System 350™ Pressure Application: Condenser Fan Cycling

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Code No.

LIT-1922670
Issued November 18, 2008

System 350™ Pressure Application


Condenser Fan Cycling

P- 1 Y - 1 S-1 D-1

Condensing Unit

To T-1
Evaporator

F-1

F-2

From

cfc1_1.eps
Compressor

Flow Diagram

Sequence of Operation As the condenser pressure rises to 190 psig, P-1’s normally open
Electronic pressure control P-1 powered by Y-1 monitors condenser contacts closes, energizing fan F-1 to decrease the pressure via
head pressure via pressure transmitter T-1 and maintains a set point increased heat transfer.
of 160 psig. If the pressure continues to rise above 210 psig, S-1 energizes fan
F-2. As the pressure decreases towards the 160 psig setpoint, stage
module S-1 and control P-1’s contacts open.

(+)

ON
210 psig
Differen tial

ON
190 psig
D ifferential

OFF
OFFSET
160 psig
OFF

ON = Energized
OFF= De-energized
Differential = 30 psig
Offset = 20 psig

(-)
P352 AB-3C S352 AA-2C
Stage Stage
cfc3.eps

1 2
Sequence of Operation Diagram
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2008 Johnson Controls, Inc. www.johnsoncontrols.com

1 of 2
System 350™ Pressure Application (Continued)

Bill of Materials
ID Qty Code Number Description
D-1 1 D352AA-2C Digital Display Module
P352AB-2C Electronic Pressure Control (0-100 psi range)
P-1 1 P352AB-3C Electronic Pressure Control (90-250 psi range)
P352AB-4C Electronic Pressure Control (240-600 psi range)
S-1 1 (to 5) S352AA-2C SPDT Staging Module
P499 Series Electronic Electronic Pressure Transducer (Note: Each P352AB control requires a P499 transducer that operates in the
T-1 1
Transducer control’s pressure range, and a WHA-PKD3 wiring harness.)
Y-1 1 Y350R-1C 120/240 VAC Power Module

P399
Wh i te - SEN
Red - V D C
Black - C OM
Shield
P- 1 Y-1 S-1 D-1

120
VAC

F-1 F-2
cfc2.eps

Fan Motors
Wiring Diagram

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2008 Johnson Controls, Inc. www.johnsoncontrols.com

2 of 2