ADVC3 Brosura NULEC PDF
ADVC3 Brosura NULEC PDF
ADVC3 Brosura NULEC PDF
Range
schneider-electric.com
2 schneider-electric.com
ADVC Controller Range
Two Controller Solutions
ADVC Compact - IP 54 Cubicle
Offering
• Superior Reliability and
Performance
• Configurable User Interfaces
• Advanced Protection Features
• Enhanced Communications
• Analytical Tools
2 Communication Ports
6 Standard DB9, RJ45 and USB connections
are easily accessible. There is no need for
complicated customised communication cables,
Note: Refer page 4 for remaining numbered annotations. making installation and commissioning simple.
Mounted on the CAPE, you can choose the best Operator Interface for your needs:
• Menu driven setVUE Interface, or
• Fully configurable flexVUE interface
Expand your ADVC Solution into a fully integrated SCADA solution by adding modems, radios, I/O
expanders and other customer accessories to the detachable accessory trays.
The sturdy cast-aluminium tray can be moved from its mounting to the front of the cubicle making
commissioning and installation easier. Once all the accessories are positioned, simply move the tray
back into place.
The tray design caters to a wide variety of equipment and mounting configurations.
5 Extra Power
Auxiliary power, including an optional courtesy outlet, is easily accessed with a power supply unit
at the base of the cubicle. Transformers, breakers and terminals are available for auxiliary power
connection, and all wiring is protected by a safe IP20‑rated removable cover. A silicone rain-shield
also covers the miniature circuit breakers.
6 Battery Backup
Up to 46 hours* battery hold up time without power. 2 × 12 V lead-acid batteries (at base of cubicle)
provide up to 5 years trouble free operation. Both controllers offer 7 Ah batteries, and the ULTRA also
offers optional
12 Ah batteries for longer hold up, and heater, for operation to -40 ºC.
4 schneider-electric.com
Features
Advancing your electricity distribution network is easily accomplished with the host of ergonomic,
physical, protection/detection, automation, analytical and communication features. Designed around
the user, the ADVC Controller Range provides reliable and advanced protection relays/controllers for
overhead network applications.
Protection Features
• Phase over current • Under/over voltage • High current lockout
• Earth fault • Under/over frequency • Broken conductor
• Sensitive earth fault • Rate of change of frequency • Fault locator
• Negative phase sequence • Check sync • Loss of phase
• Directional protection • Neutral voltage displacement • Close on fault trip
• Directional blocking • Inrush restraint (zero detect/2nd • Automatic protection group
• Cold load harmonic) selection (up to 10 configurable
protection groups)
Protection Curves
100
Flexibility
Extended Protection Settings
Flexibility in configuring the desired action
for each of the protection elements.
Choose between ‘Alarm’ or ‘Trip’.
Automation Features
• Classic Loop Automation
• Intelligent Loop Automation Base Loop
Automation
-- Peer-to-Peer communication Scheme
-- Overload Control
-- Load shed
• Auto Change Over
6 schneider-electric.com
Specifications
Physical Specifications COMPACT ULTRA
Controller weight 30 kg 34 kg
Cubicle height 730 mm 960 mm
Cubicle width 420 mm 450 mm
Cubicle depth 302 mm 302 mm
Cubicle material 304 stainless steel 316 stainless steel
Customer compartment size [mm] 70 x 270 x 200 70 x 270 x 200 &
260 x 280 x 200
Cubicle shell sealing IP54 IP65
Electronic enclosure sealing IP65 IP65
Wind loading resistance of structure >160 km/hr >160 km/hr
Wind loading on door when latched in open position >60 km/hr >60 km/hr
Angle of door opening 135° 135°
Operating temperature range -10°C to 50°C -10°C to 50°C
Extended operating temperature range with battery heater (ULTRA only) - -40°C to 50°C
Electronics operating temperature range -40°C to 70°C -40°C to 70°C
Maximum radiation 1.1 kW/m² 1.1 kW/m²
Humidity 0 to 100% 0 to 100%
Battery COMPACT/ULTRA
Battery type (sealed lead-acid) 2 x 12 VDC
Battery capacity 7 Ah (12 Ah option on ULTRA)
Battery hold up time with panel off and without communications devices or heater at 28 hours with 7 Ah (48 hours with 12 Ah)
25°C
Capacity available for communications hold up time (Panel off, no heater or IOEX 13.8 V 20 hours
TX: 2.1 A, 15 min, RX 320 mA)
Battery recharge time
• 7 Ah battery from new to 80% nominal capacity 9.5 hours
• 12 Ah battery from new to 80% nominal capacity 13.5 hours
Battery replacement interval 5 years (Influenced by
environment)
Radios or modems may be fitted for remote communications. Space, power and data interfaces are provided within the control cubicle.
Radio/modem COMPACT/ULTRA
Radio/modem power supply voltage 5 - 15 VDC
Radio/modem power supply current 3 A cont, 8 A peak
Radio/modem power supply shut-down time 1 - 1440 mins
Radio/modem interface RS232, Ethernet, USB 2.0
Other COMPACT/ULTRA
Earthing 10 mm earth stud
© 2017 Schneider Electric. All Rights Reserved. Life Is On Schneider Electric is a trademark and the property of Schneider Electric SE, its subsidiaries and affiliated companies.
• N00-805