Hospital Raja Permaisuri Bainun Building Automation System

BAS Air Handling Unit / Fan Coil Unit Checklist


TYPE : Location:
Name : ID : Date :

Item Discription B.A.S UoM Actual UoM Date Remark


CV-C Cooling Valve % OPEN
EDH-C1 Elect duct htr stg1 cmd
EDH-C2 Elect duct htr stg2 cmd
EDH-C3 Elect duct htr stg3 cmd
EDH-C4 Elect duct htr stg4 cmd
EF-S Exhaust air fan status
FAN-ENA Fan enable
HFILT-S Hepa filter status
LSP LSP
OCC-S Occupied/unocc mode
PFILT-S Pre filter status
RM-DHSP Room dehum setpt %RH
RM-H Room humidity %RH
RM-HDM Room hum display module %RH
RM-SP Room static pressure Pa
RM-T Room temperature C
RM-TDM Room temp display module C
RM-TSP Room temp setpt C
SA-T Supply air temperature C
SF-AM Supply fan auto/man
SF-C Supply fan cmd
SF-S Supply fan status
SF-T Supply fan trip

Summary / Report Prepared By


( )

Verified By
( )
BAS : Main Block
Hospital Raja Permaisuri Bainun Building Automation System

)