Relay Setting For Transformer Primary and Secondary
Relay Setting For Transformer Primary and Secondary
Relay Setting For Transformer Primary and Secondary
23-TR-2304-01 Trafo
Secondary FLC in A from
MVA Primary FLC in A from ETAP CT Primary in A Impedance in Z%
ETAP
43.74 100 5.33
2.5
418.4 600 5.33
23-TR-7220 Trafo
Secondary FLC in A from
MVA Primary FLC in A from ETAP CT Primary in A Impedance in Z%
ETAP
17.5 100 6.5
1
1333 1600 6.5
RLSS-26
Secondary FLC in A from
MVA Primary FLC in A from ETAP CT Primary in A Impedance in Z%
ETAP
2.8 100 5.26
0.16
213 600 5.26
23-TR-0004 Trafo
Secondary FLC in A from
MVA Primary FLC in A from ETAP CT Primary in A Impedance in Z%
ETAP
14 100 4.3
0.8
1067 1250 4.3
Voltage
OC (51) OC (50) Earth (51) Earth (50)
in kV
0.22 3.36 0.04 0.27 33
1.04 0.17 0.433
Voltage
OC (51) OC (50) Earth (51) Earth (50)
in kV
0.04 0.66 0.01 0.05 33
0.44 0.07 0.433
Voltage
OC (51) OC (50) Earth (51) Earth (50)
in kV
0.18 4.07 0.03 0.33 33
1.07 0.17 0.433
Voltage
OC (51) OC (50) Earth (51) Earth (50)
in kV
0.13 3.53 0.02 0.28 33
0.77 0.13 0.433