Product data sheet ATV212HD37N4

Characteristics variable speed drive ATV212 - 37kW - 50hp -


480V - 3ph - EMC - IP21

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product Altivar 212
Product or component type Variable speed drive
Device short name ATV212
Product destination Asynchronous motors
Product specific application Pumps and fans in HVAC
Assembly style With heat sink
Network number of phases 3 phases
Motor power kW 37 kW
Motor power hp 50 hp
[Us] rated supply voltage 380...480 V - 15...10 %
Supply voltage limits 323...528 V
Supply frequency 50...60 Hz - 5...5 %
Network frequency 47.5...63 Hz
EMC filter Class C2 EMC filter integrated
Line current 68.9 A 380 V
54.4 A 480 V

Complementary
Apparent power 52 kVA 380 V
Prospective line Isc 22 kA
Continuous output current 79 A 380 V
79 A 460 V
Maximum transient current 86.9 A 60 s
Speed drive output frequency 0.5...200 Hz
Nominal switching frequency 8 kHz
Switching frequency 6...16 kHz adjustable
8...16 kHz with derating factor
Speed range 1...10

May 21, 2018


1
Speed accuracy +/- 10 % of nominal slip 0.2 Tn to Tn
Torque accuracy +/- 15 %
Transient overtorque 120 % of nominal motor torque +/- 10 % 60 s
Asynchronous motor control profile Voltage/Frequency ratio, 2 points
Voltage/Frequency ratio, 5 points
Flux vector control without sensor, standard
Voltage/Frequency ratio - Energy Saving, quadratic U/f
Voltage/Frequency ratio, automatic IR compensation (U/f + automatic Uo)
Regulation loop Adjustable PI regulator
Motor slip compensation Adjustable
Automatic whatever the load
Not available in voltage/frequency ratio motor control
Local signalling 1 LED red DC bus energized
Output voltage <= power supply voltage
Isolation Electrical between power and control
Type of cable IEC cable without mounting kit 1 45 °C copper 90 °C XLPE/EPR
IEC cable without mounting kit 1 45 °C copper 70 °C PVC
UL 508 cable with UL Type 1 kit 3 40 °C copper 75 °C PVC
Electrical connection Terminal 2.5 mm² AWG 14 VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES
Terminal 50 mm² AWG 1/0 L1/R, L2/S, L3/T
Tightening torque 24 N.m 212 lb.in L1/R, L2/S, L3/T
0.6 N.m VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES
Supply Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 % <= 10 A overload and
short-circuit protection
Internal supply 24 V DC 21...27 V <= 200 A overload and short-circuit protection
Analogue input number 2
Analogue input type Switch-configurable voltage VIA 0...10 V DC 24 V max 30000 Ohm 10 bits
Configurable voltage VIB 0...10 V DC 24 V max 30000 Ohm 10 bits
Configurable PTC probe VIB 0...6 probes 1500 Ohm
Switch-configurable current VIA 0...20 mA 250 Ohm 10 bits
Sampling duration 2 ms +/- 0.5 ms F discrete
2 ms +/- 0.5 ms R discrete
2 ms +/- 0.5 ms RES discrete
3.5 ms +/- 0.5 ms VIA analog
22 ms +/- 0.5 ms VIB analog
Response time 2 ms +/- 0.5 ms FM analog
7 ms +/- 0.5 ms FLA, FLC discrete
7 ms +/- 0.5 ms FLB, FLC discrete
7 ms +/- 0.5 ms RY, RC discrete
Accuracy +/- 0.6 % VIA for a temperature variation 60 °C
+/- 0.6 % VIB for a temperature variation 60 °C
+/- 1 % FM for a temperature variation 60 °C
Linearity error +/- 0.15 % of maximum value input VIA
+/- 0.15 % of maximum value input VIB
+/- 0.2 % output FM
Analogue output number 1
Analogue output type Switch-configurable voltage FM 0...10 V DC 7620 Ohm 10 bits
Switch-configurable current FM 0...20 mA 970 Ohm 10 bits
Discrete output number 2
Discrete output type Configurable relay logic FLA, FLC NO 100000 cycles
Configurable relay logic FLB, FLC NC 100000 cycles
Configurable relay logic RY, RC NO 100000 cycles
Minimum switching current 3 mA 24 V DC configurable relay logic
Maximum switching current 5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R
5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R
2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R
2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R
Discrete input type Programmable F 24 V DC level 1 PLC 4700 Ohm
Programmable R 24 V DC level 1 PLC 4700 Ohm
Programmable RES 24 V DC level 1 PLC 4700 Ohm
Discrete input logic Positive logic (source) F, R, RES <= 5 V >= 11 V
Negative logic (sink) F, R, RES >= 16 V <= 10 V
Acceleration and deceleration ramps Automatic based on the load
Linear adjustable separately from 0.01 to 3200 s

2
Braking to standstill By DC injection
Protection type Motor phase break motor
Break on the control circuit drive
Thermal power stage drive
Overvoltages on the DC bus drive
Against exceeding limit speed drive
Against input phase loss drive
With PTC probes motor
Input phase breaks drive
Line supply overvoltage and undervoltage drive
Line supply undervoltage drive
Overcurrent between output phases and earth drive
Overheating protection drive
Short-circuit between motor phases drive
Thermal protection motor
Dielectric strength 3535 V DC between earth and power terminals
5092 V DC between control and power terminals
Insulation resistance >= 1 MOhm 500 V DC for 1 minute
Frequency resolution 0.024/50 Hz analog input
0.1 Hz display unit
Communication port protocol APOGEE FLN
BACnet
LonWorks
METASYS N2
Modbus
Connector type 1 RJ45
1 open style
Physical interface 2-wire RS 485
Transmission frame RTU
Transmission rate 9600 bps or 19200 bps
Data format 8 bits, 1 stop, odd even or no configurable parity
Type of polarization No impedance
Number of addresses 1...247
Communication service Monitoring inhibitable
Read device identification (43)
Read holding registers (03) 2 words maximum
Time out setting from 0.1 to 100 s
Write multiple registers (16) 2 words maximum
Write single register (06)
Option card Communication card LonWorks
Operating position Vertical +/- 10 degree
Width 240 mm
Height 550 mm
Depth 244 mm
Power dissipation in W 976 W
Air flow 334 m3/h
Functionality Mid
Specific application HVAC
IP degree of protection IP21
Discrete and process manufacturing Building - HVAC : compressor for scroll
Building - HVAC : fan
Building - HVAC : pump
Power range 30...50 kW at 380...440 V 3 phases
30...50 kW at 480...500 V 3 phases
Motor starter type Variable speed drive

Environment
Electromagnetic compatibility Conducted radio-frequency immunity test level 3 IEC 61000-4-6
Voltage dips and interruptions immunity test IEC 61000-4-11
1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5
Electrical fast transient/burst immunity test level 4 IEC 61000-4-4
Electrostatic discharge immunity test level 3 IEC 61000-4-2

3
Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3
Pollution degree 3 IEC 61800-5-1
IP degree of protection IP20 on upper part without blanking plate on cover EN/IEC 61800-5-1
IP20 on upper part without blanking plate on cover EN/IEC 60529
IP21 EN/IEC 61800-5-1
IP21 EN/IEC 60529
IP41 on upper part EN/IEC 61800-5-1
IP41 on upper part EN/IEC 60529
Vibration resistance 1 gn 13...200 Hz EN/IEC 60068-2-8
1.5 mm 3...13 Hz EN/IEC 60068-2-6
Shock resistance 15 gn 11 ms IEC 60068-2-27
Environmental characteristic Classes 3C1 IEC 60721-3-3
Classes 3S2 IEC 60721-3-3
Noise level 64 dB 86/188/EEC
Operating altitude 1000...3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1
% per 100 m
<= 1000 m without derating
Relative humidity 5...95 % without condensation IEC 60068-2-3
5...95 % without dripping water IEC 60068-2-3
Ambient air temperature for operation -10...40 °C without derating
> 40...50 °C with derating factor
Ambient air temperature for storage -25...70 °C
Standards EN 55011 class A group 1
EN 61800-3
EN 61800-3 category C2
EN 61800-3 category C3
EN 61800-3 environments 1 category C1
EN 61800-3 environments 1 category C2
EN 61800-3 environments 1 category C3
EN 61800-3 environments 2 category C1
EN 61800-3 environments 2 category C2
EN 61800-3 environments 2 category C3
EN 61800-5-1
IEC 61800-3
IEC 61800-3 category C2
IEC 61800-3 category C3
IEC 61800-3 environments 1 category C1
IEC 61800-3 environments 1 category C2
IEC 61800-3 environments 1 category C3
IEC 61800-3 environments 2 category C1
IEC 61800-3 environments 2 category C2
IEC 61800-3 environments 2 category C3
IEC 61800-5-1
UL Type 1
Product certifications CSA
C-Tick
NOM 117
UL
Marking CE

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1050  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product environmental
Product end of life instructions Available

Contractual warranty
Warranty period 18 months

4
Product data sheet ATV212HD37N4
Dimensions Drawings

Dimensions

Dimensions in mm

ATV212H a b c G H K Ø

D22M3X 240 420 214 206 403 10 6


D22N4, D30N4

D37N4, D45N4 240 550 244 206 529 10 6


Dimensions in in.

ATV212H a b c G H K Ø

D22M3X 9.45 16.54 8.43 8.11 15.87 0.39 0.24


D22N4, D30N4

D37N4, D45N4 9.45 21.65 9.60 8.11 20.83 0.39 0.24


EMC mounting plate (supplied with drive)

Dimensions in mm

ATV212H b1 c1

D22M3X 122 120


D22N4, D30N4

D37N4, D45N4 113 127


Dimensions in in.

5
ATV212H b1 c1

D22M3X 4.80 4.72


D22N4, D30N4

D37N4, D45N4 4.45 5.00

6
Product data sheet ATV212HD37N4
Mounting and Clearance

Mounting Recommendations

Clearance
Depending on the conditions in which the drive is to be used, its installation will require certain precautions and the use of appropriate
accessories.
Install the unit vertically:
● Do not place it close to heating elements.
● Leave sufficient free space to ensure that the air required for cooling purposes can circulate from bottom to the top of the unit.

Mounting Types
Type A mounting

Type B mounting

Type C mounting

By removing the protective blanking cover from the top of the drive, the degree of protection for the drive becomes IP21. The protective blanking
cover may vary according to the drive model, see opposite.

7
Product data sheet ATV212HD37N4
Mounting and Clearance

Specific Recommendations for Mounting in an Enclosure

To help ensure proper air circulation in the drive:


● Fit ventilation grilles.
● Check that there is sufficient ventilation. If there is not, install a forced ventilation unit with a filter. The openings and/or fans must provide a flow rate at least e
● Use special filters with UL Type 12/IP54 protection.
● Remove the blanking cover from the top of the drive.

Sealed Metal Enclosure (IP54 Degree of Protection)


The drive must be mounted in a dust and damp proof enclosure in certain environmental conditions, such as dust, corrosive gases, high humidity
with risk of condensation and dripping water, splashing liquid, etc.This enables the drive to be used in an enclosure where the maximum internal
temperature reaches 50°C.

8
Product data sheet ATV212HD37N4
Connections and Schema

Recommended Wiring Diagram

3-Phase Power Supply

A1: ATV 212 drive


KM1: Contactor
Q1: Circuit breaker
Q2: GV2 L rated at twice the nominal primary current of T1
Q3: GB2CB05
S1, S2: XB4 B or XB5 A pushbuttons
T1: 100 VA transformer 220 V secondary
(1) Fault relay contacts for remote signalling of the drive status
(2) Connection of the common for the logic inputs depends on the positioning of the switch (Source, PLC, Sink)
(3) Reference potentiometer SZ1RV1202
NOTE: All terminals are located at the bottom of the drive. Install interference suppressors on all inductive circuits near the drive or connected on
the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.

Switches (Factory Settings)


Voltage/current selection for analog I/O (VIA and VIB)

Voltage/current selection for analog I/O (FM)

Selection of logic type

(1) negative logic


(2) positive logic

9
Product data sheet ATV212HD37N4
Connections and Schema

Other Possible Wiring Diagrams

Logic Inputs According to the Position of the Logic Type Switch


“Source” position

“Sink” position

“PLC” position with PLC transistor outputs

(1) PLC (1) PLC


2-wire control

F: Forward
R: Preset speed
(2) ATV 212 control terminals
3-wire control

F: Forward
R: Stop
RES: Reverse
(2) ATV 212 control terminals
PTC probe

(2) ATV 212 control terminals


(3) Motor

Analog Inputs
Voltage analog inputs
External +10 V

10
(2) ATV 212 control terminals (2) ATV 212 control terminals
(4) Speed reference potentiometer 2.2 to 10 kΩ

Analog input configured for current: 0-20 mA, 4-20 mA, X-Y mA

(2) ATV 212 control terminals


(5) Source 0-20 mA, 4-20 mA, X-Y mA
Analog input VIA configured as positive logic input (“Source” position)

(2) ATV 212 control terminals


Analog input VIA configured as negative logic input (“Sink” position)

(2) ATV 212 control terminals

11
Product data sheet ATV212HD37N4
Performance Curves

Derating Curves

The derating curves for the drive nominal current (In) depend on the temperature, the switching frequency and the mounting type (A, B or C).
For intermediate temperatures (45°C for example), interpolate between 2 curves.

X Switching frequency

12
Product data sheet ATV212HD37N4
Motor Starter BOM

Our Proposal: Circuit Breaker + Contactor + Drive for Motor Power 37 kW and 380 VAC

Motor power ICU Breaker Contactor (*) Motor Starter


(kW) (kA)

37 70
LC1D40AP7 ATV212HD37N4

28100
Non contractual pictures.
(*) You can select the contactor proposed or variants. Please consider examples hereafter or follow the link to the complete offer.

Motor power Coil voltage 24 48 110 115 220 230 400 Other
kW VAC - 50/60 Hz

37 LC1D40A .. B7 E7 F7 FE7 M7 P7 V7 Complete


Offer

Motor power Coil voltage 24 48 110 125 220 230 Other


kW VDC

37 LC1D40A .. BD ED - - - - Complete
Offer