Hitachi Circuit Breakers and Miniature Circuit Breakers are such as conductors, motors, and starters.
designed for circuit protection of low-voltage distribution They are designed for use in switchboard, control centers,
systems. They are suitable for application as main breakers and panel boards, combination starters, and separate individual
for protection of branch and feeder circuits and connected enclosures. In these various enclosures, they are applicable to
apparatus. These breakers provide overload protection for the requirements of lighting, distribution, and other power
conductors and short-circuit protection for all circuit elements circuits.
C ONTENTS
Applications..........................................................................................................................................1
Fuse-Free Breakers
New Line-up Series (Features) ........................................................................................................................... 2
Classification and Composition ......................................................................................................................... 4
Composition in terms of Interrupting Capacity ............................................................................................... 5
Ratings and Specifications ................................................................................................................................. 6
Construction ..................................................................................................................................................... 15
Characteristics .................................................................................................................................................. 19
Caution.............................................................................................................................................................. 20
Selection ........................................................................................................................................................... 21
Accessories ........................................................................................................................................................ 25
Dimensions ....................................................................................................................................................... 39
1
FUSE-FREE BREAKER
NEW L INE-UPS WITH FULLY INTEGRATED C ONFIGURATION,
A DVANCED P ERFORMANCE AND SIMPLIFIED OPERATION
FEATURES
New color
of
the face
2
High
breaking
performance
Breaking performance of standard type (F series) are lcs = 100%lcu which is world level performance of
the breaking current by new solution of breaking system and new breaking system reduces thermal and
mechanical stress to distribution systems and they can be used any distribution system.
3
C LASSIFICATION AND C OMPOSITION
Hitachi Fuse-Free Breakers are produced in the variety of types shown below. Any type can
be freely chosen according to the purposes of applications and circuit conditions, making it
possible to design an electric circuit with high economy and reliability.
Motor Breaker
M Series
4
C OMPOSITION IN TERMS OF INTERRUPTING C APACITY
AC 230V — 240V
Transformer capacity 750 –
– 30 50 – 100 150 200 – 500 2000 – 3000
(kVA) 1500
Interrupting capacity
5 7.5 10 14 25 35 42 50 85 100 125 175
kA (sym)
30 S-30E F-30FB
50 S-50EB S-50SB L-50E
60 S-60RB F-60RB
100 125 S-100EB S-100S S-100SB FXK125-S FXK125-H L-100E
FXK250-S FXK250-H
225 250 S-225SB, SXK225 L-225E
Frame (AF) F-250FB F-250KC
400 SX400, S-400S FX400, F-400R L-400E
600 SX600, S-600S FX600, F-600F L-600E
SX800 FX800
800 F-800RH L-800E
S-800S F-800R
1000 – 1200 FX1000, FX1200, F-1000K, F-1200K, F-1000C, F-1200C
1600 F-1600CB, F-1600B, F-1600E
AC 380V — 440V
Transformer capacity
– 50 75 – 100 200 – 500 750 – 1000 1500 – 2000 2500 – 3500
(kVA)
Interrupting capacity
1.5 2.5 5 7.5 10 15 18 22 25 30 35 50 85 125 175
kA (sym)
30 S-30E F-30FB
50 S-50EB S-50SB L-50E
60 S-60RB F-60RB
100 125 S-100S, S-100SB FXK125-S FXK125-H L-100E
FXK250-S FXK250-H
Frame (AF) 225 250 S-225SB, SXK225
F-250FB F-250KC
L-225E
SX400 FX400
400 L-400E
S-400S F-400R
SX600 FX600
600 L-600E
S-600S F-600F
FX800
800 SX800, S-800S F-800RH L-800E
F-800R
1000 – 1200 FX1000, FX1200, F-1000K, F-1200K, F-1000C, F-1200C
1600 F-1600CB, F-1600B, F-1600E
F Series
S Series
5
R ATINGS AND SPECIFICATIONS
Table 1 F series
Type F-30FB F-60RB F-60R F-100S FXK125-S FXK125-H F-100KB
Appearance
d 84 84 85 94 94 106
Net Weight (kg) 0.48 0.6 0.53 0.74 0.96 1.3 1.4 1.4 1.4 1.4 2.3
Standard Connection Type Front Terminal Front Terminal Front Terminal Front Terminal Front Terminal
Phase Separator for Line Side ○ ● (*2) ● ● (*2) ● (*2)
Alarm Switch AL ○ ○ ○ ○ (*3) ○ (*3) ○
Auxiliary Switch AUX ○ ○ ○ ○ (*3) ○ (*3) ○
Interior Shunt Trip SHT ○ ○ ○ ○ (*3) ○ (*3) ○
Accessories Undervoltage Trip UVT — — ○ — — ○
TB ○ ○ ○ ○ ○
Terminal Block
TB2 ○ ○ ○ ○ ○
STB-3H STB-2S (Up to 50A) STB-2S (Up to 50A) STB-3J
Rear-connecting STB STB-2M STB-2M STB-1B
(Up to 50A : STB-2D) BSD-3S (60A or more) BSD-3S (60A or more) (Up to 50A : STB-2)
Stud
BSD — — — —
Flush Mounting Base GKW(STB) ○ ○ ○ — — ○
Assembly GK GKW(BSD) — — — ○ (Up to 50A) ○ (Up to 50A) —
Plug-in Mounting
PK ○ ○ ○ ○ (60A or more) ○ (60A or more) ○
Base Assembly
Drawout Assembly PDK — — — — — —
Mechanical Interlock MIW MIW-2E MIW-2E MIW-1C MIW-2C MIW-3H MIW-3H MIW-3D
MMK-S — — — ○ ○ ○
Motor-operating
Exterior MMK-C — — — — — —
Mechanism
Accessories MMK — — — — — —
Lock Cover LC LC-2E LC-2E LC-1B LC-2C ○ ○ LC-2C
Handle Lock HL ○ ○ ○ ○ ○ ○
HA HA-108 HA-108 HA-107 HA-104 — — HA-106
Handle Operating
Mechanism HM- HM-
HM — — HM-57 — HM-S13 HM-S13 HM-S11
S12 S12
TMC TMC-1 TMC-1 TMC-2C TMC-2C TMC-2C TMC-3C
Front
Terminal Short Type TMC-1S TMC-1S — — — — —
Type
Cover Long Type TMC-2D TMC-2D — — — — —
Rear Type BTC BTC-1 BTC-1 BTC-2C BTC-2C BTC-2C BTC-3C
IEC Rail 35 mm ○ ○ — — — — —
Automatic Tripping Device Full Magnetic Full Magnetic Full Magnetic Thermal-Magnetic Thermal-Magnetic Full Magnetic
Trip Button ● ● ● ● ●
Attention
1. ● : Standard ○ : Option
2. 2-pole types marked with (*1) are supplied in 3-pole type.
3. Please state "For DC" in case of DC use. Especially, state please state kind of the power supply in case of from 30 to 100AF.
4. Flush Mounting Base Assembly, GKW are standard in case of up to 250AF and FX400.
5. Please state that number of poles of breakers when order MIW.
6. Installation of phase separators is required in case of types marked (*2).
7. Tripping system of F-1000K and F-1200K are induction heat system, please state frequency when ordering.
8. For DC use, the tripping character is only instantaneous trip in case of F-1000K and F-1200K.
9. The accessories marked (*3) can be installed by customers.
6
FXK250-S F-250FB FXK250-H F-250KC F-400R FX400 F-600F FX600
○ ○ ○ ○ ○ ○
— — — — —
○ ○ ○ (GK) ○ ○ (GK) ○ (GK)
○ ○ ○ ○ ○ ○
— — — — — —
MIW-4M MIW-4H MIW-4M MIW-4H MIW-5D MIW-5F MIW-5 MIW-5G
— — — — — —
— — ○ ○ ○ ○
— — — — — —
LC-4J LC-4H LC-4J LC-4H — — — —
HL-4J ○ HL-4J ○ HL-5 HL-5 HL-6 HL-6
HA-210 HA-206 HA-210 HA-206 HA-405 HA-406 HA-402 HA-402
7
Table 1 F series
Type F-800R FX800 F-800RH F-1000K F-1000C
Appearance
Number of poles 3 4 3 3 4 3 4 3 4
400 / 450 / 500 500 / 600 / 700
Rated Current (A)
700 800 600 / 700 / 800 700 800 1000 800 / 900 / 1000
(Base ambient temperature 40ºC)
adjustable adjustable
Rated Insulation Voltage Ui (V) 690 690 690 690 690
Rated Impulse withstand Voltage Uimp (kV) 8 8 8 8 8
690V — — — — —
440V 50 / 50 50 / 50 85 / 43 85 / 22 85 / 22
415V 50 / 50 50 / 50 85 / 43 85 / 22 85 / 22
Rated AC 400V 50 / 50 50 / 50 85 / 43 85 / 22 85 / 22
IEC 60947-2
Breaking 380V 50 / 50 50 / 50 85 / 43 85 / 22 85 / 22
Capacity (kA) (Icu/Ics)
240V 100 / 100 100 / 100 125 / 63 125 / 32 125 / 32
230V 100 / 100 100 / 100 125 / 63 125 / 32 125 / 32
250V 40 / 40 — — 40 / 40 — 40 / 10 — —
DC
125V 40 / 40 — — 40 / 40 — 40 / 10 — —
a d
c a 210 280 210 210 280 210 280 210 280
b 274 274 274 410 410
Dimensions (mm)
c 103 103 103 150 150
b
Attention
1. ● : Standard ○ : Option
2. 2-pole types marked with (*1) are supplied in 3-pole type.
3. Please state "For DC" in case of DC use. Especially, state please state kind of the power supply in case of from 30 to 100AF.
4. Flush Mounting Base Assembly, GKW are standard in case of up to 250AF and FX400.
5. Please state that number of poles of breakers when order MIW.
6. Installation of phase separators is required in case of types marked (*2).
7. Tripping system of F-1000K and F-1200K are induction heat system, please state frequency when ordering.
8. For DC use, the tripping character is only instantaneous trip in case of F-1000K and F-1200K.
9. The accessories marked (*3) can be installed by customers.
8
R ATINGS AND S PECIFICATIONS
3 3 4 3 4 3 3 4 3 4 3 4
500 / 600 / 700 600 / 700 / 800 600 / 700 / 800 800 / 900 / 1000 800 / 900 / 1000
1000 1200
800 / 900 / 1000 1200 1000 / 1200 1000 / 1200 1200 / 1400 / 1600 1200 / 1400 / 1600
1400 1600
adjustable adjustable adjustable adjustable adjustable
690 690 690 690 690 690 690
8 8 8 8 8 8 8
— — — — — — 45 / 34
85 / 85 85 / 22 85 / 22 85 / 85 85 / 22 85 / 22 85 / 64
85 / 85 85 / 22 85 / 22 85 / 85 85 / 22 85 / 22 85 / 64
85 / 85 85 / 22 85 / 22 85 / 85 85 / 22 85 / 22 100 / 75
85 / 85 85 / 22 85 / 22 85 / 85 85 / 22 85 / 22 100 / 75
125 / 125 125 / 32 125 / 32 125 / 125 125 / 32 125 / 32 125 / 94
125 / 125 125 / 32 125 / 32 125 / 125 125 / 32 125 / 32 125 / 94
— 40 / 10 — — — — 40 / 10 — —
— 40 / 10 — — — — 40 / 10 — —
210 210 280 210 280 210 210 280 210 280 210 280
410 410 410 410 410 410 370
150 150 150 150 150 150 140
190 190 190 190 190 190 191
26 26 33 26 33 26 37 49 37 49 27 36
Front Bar Terminal Front Bar Terminal Front Bar Terminal Front Bar Terminal Front Bar Terminal Front Bar Terminal Front Bar Terminal
● (*2) ● (*2) ● (*2) ● (*2) ● (*2) ● (*2) —
○ (*3) ○ ○ ○ (*3) ○ ○ ○
○ (*3) ○ ○ ○ (*3) ○ ○ ○
○ (*3) ○ ○ ○ (*3) ○ ○ ○
○ ○ ○ ○ ○ ○ ○
○ ○ ○ ○ ○ ○ ○
○ ○ ○ ○ ○ ○ —
— — — — — — —
○ ○ ○ ○ ○ ○ ○
— — — — — — —
○ (GK) ○ (GK) ○ (GK) ○ (GK) ○ (GK) ○ (GK) ○ (GK)
○ ○ ○ ○ — — —
— — — — — — ○
MIW-8 MIW-8 MIW-8 MIW-8 MIW-8D MIW-8D ○
— — — — — — —
○ ○ ○ ○ ○ ○ —
— — — — — — ○
— — — — — — ○
○ ○ ○ ○ ○ ○ ○
HA-801 HA-801 HA-801 HA-801 HA-801 HA-801 ○
— — — — — — —
TMC-6B TMC-6 TMC-6 TMC-6B — — —
— — — — — — —
— — — — — — —
— — — — — — —
— — — — — — —
Electronic Relay Thermal-Magnetic Electronic Relay Electronic Relay Electronic Relay Magnetic Electronic Relay
● ● ● ● ● ● ●
9
Table 2 S series
Type S-30S S-30E S-50E S-50EB S-50SB S-60RB S-100EB
Appearance
Number of poles 2 3 2 3 2 3 2 3 2 3 2 3 2 3
Rated Insulation Voltage Ui (V) 500 500 500 500 690 690 250
Rated Impulse withstand Voltage Uimp (kV) — 4 — 4 6 6 6
690V — — — — — — —
440V — — — — 2.5 / 1 5/2 —
415V — 1.5 / 1 — 1.5 / 1 2.5 / 1 5/2 —
Rated AC 400V 1.5 / 1 1.5 / 1 1.5 / 1 1.5 / 1 2.5 / 1 5/2 —
IEC 60947-2
Breaking 380V 1.5 / 1 — 1.5 / 1 — 2.5 / 1 5/2 —
Capacity (kA) (Icu/Ics)
240V 2.3 / 1.3 — 2.3 / 1.3 — 7.5 / 2 10 / 3 10 / 3
230V 2.5 / 1.3 5/2 2.3 / 1.3 5/2 7.5 / 2 10 / 3 10 / 3
250V — — — — 2.5 / 1 — 2.5 / 1 — 2.5 / 1 —
DC
125V — — — — 5/2 — 5/2 — 5/2 —
a d
c a 50 75 50 75 50 75 50 75 52 75 52 75 52 75
b 95 96 96 96 130 130 130
Dimensions (mm)
c 60 60 60 60 60 60 60
b
d 79 76 79 76 84 84 84
Net Weight (kg) 0.32 0.47 0.25 0.37 0.32 0.47 0.25 0.37 0.48 0.6 0.5 0.7 0.5 0.7
Standard Connection Type Front Terminal Front Terminal Front Terminal Front Terminal Front Terminal Front Terminal Front Terminal
Phase Separator for Line Side (*2) — — — — ○ ○ ○
Alarm Switch AL — ○ — ○ ○ ○ ○
Auxiliary Switch AUX — ○ — ○ ○ ○ ○
Interior Shunt Trip SHT — ○ — ○ ○ ○ ○
Accessories Undervoltage Trip UVT — — — — — — —
TB — — — — ○ ○ ○
Terminal Block
TB2 — ○ — ○ ○ ○ ○
STB-3K STB-3K
Rear-connecting STB — — — — STB-2M
(Up to 50A :STB-2M) (Up to 50A :STB-2M)
Stud
BSD — — — — — — —
Flush Mounting Base GKW(STB) — — — — ○ ○ ○
Assembly GK GKW(BSD) — — — — — — —
Plug-in Mounting
PK — — — — ○ ○ ○
Base Assembly
Drawout Assembly PDK — — — — — — —
Mechanical Interlock MIW — — — — MIW-2E MIW-2E MIW-2E
MMK-S — — — — — — —
Exterior Motor-operating
MMK-C — — — — — — —
Accessories Mechanism
MMK — — — — — — —
Lock Cover LC LC-0B LC-03 LC-0B LC-03 LC-2G LC-2G LC-2G
Handle Lock HL — — — — HL-2G HL-2G HL-2G
Handle Operating HA — — — — HA-108 HA-108 HA-108
Mechanism HM — — — — HM-S12 — HM-S12 — HM-S12
TMC TMC-0C TMC-0A TMC-0G TMC-0C TMC-0A TMC-0G TMC-1 TMC-1 TMC-1
Front
Terminal Short Type — — — — TMC-1S TMC-1S TMC-1S
Type
Cover Long Type — — — — TMC-2D TMC-2D TMC-2D
Rear Type BTC — — — — BTC-1 BTC-1 BTC-1
IEC Rail 35 mm ● ● ● ● ○ ○ ○
Automatic Tripping Device Full Magnetic Full Magnetic Full Magnetic Full Magnetic Full Magnetic Full Magnetic Full Magnetic
Trip Button ● — ● — ● ● ●
Attention
1. ● : Standard ○ : Option
2. 2-pole types marked with (*1) are supplied in 3-pole type.
3. Please state "For DC" in case of DC use . Especially, state please state kind of the power supply in case of from 30AF to 100AF.
4. Please state that number of poles of breakers when order MIW.
5. Installation of phase separators is required in case of types marked (*2).
6. The accessories marked (*3) can be installed by customers.
10
R ATINGS AND S PECIFICATIONS
S-100SB S-100S S-225SB SXK225 S-400S SX400 S-600S SX600 S-800S SX800
11
Table 3 L series
Type L-50E L-100E L-225E L-400E L-600E L-800E
Appearance
Number of poles 3 4 3 4 3 4 3 4 3 4 3 4
Rated Current (A) 5 10 15 15 20 30 125 150 175 250 300
500 600 700 800
(Base ambient temperature 40ºC) 20 30 50 50 60 75 100 200 225 350 400
Rated Insulation Voltage Ui (V) 690 690 690 690 690 690
Rated Impulse withstand Voltage Uimp (kV) 8 8 8 8 8 8
690V — — — — — —
440V 125 / 32 125 / 32 125 / 32 125 / 32 125 / 32 125 / 32
415V 125 / 32 125 / 32 125 / 32 125 / 32 125 / 32 125 / 32
Rated AC 400V 125 / 32 125 / 32 125 / 32 125 / 32 125 / 32 125 / 32
IEC 60947-2
Breaking 380V 125 / 32 125 / 32 125 / 32 125 / 32 125 / 32 125 / 32
Capacity (kA) (Icu/Ics)
240V 175 / 88 175 / 88 175 / 88 175 / 88 175 / 88 175 / 88
230V 175 / 88 175 / 88 175 / 88 175 / 88 175 / 88 175 / 88
250V — — — — — —
DC
125V — — — — — —
a d
c
a 90 120 90 120 140 185 140 185 210 280 210 280
b 150 150 257 257 274 274
Dimensions (mm)
c 103 103 103 103 103 103
b
Attention
1. ● : Standard ○ : Option
2. Please state "For DC" in case of DC use. Especially, state please state kind of the power supply in case of from 30 to 100AF.
3. Please state that number of poles of breakers when order MIW.
4. Installation of phase separators is required in case of types marked (*2).
5. The accessories marked (*3) can be installed by customers.
12
R ATINGS AND S PECIFICATIONS
Table 4 M series
Type MS-30E MS-50EB MS-50SB MS-100SB MFXK100-S MS-225SB MSXK225 MFXK225-S
Appearance
Number of poles 3 3 3 3 3 3 3 3
0.7 1.4 2.3
0.8 1.2 1.4 2
2.6 4.2 5.6
Rated Current (A) 2.5 4 5 6.3 10 12 16 25 125 150 125 150 125 150
7.4 9 10 14 60 75 90 60 75 90
(Base ambient temperature 40ºC) 7.1 8 10 12 32 40 45 175 225 175 225 175 225
16 25 33 40
16 25 32
45
Rated Insulation Voltage Ui (V) 500 500 690 690 690 690 690 690
Rated Impulse withstand Voltage Uimp (kV) 4 4 6 6 8 6 6 8
690V — — — — — — — —
500V — — 1.5 / 1 2.5 / 1 10 / 10 5/3 5/3 10 / 5
440V — — 2.5 / 1 10 / 3 30 / 30 15 / 8 15 / 8 30 / 15
Rated IEC 60947-2 415V 1.5 / 1 1.5 / 1 2.5 / 1 10 / 3 30 / 30 15 / 8 15 / 8 30 / 15
Breaking AC
Capacity (kA) (Icu/Ics) 400V 1.5 / 1 1.5 / 1 2.5 / 1 10 / 3 30 / 30 15 / 8 15 / 8 30 / 15
380V — — 2.5 / 1 10 / 3 30 / 30 15 / 8 15 / 8 30 / 15
240V — — 7.5 / 2 35 / 9 50 / 50 35 / 18 35 / 18 50 / 25
230V 5/2 5/2 7.5 / 2 35 / 9 50 / 50 35 / 18 35 / 18 50 / 25
a d
c
a 75 75 75 75 90 105 105 105
b 96 96 130 130 150 165 165 165
Dimensions (mm)
c 60 60 60 60 68 60 68 68
b
d 76 76 84 84 94 85 95 95
Net Weight (kg) 0.37 0.37 0.6 0.74 1.6 1.6 1.6 1.6
Standard Connection Type Front Terminal Front Terminal Front Terminal Front Terminal Front Terminal Front Terminal Front Terminal Front Terminal
Phase Separator for Line Side (*2) — — ○ ● (*2) ● (*2) ● (*2) ● (*2) ● (*2)
Alarm Switch AL ○ ○ ○ ○ ○ ○ ○ (*3) ○ (*3)
Auxiliary Switch AUX ○ ○ ○ ○ ○ ○ ○ (*3) ○ (*3)
Interior Shunt Trip SHT ○ ○ ○ ○ ○ ○ ○ (*3) ○ (*3)
Accessories Undervoltage Trip UVT — — — — — — — —
TB — — ○ ○ ○ ○ ○ ○
Terminal Block
TB2 ○ ○ ○ ○ ○ ○ ○ ○
Rear-connecting STB — — STB-2M STB-3K — — — —
Stud BSD — — — — ○ ○ ○
Flush Mounting Base GKW(STB) — — ○ ○ — — — —
Assembly GK GKW(BSD) — — — — ○ ○ ○
Plug-in Mounting
PK — — ○ ○ ○ — — ○
Base Assembly
Drawout Assembly PDK — — — — — — — —
Mechanical Interlock MIW — — MIW-2E MIW-2E MIW-4F MIW-4L MIW-4M
MMK-S — — — — ○ ○ — —
Motor-operating
Exterior MMK-C — — — — — — — —
Mechanism
Accessories MMK — — — — — — — —
Lock Cover LC LC-03 LC-03 LC-2G LC-2G ○ LC-4E LC-2F LC-4J
Handle Lock HL — — HL-2G HL-2G ○ HL-4E HL-2F HL-4J
Handle Operating HA — — HA-108 HA-108 — HA-207 HA-209 HA-210
Mechanism HM — — HM-S12 HM-S12 HM-S13 HM-S22 HM-S23 HM-S25
TMC TMC-0G TMC-0G TMC-1 TMC-1 TMC-2C TMC-4K TMC-4J TMC-4J
Front
Terminal Short Type — — TMC-1S TMC-1S — TMC-4JS TMC-4JS TMC-4JS
Type
Cover Long Type — — TMC-2D TMC-2D — — — —
Rear Type BTC — — BTC-1 BTC-1 BTC-2C BTC-4G BTC-4J BTC-4J
IEC Rail 35 mm ● ● ○ ○ — — — —
Automatic Tripping Device Full Magnetic Full Magnetic Full Magnetic Full Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic
Trip Button — — ● ● ● ● ● ●
Attention
1. ● : Standard ○ : Option
2. Please state that number of poles of breakers when order MIW.
3. Installation of phase separators is required in case of types marked (*2).
4. The accessories marked (*3) can be installed by customers.
13
Table 5 Selecting Table of a Motor Breaker for 3-phase Induction Motor
Hr.
Hr.
Min.
Min.
Tripping Time
Tripping Time
Min.
Max.
Min. value interrupting
Sec.
time
Sec.
Min. value
Sec.
Hr.
Hr.
Max. value Cold start max. value Cold start max. value
Min.
Min.
Min.
Tripping Time
Tripping Time
Min.
value
Sec.
Sec.
Sec.
Max. Max.
interrupting interrupting
time time
14
C ONSTRUCTION
Hitachi Fuse-Free Breaker is comprised a switching mechanism, arc The arc is thus confined, divided and extinguished.
extinguishing devices, and a tripping unit contained in a compact
molded case. ■ Tripping Unit
The tripping unit of the Fuse-Free Breaker is produced in two types:
■ Switching Mechanism a thermal-magnetic type and a full-magnetic type. The tripping unit is
The switching mechanism is a quick-make/quick-break type utilizing a provided for each pole of the breaker, and if any one pole operates, all
trip-free toggle mechanism. of the poles open the circuit simultaneously.
15
Fig. 2 Full magnetic Type
Handle
Molded cover
Line terminal
Load terminal
Movable
iorn core
Armature
This figure shows that the movable iron core and armature When overcurrent flows through the magnet coil, only the
do not move at less than rated current of the breaker. movable iron core moves for the pole piece, overcoming
viscosity of the silicon liquid oil.
The armature is pulled at the pole piece, overcoming the When a large current flows through the magnet coil, take
core spring by increasing of the flux, and the armature short circuit for instance, armature is pulled at pole piece
operates the tripping mechanism of the breaker. instantly without moving iron core, and it operates the
tripping mechanism of the breaker.
16
Construction of Current-Limiting Type Breakers (L series)
Current
Let thru current by
standard FFB
Let thru current by
current-limiting type FFB
Line
terminal Load Time
terminal
About 4 to 8ms
About 10 to 20ms
When a current flows through a conductor in one direction while another current
flows through a conductor in the opposite direction (as shown in the figure on the
left), an electromagnetic repulsing force act between the conductors. The current-
limiting type breaker utilizes this force to complete high-speed current interruption
within an extremely short period of time.
When a short circuit current flows through this The electromagnetic repulsing force causes The breaking mechanism has functioned to
breaker, an electromagnetic repulsing force the moving contact to swing apart from the open the circuit.
works in the direction shown above. fixed contact before the breaking mechanism
functions, accomplishing extremely quick
breaking.
17
Construction of Electronics Type Breakers (FX400 – FX1200)
Owing to high-speed current interruption, excellent current limiting Double electronic and mechanical instantaneous tripping
is achievable. Thus breaker stress with respect to temperature or characteristic protects equipments from short circuit.
mechanic is reduced circuits are securely protected.
Higher MT current Reduces Miss trip by motors rush Current Easy Coordination*
Instantaneous tripping current is now greater *than conventional Tripping characteristics include adjustable long time delay & short
models. Reduces probability of miss trip at high inrush current. time delay in proportion to long time delay (setting current x 1,000%)
Improvement of the voltage equilibrium characteristic of the earth are contribute to easier coordination with other electric appliance
leakage breaker. such as down stream circuit breakers, transformers and wires.
*In-house comparison *over 400A frame
Current
10 15 (rated current
magnification)
18
C HARACTERISTICS
Tripping time
300
At 40ºC
200
I1 x 100
I= <Maximum applicable temperature>
X (%)
Fuse-Free Breaker is applicable to ambient temperatures up to 50ºC.
Where I = value of compensation current, I1 = value of current required Application at a site whose ambient temperature exceeds 50ºC is a
at certain ambient temperature, and X = rate of increase or decrease special case, for which users are requested to contact Hitachi for advice.
of current at a certain ambient temperature compensation curve for
determining the amount of compensation for the rated current value.
The example shown below illustrates that the rated current of a device
adjusted at the base ambient temperature 40ºC at a site whose ambient
temperature is 50ºC decreases to 90% of the rating.
At 40ºC 130
120
110
100
90
80
0 10 20 30 40 50
Current (percent rated current) Ambient temperature (ºC)
19
C AUTION
1. Standard mounting is shown in the diagram below. 5. Insulation clearance on line end of FFB is as follows:
A
Line end
Line end
FFB
Load end
Load end
Fig. 14
Vertical wall Vertical wall
But reversible connection type available as follows: 6. Insulation of line side’s living parts
Maximum It is recommended that line side’s live parts of front connected type
Frame F series S series applicable Remarks
breakers are insulated by insulation tape or insulation barrier.
voltage
100AF F-100KB — 1. Please state "Reversible connection
type" when ordered.
FXK250-S, S-225SB,
225AF
FXK250-H SXK225
400AF F-400R S-400S
600AF F-600F S-600S AC460V 2. Installation of phase separators on the Insulation barrier
load side is required.
F-800F, Taping
800AF S-800S
F-800RH
1000AF F-1000K — Dimension is the same
A
1200AF F-1200K — as A of above table
20
SELECTION
1. Select a breaker type according to the purpose 2. Estimate the available short-circuit current and select
■ Protection of general wiring: Table 1 to 4 economical frames — whose interrupting capacity is higher
■ Protection of motor: Table 5 than that estimation — from among the following series:
■ Protection of branch lamp circuit: Table 6 F series: Standard type for general service
■ Protection against earth leakage S series: Small-scaled and low-cost, economical type
L series: High-performance, current-limiting, high-interrupting
<Consideration to available short circuit current> capacity type
In estimating short circuit currents, there are many considerations, such
as characteristics of transformer, connecting wire size and the distance
from the transformer to the faulty point and so on.
The below charts bring you an easy solution for selecting the breaker type.
FXK250-H
FXK125-H
FXK125-H
FXK125-S FXK250-S
21
3. Select the rated current as follows: ■ Rated Current of main circuit for motor
● Rated currents for heater and lamp circuits The motor groups connected to this circuit are divided into subgroups,
Select a circuit breaker whose current rating corresponds to the value of each consisting of motors which are started simultaneously.
the current allowable for the circuit. Each subgroup is regarded as one motor for convenience (and the sum of
● The rated current of a motor circuit is selected as follows: the full load current of each motor within this subgroup is regarded as the
full load current of this virtual motor). Then select the rated current of a
<For general type breakers for protection of wiring>
subgroup whose full-load current is largest from the Table 8, 9, 10, 11.
■ Rated current of branch circuit for motor The sum of this tentative rated current and the full-load current of all
Table 8, 9, 10, 11 shows rated currents of the breakers which have been the other subgroups is selected as the rated current of the breaker under
selected on condition that they will not effect erroneous operation at consideration.
motor starting time. Where two or more motors are connected to one
branch circuit, the sum of the rated currents of these motors forms the
basis for selecting the rated current of the breakers.
Note: (1) The starting conditions are set within 15 seconds at 500% (10 seconds at 600%) of full load current.
22
Table 10 Selecting table of Fuse-Free Breaker for Motor Branch Circuit Directly Starting 3-phase Induction Motor (200 – 220V AC)
Motor FFB
Full-load Rated Interrupting capacity (kA) Sym
Capacity
current current
(kW) 5 10 14 25 30 35 42 50 85 175
(A) (A)
0.2 1.4 15
0.4 2.6 15
0.75 4.2 15 S-30E
1.5 7.4 15 S-30FB
FXK125-S FXK125-H L-50E
2.2 10 20 S-60RB F-60RB
3.7 16 30
S-50EB,
5.5 25 50
S-50SB
7.5 33 60
11 45 75
S-100S S-100SB FXK125-S FXK125-H L-100E
15 60 100 S-100EB
S-100SB
18.5 75 100
22 90 150
30 (120) 200 S-225SB
FXK250-S FXK250-H L-225E
37 (150) 225 SXK225
45 (180) 225
55 (220) 350 S-400S F-400R
L-400E
60 (240) 400 SX400 FX400
75 (300) 500 S-600S F-600F
L-600E
90 (360) 600 SX600 FX600
<Breaker Used for Protection of Motor Against Overload> Table 12 Applicable Conditions of Motor Breaker
A motor breaker is used to protect wiring and a motor against overload. Its
rated current is about the same value as full-load current of the motor. The Starting condition
Rated current
applicable conditions are subject to the following restrictions: Starting current/
(Amperes) Starting time
full load current
1) Only one motor is installed on the circuit under consideration. 500% Within 3 sec
2) Starting current is less than 600% of the full-load current and motor 50 or less
600% Within 2 sec
load is light (for specific requirements for each rated current, refer to 500% Within 8 sec
From 51 to 150
Table 12). 600% Within 5 sec
When the above restrictions cannot be met use a general type FFB.
When ordering, please specify the Frame (selected by the interrupting capacity)
and the rated current. (About the same as full load current of the motor.)
23
4. Application to discrimination coordination
In a discrimination coordination system, only the breaker nearest the Main circuit breaker
fault opens to isolate the faulty circuit from the rest of the power system.
This system results in maximum continuity of service.
ELECTRONICS TYPE breakers are best suited to application as the Branch circuit breaker
upstream (main) breaker.
380V class
FFB for main circuit Type FX400 FX600 FX800 FX1000 FX1200 F-1600CB
FFB for branch circuit Interrupting
Interrupting Capacity(kA) Capacity (kA) 50 50 50 85 85 85
Type
F-30FB 2.5 2.5 2.5 2.5 2.5 2.5 2.5
F-50FC 7.5 4 7.5 7.5 7.5 7.5 7.5
F-60RB 10 4 7.5 7.5 10 10 10
FXK125-H 50 4 7.5 7.5 50 50 50
FXK125-S 30 4 7.5 7.5 25 25 25
FXK125-H 50 4 7.5 7.5 35 50 50
FXK250-S, F-250FB 30 4 7.5 7.5 22 22 30
FXK250-H, F-250KC 50 4 7.5 7.5 22 22 30
FX400, F-400R 50 — — 7.5 18 22 22
F-600F, FX600 50 — — — — 22 22
FX800, F-800R 50 — — — — — 22
FX1000 85 — — — — — —
FX1200 85 — — — — — —
S-50SB 2.5 2.5 2.5 2.5 2.5 2.5 2.5
S-60RB 5 4 5 5 5 5 5
S-100S, S-100SB 10 4 7.5 7.5 10 10 10
S-225SB, SXK225 15 4 7.5 7.5 15 15 15
SX400, S-400S 35 — — 7.5 22 22 22
SX600, S-600S 35 — — — — 22 22
SX800, S-800S 35 — — — — — 22
L-50E 125 4 10 10 30 30 85
L-100E 125 4 10 10 30 30 85
L-225E 125 4 7.5 7.5 22 22 50
L-400E 125 — — 7.5 18 22 22
L-600E 125 — — — — 22 22
L-800E 125 — — — — — 22
24
A CCESSORIES
Interior Accessories
■ Available accessories inside of FFB are as follows:
The Undervoltage Trip is used to automatically trip the breaker The Shunt Trip is used to trip the breaker electrically from a remote
when the line voltage drops to 35 to 70% of its normal value. point. Since this trip coil does not have a continuous rating, the coil
The standard mounting method of the breaker with this trip is circuit must be broken by making connections to the load end of
vertically on the wall with its line end positioned upward. the breaker (Fig. 20 (a)). If a separate power supply is to be used,
the customer is requested to specify an auxiliary switch to prevent
the coil from being burnt by overheating (Fig. 20 (b)).
The standard mounting method of the breaker with this trip is on
the wall with its line end positioned upward.
Lead wire
0.5mm2 PVC-insulated wire (yellow),
0.5 meter long
When the breaker is tripped, this switch closes to energize an The auxiliary switch, a device interlocked with opening and closing
indicating light or sound an alarm. It employs a microswitch operation of a breaker, is used to open or close control circuits as the
equipped with a C-contact. breaker operates. It employs a microswitch equipped with a C-contact.
■ Terminal Symbols and Connection Condition of AL Switch ■ Terminal Symbols and Connection Condition of AUX Switch
Condition of Breaker Connection condition of AL switch Condition of Breaker Connection condition of AUX switch
S-2 (S-5) A-2 (A-5)
S-1 A-1
ON and OFF ON and OFF
(S-4) (A-4)
S-3 (S-6) A-3 (A-6)
25
Terminal Block for Interior Accessories
TB TB2
3P 16.5
40
8.5
10
3P 6P
10 10
32
(F)
10
(F)
47.5
6P 16.5
(F)
10
62
10.5 3 8 10 10
32
(E)
7.9
(E)
7.9
10
7
10
16.5 7
62
12
16.5
10
TB TB2
10
(F)
Fig. 18 External View of a Breaker with Terminal Block Fig. 19 Dimensions of FFB with Terminal Block for
for an Interior Accessory Interior Accessory
SHT UVT
Type
Voltage Input (VA) Voltage Input (VA)
S-30E, S-50EB, 100
— —
S-225SB, SXK225 (for 400V: 200VA)
AC 100-110V 50Hz 60Hz
F-30FB, S-50SB, F-60RB, F-50KB, AC 200-220V AC 100V AC 100V
L-50E, S-100EB, S-100S, S-100SB, AC 230-240V 200V 110V 20
F-100S, F-100RB, F-100KB, L-100E AC 380V 230V 200V
AC 400-440V 240V 220V
FXK125-S, FXK125-H, FXK250-S, FXK250-H, AC 480V
— —
F-250FB, F-250KC
( )
200
L-225E, S-400S, SX400, F-400R, Common use for 50Hz 60Hz
50 and 60 Hz 20
FX400, L-400E AC 100V AC 100V
200V 110V
S-600S, SX600, F-600F, FX600, L-600E, DC 100V 230V 200V
S-800S, SX800, F-800R, F-800RH, FX800, DC 110V 240V 220V 30
L-800E, FX1000, FX1200, F-1000C, F-1000K,
400V 400V
F-1200C, F-1200K, F-1600CB, F-1600B
415V 440V
26
Table 16 Applicability of interior accessories
✶ FXK125-S
✶ FX600 F-1200K
✶ FXK125-H
F ✶ FX800 F-1600B ✶ FX1000
F-30FB F-100S ✶ FXK250-H ✶ FX400
F-600F F-800R ✶ FX1200
F-60RB F-100KB ✶ FXK250-S ✶ F-400R
F-1000K F-1600CB
Type S F-250FB
F-800RH
F-250KC
AL 1C 1C 1C 1C 1C 1C 1C 2C 2C 2C
AUX 1C 1C 1C 1C 1C 1C 1C 2C 2C 2C
SHT
UVT
AL 1C 1C 1C 1C 1C 1C 2C 1C 2C 1C 2C
+
AUX 1C 1C 1C 1C 1C 1C 2C 2C 2C
AL
+ 1C 1C 1C 1C 2C 2C 2C
SHT
AL
+ 1C 2C 2C 2C
UVT
AUX
+ 1C 1C 1C 2C 2C 2C
SHT
AUX
+ 1C 2C 2C 2C
UVT
AL
+ 1C 1C 1C 2C 1C 2C 1C 2C
AUX
+ 1C 1C 1C 2C 2C 2C
SHT
AL
+ 1C 2C 1C 2C 1C 2C
AUX
+ 1C 2C 2C 2C
UVT
Notes:
1. 2C means that it can be mounted 1C, if required.
2. *: Terminal block (TB) for UVT wiring is equipped.
3. The accessories of marked ✶ types can be installed by customers.
4. AL 2C or AUX 2C is available in case of FXK125-S / H and FXK250-S / H
27
Exterior Accessories
■ Accessories mounted on the outside of breaker are as follows: 3. Flush-mounting Base Assembly (GKW, GK)
■ Rear Connecting Stud (STB) and Bar Stud (BSD) The flush-mounting base assembly is an accessory for mounting a
■ Plug-in Mounting Base Assembly (PK) breaker on a switchboard. A breaker is secured via insulating bushings
■ Flush Mounting Base Assembly (GK) to an exclusive mounting frame by using screws as same method as
■ Mechanical Interlock (MI) the rear connecting stud or bar stud. A rectangular hole sized a little
■ Motor Operating Mechanism (MMK, MMK-C) larger than that of a breaker is cut into the switchboard and the breaker
■ Electro-magnetic Operating Mechanism (MK-C) is embedded into this hole and secured to the switchboard by the
■ Handle Operating Mechanism mounting frame. The flush plate is mounted on the breaker.
28
6. Motor Operating Mechanism (MMK-S)
This mechanism is suitable to remote control a breaker by utilizing a motor.
Since the control circuit is self holding type, the operation of this
mechanism is completed by brief closing of push button switch contact.
As soon as completing of operation, the control circuit is opened and
the motor is stopped by instant operation of a limit switch.
The manual operation is also available.
29
DIMENSIONS OF MMK-S
F-100KB
FXK125-S, FXK125-H
Drilling plan
S-225SB
Drilling plan
SX400, FX400
L-50E
L-100E
30
7. Motor Operating Mechanism (MMK-C)
This mechanism is suitable to remote control a breaker by utilizing a
motor. There is one type as follows.
MMK-C (Compact Type): The breaker is operated by rotation of a single
phase series commutator motor with reduction gear.
31
DIMENSIONS OF MMK-C
L-225E
(Standard Type)
(Built-in Type)
FX400, F-400R
SX400, L-400E
(Standard Type)
(Built-in Type)
32
FX600, F-600F
SX600, L-600E
(Standard Type)
(Built-in Type)
FX800, F-800R
F-800RH, SX800
L-800E
(Standard Type)
(Built-in Type)
33
FX1000, F-1000K
(Standard Type)
(Built-in Type)
FX1200, F-1200K
(Standard Type)
(Built-in Type)
34
F-1600B, F-1600CB ø13.5 holes
(Standard Type)
Manual
handle
(Built-in Type)
35
8. Terminal Cover (TMC)
B
A
D
C
Dimensions
Types Applicable breakers Remarks
A B C D
TMC-0G S-30E, S-50EB 75 (50) 19.5 56 5
TMC-1 75 (50) 48 59.5 28
F-30FB, S-50SB, S-60SB,
TMC-1S 75 (50) 25 56 5 Short type
F-60RB, S-100EB, S-100SB
TMC-2D 75 (50 56 59.5 36 Long type
S-100S, F-100S,
TMC-2C 90 (60) 63 63 36
FXK125-S, FXK125-H
TMC-3C F-100KB, L-50E, L-100E 90 (60) 56 85.5 36
TMC-4K S-225SB 105 79 56 50
TMC-4J SXK225 105 79 53 50
TMC-4JS FXK250-S, FX-250-H 105 28 51 5 Short type
TMC-4H F-250FB, F-250KC 105 71 99 40
L-225E, S-400S, F-400FB,
TMC-5B 147 147 99 110
L-400E
S-600S, F-600F, L-600E,
SX600, FX600, S-800S,
TMC-5D 210 154 91.5 129
F-800R, F-800RH, L-800E,
SX800, FX800
TMC-6 F-1000K, F-1200K 210 159 145 130
TMC-6B FX1000, FX1200 210 159 138.5 130
Remarks Dimensions with ( ) are for 2-pole types
Fig. 31
36
Handle Operating Mechanism
(with padlock)
Fig. 32
Max. A
Max. A
Max. B
Max. B
Center line
of FFB (ELB) Center line
handle of FFB (ELB)
Stopper for handle
Stopper for door interlock 4-ø5.5 Mounting holes
door interlock Use the padlock Release
Release lever lever Use the padlock
(30mm dimension) Stopper for
(30mm dimension) Center line
Door interlock
Door Center line (Mounted on of FFB (ELB)
Handle
of FFB (ELB) case side) handle
lever
center handle 4-ø5.5 Mounting
holes (For
Stopper mounting
Door
for door name plate)
4-ø5.5 Mounting
interlock Handle lever
ø11 hole holes center
(Mounted ø60 hole
on case 4-ø6 ø11 hole
side) Door drilling Mounting holes
for handle mechanism
Center line of Door drilling
(ELB) FFB
(ELB) FFB Center line of FFB handle (ELB) for handle mechanism
mounting panel
mounting panel FFB handle (ELB)
37
Handle Operating Mechanism
Door
Dimension in (mm) Panel
Face plate Panel
Latch Holder
Flush
Max. C
plate
ø
Dimensions of padlock
Center
Max. B
Door interlock (Padlock isn’t attachment)
release lever 1. Diam. B= Ø6 or under line of FFB
Padlock Dimension A 2. Width C= 19 or more
3.Length of straight part D
Setting position
Setting position =10.5 or more Flush
of right hinge of door
of left hinge of door plate
Centerline
Centerline
Ø90hole
Center line of
Drilling plan of doors
FFB handle
Hinge
4-ø15 holes
Fig. 36-1
s
le
Ho
3 8
ø1
Center line of
FFB handle
Over 150
(When hinge
Fig. 36-3 is 10)
Length between
hinge and breaker
Dimension ■ Padlock
Handle Type Applicable Breakers Bolt
Fig. A B C D L: Straight length
F-100KB 132
HM-S11 M4 x 50 Fig.36-1 — — —
L-50E, L-100E 149
F-30FB, S-50SB, S-60SB (Padlock is not attached as standard)
HM-S12 M4 x 65 Fig.36-1 108.5 — — —
F-60RB, S-100EB, S-100SB
HM-S13 FXK125-S, FXK125-H M4 x 70 Fig.36-1 118 — — —
HM-S21 F-250FB, F-250KC M4 x 50 Fig.36-1 150.5 — — —
HM-S22 S-225SB M4 x 45 Fig.36-1 110.5 — — —
HM-S23 SXK225 M4 x 45 Fig.36-1 118 — — — Fig. 37
HM-S25 FXK250-S, FXK250-H M4 x 45 Fig.36-1 118 — — —
S-600S, S-800S, F-600F ■ Padlock Dimension
HM-402 M6 x 130 Fig.36-2 176 137 137 0
F-800R, F-800RH, L-600E, L-800E
HM-405 L-225E, S-400S, F-400R, L-400E M6 x 130 Fig.36-2 170 137 140 6 A B L
HM-406 SX400, FX400 M6 x 130 Fig.36-2 170 137 140 6 HM-402, 405, 406, 407 45 6 — 6.5 Over 16
HM-407 SX600, FX600, SX800, FX800 M6 x 130 Fig.36-2 176 137 137 0
38
DIMENSIONS
S-30S / S-50E
Hr.
Max. value of less
than 30A
Min.
Max. value
of 31 to 50A
Tripping Time
Base ambient
temperature 40ºC
300
Min. 200
value
Sec.
160
140
120
100
80
60
0 10 20 30 40 50
-5
■ Dimensions
(2) Mounting holes (2) Mounting holes Terminal Cover
for M4 screw for M4 screw
M5 screw
2 pole 3 pole
■ Terminal Arrangement
39
S-30E / S-50EB
Hr.
(MS-30E / MS-50EB)
Min.
Max.
Tripping Time
Min. Base ambient
temperature 40ºC
■ Dimensions
2 pole 3 pole
2 pole 3 pole
■ Terminal Arrangement
Applicable wire
Max. applicable crimping ø1.6 – 22mm2
terminal: 14 mm2
ø5.5
M5 screw
(Max.)
40
S-30FB / S-50SB
Hr.
Max. value of less than 30A
Min.
(MS-50SB) Max. value of 31 to 50A
Max. value for DC
application
Tripping Time
Min. Base ambient
value temperature 40ºC
for AC
Sec.
Min.
■ Dimensions
2 pole 3 pole
■ Drilling Plan
2 pole 3 pole
For front mounting bolts For rear connecting studs
2 pole 3 pole
41
F-60RB
Hr.
Max. value of less than 30A
S-60RB
Min.
Max. value of 31 to 60A
Max. value for DC
Tripping Time
application
Base ambient
Min. temperature 40ºC
value
for AC
Sec.
■ Dimensions
2 pole 3 pole
■ Drilling Plan
2 pole 3 pole
For front mounting bolts For rear connecting studs
42
L-50E
Hr.
Max. value of 31 to 50A
Min.
Max. value of less than 30A
Tripping Time
Base ambient
temperature 40ºC
Min.
Sec.
■ Dimensions
■ Drilling Plan
3 pole 3 pole
For front mounting bolts For rear connecting studs
Max. applicable
pressure type Breaker underside
wire connector:
22mm2
M6 screw
Insulating bushing
Wire connection (15 to 50A)
M8 screw
3 pole
43
Hr.
Hr.
S-100EB / S-100SB Max. value of less
Min.
Max. value
Min.
than 30A
Tripping Time
Tripping Time
Max. value for
DC application
Min. Min.
value value
Sec.
Sec.
Min. value
for DC
Overcurrent Tripping
Characteristic Curve
■ Dimensions
Temperature
Compensation Curve
2 pole 3 pole
2 pole
Applicable
M8 screw pressure type Mounting plate
wire connector:
38mm2
M4 Mounting screw
Breaker
underside
R2
Insulating
tube M10 screw
44
S-100S
Base ambient
temperature 40ºC
Tripping Time
■ Dimensions
■ Drilling Plan
Breaker underside
Max. applicable
pressure type
wire connector:
38mm2
Mounting
plate
M8 screw
Insulating
bushing
M10 screw
2 pole 3 pole
45
Hr.
Hr.
FXK125-S / FXK125-H
Max. value of 51 to 125A
Min.
Min.
Max. value of 31 to 50A
(MFXK100-S)
Max. value
Tripping Time
Tripping Time
Max.
interrupting Min. value Max.
time interrupting
Sec.
Sec.
Min. value time
Current Current
(percent rated current) (percent rated current)
■ Dimensions
■ Drilling Plan
Max. applicable
pressure type
wire connector:
60mm2 (22mm2)
M8 screw 24
(M6 screw) 9.5
22
46
L-100E
Hr.
Max. value of 31 to 100A
Min.
Max. value of
Tripping Time
less than 30A
Min.
value of Base ambient
31 to 100A temperature 40ºC
Min. value of
Sec.
Current Ambient Temperture (ºC)
(percent rated current)
■ Dimensions
3 pole 3 pole
For front mounting bolts For rear connecting studs
Max. applicable
Breaker underside
pressure type
wire connector:
38mm2 (22mm2)
M8 screw
(M6 screw)
47
S-225SB
Hr.
Hr.
Cold start max. value
Min.
Max. value
(MS-225SB)
Min.
Hot start
max. value
Tripping Time
Tripping Time
Min. value
Min. value
Max.
Sec.
Sec.
Max. interrupting
interrupting time
time
■ Dimensions
Base ambient
temperature 40ºC
(4) Mounting holes
for M4 screw
2 pole 3 pole
ø10 holes
48
SXK225
Hr.
Hr.
Cold start max. value
Min.
Max. value
(MSKX225)
Min.
Hot start
max. value
Tripping Time
Tripping Time
Min. value Min. value
Sec.
Sec.
Max.
interrupting Max.
time interrupting
time
■ Dimensions
Base ambient
temperature 40ºC
Compensation rate
Screw of slide cover
Trip button
Ambient Temperture (ºC)
2-M4 Mounting
screw hole
ø10 hole
Max. applicable crimping
Terminal Arrangement 46
terminal: 150mm2
M8 screw
A system studs
(Standard)
B system studs
25 right
t6.5
and left
24 pole
49
FXK250-S / FXK250-H
Hr.
Max. value
(MFXK225-S)
Min.
Tripping Time
Base ambient
temperature 40ºC
Min. value
Current
(percent rated current) Ambient Temperture (ºC)
■ Dimensions
Phase insulator
(Removable)
Trip button
2-M4
Mounting
holes
50
L-225E
Hr.
Max. value
Min.
Tripping Time
Base ambient
temperature 40ºC
Min. value
Current
(percent rated current) Ambient Temperture (ºC)
■ Dimensions
■ Drilling Plan
ø9 hole
A system studs
(Standard)
B system studs
(Customer-changeable)
Center pole
51
S-400S/F-400R /L-400E
Hr.
Max. value
Min.
Tripping Time
Base ambient
temperature 40ºC
Min. value
Current
(percent rated current) Ambient Temperture (ºC)
■ Dimensions
■ Drilling Plan
M10 bolt
A system studs
(Standard)
B system studs
(Customer-changeable)
Center pole
52
Hr.
SX400 / FX400
Min.
Tripping Time
Max.
Sec.
interrupting
time
■ Dimensions
Trip button
■ Drilling Plan
4-M6 screw hole or ø7 hole
4-M6 screw hole or ø7 hole
6-ø35 hole
A system studs
(Standard)
B system studs
(Customer-changeable)
Center pole
53
S-600S/F-600F/L-600E
Hr.
Max. value
Min.
Min. Magnetic Base ambient
Tripping Time
value trip range temperature 40ºC
(in 4 steps)
Position
Sec.
Max. interrupting time
Current
(percent rated current) Ambient Temperture (ºC)
■ Dimensions
■ Drilling Plan
(4) M6 tap holes
(4) M6 tap holes or ø(4) 7 holes
or ø(4) 7 holes
ø(6) 48 holes
ø13.5 hole
M12 bolt
Standard mounting
of bar studs are
flatwise A system
54
Hr.
SX600 / FX600
Min.
Tripping Time
Max.
Sec.
interrupting
time
■ Dimensions
Center poles
Trip button
ø48 hole
Max. applicable
crimping terminal:
M12 bolt 200mm2 x 2
A system
studs
(Standard)
B system studs
55
S-800S / F-800R /
Hr.
Max. value
Min.
F-800RH / L-800E Min.
Magnetic
trip range
(in 4 steps)
Tripping Time
value
Base ambient
Position temperature 40ºC
of setting
Current
(percent rated current) Ambient Temperture (ºC)
■ Dimensions
■ Drilling Plan
(4) M6 tap holes
(4) M6 tap holes or ø(4) 7 holes
or ø(4) 7 holes ø(6) 48 holes
Standard mounting
of bar studs are
flatwise A system
56
Hr.
SX800 / FX800
Min.
Tripping Time
Max.
Sec.
interrupting
time
■ Dimensions
Trip button
ø48 hole
M12 bolt
A system studs
(Standard)
B system studs
57
F-1000C / F-1200C
Hr.
Hr.
Min.
Min.
Tripping Time
Tripping Time
Max. Max.
Sec.
Sec.
interrupting interrupting
time time
Setting range 1000A setting 500A setting Setting range 1200A setting 600A setting
at short limit at short limit
■ Dimensions
■ Drilling Plan
M12 bolt
58
Max. value
Hr.
Hr.
Max. value
F-1000K / F-1200K
Min. value
Min.
Min.
Magnetic
Magnetic trip range
trip range (in 4 steps)
Min. (in 4 steps)
value
Tripping Time
Tripping Time
Position
of setting Position
of setting
Sec.
Sec.
Max. Max.
interrupting Lo Hi interrupting
Lo Hi
time time
■ Dimensions
Base ambient
temperature 40ºC
■ Drilling Plan
M12 bolt
59
FX1000 / FX1200
Hr.
Min.
Tripping Time
Max.
interrupting
Sec.
time
Current FX1000
500A setting
(percent rated current)
FX1200
600A setting
Overcurrent Tripping
Characteristic Curve FX1000
1000A setting
FX1200
1200A setting
■ Dimensions
Auxiliary handle
Trip button
Auxiliary handle
4-M8 screw hole
M12 bolt ø13.5 hole
A system studs
(Standard)
B system studs
60
Hr.
F-1600CB
Min.
Tripping Time
Sec.
Max.
interrupting
time
Current (A)
■ Dimensions
Standard
mounting of bar
studs are flatwise
A system
less than 15
for connecting
of conductor
Bar studs are mounted
M10 x 50 bolt edgewise, If orders as
(B system studs)
61
Hr.
F-1600B
Min.
Tripping Time
Magnetic
trip range
(in 4 steps)
Position of setting
Sec.
Hi
Max.
Lo
interrupting
time
Current
(percent rated current)
■ Dimensions
■ Drilling Plan
4-M8 tap holes or ø4-10 holes 4-M8 tap holes or ø4-10 holes
320 and more
Standard
mounting of bar
studs are flatwise
A system
less than 15
for connecting
of conductor
M10 x 50 bolt Bar studs are mounted
edgewise, If orders as
(B system studs)
ø12 hole
62
Hr.
F-1600E Rated current
Min.
[T1] Setting range
Tripping Time
[I2] Setting range
Sec.
[T2] Setting range [I3] Setting range
Current
(percent rated current)
■ Dimensions
63
DIMENSIONS OF 4 POLE BREAKERS
F-60R 4 pole
Drilling plan
F-100S 4 pole
Drilling plan
F-100KB 4 pole
Drilling plan
64
F-250FB / F-250KC 4 pole
L-225E 4 pole
Drilling plan
Drilling plan
Drilling plan
65
F-800R / L-800RH 4 pole
Drilling plan
Drilling plan
F-1600CB 4 pole
F-1600B 4 pole
4-M8 screw Phase
hole separator
ø13.5 hole
Auxiliary
handle
Trip
button
Drilling plan
66
EARTH LEAKAGE BREAKERS
AND EARTH LEAKAGE RELAYS
This is a combination of a Fuse-Free Breaker and a leakage current detector for
preventing fire or electric shock due to deterioration of electric insulation.
It will provide perfect protection of a circuit against overload,
short-circuit, or earth leakage.
■ Principle of operation
This device is composed of a zero phase current transformer for
detecting leakage current, a control circuit, and a Fuse-Free Breaker
with a shunt trip.
As shown in Fig. 37, magnetic fluxes cancel out each other, inducing
no output voltage in the secondary coil while no leakage is present in
the load circuit.
i1 + i2 + i3 = 0
If leakage current (lg) occurs in the load circuit, magnetic flux øg is
induced, producing a certain voltage across the secondary coil.
i1 + i2 + i3 = ig
The induced voltage is supplied to the shunt trip coil of the Fuse-
Free Breaker, through a control circuit composed of diodes and Fig. 37 Principle of operation
semiconductor control elements, to break the circuit.
Earth Leakage
E Series R Series
Standard Breaker High Interrupting
Breaker
Relay Series
67
R ATINGS AND SPECIFICATIONS
Table 19 E series
Type EB-50E EB-100E EX30 EX50 EX50B EX50C
Appearance
Rated Voltage (AC V) 100 – 200 100 – 200 200 – 440 200 – 440 100 – 200 200 – 440
d 76 76 84 84 84 84
Net Weight (kg) 0.3 0.4 0.6 0.7 0.7 0.7 0.7
Standard Connection Type Front Terminal Front Terminal Front Terminal Front Terminal Front Terminal Front Terminal
Phase Separator for Line Side — — ○ ○ ○ ● (*2)
Test Button Lead Wire TBL ○ ○ ○ ○ ○ ○
Alarm Switch AL ○ ○ ○ ○ ○ ○
Interior Auxiliary Switch AUX ○ ○ ○ ○ ○ ○
Accessories Earth Leakage Alarm Sw. EAL — — — — — —
TB — — ○ ○ ○ ○
Terminal Block
TB2 ○ ○ ○ ○ ○ ○
STB — — STB-2M STB-2M STB-2M STB-2M
Rear-connecting Stud
BSD — — — — — —
Flush Mounting Base GKW (STB) — — ○ ○ ○ ○
Assembly GK∙ GKW (BSD) — — — — — —
Plug-in Mounting
PK — — — — — —
Base Assembly
Mechanical Interlock MIW — — MIW-2E MIW-2E MIW-2E MIW-2E
Motor-operating MMK-S — — — — — —
Exterior Mechanism MMK-C — — — — — —
Accessories
Lock Cover LC LC-03 LC-03 LC-2G LC-2G LC-2G LC-2G
Handle Lock HL — — HL-2G HL-2G HL-2G HL-2G
Handle Operating HA — — HA-108 HA-108 HA-108 HA-108
Mechanism HM — — HM-S12 HM-S12 HM-S12 HM-S12
TMC TMC-0G TMC-0H TMC-1 TMC-1 TMC-1 TMC-1
Front
Terminal Short type — — TMC-1S TMC-1S TMC-1S TMC-1S
Type
Cover Long type — — TMC-2D TMC-2D TMC-2D TMC-2D
Rear Type BTC — — BTC-1 BTC-1 BTC-1 BTC-1
IEC Rail 35 mm ● ● ○ ○ ○ ○
Automatic Tripping Device Full Magnetic Full Magnetic Full Magnetic Full Magnetic Full Magnetic Full Magnetic
Trip Button — — — — — —
Attention
1. ● : Standard ○ : Option
2. Please use right and left poles in case of using ELBs of 3 poles 200V to 1ø2W 200V wiring sysytem.
3. Please connect neutral line to middle pole of ELBs incase of using ELBs of 3 poles 200V to 1ø3W100 / 200V distribution system.
4. Standard flush mounting base assembly of up to 400AF are GKW and GK is standard in case of 600AF or more.
5. Installation of phase separators is required in case of types marked (*2)
6. IEC rail is standard installation in case of EB-50E and EB-100E, so installation screws and metal fittings are not attached.
7. The accessories marked (*3) can be installed by customers
8. Please state frequency 50 or 60Hz in case of RF-800KN, RF-1000KN, RF-1200KN.
68
R ATINGS AND S PECIFICATIONS
— (0.1) (0.1 0.2 0.5) (0.1 0.2 0.5) (0.1 0.2 0.5) (0.1 0.2 0.5) (0.1 0.2 0.5) (0.1 0.2 0.5)
69
Table 20 R series
Type RXK125-S RXK125-H RX100 RXK250-S RXK250-H RG-225BN RG-225BH RX400 RX400B
Appearance
Attention
1. ● : Standard ○ : Option
2. Please use right and left poles in case of using ELBs of 3 poles 200V to 1ø2W 200V wiring sysytem.
3. Please connect neutral line to middle pole of ELBs incase of using ELBs of 3 poles 200V to 1ø3W100 / 200V distribution system.
4. Standard flush mounting base assembly of up to 400AF are GKW and GK is standard in case of 600AF or more.
5. Installation of phase separators is required in case of types marked (*2)
6. IEC rail is standard installation in case of EB-50E and EB-100E, so installation screws and metal fittings are not attached.
7. The accessories marked (*3) can be installed by customers
8. Please state frequency 50 or 60Hz in case of RF-800KN, RF-1000KN, RF-1200KN.
70
R ATINGS AND S PECIFICATIONS
RG-400BN RG-400BH RX600B RF-600FN RX800B RF-800KN RF-1000KN RF-1000CBN RF-1200KN RF-1200CBN
200 – 440 200 – 440 440 (200) 200 – 440 440 (200) 440 (200) 440 (200) 440 (200) 440 (200)
300 / 350 / 400 400 / 450 / 500 500 / 600 / 700 600 / 700 / 800
250 300
500 / 600 500 600 600 / 700 / 800 700 800 1000 800 / 900 / 1000 1200 1000 / 1200
350 400
adjustable adjustable adjustable adjustable
8 8 8 8 8 8 8 8 8
50 ∙100 ∙200 50 ∙100 ∙200 50 ∙100 ∙200 50 ∙100 ∙200 50 ∙100 ∙200 50 ∙100 ∙200
100 ∙200 ∙500 30 100 ∙200 ∙500 100 ∙200 ∙500
500 ∙1000 500 ∙1000 500 ∙1000 500 ∙1000 500 ∙1000 500 ∙1000
0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
(100 ∙200 ∙500 ) — (100 ∙200 ∙500 ) (100 ∙200 ∙500 ) (100 ∙200 ∙500 ) (100 ∙200 ∙500 ) (100 ∙200 ∙500 ) (100 ∙200 ∙500 ) (100 ∙200 ∙500 ) (100 ∙200 ∙500 )
(0.3 0.6 1.2) — (0.3 0.6 1.2) (0.3 1.2) (0.3 0.6 1.2) (0.3 1.2) (0.3 1.2) (0.5 1.2) (0.3 1.2) (0.5 1.2)
(0.1 0.2 0.5) — (0.1 0.2 0.5) (0.1 0.5) (0.1 0.2 0.5) (0.1 0.5) (0.1 0.5) (0.2 0.5) (0.1 0.5) (0.2 0.5)
○ ○ ○ ○ ○ ○ ○ ○ ○
— — — — — — — — —
○ (GK) ○ (GK) ○ (GK) ○ (GK) ○ (GK) ○ (GK) ○ (GK) ○ (GK) ○ (GK)
— — — — — — — — —
71
C ONSTRUCTION
The Earth Leakage Circuit Breakers (ELB) consists of circuit breaker unit composed by a switching mechanism, are
extinguishers, an over-current tripping device, etc., zero-phase sequence current transformer, amplifier and others for
detecting earth leakage current. These components are accommodated in a heat-proof and arc-proof molded case and
cover. A typical example of its construction is shown in the diagram below.
Test button
Amplifier
ZCT Connecting
terminal
Operating
time selector
Reset button
72
Table 21 Applicability of interior accessories
EX30 EX225
RF-800KN
EX50 ✶ EXK225 ✶ EX600B
RG-225B (N) RF-1000KN
EB-50E EX50B ✶ RXK125-S ✶ RX600B
Frame EB-50E ✶ EX400B RF-1200KN RF-600FN
EB-100E EX50C ✶ RXK125-H ✶ EX800B
✶ RX400B ✶ RF1000CBN
EX100 ✶ RXK250-S ✶ RX800B
✶ RF1200CBN
Poles EX100B ✶ RXK250-H
Accessories 2 3 3 3, 4 3 3, 4 3
Alarm
AL 1C 1C 1C 2C 2C 2C 2C
Switch
Auxiliary
AUX 1C 1C 1C 2C 2C 2C 2C
Switch
Alarm AL 1C 1C 2C 1C 1C 1C
+ + —
Auxiliary AUX 1C 1C 2C 2C 2C 2C
Earth
Leakage
EAL — — — — —
Alarm
Switch Equipped normaly Equipped normaly
Alarm AL 1C 1C
+ + 2C 2C
Auxiliary AUX — — — — —
+ +
EAL Switch EAL Equipped normaly Equipped normaly
Test Button
TBL
Lead Wire
Appearance
Dimensions (mm) b 80
b
c 115
Weight (kg) 0.45
Notes: (1) Interchangeable by manual operation.
(2) Rating with ( ) are manufactured by customer’s order.
(3) Rated Voltage Applicable Circuit Voltage Remarks
100V 100 ∙ 110V Interchangealbe by
200V 200 ∙ 220V tap changing
240V 230 ∙ 240V
380V 380V
415V 400 ∙ 415 ∙ 440 ∙ 460V (60Hz)
73
Table 23 Contact Specifications
Load Resistive Load cosø = 1 Inductive Load cosø = 0.3, L / R = 7ms
Rated Thermal Current (A) 3
AC 120V 3 2
AC 240V 3 1.5
Rated Current (A) AC 415V 1 0.5
DC 24V 3 1.5
DC 100V 0.2 0.2
Appearance
Number of Poles 3 4 3 4 3 4 3 4 3 4 3 4
Continuous Thermal Current (A) 400 600 800 1000 1200 2000
Rated Voltage (AC V) 600
Frequency (Hz) 50, 60
Rated withstand Current (kA) 100 (peak value) 150 (peak value)
Rated Sensitivity Current Refer to Earth Leakage Relays
Operating Time (sec.) Ditto
A 220 315 220 315 240 320 240 320 240 320 310 380
a c
B 348 348 348 348 380 380 380 380 380 380 300 300
Dimensions (mm)
b1
B1 400 400 460 460 480 480 480 480 480 480 600 600
b
C 187 214 187 214 214 239 214 239 214 239 242 284
Weight (kg) 11 15 11.2 16 12.3 17 12.3 17 13 18 30 42
74
A PPLICATION OF E ARTH L EAKAGE R ELAYS
75
DIMENSIONS
Hr.
EB-50E
Min.
Max.
Tripping Time
Base ambient
Min.
temperature 40ºC
Sec.
■ Dimensions
Test button
Earthleakage Earthleakage
trip indicator trip indicator
Test button
Max. applicable
pressure-type
wire connector: Applicable wire
14mm2 conductor
ø1.6 – 22mm2
M5 screw
76
Hr.
EX30 / EX50 / EX50B Max. value for 31A or more
Min.
Max. value for
30A or less
Tripping Time
Base ambient
temperature 40ºC
Min.
value
■ Dimensions
2-mounting holes for
M4 screw
Rated sensitivity
current selector
(if provided)
ø5.5 holes
Earthleakage
trip indicator
Test button
Applicable wire
conductor
ø1.6 – 22mm2
M5 screw
77
Hr.
EX50C Max. value for 31A or more
Min.
Max. value for
30A or less
Tripping Time
Base ambient
temperature 40ºC
Min.
Sec.
Current Ambient Temperture (ºC)
(percent rated current)
■ Dimensions
2-mounting holes for
M4 screw Phase separator
Rated sensitivity
current selector
(if provided)
Earth leakage
indicator
Test button
■ Drilling Plan
2-M4 tap holes
or ø5 holes
78
EB-100E
Hr.
Max.
Min.
Tripping Time
Min. Base ambient
temperature 40ºC
■ Dimensions
ø5.5 holes
Test button
Earthleakage
trip indicator
■ Drilling Plan
2-M4 screw hole
or ø5 hole
Max. applicable
pressure-type
wire connector:
38mm2
M8 screw
79
EX100
Hr.
Max. value
Min.
Tripping Time
Base ambient
temperature 40ºC
Min. value
■ Dimensions
Mounting hole
for M4 screw
Earth leakage
indicator
Test button
■ Drilling Plan
2-M4 tap holes
or ø5 holes
Max. applicable
pressure-type
wire connector:
38mm2 Applicable wire
M8 screw conductor
ø1.6 – 22mm2
80
EX100B
Hr.
Max. value
Min.
Tripping Time
Base ambient
temperature 40ºC
Min. value
■ Dimensions
Mounting hole
for M4 screw
Earthleakage
trip indicator
Test button
■ Drilling Plan
2-M4 tap holes
or ø5 holes
Max. applicable
pressure-type
wire connector:
38mm2 Applicable wire
M8 screw conductor
ø1.6 – 22mm2
81
Hr.
Hr.
RXK125-S / RXK125-H
Max. value of 51 to 125A
Min.
Min.
Max. value of 31 to 50A
Max. value
Tripping Time
Tripping Time
Max.
interrupting Min. value Max.
time interrupting
Sec.
Sec.
Min. value time
Current Current
(percent rated current) (percent rated current)
■ Dimensions
Phase insulator
(Removable)
Test button
Rated sensitivity
current selector
(if provided)
Earth leakage
trip indicator Trip button
■ Drilling Plan
2-M4 screw holes or ø5 holes
82
EX225
Hr.
Max. value
Min.
Tripping Time
Base ambient
temperature 40ºC
Min. value
■ Dimensions
Mounting hole
Phase separator for M4 screw
Earthleakage
indicator
Rated sensitivity
current selector
(if provided)
Test button
■ Drilling Plan
83
EXK225
Hr.
Max. value
Min.
Tripping Time
Base ambient
temperature 40ºC
Min. value
■ Dimensions
Phase separator
Rated sensitivity
current selector
(if provided)
Trip
button
Test button
Operating time
selector
Earthleakage
trip indicator
■ Drilling Plan
Max. applicable
pressure-type
wire connector:
150mm2
M8 screw
84
RXK250-S / RXK250-H
Hr.
Max. value
Min.
Tripping Time
Base ambient
temperature 40ºC
Min. value
■ Dimensions
Mounting hole for
M4 screw
Earthleakage
trip indicator
Rated sensitivity
current selector
(if provided)
Test button
■ Drilling Plan
85
EX400 / RX400
Hr.
Max. value
Min.
Base ambient
Tripping Time
Min. value temperature 40ºC
■ Dimensions
Phase separator
Mounting hole for M4 screw
Rated sensitivity
current selector
(if provided)
Earthleakage indicator
Operating time selector
(Time delay type only)
Test button
■ Drilling Plan
M10 bolt
86
EX400B / RX400B
Hr.
Min.
Tripping Time
Max.
Sec.
interrupting
time
200A setting
Current
400A setting
(percent rated current)
■ Dimensions
Rated
Rated sensitivity sensitivity
current selector current
selector
Operating
time
Operating time
selector
selector
Earth
leakage
Earth leakage indicator
indicator
Test
Test button button
Rated current
Rated current selector
selector Trip button
Trip button
■ Drilling Plan
4-M6 screw hole
or ø7 hole
■ Terminal Arrangement
M10 bolt
87
Hr.
EX600B / RX600B
Min.
Tripping Time
Max.
Sec.
interrupting
time
Overcurrent Tripping
Characteristic Curve
■ Dimensions
4-M6 mounting hole Phase separator
Test button
Rated sensitivity
current selector
Operating time
selector
Earth leakage
indicator
Trip button
■ Drilling Plan
4-M6 screw hole
or ø7 hole
■ Terminal Arrangement
M12 bolt
88
Hr.
EX800B / RX800B
Min.
Tripping Time
Max.
Sec.
interrupting
time
Overcurrent Tripping
Characteristic Curve
■ Dimensions
Phase separator
4-M6 mounting hole
Test button
Rated sensitivity
current selector
Operating time
selector
Earth leakage
indicator
Trip button
■ Drilling Plan
4-M6 screw hole
or ø7 hole
■ Terminal Arrangement
M12 bolt
89
Hr.
RF-1000KN
Max. value
Min.
Adjustable
magnetic
trip range
Min. (in 4 steps)
value
Tripping Time
Base ambient
temperature 40ºC
Position
of setting
■ Dimensions
■ Drilling Plan
M12 bolt
90
Hr.
RF-1000CBN
Min.
Tripping Time
Max.
Sec.
interrupting
time
1000A setting
(time highly type)
Overcurrent Tripping
Characteristic Curve
■ Dimensions
Phase separator
Trip button
Rated current
selector
Sealed cover
Rated sensitivity
current selector
Test button
Earth leakage indicator
and reset button
■ Drilling Plan
M12 bolt
91
Hr.
RF-1200KN
Max. value
Min.
Adjustable
magnetic
trip range
Min. (in 4 steps)
value
Tripping Time
Base ambient
temperature 40ºC
Position
of setting
■ Dimensions
■ Drilling Plan
M12 bolt
92
Hr.
RF-1200CBN
Min.
Tripping Time
Max.
Sec.
interrupting
time
1200A setting
(time highly type)
Overcurrent Tripping
Characteristic Curve
■ Dimensions
Phase separator
Trip button
Rated current
selector
Sealed cover
Rated sensitivity
current selector
Test button
Earth leakage indicator
and reset button
■ Drilling Plan
4-M10 screw hole or ø11 hole
M12 bolt
93
Hr.
RX100 4P Max. value for 31 to 100A
Min.
Max. value for
30A or less
Tripping Time
Base ambient
Min. temperature 40ºC
value
for 31 to
100A
Min.
Phase separator
Rated sensitivity
current selector ø8.5 hole
(if provided) (ø6.5 hole for 50A or less)
Test button
Earth leakage
trip indicator
■ Drilling Plan
4-M4 tap holes
or ø5 holes
Center of handle
M8 screw
(M6 screw for Applicable wire
50A or less) conductor
ø1.6 – 22mm2
94
Hr.
RG-225BH 4P Max. value
Min.
RG-225BN 4P
Tripping Time
Base ambient
Min. value temperature 40ºC
■ Dimensions
Phase separator
Earth leakage
trip indicator Test button
ø5.5 holes
Rated sensitivity
current selector
■ Drilling Plan
4-M6 tap holes
or ø7 holes
Max. applicable
pressure-type
wire connector:
100mm2
M10
95
Hr.
RG-400BN 4P Max. value
Min.
RG-400BH 4P
Tripping Time
Min. Base ambient
value temperature 40ºC
Sec.
■ Dimensions
Phase separator
Test button
Earth leakage
trip indicator
Rated sensitivity
current selector
ø11 holes
■ Drilling Plan
M10 bolt
96
RF-600FN 4P
Hr.
Max. value
Min.
Adjustable
Min. magnetic
value trip range
Tripping Time
(in 4 steps)
Base ambient
temperature 40ºC
Position
of setting
Sec.
■ Dimensions
Phase separator
4-mounting holes for M8 screw
ø13.5 holes
Test button
■ Drilling Plan
4-M8 tap holes or ø9 holes
M12 bolt
97
Hr.
RF-800KN 4P
Max. value
Min.
Adjustable
magnetic
trip range
(in 4 steps)
Min.
Tripping Time
value
Base ambient
Position temperature 40ºC
of setting
Compensation rate
Max.
interrupting
time
■ Dimensions
■ Drilling Plan
M12 bolt
98
Hr.
RF-1000KN 4P
Max. value
Min.
Adjustable
RF-1200KN 4P
magnetic
trip range
Min. (in 4 steps)
value
Tripping Time
Base ambient
temperature 40ºC
Position
of setting
Compensation rate
Max.
interrupting
time
■ Dimensions
68.5
t15
■ Drilling Plan
M12 bolt
99
Rated sensitivity
■ Dimensions Mounting holes current selector
R-NZB
Rated sensitivity
■ Dimensions Mounting holes current selector
100
Rated sensitivity
■ Dimensions Mounting holes current selector
Rated sensitivity
■ Dimensions Mounting holes current selector
R-NZBL
101
Rated sensitivity
■ Dimensions Mounting holes current selector
102
■ Dimensions ■ Drilling Plan
Z-400B
Terminal
screw for
M3.5
ø13.5
holes 4-M6 tap holes 4-M6 tap holes
or ø4-8 holes or ø4-8 holes
3 pole 3 pole 4 pole
M12 bolt
ø13.5
holes
4 pole
Z-600B
Terminal
screw for
M3.5
ø13.5
holes 4-M6 tap holes 4-M6 tap holes
or ø4-8 holes or ø4-8 holes
3 pole 3 pole 4 pole
M12 bolt
ø13.5
holes
4 pole
Z-800B Terminal
screw for
M3.5
ø13.5
holes
4-M8 tap 4-M8 tap
holes or holes or
3 pole 3 pole ø4-10 holes 4 pole ø4-10 holes
M12 bolt
ø13.5
holes
4 pole
103
■ Dimensions ■ Drilling Plan
Z-1000B Terminal
screw for
M3.5
ø13.5
holes
4-M8 tap 4-M8 tap
holes or holes or
3 pole 3 pole ø4-10 holes 4 pole ø4-10 holes
M12 bolt
ø13.5
holes
4 pole
Z-1200B Terminal
screw for
M3.5
ø13.5
holes
4-M8 tap 4-M8 tap
holes or holes or
3 pole 3 pole ø4-10 holes 4 pole ø4-10 holes
M12 bolt
ø13.5
holes
4 pole
Z-2000B
Terminal
screw for
M3.5
ø4-11 holes
4-M8 tap 4-M8 tap
holes or holes or
ø4-12 ø4-12
3 pole 3 pole holes 4 pole holes
Terminal
screw for
M3.5
■ Terminal Arrangement
M10 bolt
ø11 holes
4 pole
104
ZR-15 — 120
■ Dimensions
2-M4 mounting holes Mounting holes Surface K Mounting holes
Surface L
ø15 holes
ø30 holes
ZR-15 ZR-30B
Surface L
4-øH holes
ø58 holes
s
le
ho
øD
105
E ARTH L EAKAGE BREAKERS FOR WELDERS
Hr.
Min.
Max. value
Sec.
Setting
time (sec.)
■ Selection
Specifications of Welder Setting Current
Rated Current of ELCB (A) of Instantaneous
Rated Voltage (AC V) Rated Capacity (kVA) Maximum Input (typ.)(kVA) Tripping Current (A)
35 111 225 1200
50 106 225 1200
200
75 219 400 2250
100 330 400 3500
35 111 225 600
50 106 225 600
75 219 225 1200
415 100 330 225 1700
125 (395) 400 2250
150 (475) 400 2500
200 (630) 400 3500
( ): for reference value
106
■ Dimensions
RXW225
4-M4 mounting hole
Earth leakage indicator M8 screw
Indication lamp
Test button
Rated sensitivity
current selector
Operation time selector
RGW-400B
easy installation
ø11 holes
4-mounting hole for M6 screw
Continuous
currrnt and
earth leakage Test button
indicator
■ Drilling Plan
M6 tap holes or ø7 holes
107
MINIATURE CIRCUIT BREAKERS
MCB is applicable to electric circuit with rated voltage 230/400V, 240/415V AC,
frequency 50/60Hz and rated current is up to 63A.
The product provides against overload and short circuit and equipments in
household and commercial installations.
MCB is also used as non-frequent changeover of electric circuit.
n Type D 4A Brown
Instant tripping characteristics : 10–20In 6A Green
Application : high current surge device such as transformers, motors
with heavy load
10A Red
16A Grey
20A Blue
APPROVAL 25A Yellow
32A Purple
n CE marking 40A Black
108
SPECIFICATIONS
Rated current 1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63A
Characteristics B, C, D curve
1P 2, 3, 4P 1P 2, 3, 4P
Breaking capacity 10kA
6kA 6kA 10kA
at 230/400VAC at 400VAC at 240/415VAC at 415VAC
Standards IEC60898
1changeover contact
6A at 230VAC,3A at 415VAC(AX)
6A at 230VAC,3A at 415VAC(AL)
Alarm switch 2A at 48VAC,1A at 125VAC
Not applicable
(Optional)
Lug terminal
Cable capacity 2.5mm2
9mm wide
(mm) (mm)
Dimension
109
C HARACTERISTIC CURVE AND C OMPENSATION CURVE
110
RESIDUAL CURRENT CIRCUIT BREAKERS
RCCB is applicable to electric circuits with rated voltage 240/415VAC, frequency 50/60Hz
and rated current up to63A. The RCCBs provides indirect protection to the operator’s body
under such condition that the exposed live parts should be connected to a proper earthing
pole. The RCCB also provides protection against the fi re danger caused by earth fault
current due to function failure of over current protection device.
RK63 series
FEATURES APPROVAL
n RCCBs with rated sensitivity up to 30mA can be used as n CE marking
supplementary protecting device in case other protecting
n CB Certificate
device fails its protection against electric shock.
111
SPECIFICATIONS
Type RK63
Standards IEC61008
(mm)
Dimension
4P 2P
112
MIN. SALES LOT
n MCBs
BK63 2P BTK63 2P 60
BK63 3P BTK63 3P 40
BK63 4P BTK63 4P 30
n RCCBs
RK63 2P 60
RK63 4P 30
113
AIR CIRCUIT BREAKERS
ORDERING
ACB
&
Accessories
AKH
3P/4P
Standard
40 4000AF D 3 3P (F) 40 4000A
type
RST(N)
AKS
4P
Reverse
50 5000AF W 4 4P (F, Y) 50 5000A
phase type
NRST
3P/4P
40 4000AF Standard 40 4000A
D 3 3P (G)
type
RST(N)
AKH AKS 50 5000AF 50 5000A
4P
Reverse
W 4 4P (G, Z)
63 6300AF phase type 63 6300A
NRST
114
Motor rated voltage Shunt coil rated voltage Trip relay
MA Without Motor D0 Without Shunt coil
M1 AC / DC 100 – 130V D1 AC / DC 100 – 130V
M2 AC / DC 200 – 250V D2 AC / DC 200 – 250V
M3 DC 125V D3 DC 125V
M4 DC 24 – 30V D4 DC 24 – 30V
M5 DC 48 – 60V D5 DC 48 – 60V
M6 AC 380 – 415V D6 AC 380 – 480V
M7 AC 440 – 480V D7 AC 48V
M8 AC 48V
Closing coil rated voltage Closing coil rated voltage UVT coil rated voltage
D0 Without Closing coil AX Standard OFF-Charge 3a3b U0 Without UVT coil
D1 AC / DC 100 – 130V AC Standard ON-Charge 3a3b U1 AC / DC 100 – 130V
D2 AC / DC 200 – 250V BX Standard OFF-Charge 5a5b U2 AC / DC 200 – 250V
D3 DC 125V BC Standard ON-Charge 5a5b U3 DC 125V
D4 DC 24 – 30V HX High capacity OFF-Charge 5a5b U4 DC 24 – 30V
D5 DC 48 – 60V HC High capacity ON-Charge 5a5b U5 DC 48 – 60V
D6 AC 380 – 480V CC Standard ON-Charge 6a6b U6 AC 380 – 480V
D7 AC 48V JC High capacity ON-Charge 6a6b U7 AC 48V
*UVT Delay module is available over
AC / DC 48V
Accessories
115
ORDERING
Cradle
AL
Rated current
ACB cradle No. of pole Connections Safety shutter
& frmae
H16D AKH-06 – 16D 3 3P H Horizontal type Without
E
H20D AKH-20D 4 4P V Vertical type safety shutter
H32E AKH-20 – 32E P Front type With safety
F
H40E AKH-40E Mixed type shutter
H50G AKH-40 – 50G M Line: Horizontal
H63G AKH-63G Load: Vertical
N16D AKN-06 – 16D Mixed type Arc cover
S20D AKS-20D N Line: Vertical
Load: Horizontal Without
S32E AKS-20 – 32E N
Arc cover
S40E AKS-40E
Terminal With
S50F AKS-40 – 50F S
connections Arc cover
S50G AKS-40 – 50G
S63G AKS-63G Manual
J
connection
Automatic
A
connection
116
ORDERING
Trip relay
Trip relay type Communication & protection Control voltage & frequency
0 Without trip relay 0 Without trip relay 0 Without trip relay
N G 0
N Normal 0 Without comm. 0 Self-Power, 60Hz
*LSIG configuration as standard 5 Self-Power, 50Hz
- with LED indicators
- without output contacts
*Ground fault system by bector sum
A G 0
A Ammeter G Earth leakage 0 Self-Power, 60Hz
Z Earth leakage (extemal CT, fault current ≤ 30A) 1 AC / DC 100 – 250V, 60Hz
E Earth leakage (extemal CT, fault current > 30A) 2 DC 24 – 60V, 60Hz
C Earth leakage + Comm. 5 Self-Power, 50Hz
K Earth leakage (extemal CT, fault current ≤ 30A) + Comm. 6 AC / DC 100 – 250V, 50Hz
X Earth leakage (extemal CT, fault current > 30A) + Comm. 7 DC 24 – 60V, 50Hz
*LSIG configuration as standard
*Ground fault system
G, C: 4pole unit - fault current over 20% of rated currenty by vector sum
3pole unit - phase unbalanced current over 20% of rated current
Z, K: external CT - out ZCT applied
E, X: external CT - private ZCT applied
*Comm. works under control power
*LSIG output contact works under control power
(LED indicators works without control power)
P G 1
P Power meter C Earth leakage + Comm. 1 AC / DC 100 – 250V, 60Hz
K Earth leakage (extemal CT, fault current ≤ 30A) + Comm. 2 DC 24 – 60V, 60Hz
X Earth leakage (extemal CT, fault current > 30A) + Comm. 6 AC / DC 100 – 250V, 50Hz
A Pre-Trip Alarm + Comm. 7 DC 24 – 60V, 50Hz
*LSIG configuration as standard
*Ground fault system
C: vector sum
K: external CT - out ZCT applied
X: external CT - private ZCT applied
*Comm. works under control power
*Applicable to generator protection purpose
*Voltage module required for P and S types. (supplied separately)
*Ground fault function unavailable at A (Pre-Trip Alarm + Comm.)
S C 1
S Supreme meter C Earth leakage + Comm. 1 AC / DC 100 – 250V, 60Hz
K Earth leakage (extemal CT, fault current ≤ 30A) + Comm. 2 DC 24 – 60V, 60Hz
X Earth leakage (extemal CT, fault current > 30A) + Comm. 6 AC / DC 100 – 250V, 50Hz
A Pre-Trip Alarm + Comm. 7 DC 24 – 60V, 50Hz
*LSIG configuration as standard
*Ground fault system
C: vector sum
K: external CT - out ZCT applied
X: external CT - private ZCT applied
*Comm. works under control power
*Applicable to generator protection purpose
*Voltage module required for P and S types. (supplied separately)
*Ground fault function unavailable at A (Pre-Trip Alarm + Comm.)
Note) The function like Metering, Communication, ZSI, Remote Reset and DO control are not available only under Self-Power condition.
117
R ATINGS
AKH
series
118
AKH-06E AKH-08E AKH-10E AKH-13E AKH-16E AKH-20E AKH-25E AKH-32E AKH-40E AKH-40G AKH-50G AKH-63G
630 800 1000 1250 1600 2000 2500 3200 4000 4000 5000 6300
630 800 1000 1250 1600 2000 2500 3200 4000 4000 5000 6300
630 800 1000 1250 1600 2000 2500 3200 4000 4000 5000 6300
1,000 1,000
690 690
12 12
50 / 60 50 / 60
3, 4 3, 4
100 150
100 150
85 100
100% 100%
220 330
220 330
187 220
85 100
75 100
65 100
40 40
80 80
15,000 10,000
20,000 15,000
5,000 2,000
10,000 5,000
● ○ ○
○ ● ●
○ - -
○ - -
87 / 103 104 / 147 181 / 223 186 / 230
85 / 101 102 / 145 179 / 221 184 / 228
44 / 55 58 / 70 97 / 117 102 / 124
44 / 55 63 / 100 98 / 123 103 / 130
42 / 53 61 / 98 96 / 121 101 / 128
430 x 412 x 375 460 x 785 x 375
430 x 527 x 375 460 x 1,015 x 375
300 x 378 x 295 300 x 751 x 295
300 x 493 x 295 300 x 981 x 295
N, A, P, S type N, A, P, S type
KEMA KEMA
119
R ATINGS
AKN AKS
series
120
AKS-20E AKS-25E AKS-32E AKS-40E AKS-50F AKS-40G AKS-50G AKS-63G
2000 2500 3200 4000 4000 5000 4000 5000 6300
630, 800
1000, 1250 2500 3200 4000 4000 5000 4000 5000 6300
1600, 2000
(0.4 – 1.0) x In max (0.4 – 1.0) x In max (0.4 – 1.0) x In max
630, 800
1000, 1250 2500 3200 4000 4000 5000 4000 5000 6300
1600, 2000
1,000 1,000 1,000
690 690 690
12 12 12
50 / 60 50 / 60 50 / 60
3, 4 3, 4 3, 4
85 100 120
85 100 120
85 85 100
100% 100% 100%
187 220 264
187 220 264
187 187 220
85 85 100
75 75 90
65 65 85
40 40 40
80 80 80
15,000 10,000 10,000
20,000 15,000 15,000
5,000 2,000 2,000
10,000 5,000 5,000
● ○ ○ ○
○ ● ● ●
○ - - -
○ - - -
87 / 103 104 / 147 145 / 173 181 / 223 186 / 230
85 / 101 102 / 145 143 / 171 179 / 221 184 / 228
44 / 50 58 / 70 78 / 90 97 / 117 102 / 124
44 / 55 63 / 100 76 / 94 98 / 123 103 / 130
42 / 53 61 / 98 74 / 92 96 / 121 101 / 128
430 x 412 x 375 460 x 629 x 375 460 x 785 x 375
430 x 527 x 375 460 x 799 x 375 460 x 1,015 x 375
300 x 378 x 295 300 x 597 x 295 300 x 751 x 295
300 x 493 x 295 300 x 767 x 295 300 x 981 x 295
N, A, P type N, A, P type N, A, P type
KEMA KEMA KEMA
121
DIMENSIONS
Fixed type
2000AF
630 – 1600A:
AKH / AKN / AKS-06 – 16D
Front view
Vertical type
122
Horizontal type
Front connection
type
123
DIMENSIONS
Draw-out type
2000AF
630 – 1600A:
AKH / AKN / AKS-06 – 16D
Front view
Vertical type
124
Horizontal type
Front connection
type
125
DIMENSIONS
Fixed type
2000AF
2000A:
AKH / AKS-20D
Front view
Vertical type
126
Draw-out type
2000AF
2000A:
AKH / AKS-20D
Front view
Vertical type
127
DIMENSIONS
Fixed type
4000AF
2000 – 3200A:
AKH / AKN / AKS-20 – 32E
Front view
Vertical type
128
Horizontal type
Front connection
type
129
DIMENSIONS
Draw-out type
4000AF
2000 – 3200A:
AKH / AKN / AKS-20 – 32E
Front view
Vertical type
130
Horizontal type
Front connection
type
131
DIMENSIONS
Fixed type
4000AF
4000A:
AKH / AKS-40E
Front view
Vertical type
132
Horizontal type
133
DIMENSIONS
Draw-out type
4000AF
4000A:
AKH / AKS-40E
Front view
Vertical type
134
Horizontal type
135
DIMENSIONS
Fixed type
5000AF
4000 – 5000A:
AKS-40 – 50F
Front view
Vertical type
136
Horizontal type
18
137
DIMENSIONS
Draw-out type
5000AF
4000 – 5000A:
AKS-40 – 50F
Front view
Vertical type
138
Horizontal type
139
DIMENSIONS
Fixed type
6300AF
4000 – 6300A:
AKH / AKS-40 – 50G
Front view
Vertical type
140
Horizontal type
4000A – 5000A
6300A
141
DIMENSIONS
Draw-out type
6300AF
4000 – 6300A:
AKH / AKS-40 – 50G
Front view
Vertical type
142
Horizontal type
4000A – 5000A
6300A
143