This document provides instructions for installing and operating a digital controller model XR72CX. It contains the following information:
1. General warnings about safety, intended use, and maintenance.
2. A description of the controller's functions including temperature control, defrost control, four output relays, and the ability to connect to external monitoring devices.
3. Details about how the controller manages loads like compressors, defrost cycles, evaporator fans, temperature probes, and alarms.
This document provides instructions for installing and operating a digital controller model XR72CX. It contains the following information:
1. General warnings about safety, intended use, and maintenance.
2. A description of the controller's functions including temperature control, defrost control, four output relays, and the ability to connect to external monitoring devices.
3. Details about how the controller manages loads like compressors, defrost cycles, evaporator fans, temperature probes, and alarms.
Original Description:
hướng dẫn sử dụng bộ điều khiển nhiệt độ Dixell - xr72cx
This document provides instructions for installing and operating a digital controller model XR72CX. It contains the following information:
1. General warnings about safety, intended use, and maintenance.
2. A description of the controller's functions including temperature control, defrost control, four output relays, and the ability to connect to external monitoring devices.
3. Details about how the controller manages loads like compressors, defrost cycles, evaporator fans, temperature probes, and alarms.
This document provides instructions for installing and operating a digital controller model XR72CX. It contains the following information:
1. General warnings about safety, intended use, and maintenance.
2. A description of the controller's functions including temperature control, defrost control, four output relays, and the ability to connect to external monitoring devices.
3. Details about how the controller manages loads like compressors, defrost cycles, evaporator fans, temperature probes, and alarms.
dIXEL Installing and Operating Instructions 1592020080
3.4.2 Cyclical activation of the fans with compressor off.
Digital controller with defrost and fans management When Fnc = c-n or c-Y (fans in parallel to the compressor), by means of the Fon and FoF parameters the fans can carry out on and off cycles even if the compressor is switched off. When the XR72CX compressor is stopped the fans go on working for the Fon time. With Fon =0 the fans remain always off, when the compressor is off.
4. FRONT PANEL COMMANDS
1. GENERAL WARNING
1.1 PLEASE READ BEFORE USING THIS MANUAL
• This manual is part of the product and should be kept near the instrument for easy and quick reference. • The instrument shall not be used for purposes different from those described hereunder. It cannot be used as a safety device. • Check the application limits before proceeding.
1.2 SAFETY PRECAUTIONS
• Check the supply voltage is correct before connecting the instrument. • Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden : To display target set point; in programming mode it selects a parameter or confirm an temperature changes with high atmospheric humidity to prevent formation of condensation operation. • Warning: disconnect all electrical connections before any kind of maintenance. • Fit the probe where it is not accessible by the End User. The instrument must not be opened. (DEF) To start a manual defrost • In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.p.A.” (see address) with a detailed description of the fault. • Consider the maximum current which can be applied to each relay (see Technical Data). (UP): To see the max. stored temperature; in programming mode it browses the parameter • Ensure that the wires for probes, loads and the power supply are separated and far enough from each codes or increases the displayed value. other, without crossing or intertwining. (DOWN) To see the min stored temperature; in programming mode it browses the parameter • In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with codes or decreases the displayed value. inductive loads could be useful. To switch the instrument off, if onF = oFF. 2. GENERAL DESCRIPTION Model XR72CX, format 32 x 74 mm, is microprocessor based controller, suitable for applications on Not used. medium or low temperature ventilated refrigerating units. It has four relay outputs to control KEY COMBINATIONS: compressor 1, compressor 2, fan and defrost, which can be either electrical or reverse cycle (hot gas). It is also provided with up to four NTC or PTC probe inputs, the first one for temperature + To lock & unlock the keyboard. control, the second one, to be located onto the evaporator, to control the defrost termination + To enter in programming mode. temperature and to managed the fan. The digital input can operate as third temperature probe. The fourth one, to connect to the HOT KEY terminals is used to signal the condenser temperature alarm + To return to the room temperature display. or to display a temperature. The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX, to a 4.1 USE OF LEDS network line ModBUS-RTU compatible such as the dIXEL monitoring units of X-WEB family. It Each LED function is described in the following table. allows to program the controller by means the HOT KEY programming keyboard. The instrument is fully configurable through special parameters that can be easily programmed LED MODE FUNCTION through the keyboard. ON Compressor enabled
ON Defrost enabled 3.1 COMPRESSOR Flashing Drip time in progress The regulation is performed according Temper. ON Fans enabled to the temperature measured by the thermostat probe with a positive Flashing Fans delay after defrost in progress. SET differential from the set point: if the ON An alarm is occurring temperature increases and reaches set Time point plus differential the compressor is ON Continuous cycle is running started and then turned off when the Compr. ON Energy saving enabled temperature reaches the set point value ON °C/°F ON Measurement unit again. °C/°F Flashing Programming phase In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters “COn” and “COF”. 5. MAX & MIN TEMPERATURE MEMORIZATION 3.2 2ND COMPRESSOR MANAGEMENT – XR72C ONLY 5.1 HOW TO SEE THE MIN TEMPERATURE The relay of the second compressor is activated in parallel with the relay of the first compressor, with a possible delay set in the AC1 parameter. Both the compressors are switched off at the same time. 1. Press and release the n key. 2. The “Lo” message will be displayed followed by the minimum temperature recorded. 3.3 DEFROST 3. By pressing the n key again or by waiting 5s the normal display will be restored. Two defrost modes are available through the “tdF” parameter: defrost through electrical heater (tdF = EL) and hot gas defrost (tdF = in). Other parameters are used to control the interval between 5.2 HOW TO SEE THE MAX TEMPERATURE defrost cycles (IdF), its maximum length (MdF) and two defrost modes: timed or controlled by the 1. Press and release the o key. evaporator’s probe (P2P). 2. The “Hi” message will be displayed followed by the maximum temperature recorded. At the end of defrost dripping time is started, its length is set in the FSt parameter. With FSt =0 the 3. By pressing the o key again or by waiting 5s the normal display will be restored. dripping time is disabled. 5.3 HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 3.4 CONTROL OF EVAPORATOR FANS 1. Hold press the SET key for more than 3s, while the max. or min temperature is displayed. (rSt The fan control mode is selected by means of the “FnC” parameter: message will be displayed) FnC = C_n: fans will switch ON and OFF with the compressor and not run during defrost; 2. To confirm the operation the “rSt” message starts blinking and the normal temperature will be FnC = o_n fans will run even if the compressor is off, and not run during defrost; displayed. After defrost, there is a timed fan delay allowing for drip time, set by means of the “Fnd” parameter. FnC = C_Y fans will switch ON and OFF with the compressor and run during defrost; 6. MAIN FUNCTIONS FnC = o_Y fans will run continuously also during defrost An additional parameter “FSt” provides the setting of temperature, detected by the evaporator probe, 6.1 HOW TO SEE THE SETPOINT above which the fans are always OFF. This is used to make sure circulation of air only if his 1.Push and immediately release the SET key: the display will show the temperature is lower than set in “FSt”. Set point value; 3.4.1 Forced activation of fans 2. Push and immediately release the SET key or wait for 5 seconds to This function managed by the Fct parameter is designed to avoid short cycles of fans, that could display the probe value again. happen when the controller is switched on or after a defrost, when the room air warms the evaporator. Functioning: if the difference of temperature between the evaporator and the room 6.2 HOW TO CHANGE THE SETPOINT probes is more than the value of the Fct parameter, the fans are switched on. With Fct=0 the function 1. Push the SET key for more than 2 seconds to change the Set point value; is disabled. 2. The value of the set point will be displayed and the “°C” or “°F” LED starts blinking; 3. To change the Set value push the o or n arrows within 10s. 4. To memorise the new set point value push the SET key again or wait 10s.
dIXEL Installing and Operating Instructions 1592020080 6.3 HOW TO START A MANUAL DEFROST CCt Compressor ON time during continuous cycle: (0.0÷24.0h; res. 10min) Allows to set the length of the continuous cycle: compressor stays on without interruption for the CCt time. Can be Push the DEF key for more than 2 seconds and a manual defrost will start. used, for instance, when the room is filled with new products. CCS Set point for continuous cycle: (-50÷150°C) it sets the set point used during the continuous cycle. COn Compressor ON time with faulty probe: (0÷255 min) time during which the compressor is 6.4 HOW TO CHANGE A PARAMETER VALUE active in case of faulty thermostat probe. With COn=0 compressor is always OFF. To change the parameter’s value operate as follows: COF Compressor OFF time with faulty probe: (0÷255 min) time during which the compressor is 1. Enter the Programming mode by pressing the Set + n keys for 3s (the “°C” or “°F” LED starts OFF in case of faulty thermostat probe. With COF=0 compressor is always active. blinking). DISPLAY 2. Select the required parameter. Press the “SET” key to display its value CF Temperature measurement unit: °C=Celsius; °F=Fahrenheit. WARNING: When the 3. Use “UP” or “DOWN” to change its value. measurement unit is changed the SET point and the values of the parameters Hy, LS, US, Ot, 4. Press “SET” to store the new value and move to the following parameter. ALU and ALL have to be checked and modified if necessary). To exit: Press SET + UP or wait 15s without pressing a key. rES Resolution (for °C): (in = 1°C; dE = 0.1 °C) allows decimal point display. NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire. Lod Instrument display: (P1; P2, P3, P4, SET, dtr): it selects which probe is displayed by the instrument: P1 = Thermostat probe; P2 = Evaporator probe; P3 = Third probe(only for model 6.5 THE HIDDEN MENU with this option enabled); P4 = Fourth probe, SET = set point; dtr = percentage of The hidden menu Includes all the parameters of the instrument. visualization. 6.5.1 HOW TO ENTER THE HIDDEN MENU rEd X- REP display (optional): (P1; P2, P3, P4, SET, dtr): it selects which probe is displayed by 1. Enter the Programming mode by pressing the Set + n keys for 3s (the “°C” or “°F” LED starts X- REP: P1 = Thermostat probe; P2 = Evaporator probe; P3 = Third probe(only for model with blinking). this option enabled); P4 = Fourth probe, SET = set point; dtr = percentage of visualization. dLy Display delay: (0 ÷20.0m; risul. 10s) when the temperature increases, the display is updated 2. Released the keys, then push again the Set+n keys for more than 7s. The Pr2 label will be of 1 °C/1°F after this time. displayed immediately followed from the HY parameter. dtr Percentage of the second and first probe for visualization when Lod = dtr (0÷100; 100 = NOW YOU ARE IN THE HIDDEN MENU. P1, 0 = P2 ): if Lod = dtr it allows to set the visualization according to the percentage of the 3. Select the required parameter. first and second probe, as for the following formula (dtr(P1-P2)/100 + P2). 4. Press the “SET” key to display its value 5. Use o or n to change its value. DEFROST 6. Press “SET” to store the new value and move to the following parameter. tdF Defrost type: EL = electrical heater; in = hot gas To exit: Press SET + o or wait 15s without pressing a key. dFP Probe selection for defrost termination: nP = no probe; P1 =thermostat probe; P2 = NOTE1: if none parameter is present in Pr1, after 3s the “noP” message is displayed. Keep the keys evaporator probe; P3 =configurable probe; P4 = Probe on Hot Key plug. pushed till the Pr2 message is displayed. dtE Defrost termination temperature: (-50÷50 °C/ NOTE2: the set value is stored even when the procedure is exited by waiting the time-out to expire. -58÷122°F) (Enabled only when EdF=Pb) sets the temperature measured by the evaporator probe, which causes the end of defrost. 6.5.2 HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE IdF Interval between defrost cycles: (0÷120h) Determines the time interval between the FIRST LEVEL AND VICEVERSA. beginning of two defrost cycles. Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL” MdF (Maximum) length for defrost: (0÷255min) When P2P = n, (not evaporator probe: timed (user level) by pressing “SET + n”. defrost) it sets the defrost duration, when P2P = y (defrost end based on temperature) it sets In HIDDEN MENU when a parameter is present in First Level the decimal point is on. the maximum length for defrost. dSd Start defrost delay: ( 0÷99min) This is useful when different defrost start times are necessary 6.6 HOW TO LOCK THE KEYBOARD to avoid overloading the plant. 1. Keep pressed for more than 3 s the UP + DOWN keys. dFd Temperature displayed during defrost: (rt = real temperature; it = temperature at defrost 2. The “POF” message will be displayed and the keyboard will be locked. At this point it will be start; SEt = set point; dEF = “dEF” label) possible only to see the set point or the MAX o Min temperature stored dAd MAX display delay after defrost: (0÷255min). Sets the maximum time between the end of 3. If a key is pressed more than 3s the “POF” message will be displayed. defrost and the restarting of the real room temperature display. Fdt Drip time: (0÷120 min) time interval between reaching defrost termination temperature and the 6.7 TO UNLOCK THE KEYBOARD restoring of the control’s normal operation. This time allows the evaporator to eliminate water drops that might have formed due to defrost. Keep pressed together for more than 3s the o and n keys, till the “Pon” message will be dPo First defrost after start-up: (y = immediately; n = after the IdF time) displayed. dAF Defrost delay after continuous cycle: (0÷23.5h) time interval between the end of the fast freezing cycle and the following defrost related to it. 6.8 THE CONTINUOUS CYCLE FANS When defrost is not in progress, it can be activated by holding the “o” key pressed for about 3 FnC Fans operating mode: C-n= runs with the compressor, OFF during defrost; seconds. The compressor operates to maintain the “ccS” set point for the time set through the “CCt” o-n = continuous mode, OFF during defrost; parameter. The cycle can be terminated before the end of the set time using the same activation key C-Y = runs with the compressor, ON during defrost; “o” for 3 seconds. o-Y = continuous mode, ON during defrost; Fnd Fans delay after defrost: (0÷255min) Interval between end of defrost and evaporator fans 6.9 THE ON/OFF FUNCTION start. With “onF = oFF”, pushing the ON/OFF key, the instrument is switched off. The “OFF” Fct Temperature differential avoiding short cycles of fans (0÷59°C; Fct=0 function disabled). If message is displayed. In this configuration, the regulation is disabled. the difference of temperature between the evaporator and the room probes is more than the To switch the instrument on, push again the ON/OFF key. value of the Fct parameter, the fans are switched on. FSt Fans stop temperature: (-50÷50°C/122°F) setting of temperature, detected by evaporator WARNING: Loads connected to the normally closed contacts of the relays are always probe, above which fans are always OFF. supplied and under voltage, even if the instrument is in stand by mode. Fon Fan ON time: (0÷15 min) with Fnc = C_n or C_y, (fan activated in parallel with compressor). it sets the evaporator fan ON cycling time when the compressor is off. With Fon =0 and FoF ≠ 0 7. PARAMETERS the fan are always off, with Fon=0 and FoF =0 the fan are always off. FoF Fan OFF time: (0÷15 min) with Fnc = C_n or C_y, (fan activated in parallel with compressor). it REGULATION sets the evaporator fan off cycling time when the compressor is off. With Fon =0 and FoF ≠ 0 Hy Differential: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point. Compressor Cut IN the fan are always off, with Fon=0 and FoF =0 the fan are always off. is Set Point + differential (Hy). Compressor Cut OUT is when the temperature reaches the set FAP Probe selection for fan management: nP = no probe; P1 =thermostat probe; P2 = evaporator point. probe; P3 =configurable probe; P4 = Probe on Hot Key plug. LS Minimum set point: (- 50°C÷SET/-58°F÷SET): Sets the minimum value for the set point. ALARMS US Maximum set point: (SET÷110°C/ SET÷230°F). Set the maximum value for set point. Ot Thermostat probe calibration: (-12.0÷12.0°C; -120÷120°F) allows to adjust possible offset of ALC Temperature alarms configuration: (Ab; rE) the thermostat probe. Ab= absolute temperature: alarm temperature is given by the ALL or ALU values. rE = P2P Evaporator probe presence: n= not present: the defrost stops by time; y= present: the defrost temperature alarms are referred to the set point. Temperature alarm is enabled when the stops by temperature. temperature exceeds the “SET+ALU” or “SET-ALL” values. OE Evaporator probe calibration: (-12.0÷12.0°C; -120÷120°F). allows to adjust possible offset of ALU MAXIMUM temperature alarm: (SET÷110°C; SET÷230°F) when this temperature is reached the evaporator probe. the alarm is enabled, after the “ALd” delay time. P3P Third probe presence (P3): n= not present:, the terminal operates as digital input.; y= ALL Minimum temperature alarm: (-50.0 ÷ SET°C; -58÷230°F when this temperature is reached present:, the terminal operates as third probe. the alarm is enabled, after the “ALd” delay time. O3 Third probe calibration (P3): (-12.0÷12.0°C; -120÷120°F). allows to adjust possible offset of AFH Differential for temperature alarm/ fan recovery: (0,1÷25,5°C; 1÷45°F) Intervention the third probe. differential for recovery of temperature alarm. It’s also used for the restart of the fan when the P4P Fourth probe presence: (n = Not present; y = present). FSt temperature is reached o4 Fourth probe calibration: (-12.0÷12.0°C) allows to adjust possible offset of the fourth probe. ALd Temperature alarm delay: (0÷255 min) time interval between the detection of an alarm odS Outputs activation delay at start up: (0÷255min) This function is enabled at the initial start up condition and alarm signalling. of the instrument and inhibits any output activation for the period of time set in the parameter. dAO Exclusion of temperature alarm at startup: (from 0.0 min to 23.5h) time interval between the AC Anti-short cycle delay: (0÷50 min) minimum interval between the compressor stop and the detection of the temperature alarm condition after instrument power on and alarm signalling. following restart. CONDENSER TEMPERATURE ALARM AC1 2nd compressor delay at start up (0÷255s) Time interval between the switching on of the first AP2 Probe selection for temperature alarm of condenser: nP = no probe; P1 =thermostat probe; compressor and the second one. P2 = evaporator probe; P3 =configurable probe; P4 = Probe on Hot Key plug. rtr Percentage of the second and first probe for regulation (0÷100; 100 = P1, 0 = P2 ): it AL2 Low temperature alarm of condenser: (-55÷150°C) when this temperature is reached the allows to set the regulation according to the percentage of the first and second probe, as for the LA2 alarm is signalled, possibly after the Ad2 delay. following formula (rtr(P1-P2)/100 + P2).
dIXEL Installing and Operating Instructions 1592020080 Au2 High temperature alarm of condenser: (-55÷150°C) when this temperature is reached the 8.8 DIGITAL INPUTS POLARITY HA2 alarm is signalled, possibly after the Ad2 delay. AH2 Differential for temperature condenser alarm recovery: (0,1÷25,5°C; 1÷45°F) The digital input polarity depends on the “i1P” parameter. Ad2 Condenser temperature alarm delay: (0÷255 min) time interval between the detection of the i1P=CL: the input is activated by closing the contact. condenser alarm condition and alarm signalling. i1P=OP: the input is activated by opening the contact dA2 Condenser temperature alarm exclusion at start up: (from 0.0 min to 23.5h, res. 10min) bLL Compressor off with low temperature alarm of condenser: n = no: compressor keeps on 9. TTL SERIAL LINE – FOR MONITORING SYSTEMS working; Y = yes, compressor is switched off till the alarm is present, in any case regulation The TTL serial line, available through the HOT KEY connector, allows by means of the external restarts after AC time at minimum. TTL/RS485 converter, XJ485-CX, to connect the instrument to a monitoring system ModBUS-RTU AC2 Compressor off with high temperature alarm of condenser: n = no: compressor keeps on compatible such as the X-WEB500/3000/300. working; Y = yes, compressor is switched off till the alarm is present, in any case regulation restarts after AC time at minimum. 10. X-REP OUTPUT – OPTIONAL DIGITAL INPUT As optional, an X-REP can be connected to the instrument, trough the HOY KEY i1P Digital input polarity: oP: the digital input is activated by opening the contact; CL: the digital connector. The X-REP output EXCLUDES the serial connection. input is activated by closing the contact. To connect the X-REP to the i1F Digital input configuration: EAL = external alarm: “EA” message is displayed; bAL = serious instrument the following connectors alarm “CA” message is displayed. PAL = pressure switch alarm, “CA” message is displayed; must be used CAB-51F(1m), CAB- dor = door switch function; dEF = activation of a defrost cycle; AUS =not enabled; Htr = kind of 52F(2m), CAB-55F(5m), action inversion (cooling – heating); FAn = not set it; ES = Energy saving. did: (0÷255 min) with i1F= EAL or i1F = bAL digital input alarm delay: delay between the 11. INSTALLATION AND MOUNTING detection of the external alarm condition and its signalling. Instrument XR72CX shall be mounted on vertical panel, in a with i1F= dor: door open signalling delay 29x71 mm hole, and fixed using the special bracket supplied. with i1F = PAL: time for pressure switch function: time interval to calculate the number of The temperature range allowed for correct operation is 0÷60 °C. the pressure switch activation. Avoid places subject to strong vibrations, corrosive gases, nPS Pressure switch number: (0 ÷15) Number of activation of the pressure switch, during the “did” excessive dirt or humidity. The same recommendations apply to interval, before signalling the alarm event (I2F= PAL). probes. Let air circulate by the cooling holes. If the nPS activation in the did time is reached, switch off and on the instrument to restart normal regulation. odc Compressor and fan status when open door: no = normal; Fan = Fan OFF; CPr = Compressor OFF; F_C = Compressor and fan OFF. rrd Outputs restart after doA alarm: no = outputs not affected by the doA alarm; yES = outputs 12. ELECTRICAL CONNECTIONS restart with the doA alarm; The instrument is provided with screw terminal block to connect cables with a cross section up to 2,5 HES Temperature increase during the Energy Saving cycle : (-30,0°C÷30,0°C/-22÷86°F) it sets mm2. Before connecting cables make sure the power supply complies with the instrument’s the increasing value of the set point during the Energy Saving cycle. requirements. Separate the probe cables from the power supply cables, from the outputs and the OTHER power connections. Do not exceed the maximum current allowed on each relay, in case of heavier Adr Serial address (1÷244): Identifies the instrument address when connected to a ModBUS loads use a suitable external relay. compatible monitoring system. PbC Type of probe: it allows to set the kind of probe used by the instrument: PbC = PBC probe, ntc 12.1 PROBE CONNECTION = NTC probe. The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid onF on/off key enabling: nu = disabled; oFF = enabled; ES = not set it. infiltration. It is recommended to place the thermostat probe away from air streams to correctly dP1 Thermostat probe display measure the average room temperature. Place the defrost termination probe among the evaporator dP2 Evaporator probe display fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during dP3 Third probe display- optional. defrost, to prevent premature defrost termination. dP4 Fourth probe display. rSE Real set point: it shows the set point used during the energy saving cycle or during the 13. HOW TO USE THE HOT KEY continuous cycle. rEL Software release for internal use. Ptb Parameter table code: readable only. 13.1 HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD) 1. Program one controller with the front keypad. 8. DIGITAL INPUT (ENABLED WITH P3P = N) 2. When the controller is ON, insert the “Hot key” and push o key; the "uPL" message The free voltage digital input is programmable in different configurations by the “i1F” parameter. appears followed a by flashing “End” 3. Push “SET” key and the End will stop flashing. 4. Turn OFF the instrument remove the “Hot Key”, then turn it ON again. 8.1 DOOR SWITCH INPUT (i1F = dor) It signals the door status and the corresponding relay output status through the “odc” parameter: no NOTE: the “Err” message is displayed for failed programming. In this case push again o key if you = normal (any change); Fan = Fan OFF; CPr = Compressor OFF; F_C = Compressor and fan OFF. want to restart the upload again or remove the “Hot key” to abort the operation. Since the door is opened, after the delay time set through parameter “did”, the door alarm is enabled, the display shows the message “dA” and the regulation restarts is rtr = yES. The alarm 13.2 HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY stops as soon as the external digital input is disabled again. With the door open, the high and low temperature alarms are disabled. (DOWNLOAD) 1. Turn OFF the instrument. 8.2 GENERIC ALARM (i1F = EAL) 2. Insert a programmed “Hot Key” into the 5 PIN receptacle and then turn the Controller ON. 3. Automatically the parameter list of the “Hot Key” is downloaded into the Controller memory, As soon as the digital input is activated the unit will wait for “did” time delay before signalling the the “doL” message is blinking followed a by flashing “End”. “EAL” alarm message. The outputs status don’t change. The alarm stops just after the digital input is 4. After 10 seconds the instrument will restart working with the new parameters. de-activated. 5. Remove the “Hot Key”.. NOTE the message “Err” is displayed for failed programming. In this case turn the unit off and then 8.3 SERIOUS ALARM MODE (i1F = bAL) on if you want to restart the download again or remove the “Hot key” to abort the operation. When the digital input is activated, the unit will wait for “did” delay before signalling the “CA” alarm message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de- 14. ALARM SIGNALS activated. Message Cause Outputs “P1” Room probe failure Compressor output acc. to par. “Con” and “COF” 8.4 PRESSURE SWITCH (i1F = PAL) “P2” Evaporator probe failure Defrost end is timed If during the interval time set by “did” parameter, the pressure switch has reached the number of “P3” Third probe failure Outputs unchanged activation of the “nPS” parameter, the “CA” pressure alarm message will be displayed. The compressor and the regulation are stopped. When the digital input is ON the compressor is always “P4” Fourth probe failure Outputs unchanged OFF. If the nPS activation in the did time is reached, switch off and on the instrument to “HA” Maximum temperature alarm Outputs unchanged. restart normal regulation. “LA” Minimum temperature alarm Outputs unchanged. "HA2" Condenser high temperature It depends on the “Ac2” parameter 8.5 START DEFROST (i1F = dFr) "LA2" Condenser low temperature It depends on the “bLL” parameter It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation “dA” Door open Compressor and fans restarts will restart only if the digital input is disabled otherwise the instrument will wait until the “MdF” safety “EA” External alarm Output unchanged. time is expired. “CA” Serious external alarm (i1F=bAL) All outputs OFF. “CA” Pressure switch alarm (i1F=PAL) All outputs OFF 8.6 INVERSION OF THE KIND OF ACTION: HEATING-COOLING (i1F = Htr) This function allows to invert the regulation of the controller: from cooling to heating and viceversa. 14.1 ALARM RECOVERY Probe alarms P1”, “P2”, “P3” and “P4” start some seconds after the fault in the related probe; they 8.7 ENERGY SAVING (i1F = ES) automatically stop some seconds after the probe restarts normal operation. Check connections The Energy Saving function allows to change the set point value as the result of the SET+ HES before replacing the probe. (parameter) sum. This function is enabled until the digital input is activated. Temperature alarms “HA”, “LA” “HA2” and “LA2” automatically stop as soon as the temperature returns to normal values. Alarms “EA” and “CA” (with i1F=bAL) recover as soon as the digital input is disabled.
dIXEL Installing and Operating Instructions 1592020080 Alarm “CA” (with i1F=PAL) recovers only by switching off and on the instrument. Labe Name Range °C/°F Level COn Compressor ON time with faulty probe 0 ÷ 255 min 15 Pr2 14.2 OTHER MESSAGES COF Compressor OFF time with faulty probe 0 ÷ 255 min 30 Pr2 Pon Keyboard unlocked. CF Temperature measurement unit °C ÷ °F °C Pr2 PoF Keyboard locked rES Resolution in=integer; dE= dec.point dE Pr1 noP In programming mode: none parameter is present in Pr1 Lod Probe displayed P1;P2 P1 Pr2 On the display or in dP2, dP3, dP4: the selected probe is nor enabled rEd2 X-REP display P1 - P2 - P3 - P4 - SEt - dtr P1 Pr2 15. TECHNICAL DATA dLy Display temperature delay 0 ÷ 20.0 min (10 sec.) 0 Pr2 dtr P1-P2 percentage for disply 1 ÷ 99 50 Pr2 Housing: self extinguishing ABS. tdF Defrost type EL=el. heater; in= hot gas EL Pr1 Case: XR72CX frontal 32x74 mm; depth 60mm; Mounting: XR72CX panel mounting in a 71x29mm panel cut-out dFP Probe selection for defrost termination nP; P1; P2; P3; P4 P2 Pr2 Protection: IP20; Frontal protection: XR72CX IP65 dtE Defrost termination temperature -50 ÷ 50 °C 8 Pr1 Connections: Screw terminal block ≤ 2,5 mm2 wiring. IdF Interval between defrost cycles 1 ÷ 120 ore 6 Pr1 Power supply: according to the model: 12Vac/dc, ±10%; 24Vac/dc, ±10%; 230Vac ±10%, MdF (Maximum) length for defrost 0 ÷ 255 min 30 Pr1 50/60Hz, 110Vac ±10%, 50/60Hz dSd Start defrost delay 0÷99min 0 Pr2 Power absorption: 3VA max dFd Displaying during defrost rt, it, SEt, DEF it Pr2 Display: 3 digits, red LED, 14,2 mm high; Inputs: Up to 4 NTC or PTC probes. dAd MAX display delay after defrost 0 ÷ 255 min 30 Pr2 Digital input: free voltage contact Fdt Draining time 0÷120 min 0 Pr2 Relay outputs: compressor 1 SPST 8(3) A, 250Vac; SPST 16(6)A 250Vac dPo First defrost after startup n=after IdF; y=immed. n Pr2 defrost: SPDT 8(3) A, 250Vac or SPST 16(6)A 250Vac dAF Defrost delay after fast freezing 0 ÷ 23h e 50’ 0.0 Pr2 fan: SPST 5A, 250Vac or SPST 16(6)A 250Vac Fnc Fan operating mode C-n, o-n, C-y, o-Y o-n Pr1 compressor 2: SPDT 8(3) A, 250Vac or SPST 16(6)A 250Vac Fnd Fan delay after defrost 0÷255min 10 Pr1 Data storing: on the non-volatile memory (EEPROM). Fct Differential of temperature for forced 0÷50°C Kind of action: 1B; Pollution grade: 2;Software class: A.; 10 Pr2 activation of fans Rated impulsive voltage: 2500V; Overvoltage Category: II Operating temperature: 0÷60 °C;Storage temperature: -30÷85 °C. FSt Fan stop temperature -50÷50°C/-58÷122°F 2 Pr1 Relative humidity: 20÷85% (no condensing) Fon Fan on time with compressor off 0÷15 (min.) 0 Pr2 Measuring and regulation range: NTC probe: -40÷110°C (-40÷230°F); FoF Fan off time with compressor off 0÷15 (min.) 0 Pr2 PTC probe: -50÷150°C (-58÷302°F) FAP Probe selection for fan management nP; P1; P2; P3; P4 P2 Pr2 Resolution: 0,1 °C or 1°C or 1 °F (selectable); Accuracy (ambient temp. 25°C): ±0,7 °C ±1 digit ALc Temperat. alarms configuration rE= related to set; Ab Pr2 Ab = absolute 16. CONNECTIONS ALU MAXIMUM temperature alarm Set÷110.0°C; Set÷230°F 110 Pr1 The X-REP output excludes the TTL output.. It’s present in the following codes: ALL Minimum temperature alarm -50.0°C÷Set/ -58°F÷Set -50.0 Pr1 XR72CX- xx2xx, XR72CX –xx3xx; AFH Differential for temperat. alarm recovery (0,1°C÷25,5°C) (1°F÷45°F) 1 Pr2 ALd Temperature alarm delay 0 ÷ 255 min 15 Pr2 16.1 XR72CX – 8A OR 16A COMP. RELAY - 12VAC/DV OR 24 VAC/DV dAO Delay of temperature alarm at start up 0 ÷ 23h e 50’ 1.3 Pr2 NOTE: The compressor AP2 Probe for temperat. alarm of condenser nP; P1; P2; P3; P4 P4 Pr2 relay is 8(3)A or 16(6)A AL2 Condenser for low temperat. alarm (-55 ÷ 150°C) (-67÷ 302°F) -40 Pr2 according to the model. AU2 Condenser for high temperat. alarm (-55 ÷ 150°C) (-67÷ 302°F) 110 Pr2 24Vac/dc supply: AH2 Differ. for condenser temp. alar. recovery [0,1°C ÷ 25,5°C] [1°F ÷ 45°F] 5 Pr2 connect to the terminals 5 Ad2 Condenser temperature alarm delay 0 ÷ 254 (min.) , 255=nU 15 Pr2 and 6. dA2 Delay of cond. temper. alarm at start up 0.0 ÷ 23h 50’ 1,3 Pr2 Compr. off for condenser low n Pr2 bLL temperature alarm n(0) - Y(1) Compr. off for condenser high n Pr2 AC2 temperature alarm n(0) - Y(1) i1P Digital input polarity oP=opening;CL=closing cL Pr1 i1F Digital input configuration EAL, bAL, PAL, dor; dEF; Htr, AUS dor Pr1 did Digital input alarm delay 0÷255min 15 Pr1 Nps Number of activation of pressure switch 0 ÷15 15 Pr2 16.2 XR72CX –4 X 16A - 12VAC/DC odc Compress and fan status when open no; Fan; CPr; F_C F-c Pr2 door rrd Regulation restart with door open alarm n–Y y Pr2 HES Differential for Energy Saving (-30°C÷30°C) (-54°F÷54°F) 0 Pr2 PbC Kind of probe Ptc; ntc 1 Pr2 Adr Serrial address 1÷247 1 Pr2 onF on/off key enabling nu, oFF; ES ntc Pr1 dP1 Room probe display -- nu Pr2 dP2 Evaporator probe display -- -- Pr1 dP3 Third probe display -- -- Pr1 dP4 Fourth probe display -- -- Pr1 rSE Valore set operativo actual set -- Pr2 rEL Software release -- -- Pr2 Ptb Map code -- -- Pr2 2 Only for models XR72CX–xx2xx, XR72CX–xx3xx;
17. DEFAULT SETTING VALUES
Labe Name Range °C/°F Level Set Set point LS÷US -5.0 --- Hy Differential 0,1÷25.5°C/ 1÷ 255°F 2.0 Pr1 LS Minimum set point -50°C÷SET/-58°F÷SET -50.0 Pr2 US Maximum set point SET÷110°C/ SET ÷ 230°F 110 Pr2 Ot Thermostat probe calibration -12÷12°C /-120÷120°F 0.0 Pr1 P2P Evaporator probe presence n=not present; Y=pres. Y Pr1 OE Evaporator probe calibration -12÷12°C /-120÷120°F 0.0 Pr2 P3P Third probe presence n=not present; Y=pres. n Pr2 O3 Third probe calibration -12÷12°C /-120÷120°F 0 Pr2 P4P Fourth probe presence n=not present; Y=pres. n Pr2 O4 Fourth probe calibration -12÷12°C /-120÷120°F 0 Pr2 OdS Outputs delay at start up 0÷255 min 0 Pr2 AC Anti-short cycle delay 0 ÷ 50 min 1 Pr1 Dixell S.p.A. Z.I. Via dell’Industria, 27 AC1 2nd compressor delay 0 ÷ 255s 1 Pr1 32010 Pieve d’Alpago (BL) ITALY rtr P1-P2 percentage for regulation 0 ÷ 100 (100=P1 , 0=P2) 100 Pr2 tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13 CCt Continuos cycle duration 0.0÷24.0h 0.0 Pr2 E-mail: dixell@dixell.com - http://www.dixell.com CCS Set point for continuous cycle (-55.0÷150,0°C) (-67÷302°F) -5 Pr2