Technical Parameters

Detecting gas Natural Gas CH4/LP gas /natural gas+LP gas


Work voltage DC10V~24V
Static current ≤100mA
Alarm current ≤150mA
TEST RANGE 0~100% LEL Alarm density 6% LEL
Alarm density error ±3% LEL
Buzzer ≥70(1m)
STANDALONE COMBUSTIBLE Operating condition 0 ℃~+55℃ relative humidity:≤95%(indoor use type)
Stability Regular alarm density error±5%LEL
Repeatability Repeated test alarm density error±3%LEL
GAS DETECTOR Sampling method Natural diffusion
Alarm mode Sound & flash, NO/NC
Dimension 120*68*32mm
Weight 103g

We have selected advanced plane semiconductor gas Installation


detector for this product, which has the inner temperature
1. Suitable installation is 0.3-1.0m lower than ceiling and at least
compensation module, it is more safety and stability, Suitable
1.5M far from the gas source radius.
for house, hotel, flat etc. indoor places which might exist
combustible gas. This product has passed China certificate
Please do not install the detector in this area;
center for fire products ministry of public security (CCCF),
The vertical position of Ceiling & gas source
it accords with the standard requirement of GB15322.2-2003 is the center, Circle with radius of 1.5m.
section 2 about the combustible gas detector: test range Detector

0~100% LEL standalone combustible gas detector.

Diagrammatic sketch

Gas stove

1. Auto-check / switch key


normal work indicator
alarm indicator
fault indicator 2. Fix the board on the selected place by screw, insert the
2. Gas convection windows detector and revolve it, then check whether it is firm or not.

Pluggable terminal

Slide cover
Please slide the cover 3. For home installation should pay attention, please do not install
following the arrow direction
the detector near the gas stove, to avoid detector bake by the
stove flame, do not install in the place with large lampblack, to
avoid wrong alarm or cause the detector air intake not smooth,
which greatly affect to sensibility of the detector, please do not
fix near the ventilators, windows, doors, shower room with
much source of steam.

Outlet hole design


It is easy to cut one/two pieces
here to have the outlet hole
Usage detector. User needs to clean the gas convention window with a
little cleanser every 3 month, meanwhile should avoid the cleanser
This product can be used independently as detector, and can be flowing into the detector, please retest the detector after cleaning.
used with networking(control panel) too, output NO/NC signal. Emergency treatment
1. Independent
The detector will keep alarm if the gas density in the air reach or
(1) Choose a suitable position to install the detector according to beyond the alarm density, now you should:
the installation. 1.Shut down the valve of the tube immediately.
(2) Connect the power, the buzzer sound ”di”, detector turns into 2.Open window to make indoor air flowing rapidly.
warm up state, then the yellow,Red, green LED flash 1 time in 3.Extinguish all fire source and do not use anything can make
every 3 seconds. When the Red ,yellow LED off, and the spark, e.g. : lighter, match, etc.);
green LED flash 1 time in every 3 seconds, the detector 4.Avoid opening or closing any kind of electrical facilities;
comes into normal work state.
5.Find out the reason of gas leaking and inform professional
(3) In normal work state, press the test key once, the detector person in time to deal with it. If user check and find out the
enters into self-check state, red,green,yellow LED flash 3 times, detector give fault alarm, user should check whether the detector
Buzzer sound 3 times, at this moment relay is not working.
installation position is appropriate.
2. Networking usage
LED information
(1) reference “installation” fix the detector in appropriate position.
Choose the NO/NC contact, connect the detector with control Red LED flash Gas leaking alarm
panel.
Yellow LED keep on Internal error of detector
(2) Connect the power, the buzzer sound ”di”, detector turns into
warm up state, then the yellow,Red, green LED flash 1 time in Green LED flash Normal work state
every 3 seconds. When the Red,yellow LED off, and the green
LED flash 1 time in every 3 seconds, the detector comes into Red,Yellow,green LED all flash Warm up state
normal work state.
(3) In normal work state, press the test key once, the detector Install environment
enters into self-check state, red,green,yellow LED flash 3 times,
Buzzer sound 3 times, at this moment relay is not working. Any electrical products have the using environment requirement,
this product installation should pay extra attention following items:
3. Alarm state 1.Avoid the product to touch high temperature water vapor, long
Detector detect combustible gas leaking, when the combustible time influenced of lampblack; if could not avoid, should install
gas density get to the active value, red led indicator flash 3 times exhaust fan, ventilator etc. Equipment near to the detector.
in every 3 seconds, the buzzer sound ”di di di”,the movement of 2.Avoid to install in high humidity environment; that means the
relay output the alarm signal.After combustible gas being eliminate, place with plenty of water vapor, water.
detector automatically recovery to normal state, you could press 3.Avoid to install in high or low temperature, should be above
“auto-check/switch” key, eliminate alarm. Eliminate alarm state only
last 12 minutes, 12 minutes later return to normal monitor state, to 55℃ or under -20℃ .
avoid user mistakenly touch to close the alarm signal all the time. 4.Please be far always from following gases: organic silicon vapor,
formaldehyde, methyl-benzene, acetic acid, hydrogen sulfide, etc
4.Fault state which mainly produced by house decoration, decoration material,
When detector internal Fault state maintains more than 5 seconds, such as binder, wall painting, hairspray, silicon rubber etc. These
yellow LED will keep on and the buzzer keep sounding.Please gases would cause the detector damage, not possible to recovery,
shut down the power and re-open the power again. The detector and cause the detector give fault alarm. In addition high density
will self-check. formaldehyde vapor would cause the fault alarm.

Test Notices
After fix well the gas leakage detector, you could give small amount
1. Please install the detector according to user manual recommended sketch
of gas which is around 5cm from the gas convention window to test
map. If not possible to meet the condition, installation person should consider
the detector alarm state by lighter non-ignition mode, when alarm the relative factors of “installation environment”,find out the best position to fix
would come with the output of networking signal, could be judge as it. To make sure detector under valid monitor range.
system networking access testing. Due to the Inherent characteristics
2.In order to low down cost of the project installation maintenance and reduce
of semiconductor detector, please do not release plenty of gas with the fault alarm due to the improper construction, the installation person should
high density to test the detector, and do not frequently or long time conduct an initial assessment of the kitchen function, distribution, setting to
testing the detector which might caused the damage of detector confirm the best position of wiring and installing before installation & wiring.
sensitive material and the great fall of the detector sensitivity, all
would result in fault alarm. The alarm density of gas is setting 3.Please do make sure to realize that the gas released from house decoration
is a damage for the detector, could not be recovery which might cause the fault
according to the criteria of GB15322.2-2003 regulated value, the
alarm or invalid. During the decoration time, we suggest user to use regular
detector would stop alarming and turn into detecting state while the environment protection material, do not take off products blister, it could
gas density is lower than alarm level. automatic deposit dust proof. Open the door and window, keep indoor
ventilation, if it is possible, you could take off the detector temporary.
Test skill
Control the lighter gas density from small to large manually, with
different mode of ignition, distance around 5cm from the gas Matters need attention
convention window (do not test it directly to the detector) to release
the gas (check and make sure the red led light will flash) slowly from 1. The product must work with correct connection and right power
thin to thick, keep it until detector alarm with red light flash, then supplier, the detector could not work normally no matter
immediately remove the lighter. The direct impact of high density what ‘s reason caused the power off,.
gas to the detector should be avoid when it is being test. 2. Please take off the blister in time after the detector keeping
work for 24 hours powering on.
Maintenance 3. The product should keep periodic maintenance according to
the user manual.
After long time use of gas detector, the gas convention window
4. The detector could not work without life time limit,our
would caused the adhesion of oil, which effect the sensitive of recommended validity life is 3 year, it should be test every
half year, and you should repair or change after find it invalid.
5. The product could not use high density(>100% LEL)gas to
test, otherwise it might reduce the sensor sensitivity, and
cause the sensor could not work normally.
6. The product could reduce the accident, but could not make
sure a hundred percent safe. For your safety, please keep
precaution and enhance safety consciousness in daily life,
besides using our products correctly.