40-40I Flame Detector
40-40I Flame Detector
40-40I Flame Detector
40/40I
Triple IR (IR3) Flame Detector
Superior performance, reliability and immunity to false alarms
OUTPUTS
Relays Alarm, Fault and Auxiliary
SPST volt-free contacts rated 5A at 30 VDC or 250 VAC.
0-20mA (stepped) Sink (source option) configuration
Fault: 0 +1mA Warning: 16mA ± 5%
BIT Fault: 2mA ± 10% Alarm: 20mA ± 5%
Normal: 4mA ± 10% Resistance Loop: 100-600 Ω
HART Protocol Optional HART communications on the 0-20mA analog current (FSK) - used for maintenance,
configuration changes and asset management, available in mA source output wiring options
RS-485 RS-485 Modbus compatible communication link that can be used in computer controlled
installations
MECHANICAL SPECIFICATIONS
Materials - Stainless Steel 316L with electro polish finish
Enclosure options - Heavy duty copper free aluminum (less than 1%), red epoxy enamel finish
Mounting Stainless Steel 316L with electro polish finish
Dimensions Detector 4" x 4.6" x 6.18" (101.6 x 117 x 157 mm)
Weight Detector (St.St.) 6.1 lb (2.8 kg) Tilt mount 2.2 lb (1.0 kg)
Detector, aluminum 2.8 lb (1.3 kg)
Environmental Standards Meets MIL-STD-810C for Humidity, Salt & Fog, Vibration, Mechanical Shock, High Temp, Low Temp
Water and Dust IP66 and IP67 per EN60529, NEMA 250 6P
APPROVALS
Hazardous Area ATEX and IECEx Ex II 2 GD,
Ex de IIC T5 (-55ºC to +75ºC) Ex de IIC T4 (-55ºC to +85ºC)
Ex tD A21 IP66/X7 T 95ºC Ex tD A21 IP66/X7 T 105ºC
FM/FMC/CSA Class I Div. 1, Groups B, C & D
Class II/III Div. 1, Groups E, F & G
Performance EN54-10 (LPCB)
FM-3260 (FM)
DNV Marine Approval
Reliability IEC61508 - SIL2 (TUV)
ACCESSORIES
Fire Simulator 20/20-310 U-Bolt/Pole Mount 789260-2 (2" pole) Mini Laptop Kit 777820 Laser Pointer 777166
Tilt Mount 40/40-001 789260-1 (3" pole) Weather Protector 777163 (Detector area coverage)
Duct Mount 777670 USB RS485 Harness Kit 794079-5 Air Shield 777161