Ijet V3i4p7
Ijet V3i4p7
Ijet V3i4p7
Abstract:
In this paper performance analysis of solar thermal cooling system for an office building has been analyzed.
Analysis has been carried through simulation of a typical office building considered to be located in four
different cities, representing four climatic zones of India namely Ahmedabad (Hot and dry), Bangalore
(Moderate), Chennai (Warm and humid) and Delhi (Composite). Results indicate that the highest solar
fraction has been observed as 0.71, 0.75, 0.77, and 0.78 for hot and dry, moderate, warm and humid and
composite climate respectively. The primary energy savings are higher for the moderate climate (Bangalore) and
lowest for the warm and humid climate (Chennai).
Annual CoolingDemand
Fig.2: 3 D view of Building 200 80
Primary energy
60
savings (%)
increases because more heat is collected by the collector
but its effect will be much more if this heat is effectively 40
utilized to produce the cooling effect. In the warm and
humid climate (Chennai) the building cooling load is very 20
high and the heat is effectively utilized so change in solar
0
fraction is higher with the increase in collector area than
other cities. If the collector area is increased from 70 m2 to 70 80 90 100 110
110 m2 the solar fraction increases from 51 % to 71 % in Collector area m2
warm and humid climate (Chennai), 59% to 75 % in hot
and dry conditions (Ahmedabad), 66% to 77% in Fig. 5 Variation of Primary Energy Savings with
moderate climate (Bangalore) and 63% to 78 % in collector area
composite climate(Delhi) Fig 5. shows the variation in primary energy savings with
Hot and Dry (Ahmedabad)
Moderate (Bangalore)
different collector areas. It is observed from the graph 5
Warm and Humid (Chennai) that the primary energy savings are increased with the
Composite (Delhi) increase in collector area (FPC), because more heat is
1.00 collected by the solar thermal collector for the same
0.90 cooling demand. The primary energy savings are higher
Solar Fraction