. /P-CON signal switching
Method of looking for reference points: 1. Forward direction 2. Reverse direction
■Adjusting offset
Offset of each points has two correspondent parameters: one unit of the parameter is 【x 10000 reference pulse】and the
other is 【x 1 reference pulse】. Setting range of both parameters is: (-9999----+9999), while offset value equals sum of
those two values.
For example:
No.0 offset correspond to parameter Pn600【x 10000 reference pulse】 and Pn601【x 1 reference pulse】. Set Pn600
= 100, Pn601=-100.
No.0 offset value = Pn600x10000 reference pulse + Pn601x1 reference pulse
= 100x10000 reference pulse + (-100)x1 reference pulse
= 999900 reference pulse
With the same principle, we can conclude: in order to get the same results, we also can set Pn600 = 99 and Pn601 =
9900.
Thus, we can see when the two parameters are not zero; we can get same result by two ways: one is to set the two
parameters both negative or both positive, or one negative the other positive.
■Speed
Speed mentioned here refers to the steady speed during which the motor is running, which is similar to the pulse
frequency given from the external pulse reference in position control.However, this speed has nothing to do with the
electronic gear; it is the actual speed of the motor.
- 106 -
ProNet Series AC Servo User's Manual
Setting
Para. No. Name and description Default
range
[0] Clear error pulse when S-0FF, not clear error pulse
when overtravel.
Pn004.1 0~2 0
[1] Not clear error pulse
[2] Clear error pulse When S-OFF or over travel
Usually, the set speed of the reference point (Pn685) is high, and the moving speed (Pn686) is low. Note: if moving
speed is too high, precision of finding a reference point would be affected.
When looking for a reference point, /PCL and /NCL are no longer programmed to limit external current.
- 107 -
ProNet Series AC Servo User's Manual
■ Related parameter
Para. No. Description Observation
Choose between cycle run and single run. Changing steps will be performed till
0: Cycle run, /PCL as start signal, /NCL reverse to the end point is completed comma
look for reference point. and the next change will start from
1: Single run, /PCL as start signal, /NCL reverse to the start point during multi-points
Pn681.0 look for reference point. cycle run.
2. Cycle run, /NCL as start signal, /PCL reverse to Point control program will not
look for reference point. change steps after the end point is
3. Single run, /NCL as start signal, /PCL reverse to completed during multi- points single
look for reference point. run.
Change steps by external /P-CON
Change step and start mode
signals. The signal will be valid when
0: Delay changing steps, the start signal is not
drive output reaches the desired
needed.
Pn681.1 position. When input signal changes,
1: Change steps by /P-CON, start signal not needed.
the signal is valid, then steps will be
2. Delay changing steps, need start signal.
changed by consequence from start
3. Change steps by /P-CON, need start signal.
point to end point.
Change step input signal mode
Pn681.2 [0] High or low level
[1] sign pulse
Incremental: relative moving
distance (distance from current point
to next point) programming.
0: Incremental
Pn682 Absolute: absolute moving distance
1: Absolute
(distance between operating
platform and the reference point)
programming.
- 108 -
ProNet Series AC Servo User's Manual
In position control mode, the servomotor always needs to operate at a fixed position. This position is normally regarded as
the zero position. When the host controller is turned on, the zero position adjustment is required before processing. This
zero position will be regarded as the reference point. ESTUN servo drives can perform this function by the homing
function.
(2)Related parameter:
- 109 -
ProNet Series AC Servo User's Manual
Pn511 H.□□8□ CN1-5 CN1-6 The signal is output from output terminal CN1-5,6.
Pn511 H.□8□□ CN1-9 CN1-10 The signal is output from output terminal CN1-9,10.
·After changing Pn510, turn OFF the main circuit, and control power supplies, and then turn them ON again to enable
the new settings.
·/HOME signal is only enabled at low level.
Please set Pn689 according to the actual operation in position control mode. When starting the homing function, the
servomotor will run at the speed of Pn685 when detecting the rising edge of SHOM signal; the servomotor will run at the
speed of Pn686 according to the setting of Pn689.1 when detecting the valid ORG signal.
When input ORG and the encoder C-Pulse is being detected, the servo drive will begin to calculate the number of homing
offset pulses. When offset pulses is completed, the servomotor stops and outputs homing completion signal /HOME, then
homing control is completed.
Pn685 (Hitting the origin signal (ORG)) is usually set at high speed, Pn686 (Leaving the origin signal ORG) is usually set
at low speed.
Please be attention that if Pn686 is setting too high, the precision of mechanical zero position will be affected.
After hitting the origin signal ORG, the motor will return to find C-pulse; the figure is shown as below:
Speed Pn 685
(rpm)
Pn 686
ORG
Encoder C-pulse
- 110 -
ProNet Series AC Servo User's Manual
Corresponding position:
After hitting the origin signal ORG, the motor will find C-pulse directly; the figure is shown as below:
Speed Pn 685
rpm
Pn 686
Find C-pulse without
0rpm returning
ORG
Encoder C-pulse
Corresponding position:
Mechanical shaft
Encoder C-pulse
ORG
Rising edge
SHOM
- 111 -
ProNet Series AC Servo User's Manual
The following parameters must be set for torque control operation with analog voltage reference.
Parameter Meaning
Pn005 H.□□2□ Control mode selection:Torque control(analog voltage reference)
- 112 -
ProNet Series AC Servo User's Manual
By applying a torque reference determined by the analog voltage reference to the servo drive, the servomotor torque can
GND
The internal torque reference can also be checked with an analog monitor.
- 113 -
ProNet Series AC Servo User's Manual
After completion of the automatic adjustment, the amount of offset is stored in the servo drive. The amount of offset can
be checked in the manual adjustment of torque reference offset(Fn004).
The automatic adjustment of analog reference offset(Fn003) cannot be used when a position loop has been formed with
the host controller and the error pulse is changed to zero at the servomotor stop due to servolock.
Use the torque reference offset manual adjustment(Fn004).
Note:
The analog reference offset must be automatically adjusted with the servo OFF.
- 114 -
ProNet Series AC Servo User's Manual
During torque control, the servomotor is controlled to output the specified torque, which means that the servomotor speed
is not controlled. Accordingly, when an excessive reference torque is set for the mechanical load torque, it will prevail over
the mechanical load torque and the servomotor speed will greatly increase.
This function serves to limit the servomotor speed during torque control to protect the machine.
Without Speed Limit With Speed Limit
- 115 -
ProNet Series AC Servo User's Manual
The function of internally set speed selection allows speed control operation by externally selecting an input signal from
among seven servomotor speed setting made in advance with parameters in the servo drive. The speed control
operations within the three settings are valid. There is no need for an external speed or pulse generator.
- 116 -
ProNet Series AC Servo User's Manual
Parameter Meaning
Pn005 H.□□3□ Control mode selection:
Speed control(contact reference) Speed control(zero reference)
Pn316
Setting Range Setting Unit Factory Setting Setting Validation
Pn317
Setting Range Setting Unit Factory Setting Setting Validation
Pn318
Setting Range Setting Unit Factory Setting Setting Validation
Pn319
Setting Range Setting Unit Factory Setting Setting Validation
Pn320
Setting Range Setting Unit Factory Setting Setting Validation
Pn321
Setting Range Setting Unit Factory Setting Setting Validation
Pn322
Setting Range Setting Unit Factory Setting Setting Validation
- 117 -
ProNet Series AC Servo User's Manual
The following input signals are used to switch the operating speed.
Type Signal Name Connector Pin Number Meaning
Input /P-CON CN1-15 Selects the internally set speed.
Input /P-CL CN1-41 Selects the internally set speed.
Input /N-CL CN1-42 Selects the internally set speed.
Use ON/OFF combinations of the following input signals to operate with the internally set speeds.
When Pn005.1=3: Selects the internally set speed (contact reference) Speed control (zero reference)
Input Signal
Speed
/P-CON /P-CL /N-CL
Input Signal
Speed
/P-CON /P-CL /N-CL
- 118 -
ProNet Series AC Servo User's Manual
The servo drive provides the following three methods for limiting output torque to protect the machine.
NO. Limiting Method Reference Section
1 Internal torque limit 4.9.1
2 External torque limit 4.9.2
3 Torque limiting by analog voltage reference 4.9.3
Maximum torque is always limited to the values set in the following parameters.
Forward Torque Limit
Speed Position Torque
Pn401 Setting Range Setting Unit Factory Seeting Setting Validation
0~300 1% 300 Immediately
Reverse Torque Limit
Speed Position Torque
Pn402 Setting Range Setting Unit Factory Seeting Setting Validation
0~300 1% 300 Immediately
·The setting unit is a percentage of rated torque.
·The maximum torque of the servomotor is used, even though the torque limit is set higher than the maximum torque of
the servomotor. (as is the case with the 300% factory setting)
Pn402
t
t
Pn401
Speed Speed
Limiting torque
Maximum torque
■Note:
Too small a torque limit setting will result in insufficient torque during acceleration and deceleration.
- 119 -
ProNet Series AC Servo User's Manual
This function allows the torque to be limited at specific times during machine operation, for example, during press stops
An input signal is used to enable the torque limits previously set in parameters.
(1)Related Parameters
Forward External Torque Limit
Speed Position Torque
Pn403 Setting Range Setting Unit Factory Setting Setting Validation
0~300 1% 100 Immediately
Reverse External Torque Limit
Speed Position Torque
Pn404 Setting Range Setting Unit Factory Setting Setting Validation
0~300 1% 100 Immediately
Note: The setting unit is a percentage of rated torque (i.e., the rated torque is 100%).
(2)Input Signals
Signal Connector Pin
Type Setting Meaning Limit Value
Name Number
CN1-41 ON(low level) Forward external torque limit Pn403
Input /P-CL
(factory setting) OFF(high level) Forward internal torque limit Pn401
CN1-42 ON(low level) Reverse external torque limit Pn404
Input /N-CL
(factory setting) OFF(high level) Reverse internal torque limit Pn402
When using this function, make sure that there are no other signals allocated to the same terminals as /P-CL and /N-CL.
Torque
High 0
level
Pn403
Speed
/N-CL
(Reverse
External
Torque Pn404
Torque
Limit Input)
Low
0
level
Speed
Pn401
Note: Select the servomotor rotation direction by setting Pn001=b.□□□0 (standard setting, CCW=Forward direction).
- 120 -
ProNet Series AC Servo User's Manual
Torque limiting by analog voltage reference limits torque by assigning a torque limit in an analog voltage to the T-REF
terminals (CN1-26,27). This function can be used only during speed or position control, not during torque control.
Refer to the following block diagram when the torque limit with an analog voltage reference is used for speed control.
Important:
·There is no issue with input voltage polarity of the analog voltage reference for torque limiting.
·The absolute values of both + and – voltages are input, and a torque limit value corresponding to that absolute
value is applied in the forward or reverse direction.
Related Parameters
Parameter Meaning
Pn001 b.□1□□ Use the T-REF terminal to be used as an external torque limit input.
- 121 -
ProNet Series AC Servo User's Manual
The methods and conditions for switching the servo drive control modes are described below.
The following control mode combinations can be selected according to the individual application of the user.
Parameter Control Method
H.□□4□ Speed control (contact reference) Speed control (analog voltage reference)
H.□□5□ Speed control (contact reference) Position control (pulse train reference)
H.□□6□ Speed control (contact reference) Torque control (analog voltage reference)
H.□□7□ Position control (pulse train reference) Speed control (analog voltage reference)
H.□□8□ Position control (pulse train reference) Torque control (analog voltage reference)
Pn005 H.□□9□ Torque control (analog voltage reference) Speed control (analog voltage reference)
H.□□A□ Speed control (analog voltage reference) Zero clamp
H.□□B□ Position control (pulse train reference) Position control (inhibit)
H.□□C□ Position control (contact reference)
H.□□D□ Speed control (Parameter reference)
H.□□E□ Special control
With the sequence input signals in the factory setting, the control mode will switch when both /P-CL and /N- CL signals
- 122 -
ProNet Series AC Servo User's Manual
The following diagram shows the right way to connect the Alarm Output.
An external +24V I/O power supply is required since there is no +24V power source available inside the servo drive.
Output → ALM+ 1CN- 7 Servo alarm output
Output → ALM- 1CN- 8 Servo alarm output uses grounding signal
ALM outputs a signal when the servo drive is detected in an abnormal state.
Normally, the external circuit consists of /ALM should be able to switch off the power of servo drive.
When “servo alarm(ALM)” happens, always remove alarm reasons first , and then turn the input signal "/ALM-RST" to ON
position to reset alarm status.
Normally, the external circuit can switch off the power supply of the servo drive when an alarm occurs. When
powered on again, the servo drive removes the alarm automatically, so the alarm reset is not required to be connected. In
addition, the alarm reset is enabled with the panel operator.
Note: When an alarm occurs, remove the alarm reason before resetting the alarms.
- 123 -
ProNet Series AC Servo User's Manual
·Related parameter
Rotation Detection Speed TGON
Speed Position Torque
Pn503
Setting range Setting unit Factory setting Setting validation
0~3000 rpm 20 Immediately
·This parameter sets the range in which the rotation detection output signal (/TGON) is output
·When the servomotor rotation speed is above the value set in the Pn503,the servomotor rotation speed signal
(/TGON) is output.
·The rotation detection signal can also be checked on the panel operator.
·This signal indicates that the servo drive received the servo ON signal and completed all preparations.
·It is an output when there are no servo alarms and the main circuit power supply is turned ON.
Not including this setting in ON (low level) With encoder C pluse output
the default setting,
Output /PGC please choose terminal Without encoder C pluse
OFF (high level)
output by setting output
parameter Pn511.
This signal indicates when the servo drive circumrotates to the C pulse position; there is a correlation between the width
- 124 -
ProNet Series AC Servo User's Manual
When machine is on over travel state,OT signal is OFF;Host controller can use this signal to stop sending
reference.
Related parameter
POT/NOT
Speed Position Torque
Pn000
Setting Range Unit Factory Setting Setting Validation
0~1111 - 0 After restart
Pn000.1=1,external POT disabled;Pn000.2=1, external NOT disabled;
Pn000.1=1 and Pn000.2=1,OT signal is ON.
Servo Drive
24V Power
supply
Photocoupler output +24V
1CN- /CLT+
Max.applicable Voltage:
DC30V
Max.applicable current: 1CN- /CLT-
DC50mA
->Output /CLT Torque limit output Speed, torque control, position control
- 125 -
ProNet Series AC Servo User's Manual
Please use the following user constants to define output signals and pins when using /CLT signal.
Pn511.0=3
1CN-11,1CN-12
/CLT
Torque limit Pn511.1=3
output 1CN-05,1CN-06
Pn511.2=3
1CN-09,1CN-10
Output terminal
- 126 -
ProNet Series AC Servo User's Manual
Online autotuning calculates the load moment of inertia during operation of the servo drive and sets parameters so that
the servo gains are consistent with the machine rigidity.
Online autotuning may not be effective in the following cases:
• The motor high speed is lower than 100 rpm.
• The motor acceleration or deceleration is lower than 5000rpm/s.
• Load rigidity is low and mechanical vibration occurs easily or friction is high.
•The speed load moment is changed greatly.
• Mechanical gas is very large.
If the condition meets one of the above cases or the desired operation cannot be achieved by the online autotuning,
set the value in Pn106 (Load inertia percentage) and perform the adjustment manually.
- 127 -
ProNet Series AC Servo User's Manual
!WARNING
■Do not perform extreme adjustment or setting changes causing unstable servo operation.Failure to observe
this warning may result in injury and damages to the machine.
■ Adjust the gains slowly while confirming motor operation.
Start
No
Yes
No
No
End
- 128 -
ProNet Series AC Servo User's Manual
Related parameters:
Parameter Setting Factory Setting
Name Unit
No. Range Setting Invalidation
Online autotuning setting
0:Manual gain adjustment
1,2,3= Normal mode;4,5,6=Vertical load
Pn100 — 0~6 1 After restart
1,4 = Load inertia without variation;
2,5 = Load inertia with little variation;
3,6= Load inertia with great variation
There are 16 machine rigidity settings for online autotuning, When the machine rigidity setting is selected, the servo
gains (speed loop gain, speed loop integral time constant, position loop gain) are determined automatically. The
factory setting for the machine rigidity setting is 5.
Machine Position Loop Gain【s-1】 Speed Loop Gain【Hz】 Speed Loop Integral Time
Rigidity Setting Pn104 Pn102=Pn104*( Pn128+1) Constant【0.1ms】
Pn103
0 10 40 800
1 15 60 600
2 20 80 450
3 25 100 400
4 30 120 300
5 40 160 200
6 65 260 140
7 80 320 110
8 100 400 90
9 120 480 80
10 140 560 70
11 160 640 60
12 180 720 55
13 210 840 50
14 250 1000 40
15 300 1200 30
- 129 -
ProNet Series AC Servo User's Manual
Chapter 5
Panel Operator
The panel operator is a built-in operator that consists of display section and keys located on the front panel of the servo
drive.
Parameter setting, status display ,and execution of utility function are enabled using the panel operator.
The names and functions of the keys on the panel operator are shown as follows:
Panel Corresponding
Function
Symbol Key Name
·To display the parameter settings and setting values.
▲ INC key
·To increase the setting value.
▼ DEC key
·To decrease the setting value.
·To select a basic mode, such as the display mode, parameter setting
M MODE key mode, monitor mode, or utility function mode.
◄ ENTER key To display the parameter settings and setting values, and release ararm.
Note: In this manual, the Panel Symbol is represented by Corresponding Key Name for easy understanding.
Servo alarms can be reset by pressing the ENTER key when the panel operator in display mode. Servo alarms can also
There is no need to clear the servo alarms if it turns the main circuit power supply OFF.
Note:After an alarm occurs, remove the cause of the alarm before resetting it.
- 130 -
ProNet Series AC Servo User's Manual
The basic modes include status display mode, parameter setting mode, monitor mode, and utility function mode. Each
time the MODE key is pressed, the next mode in the sequence is selected.
Select a basic mode to display the operation status, set parameters and operation references.
The basic mode is selected in the following order.
Power ON
Monitor mode
The status display mode displays the servo drive status as bit data and codes.
Selecting Status Display Mode
The status display mode is selected when the power supply is turned ON. If it is not displayed, select this mode by
pressing MODE key.
Note that the display differs between the speed/torque control and position control types.
- 131 -
ProNet Series AC Servo User's Manual
2
○ Base lock Lit for base block. Not lit at servo ON. Base block Lit for base block. Not lit at servo ON.
Codes Display
Code Meaning
Baseblock
Servo OFF (servomotor power OFF)
Run
Servo ON(servomotor power ON)
Forward Run Prohibited
CN1-16(P-OT)is OFF.
Reverse Run Prohibited
CN1-17(N-OT)is OFF.
Alarm Status
Displays the alarm number.
Press ENTER key to clear the present servo alarm.
- 132 -
ProNet Series AC Servo User's Manual
The servo drive offers a large number of functions, which can be selected or adjusted by the parameter settings. Refer to
A.1 Parameter List for details.
■Parameter Setting Procedures
The parameter settings can be used for changing parameter data. Before changing the data, check the permitted range of
the parameter.
The example below shows how to change parameter Pn102 from “100” to “85”.
1. Press MODE key to select the parameter setting mode.
4. Press the INC or DEC key to change the data to the desired number 00085. Hold the key to accelerate the changing
of value. When the maximum value or minimum value is reached, pressing INC or DEC key respectively, will have no
effect.
5. Press the ENTER or MODE key once to return to the display of Pn102.
- 133 -
ProNet Series AC Servo User's Manual
The monitor mode allows the reference values input into the servo drive, I/O signal status, and servo drive internal status
to be monitored.
The example below shows how to display the value (1500) stored in Un001.
1.Press MODE key to select the monitor mode.
2.Press the INC or DEC key to select the monitor number to display.
3.Press the ENTER key to display the data for the monitor number selected at step 2.
4.Press the ENTER key once more to return to the monitor number display.
- 134 -
ProNet Series AC Servo User's Manual
- 135 -
ProNet Series AC Servo User's Manual
- 136 -
ProNet Series AC Servo User's Manual
In utility function mode, the panel operator can be used to run and adjust the servo drive and servomotor.
The following table shows the parameters in the utility function mode.
Parameter No. Function
Fn000 Alarm traceback data display
Fn001 Parameter setting initialization
Fn002 JOG mode operation
Fn003 Automatic adjustment of speed reference offset
Fn004 Manual adjustment of speed reference offset
Fn005 Automatic adjustment of servomotor current detection
Fn006 Manual adjustment of servomotor current detection
Fn007 Software version display
Fn008 Position teaching
Fn009 Static inertia detection
Fn010 Absolute encoder multiturn data and alarm reset
Fn011 Absolute encoder related alarms reset
Note: Fn010、Fn011 only can be used when the servomotor mounted the absolute encoder.
The alarm traceback display can display up to 10 previously occurred alarms.The alarm is displayed on Fn000, which is
stored in the alarm traceback data.
Follow the procedures below to confirm alarms which have been generated.
1. Press the MODE key to select the utility function mode.
2. Press the INC or DEC key to select the function number of alarm trace back data display.
3. Press the ENTER key once, the latest alarm data is displayed.
Alarm Sequence Number Alarm Code
4. Press the INC or DEC key to display other recent alarms that have occurred.
Note: Hold the ENTER key for one second with alarm code displaying, all the alarm traceback datas will be cleared.
- 137 -
ProNet Series AC Servo User's Manual
4. Hold the ENTER key for one second, the parameters will be initialized.
5. Release the ENTER key to ruturn to the utility function mode display Fn001.
Note:
Press the ENTER key during servo ON does not initialize the parameter settings.
Initialize the parameter settings with the servo OFF.
- 138 -
ProNet Series AC Servo User's Manual
4. Press the MODE key to enter into servo ON (servomotor power ON) status.
5. Press the MODE key to switch between the servo ON and servo OFF status.The servo drive must be in servo ON
status when the servomotor is running.
6. Press the INC or DEC key to rotate the servomotor.
7. Press the ENTER key to return to utility function mode display Fn002. Now the servo is OFF(servomotor power OFF).
- 139 -
ProNet Series AC Servo User's Manual
When using the speed/torque (analog reference) control, the servomotor may rotate slowly even if 0V is specified as the
This happens if the host controller or external circuit has a slight offset (in the unit of mV) in the reference voltage.
The reference offset automatic adjustment mode automatically measures the offset and adjusts the reference voltage. It
The servo drive automatically adjusts the offset when the host controller or external circuit has the offset in the reference
voltage.
After completion of the automatic adjustment, the amount of offset is stored in the servo drive. The amount of offset can be
checked in the speed reference offset manual adjustment mode (Fn004). Refer to 4.5.3 (2) Manual Adjustment of the
1. Turn OFF the servo drive, and input the 0V reference voltage from the host controller or external circuit.
4. Press the ENTER key to enter into the speed reference offset automatic adjustment mode.
5. Press the MODE key for more than one second, the reference offset will be automatically adjusted.
- 140 -
ProNet Series AC Servo User's Manual
6. Press the ENTER key to return to the utility function mode display Fn003.
Manual adjustment of the speed/torque reference offset is used in the following cases:
If a position loop is formed with the host controller and the error is zeroed when servolock is stopped.
To deliberately set the offset to some value.
Use this mode to check the offset data that was set in the automatic adjustment mode of the speed/torque reference
offset.
This mode operates in the same way as the automatic adjustment mode, except that the amount of offset is directly input
Note:
When the offset using in automatic adjustment exceeds the manual adjustment range (-1024~+1024),
manual adjustment will be invalid.
3. Press the ENTER key to enter into the speed reference offset manual adjustment mode.
- 141 -
ProNet Series AC Servo User's Manual
5. Hold the ENTER key, the speed reference offset will be displayed.
Automatic servomotor current detection offset adjustment is performed at ESTUN before shipping. Basically, the user
does not need to perform this adjustment.
Perform this adjustment only if highly accurate adjustment is required for reducing torque ripple caused by current offset.
This section describes the automatic and manual servomotor current detection offset adjustment.
Note:
·Offset-adjustment of the servomotor current detection signal is possible only while power is supplied to the main
circuit power supply and with the servo is the OFF state.
·Execute the automatic offset adjustment if the torque ripple is too big when compared with that of other servo
drives.
·If this function, particularly manual adjustment, is executed carelessly, it may worsen the characteristics.
3. Press the ENTER key to enter into the automatic adjustment of the servomotor current detection signal mode.
4. Press the MODE key,the display will blinks for one second. The offset will be automatically adjusted.
5. Press the ENTER key to return to the utility function mode display Fn005.
- 142 -
ProNet Series AC Servo User's Manual
Thus, the automatic offset-adjustment of the servomotor current detection signal is complete.
3. Press the ENTER key to enter into the manual adjustment of the servomotor current detection signal.
4. Press the MODE key to switch between the phase U(o _ CuA) and phase V(1_ Cub) servomotor current detection
offset adjustment.
5. Hold the ENTER key for one second to display the phase V offset amount.
7. Press the ENTER key for one second to return to the display in step 3 or 4.
8. Press the ENTER key to return to the utility function mode display Fn006.
Thus, the manual offset-adjustment of the servomotor current detection signal is completed.
Note:
The adjusting range of the servomotor current detection offset is -1024 to +1024.
- 143 -
ProNet Series AC Servo User's Manual
Select Fn007 in utility function mode to check the current software version of the drive.
1. Press the MODE key to select the utility function mode.
2. Press the INC or DEC key to select the utility function number Fn007.
3. Press the ENTER key to display the DSP software version (the highest bit displays d or E or F or 0).
4. Press the MODE key to display the FGPA/CPLD software version (the highest bit displays P).
4. Press the MODE key to rotate the servomotor, and the servomotor dynamic speed will be displayed.
5. The unit of the servomotor and load total inertia displayed when servomotor stops is kg.cm²
- 144 -
ProNet Series AC Servo User's Manual
Note:Make sure that the servomotor completes at least 6 full revolutions in the CCW direction before detection.
4. Press the MODE key to reset the absolute encoder multiturn data and alarm.
5. Thus the absolute encoder multiturn data and alarm reset is complete.
Important:
This function will clear the absolute position of the encoder; the mechanical safety must be noted.
When the multiturn data is cleared, other encoder alarms will be reset at the same time.
- 145 -
ProNet Series AC Servo User's Manual
Chapter 6
MODBUS Communication
ProNet series servo drives provide the MODBUS communication function with RS-485 interface,
which can be used to easily set parameters or to perform monitoring operations and so on.
The definitions of the servo drive communication connector terminals are as follows.
CN3:
Terminal No. Name Function
1 —
Reserved
2 —
3 485+ RS-485 communication terminal
4 ISO_GND
Isolated ground
5 ISO_GND
6 485- RS-485 communication terminal
7 CANH CAN communication terminal
8 CANL CAN communication terminal
Note: Do not short terminal 1 and 2 of CN3.
CN4:
Terminal No. Name Function
1 — Reserved
2 — Reserved
3 485+ RS-485 communication terminal
4 ISO_GND
Isolated ground
5 ISO_GND
6 485- RS-485 communication terminal
7 CANH CAN communication terminal
8 CANL CAN communication terminal
Note:
1. The length of the cable should be less than 100 meters and in a environment with minimal electrical
disturbance/interference. However, if the transmission speed is above 9600bps, please use the communication cable
within 15 meters to ensure transmission accuracy..
2. A maximum of 31 servo drives can be connected when RS485 is used. Terminating resistances are used at both ends
of the 485 network. If more devices are wanted to connect, use the repeaters to expand.
3. CN3 of servo drive is always used as communication cable input terminal,and CN4 is always used as communication
cable output terminal(If still need to connect slave stations,the communication cable is connected from CN4 terminal to
the next slave station; if need not, add balance resistor in CN4 terminal.).It is prohibited to connect CN3 of any two servo
- 146 -
ProNet Series AC Servo User's Manual
drives directly when multiple ProNet series servo drives are connected.
Example:
When a RS-485 network is composed of a PLC and three servo drives (A, B, and C), the cable wiring is shown as follows:
PLC→CN3 of A, CN4 of A→CN3 of B, CN4 of B→CN3 of C, CN4 of C→120Ω terminating resistance.
Setting
Parameter No. Description Control Mode Meaning
Validation
Pn700.0 MODBUS baud rate
[0] 4800bps
[1] 9600bps
[2] 19200bps
Pn700.1 Communication protocol
selection
[0] 7,N,2(MODBUS,ASCII)
[1] 7,E,1(MODBUS,ASCII)
[2] 7,O,1(MODBUS,ASCII)
[3] 8,N,2(MODBUS,ASCII)
Pn700 Hex After restart ALL [4] 8,E,1(MODBUS,ASCII)
[5] 8,O,1(MODBUS,ASCII)
[6] 8,N,2(MODBUS,RTU)
[7] 8,E,1(MODBUS,RTU)
[8] 8,O,1(MODBUS,RTU)
Pn700.2 Communication protocol
selection
[0] SCI communication with no
protocol
[1] MODBUS SCI communication
Pn700.3 Reserved
Axis address of MODBUS protocol
Pn701 Axis address After restart ALL
communication
- 147 -
ProNet Series AC Servo User's Manual
MODBUS communication protocol is only used when Pn700.2 is set to 1. There are two modes for MODBUS
communication: ASCII (American Standard Code for information interchange) mode and RTU (Remote Terminal Unit)
mode.
The next section describes the two communication modes.
ASCII Mode:
Every 8-bit data is consisted by two ASCII characters. For example: One 1-byte data 64 H(Hexadecimal expression)is
expressed as ASCII code ‘64’, which contains ‘6’ as ASCII code 36H and ‘4’ as ASCII code 34H.
RTU Mode:
Every 8-bit data is consisted by two 4-bit hexadecimal data, that is to say, a normal hexadecimal data. For example:
decimal data 100 can be expressed as 64H by 1-byte RTU data.
Data Structure:
10-bit character form(7-bit data)
- 148 -
ProNet Series AC Servo User's Manual
RTU Mode:
STX Sleep interval of at least 4 bytes transmission time.
ADR Communication address=>1-byte
CMD Reference code=>1-byte
DATA(n-1) Data content=>n-word=2n-byte,n≦12
……
DATA(0)
CRC CRC checking code=>1-byte
End 1 Sleep interval of at least 4 bytes transmission time.
- 149 -
ProNet Series AC Servo User's Manual
RTU mode: Sleep interval of at least 4 bytes transmission time (automatically changed according to different
communication speed).
ADR(communication address)
Valid communication address:1 to 254
For example: communicate with the servo drive which address is 32(20 in hex):
ASCII mode:ADR=‘2’,‘0’=>‘2’=32H,‘0’=30H
RTU mode:ADR=20H
CMD(command reference)and DATA(data)
Data structure is determined by command code. Regular command code is shown as follows:
Command code: 03H,read N words(word),N ≦ 20.
For example: read 2 words starting from 0200 H from the servo drive which address is 01 H.
ASCII mode:
Reference information: Response information:
STX “:”
‘0’ STX “:”
ADR ‘0’
‘1’ ADR
‘0’ ‘1’
CMD ‘0’
‘3’ CMD
‘0’ ‘3’
- 150 -
ProNet Series AC Servo User's Manual
ASCII mode:
Reference information: Response information:
STX “:” STX “:”
‘0’ ‘0’
ADR ADR
‘1’ ‘1’
‘0’ ‘0’
CMD CMD
‘6’ ‘6’
‘0’ ‘0’
‘2’ ‘2’
Data start address Data start address
‘0’ ‘0’
‘0’ ‘0’
‘0’ ‘0’
‘0’ Content of data start ‘0’
Data content
‘6’ address 0200H ‘6’
‘4’ ‘4’
‘9’ ‘9’
LRC checking LRC checking
‘3’ ‘3’
End 1 (0D H)(CR) End 1 (0D H )(CR)
End 0 (0A H)(LF) End 0 (0A H )(LF)
RTU mode:
Reference information: Response information:
ADR 01 H ADR 01 H
CMD 06 H CMD 06 H
02 H (high-bit) 02 H (high-bit)
Data start address Data start address
00 H (low-bit) 00 H (low-bit)
00 H (high-bit) 00 H (high-bit)
Data content Data content
64 H (low-bit) 64 H (low-bit)
CRC checking 89 H (low-bit) CRC checking 89 H (low-bit)
CRC checking 99 H (high-bit) CRC checking 99 H (high-bit)
- 151 -
ProNet Series AC Servo User's Manual
- 152 -
ProNet Series AC Servo User's Manual
ASCII mode:
Communication is ended with (0DH) - [carriage return] and (0AH) - [new line].
RTU mode:
When the time exceeds the sleep interval by at least 4 bytes transmission time while in the current communication speed,
it means the communication is finished.
Example:
The following example uses C language to generate CRC value. The function needs two parameters.
unsigned char * data;
unsigned char length;
The function will return unsigned integer type CRC value.
- 153 -
ProNet Series AC Servo User's Manual
When the first and second communication faults occur, the servo drive is running normally, and will feed back an error
frame.
When the third communication fault occurs, transmission data will be recognized as invalid to give up, and no error frame
is returned.
For example: Servo drive axis number is 03H,write data 06H into parameter Pn100 is not allowed , because the range of
parameter Pn100 is 0~6. The servo drive will feedback an error frame, the error code is 03H (Beyond the parameter’s
maximum value or minimum value).
Host controller data frame:
start Slave station address Command Data address,content Checking
03H 06H 0002H 0006H
Besides, if the data frame sent from host controller slave station address is 00H, it determines the data to be broadcast
data. The servo drives will not feed back any frames.
- 154 -
ProNet Series AC Servo User's Manual
Communication
data address Meaning Description Operation
Hex
Parameter area Corresponding parameters in Read/write
0000 ~ 02FD
parameter list
07F1 ~07FA Alarm information memory area Ten alarms historical record Read only
- 155 -
ProNet Series AC Servo User's Manual
Communication
data address Meaning Description Operation
Hex
17-bit encoder multi-turn Unit:1 revolution Read only.
1010
information Only for 17-bit
Unit:1 pulse Encoder.
17-bit encoder single-turn
1011 Multi-turn:16 bits
information
Single-turn:17 bits
17-bit encoder single-turn
1012
information high bits
1021 Clear historical alarms 01:Clear Write only
1022 Clear current alarms 01:Clear Write only
01:Enable
1023 JOG servo enabled Write only
00:Disable
01:Forward rotation
1024 JOG forward rotation Write only
00:Stop
01:Reverse rotation
1025 JOG reverse rotation Write only
00:Stop
JOG forward rotation at node 01:Forward rotation
1026
position( start signal has been set) 00:Stop
JOG reverse rotation at node 01:Reverse rotation
1027
position(start signal has been set) 00:Stop
01:Pause
1028 Pause at node position
00:Cancel pause
Note:
1. Parameter area(communication address 0000~00DEH)
Parameter address is relevant to the parameters in the parameter list.
For example, parameter Pn000 is relevant to communication address 0000H; parameter Pn101 is relevant to
communication address 0065H. Read/write operation to address 0000H is the read/write operation to Pn000. If the
communication input data is not within the parameter range, the data will be aborted, and servo drive will return an
operation unsuccessful signal.
- 156 -
ProNet Series AC Servo User's Manual
5. Software version(090FH)
Use digit to represent servo drive software version. For example, if the read out data is D201H,it means the software
version is D-2.01.
- 157 -
ProNet Series AC Servo User's Manual
Chapter 7
Servo drive Model: ProNet- 02A 04A 08A 10A 15A 20A 30A 50A 10D 15D 20D 30D 50D 70D 75D 1AD 1ED 2BD 02B 04B 08B
Servo drive Model: ProNet-E- 02A 04A 08A 10A 15A 20A 30A 50A 10D 15D 20D 30D 50D — — — — — 02B 04B 08B
Applicable Servomotor EMG- — — — 10A 15A 20A 30A 50A 10D 15D 20D 30D — — — — — — — — —
Model: EML- — — — 10A — 20A 30A 40A 10D — 20D 30D 40D — — — — — — — —
Continuous Output Current[Arms] 1.4 2.8 4.0 6.0 9.0 12.0 18.0 28.0 3.2 5.0 6.4 9.0 15.0 18.0 18.0 28.0 38.0 55.0 2.7 5.8 8.2
Max. Output Current [Arms] 4.2 8.4 12.0 18.0 28.0 42.0 45.0 62.0 9.6 15.0 19.2 27.0 45.0 48.0 48.0 65.0 100.0 128.0 8.1 15.1 24.6
Main Input Power Supply Capacity [kVA] 0.5 0.9 1.3 1.8 2.5 3.5 4.5 7.5 1.8 2.8 3.5 5.0 8.2 12.0 12.0 18.0 22.0 32.0 0.5 0.9 1.3
DC24V Power Supply Capacity [W] — — — — — — — — 30.0 30.0 30.0 45.0 45.0 45.0 45.0 — — — — — —
Single-
Three-phase
phase 200 ~ Three-phase Three-phase
380~440VAC Single-phase 100~120VAC
Main Circuit 200~230VAC 380~480VAC
230VAC +10%~ +10%~ +10%~-15% (50/60Hz)
+10%~-15% (50/60Hz) +10%~-15%(50/60Hz)
-15% (50/60Hz) -15%(50/60Hz)
Input Power Supply
Single-phase
Single-phase
24VDC 380~440VAC Single-phase 100~120VAC
Control Circuit 200~230VAC
+10%~-15% +10%~ +10%~-15% (50/60Hz)
+10%~-15% (50/60Hz)
-15%(50/60Hz)
- 158 -
ProNet Series AC Servo User's Manual
Servo drive Model: ProNet- 02A 04A 08A 10A 15A 20A 30A 50A 10D 15D 20D 30D 50D 70D 75D 1AD 1ED 2BD 02B 04B 08B
Servo drive Model: ProNet-E- 02A 04A 08A 10A 15A 20A 30A 50A 10D 15D 20D 30D 50D — — — — — 02B 04B 08B
Resolver:65536P/R(Max.)
Ambient temperature:-20~+55℃
Ambient/Storage Temperature
Storage temperature:-25~+55℃
Operating Ambient/Storage Humidity 5%~95% RH (with no condensation)
Conditions Elevation 1000m or less
Vibration/ShockResistance Vibration Resistance:4.9m/s2,Impact Resistance:19.6m/s2
Electric Power System TN system *3
Configuration Base-mounted
Load
0~100% load:±0.01% or less(at rated speed)
Regulation
Performance Speed Voltage
Rated voltage ±10%:0%(at rated speed)
Regulation Regulation
Temperature
25±25℃:±0.1% or less(at rated speed)
Regulation
Reference ±10VDC at rated torque(Variable setting range:±0~10VDC)
Analog Voltage Max. input voltage:±12V
Torque Input
Reference About 10MΩ or above
Control Impedance
Input
Circuit Time
10μs
Constant
Reference ±10VDC at rated speed(Variable setting range:±0~10VDC)
Voltage Max. input voltage:±12V
Analog Input Input
About 10MΩ or above
Reference Impedance
Circuit Time
10μs
Constant
Speed
Rotation
Control
Speed Direction With /P-CON signal
Selection
Selection
Speed
Speed 1 to 7
Selection
Soft
Function 0~10s(Can be set individually for acceleration and deceleration.)
Start
- 159 -
ProNet Series AC Servo User's Manual
Servo drive Model: ProNet- 02A 04A 08A 10A 15A 20A 30A 50A 10D 15D 20D 30D 50D 70D 75D 1AD 1ED 2BD 02B 04B 08B
Servo drive Model: ProNet-E- 02A 04A 08A 10A 15A 20A 30A 50A 10D 15D 20D 30D 50D — — — — — 02B 04B 08B
Setting
Sign + pulse train;CCW + CW pulse train;
Type
90°phase difference 2-phase (phase A + phase B)
Form Non-insulated linde driver (about + 5V), open collector
Pulse ×1 multiplier:4Mpps
Reference ×2 multiplier:2Mpps
Position
Frequency ×4 multiplier:1Mpps
Control
Open collector:200Kpps
Frequency will begin to decline when the duty ratio error occurs..
Position
Position
Reference 16 postion nodes can be set.
Setting
Setting
Encoder Dividing Pulses Phase-A, phase-B, phase-C, line driver output
Output Number of dividing pulses:any
Number of
8 channels
Sequence channels
Signal allocations and positive/negative logic modifications:
Input
Function Servo ON(/S-ON),P control(/P-CON),alarm reset(/ALM-RST),position error clear(/CLR),forward run prohibited(P-OT),reverse run prohibited(N-OT),forward current
limit(/P-CL),reverse current limit(/N-CL) and so on.
Number of
4 channels
Sequence channels
I/O Signals
Signal allocations and positive/negative logic modifications:
Output
Function Positioning completion(/COIN), speed coincidence(/V-CMP),servomotor rotation detection(/TGON), servo ready(/S-RDY),torque limit output(/CLT), brake interlock output (/BK),
encoder C pulse(/PGC) and Over travel (/OT).
Regenerative Functions 0.75kW~7.5kW:internal regenerative resistor;11kW~22kW:external regenerative resistor
Protection Functions Overcurrent, overvoltage,low voltage, overload,regeneration error,overspeed,etc.
Utility Function Alarm trace back、JOG operation、load inertia detection, etc.
Display Function CHARGE(Red)、POWER(Green)、five 7-segment LEDS (Built-in panel operator)
RS-485 communication port,MODBUS protocol ;CAN communication port,CANopen protocol;
Communication Functiion
EtherCAT communication module,CiA402 protocol;POWERLINK communication module,CiA402 protocol
- 160 -
ProNet Series AC Servo User's Manual
ProNet-02/04A
ProNet-E-02/04A
Unit:mm
Nameplate
ProNet-04B/08A/10A
ProNet-E-04B/08A/10A
Unit: mm
Nameplate
Air Flow (32)
Extended Module
D P 100
13.8
10
0°
ADDL ADDH
CHARGE POWER
CN3
COMM
L1
L2
CN4
CN5
L3
1
2
Air Flow
L1C
CN1
L2C
B1
B2
B3
U
V
W
CN2
Air Flow
Cooling Fan
Air Flow
- 161 -
ProNet Series AC Servo User's Manual
ProNet-08B/10D/15A/15D/20A/20D
ProNet-E-08B/10D/15A/15D/20A/20D
Unit:mm
94.4 (32)
Air Flow Extended Module Nameplate
SERVODRIVE 200V
PRONET-10A
D P 1 00
13.8
10
0°
ADDL ADDH
96
CHARGE POWER
CN3
COMM
注 意
危 险
L1
L2
CN4
Disconnect all power and wait 5 minutes before servicing.
通电时请勿触摸散热片!有烫伤的危险。
切断电源5分钟内,请勿触摸驱动器端子和配线!有触电的危险。
CN5
L3
1
186
2
Air Flow
L1C
CN1
L2C
B1
B2
B3
Three Terminals
U
V
W
CN2
Cooling Fan 4.8
Air Flow Ground Terminal
5.5
2-M4 Screw
Mounting Hole Diagram 4-M4 Screw Holes (75)
100 24 180
(Mounting Pitch)
Figure
186
175
Air Flow
5.5 89
100
ProNet-30A/30D/50A/50D/70D
ProNet-E-30A/30D/50A/50D
Unit:mm
(32) Nameplate
6
Mounting Hole Diagram 4-M5 Screw Holes Air Flow Extended Module
SERVODRIVE 200V
PRONET-50A
13.8
D P 10 0
10
0°
ADDL ADDH
CHARGE POWER
ALM
CN3
COMM
CN4
CN5
务必在阅读使用说明书后,按其步骤操作。 Read manual carefully and follow the direction.
WARNING May cause electric shock.
CAUTION Do not touch heatsink. May cause burn.
Use proper grounding techniques.
接地端子必须接地。
注 意
危 险
(Mounting Pitch)
CN1
Disconnect all power and wait 5 minutes before servicing.
通电时请勿触摸散热片!有烫伤的危险。
切断电源5分钟内,请勿触摸驱动器端子和配线!有触电的危险。
Figure
270.5
258.5
270.5
CN2
Terminal
(14-M4 Screw)
5.5
6 112
(Mounting Pitch) Ground Terminal
Air Flow 2-M4 Screw
125 125 24 (75) 204.5
10
5°
(38)
Cooling Fan
- 162 -
ProNet Series AC Servo User's Manual
ProNet-75D/1AD/1ED/2BD
Unit:mm
Air Flow
- 163 -
ProNet Series AC Servo User's Manual
Appendix A
Parameter
- 164 -
ProNet Series AC Servo User's Manual
- 165 -
ProNet Series AC Servo User's Manual
- 166 -
ProNet Series AC Servo User's Manual
- 167 -
ProNet Series AC Servo User's Manual
- 168 -
ProNet Series AC Servo User's Manual
- 169 -
ProNet Series AC Servo User's Manual
capacity.
- 170 -
ProNet Series AC Servo User's Manual
Funtion selection switches Pn000~Pn006 Control mode, stop mode, and some functions selection
Parameters of servo gain Pn100~Pn129 Position gain, speed gain,rigidity,etc.
Position control related parameters Pn200~Pn205 PG divided ratio, electronic gear, etc.
Speed control related parameters Pn300~Pn322 Speed reference input, soft start, etc.
Torque control related parameters Pn400~Pn406 Torque limit, etc.
Parameters to control I/O port Pn500~Pn520 Allocation of I/O port function
Point-to-point control and homing control Pn600~Pn686 Internal point-to-point control and homing control related
related parameters parameters
Communication parameters Pn700~Pn701 Setting of communication parameters
- 171 -
ProNet Series AC Servo User's Manual
- 172 -
ProNet Series AC Servo User's Manual
Pn203
Pn201 Electronic gear numerator 2 Pn201
Electronic gear numerator 1 PCON enabled Electronic gear numerator 1
PCON disabled PCON disabled
Reference pulse
t1 t2
t1,t2>1ms
Pn002.1 Reserved
Pn002.2 Absolute encoder selection
[0] Use absolute encoder as an absolute encoder
[1] Use absolute encoder as an incremental encoder
Pn002.3 Reserved
Pn003.0 Reserved
Pn003.1 Reserved
Pn003.2 Low speed compensation
[0] Without low speed correction
[1] With low speed correction to avoid servomotor
creeping, but the degree of correction is
Pn003 Binary After restart ALL determined by the setting in Pn219.
Pn003.3 Overload enhancement
[0] Without overload enhancement function
[1] With overload enhancement function, which can
enhance the overload capacity when servomotor
exceeds the 2 times rated overload. It is used in
frequent power ON/OFF occasions.
- 173 -
ProNet Series AC Servo User's Manual
- 174 -
ProNet Series AC Servo User's Manual
- 175 -
ProNet Series AC Servo User's Manual
- 176 -
ProNet Series AC Servo User's Manual
- 177 -
ProNet Series AC Servo User's Manual
Speed reference
Error counter
Pn111
Pn500
- 178 -
ProNet Series AC Servo User's Manual
- 179 -
ProNet Series AC Servo User's Manual
- 180 -
ProNet Series AC Servo User's Manual
- 181 -
ProNet Series AC Servo User's Manual
- 182 -
ProNet Series AC Servo User's Manual
- 183 -
ProNet Series AC Servo User's Manual
- 184 -
ProNet Series AC Servo User's Manual
Pn523 Reserved — — —
Pn524 Reserved — — —
When load percentage is larger than overload alarm
Overload alarm
threshold, A04 will occur soon.
Pn525 threshold Immediately P,S,T
Pn525 is recommended to set below 120, otherwise
the servo drive and motor will be damaged.
Temperature
threshold of motor When servomotor winding temperature exceeds
Pn526 overheat alarm Immediately P,S,T Pn526 setting, A19 will occur. (Only enabled in
(Only enabled in ProNet–75/1A/1E/2B )
ProNet–75/1A/1E/2B)
[0]:Do not inverse signal.
[1]:Inverse signal
- 185 -
ProNet Series AC Servo User's Manual
- 186 -
ProNet Series AC Servo User's Manual
- 187 -
ProNet Series AC Servo User's Manual
- 188 -
ProNet Series AC Servo User's Manual
- 189 -
ProNet Series AC Servo User's Manual
Appendix B
Alarm Display
Alarm Alarm
Alarm Name Meaning
Display Output
A.06 ╳ Position error pulse overflow Position error pulse exceeded parameter (Pn504)
A.20 ╳ Power line phase shortage One phase does not bring into main circuit power supply.
A.21 ╳ Instantaneous power off alarm An power off for more than one period is occurred in AC.
- 190 -
ProNet Series AC Servo User's Manual
Alarm Alarm
Alarm Name Meaning
Display Output
A.23 ╳ Brake overcurrent alarm Bleeder resistor is too small, or bleeder module is faulty.
A.47 ╳ Battery voltage below 2.5V Absolute encoder multiturn information is lost.
A.53 ╳ Serial encoder calcaution error Encoder or the encoder decoding circuit is faulty.
Parity bit or end bit in serial encoder Encoder signal is disturbed or the encoder decoding circuit
A.54 ╳
control domain error is faulty.
Serial encoder communication data Encoder signal is disturbed or the encoder decoding circuit
A.55 ╳
checking error is faulty.
End bit in serial encoder control Encoder signal is disturbed or the encoder decoding circuit
A.56 ╳
domain error is faulty.
A.58 ╳ Serial encoder data empty The EEPROM data of serial encoder is empty.
A.59 ╳ Serial encoder data format error The EEPROM data format of serial encoder is incorrect.
- 191 -
ProNet Series AC Servo User's Manual
Alarm Alarm
Alarm Name Meaning
Display Output
Communication module can not
A.63 ╳ receive the servo drive response Communication module is faulty.
data.
Communication module and bus
A.64 ╳ Bus communication is faulty.
connectionless
CAN communication is faulty because of abnormal
A.66 ╳ CAN communication abnormal
communication connection or disturbance.
A.67 ╳ Receiving heartbeat timeout The master station sends heartbeat time timeout
Synchronization signal monitoring The filling time and the cycle of the synchronous signal
A.69 ╳
cycle is longer than setting does not match.
- 192 -