Functional Specification FOR Fire & Gas Detection System
Functional Specification FOR Fire & Gas Detection System
Functional Specification FOR Fire & Gas Detection System
FUNCTIONAL SPECIFICATION
FOR
35 1
APPROVED BY
OFFSHORE FUNCTIONAL SPECIFICATION VOL No III
DESIGN SECTION FOR FIRE & GAS DETECTION
MUMBAI REGION SYSTEM REV No 1
INDEX OF CONTENTS
9.0 Documentation 33
1.1 This specification defines the minimum requirements for the design, engineering,
fabrication, inspection-testing, supply, installation and commissioning of Fire & Gas
Detection System for use on offshore platform.
1.2 This specification describes the field detection and actuating equipment for the Fire &
Gas Detection System, and the functionality of the system as a whole. It does not
cover the detailed specifications of:
1.3 Any deviations from the requirements of this specification shall be stated in
‘Deviation List’ in contractor’s proposal. Unless specific deviations are stated, it shall
be understood that the Fire & Gas Detection system is in accordance with the
specification.
1.4 Contractor’s proposal shall also include revision status sheets, which shall show
revision status of each page of the proposal / purchase specification for every
submission.
1.5 Any ambiguity in this specification and the reference specifications pertaining to the
requirements of Fire & Gas Detection System shall be referred to the company for
clarification prior to finalisation of Purchase Specification.
NIL
OFFSHORE FUNCTIONAL SPECIFICATION VOL No III
DESIGN SECTION FOR FIRE & GAS DETECTION
MUMBAI REGION SYSTEM REV No 1
3.1 The Fire and Gas Detection System shall include the following equipment:
f) Means for display in the instrument equipment room of individual loop/ zone.
3.2 The configuration & requirement of components of Fire & Gas Detection system as
described in cl.no. 3.1 above shall be governed by cl.no. 4.1.3 together with
cl.nos.4.1.4, 4.1.5 & 4.1.6.
4.1 GENERAL
4.1.1 The Fire & Gas Detection system is required to address the risk associated with
imminent or established fire and combustible/ toxic gas release.
4.1.3 Unless otherwise specified all contacts shall be volt free contacts which shall be
SPDT type, rated 24 VDC – 2 amps.
OFFSHORE FUNCTIONAL SPECIFICATION VOL No III
DESIGN SECTION FOR FIRE & GAS DETECTION
MUMBAI REGION SYSTEM REV No 1
4.1.4 The Fire & Gas Detection system scheme shall be one out of the following three
schemes (refer ‘Basic Bid Work’ for type of scheme to be followed for the project)-
a) Scheme- I.
b) Scheme- II.
c) Scheme- III.
4.1.5 Scheme- I. In Scheme- I Fire & Gas Detection system shall be referred to as Gas
Detection System (GDS). The following shall constitute GDS-
b) Field Devices including Pneumatic Fusible plug loops, FSD & ESD valves,
flashing and audible alarm beacons
c) Interface to the field actuating devices including deluge valve actuation logic.
4.1.6 Scheme- II. In Scheme- II Fire & Gas Detection system shall be referred to as Gas
Detection System (GDS). The following shall constitute GDS-
c) Gas detectors controller / monitor card mounting unit with relays logics, etc.
which shall be installed in SAFE area.
d) Interface to the field actuating devices including deluge valve actuation logic.
OFFSHORE FUNCTIONAL SPECIFICATION VOL No III
DESIGN SECTION FOR FIRE & GAS DETECTION
MUMBAI REGION SYSTEM REV No 1
4.1.7 Scheme- III. In Scheme- III Fire & Gas Detection system shall constitute the
following-
d) Interfaces to other systems of the platform including DCS, ESD system, RTU,
Package equipment (such as Gas Turbines, Process gas compressors) fire &
gas detection system, Paging system, emergency generator, pneumatic panel.
f) Means for display in the instrument equipment room of individual loop/ zone.
All the equipment, as detailed in this specification, shall be connected to PLC (Refer
Specification MR / OD / INST / FS / C 101).
The F&G system will be powered from a dedicated dual 24 VDC battery back-up
supply, which will provide stable supply, allowing orderly shutdown and monitoring
if power is lost. Power supply sizing shall also consider requirement of installed
spares & spare space in F&G system ‘Control Devices’. The back-up system capacity
shall allow continued monitoring by the F&G system for a nominal period of not less
than 24 hours. This period shall be confirmed by the contractor following project risk
assessments and HAZOP. A common power supply fault alarm shall be provided for
OFFSHORE FUNCTIONAL SPECIFICATION VOL No III
DESIGN SECTION FOR FIRE & GAS DETECTION
MUMBAI REGION SYSTEM REV No 1
connection to RTU (for Scheme- I, II) / DCS (for Scheme- III). Contacts shall be volt
free contacts.
4.2.1.1 GENERAL
4.2.1.1.1 The detectors and field devices shall be suitable for the offshore climate including
regular monsoonal rains and corrosive marine environment.
4.2.1.1.2 The atmospheric conditions that detectors and field devices will be subject to are in
general as follows:
4.2.1.1.3 Detector Location: The Contractor shall specify each type of detector and their
locations and mountings, to ensure the earliest response to imminent or established
fire or hydrocarbon release or toxic (H2S) gas release, with consideration to the
following as a minimum:
c) Ease of Maintenance: The fire and gas detectors shall be installed in a location
accessible for calibration and maintenance, preferably from deck or fixed
platform, but not in frequently used access ways.
f) Certain areas shall be avoided, such as sample stations where spurious alarms
would negate the effectiveness of the detection system.
4.2.1.2.1 For the purpose of selecting gas detectors following general factors shall be
considered-
a) Combustible Gas (HC & H2) Detectors shall be able to perform to the
temperature, humidity, air velocity and vibration specification prescribed in
ISA 12.13.01. Toxic Gas (H2S) Detectors shall be able to perform to the
specifications prescribed in ISA 92.0.01 Part I.
c) Effects of Humidity: The detector housing shall be suitable for offshore salt
laden marine environment.
d) Air Velocity: Sensors shall be located away from prevailing winds, heating
and cooling system. Air circulation patterns and effects of other equipment
that affect circulation shall be taken into consideration while finalizing the
location of the detectors. Where widely varying wind direction changes are
expected, multiple detectors shall be installed to provide the required cover.
e) Vibration: Sensors shall be located away from vibration prone areas. If this is
not possible, the sensors shall be mounted on flexible mounts or flexible
conduit.
f) Combustible and toxic gas sensors shall be located in accordance with the
protection area limitations of the detector manufacturer.
h) Special consideration shall be given to the properties of the process gas (refer
Process Design Criteria for properties of process fluids), specifically its
vapour density and predominant component. For lighter-than-air gases, the
detectors shall be placed above the release point. For heavier-than-air gases,
the detectors shall be placed 300-450 mm above the grade.
i) Detector locations shall take into account the possible flow pattern of the
leaking gas or vapour and ventilation system airflow.
l) Indoor or partially enclosed installations that may require gas detection (such
as turbine enclosures, compressor stations, etc.) shall be protected with open
path or point detection system.
4.2.1.2.2.1 Fixed Hydrocarbon (HC) Gas Detectors shall be based on Infrared Absorption
Technology. Catalytic HC detectors shall not be used.
OFFSHORE FUNCTIONAL SPECIFICATION VOL No III
DESIGN SECTION FOR FIRE & GAS DETECTION
MUMBAI REGION SYSTEM REV No 1
4.2.1.2.2.2 The detecting unit included in the sensor head shall provide adequate sensitivity and
stability, under all conditions, with ±5% accuracy (For Range of 100 LEL).
4.2.1.2.2.3 The fixed HC gas detectors shall be powered from 24 V DC –ve earthed supply, with
a 4-20 mA signal loop to cover the calibrated range. Detector faults shall be signaled
by 4 mA signal.
Note: In Scheme-I, detector shall provide 2 nos. of volt free contact outputs. These 2
nos. of contact outputs shall be independently adjustable over entire range of gas
detection.
4.2.1.2.2.4 Junction Boxes: Integral explosion proof junction boxes shall be provided with the
detectors for cable termination.
4.2.1.2.2.5 Detector system shall initiate responses at two different concentrations: for warning
alarms and for initiation of executive action. Typical values of these set-points are:
4.2.1.2.2.7 Operator response shall be required to clear the audible and visual alarms.
4.2.1.2.2.9 Point HC Detectors: Point HC Detectors shall be calibrated 0-100% LEL (Lower
Explosive Limit) of Methane in air. A single point detector may be used for more
than one release point, with due consideration to the manufacturer’s specification of
the sensing area.
4.2.1.2.2.10 Open Path HC Detectors: Open Path IR detectors shall be located where the beam
will provide a clear view over process equipment. The detectors shall be selected for
the correct path length with a separate transmitter and receiver. The transmitter and
receiver shall be placed 1-2 m away from each potential source. Combined transmitter
and receiver with mirrors shall not be used. Units shall not be affected by direct
sunlight, fog or mist.
4.2.1.2.2.11 Combination of Open Path and Point IR Detectors: If multiple release sources are
present in a process unit, then both point and line-of-sight detection may be used.
OFFSHORE FUNCTIONAL SPECIFICATION VOL No III
DESIGN SECTION FOR FIRE & GAS DETECTION
MUMBAI REGION SYSTEM REV No 1
4.2.1.2.3.1 The number of Portable HC Gas Detectors required per platform shall be as per the
Basic Bid Work.
4.2.1.2.3.2 The portable HC detectors shall be capable of detecting 0 – 100% LEL of HC and
shall have an accuracy of ±5% (For Range of 100 LEL).
4.2.1.2.3.3 The portable HC gas detector shall have an integral audio-visual alarm and shall be
factory calibrated for 20% and 60% LEL HC. Alarm shall be adjustable over the
entire detection range of gas detectors.
4.2.1.2.3.4 The portable HC detectors shall be battery operated. The batteries shall be
rechargeable and shall be suitable for 110 V, 50 Hz.
4.2.1.2.3.5 The portable HC detector shall be capable of generating a “Battery Low” Alarm.
4.2.1.2.3.6 The portable HC detectors shall also include accessories such as carrying case,
aspirator, calibration adaptor, charging kit, etc.
4.2.1.2.3.7 The portable HC detector shall be suitable for Class I, Div I, Group B, C, D, T3
hazardous area.
4.2.1.2.4.2 The fixed H2S gas detectors shall be powered from 24 V DC –ve earthed supply, with
a 4-20 mA signal loop to cover the calibrated range. Detector faults shall be signaled
by 4 mA signal.
Note: In Scheme-I, detector shall provide 2 nos. of volt free contact outputs. These 2
nos. of contact outputs shall be independently adjustable to over entire range of gas
detection.
4.2.1.2.4.3 The H2S detectors shall be capable of detecting 0 – 100ppm of H2S and shall have an
accuracy of ±3 ppm or 10% (relative) whichever is better.
4.2.1.2.4.4 The fixed H2S detectors shall initiate responses at two different concentrations: for
warning alarms and for initiation of executive action.
4.2.1.2.4.5 Nominal system alarm settings shall be 5 ppm for “Alert” Level and 10 ppm for
“Danger” Level.
OFFSHORE FUNCTIONAL SPECIFICATION VOL No III
DESIGN SECTION FOR FIRE & GAS DETECTION
MUMBAI REGION SYSTEM REV No 1
4.2.1.2.4.6 The alarm condition shall not be resettable until the specific detector reading has
dropped below the warning alarm level as applicable.
4.2.1.2.4.7 Two H2S detectors shall be installed at each ventilation air intake of control rooms
and normally manned buildings.
4.2.1.2.5.1 The number of Portable H2S Gas Detectors required per platform shall be as per the
Basic Bid Work.
4.2.1.2.5.2 The portable H2S detectors shall be capable of detecting 0 – 100ppm of H2S and shall
have an accuracy of ±3 ppm.
4.2.1.2.5.3 The portable H2S gas detector shall have an integral audio-visual alarm for activation
upon detection of 10 ppm and 50 ppm of H2S.
4.2.1.2.5.4 The portable H2S detectors shall be battery operated. The batteries shall be
rechargeable and suitable for 110 V AC, 50 Hz.
4.2.1.2.5.5 The portable H2S gas detector shall be capable of generating a “Battery Low” Alarm.
4.2.1.2.5.6 The portable H2S gas detectors shall also include accessories such as carrying case,
aspirator, calibration adaptor, charging kit, etc.
4.2.1.2.5.7 The portable H2S detector shall be suitable for Class I, Div I, Group B, C, D, T3
hazardous area.
4.2.1.2.6.1 Fixed catalytic H2 Detectors shall be provided in the battery room and process areas,
which may see release of H2 gas. Minimum of two H2 detectors shall be provided in
an area.
4.2.1.2.6.2 The fixed H2 gas detectors shall be powered from 24 V DC –ve earthed supply, with
a 4-20 mA signal loop to cover the calibrated range. Detector faults shall be signaled
by 4 mA signal.
Note: In Scheme-I, detector shall provide 2 nos. of volt free contacts / outputs. These
2 nos. of contact shall be independently adjustable to over entire range of gas
detectors.
4.2.1.2.6.3 The H2 detectors shall be capable of detecting 0 – 100% LEL of H2 and shall have an
accuracy of ±5% over the entire detection range.
OFFSHORE FUNCTIONAL SPECIFICATION VOL No III
DESIGN SECTION FOR FIRE & GAS DETECTION
MUMBAI REGION SYSTEM REV No 1
4.2.1.2.6.4 The catalytic H2 detectors shall not be located in oxygen enriched or depleted
atmospheres.
4.2.1.3.1 General
4.2.1.3.1.1 The fire detection system shall comprise a variety of fire detection devices and
sensors, including:
4.2.1.3.2.1 Optical flame detectors shall be the Infra-red / Ultra Violet (IR/UV) type and shall
make use of such sensor, filters, and / or design to reject phenomena such as electric
arcs, heaters, artificial light sources, lightning and shall be completely “solar blind”.
4.2.1.3.2.2 The detectors shall be able to detect all types of flaming fires.
4.2.1.3.2.3 UV detectors may be used where they are not exposed to external UV rays, such as in
compressors and power generating enclosures.
4.2.1.3.2.4 Detectors shall be powered from 24 V DC, with a 4-20 mA signal loop to cover the
calibrated range. Detector faults shall be signaled by a 4 mA signal. Sufficient margin
shall be allowed between fault, normal and alarm levels to minimize spurious alarms.
4.2.1.3.2.5 Optical flame detectors shall have automatic, self-diagnostic circuitry that
continuously monitors the optical surfaces, sensor sensitivity and electronic circuitry,
and shall give fault status. Any detector malfunction shall be alarmed on the Fire and
Gas detection system panel and DCS.
4.2.1.3.3.1 Smoke detectors shall be installed indoors in all rooms, including concealed floor and
ceiling voids.
4.2.1.3.3.2 The smoke detectors shall incorporate an integral LED indicator for confirmation that
the unit is active.
OFFSHORE FUNCTIONAL SPECIFICATION VOL No III
DESIGN SECTION FOR FIRE & GAS DETECTION
MUMBAI REGION SYSTEM REV No 1
4.2.1.3.3.3 Detectors that are not visible, such as ceiling void or under floor, shall be provides
with remote LED’s located in the room being monitored.
4.2.1.3.3.4 Two independent smoke detector loops shall be installed in each area where executive
action is required on detection of fire.
4.2.1.3.3.5 Ionization smoke detectors shall be used in general-purpose areas to provide early
response to smoldering or flaming fires in their incipient stages. A detector base shall
be provided for connecting the individual detectors to the Fire and Gas (F&G) control
system.
4.2.1.3.3.6 Smoke detectors shall remain in alarm state until reset by the fire and gas control
system.
4.2.1.3.3.7 Photoelectric smoke detectors shall be used in electric equipment and control room
areas. A detector base shall be provided for connecting the individual detectors to the
F & G control system.
4.2.1.3.4.1 Thermal detectors shall be used in all indoor spaces including all rooms and
equipment enclosures, including concealed floor and ceilings voids.
4.2.1.3.4.2 Rate of rise thermal detectors shall be used where an early warning of smoldering
fires is required, such as storerooms and equipment rooms where air flow or high
humidity may inhibit the response of smoke detectors.
4.2.1.3.4.3 Fixed temperature or rate compensated type heat detectors shall be used within areas
unsuitable for smoke detection where a rapidly achieved high temperature can be
expected, such as machinery rooms or equipment enclosures. These shall be set at
approximately 12oC above maximum ambient temperature within the area.
4.2.1.3.4.4 Thermal detectors shall remain in alarm state until reset by the fire and gas control
system.
4.2.1.3.4.5 All visible detectors shall incorporate an LED indicator as an integral part of the
detector head or its mounting base. Concealed thermal detectors shall be provided
with an LED “repeater” that is located in a visible location. Normally, unmanned
equipment rooms or offices shall have indicators in the corridor. The detector
circuitry shall cause the LED to remain illuminated while the detector is the alarm
condition.
OFFSHORE FUNCTIONAL SPECIFICATION VOL No III
DESIGN SECTION FOR FIRE & GAS DETECTION
MUMBAI REGION SYSTEM REV No 1
4.2.1.3.5 Fusible Plug Loops, FSD (Fire Shutdown) valves & ESD (Emergency Shutdown)
valves.
4.2.1.3.5.1 Pneumatic Fusible plug loops shall be provided to alarm and initiate the F&G deluge
and ESD system, laid out and segregated according to the fire zones.
4.2.1.3.5.2 Fusible plugs shall be selected to melt at 85oC. Each area covered shall have
independent loop.
4.2.1.3.5.3 Pneumatic fusible plug loops shall also be provided with manually operated FSD
valves installed at strategic locations all over the platform as per API-RP-14C. FSD
valves shall be RED in color.
4.2.1.3.5.4 A field mounted Pneumatic panel shall be provided for fusible plug loop. Functional
specifications of pneumatic panel are addressed in Spec. no.- MR / OD / INST / FS /
3501.
4.2.1.3.5.5 For Scheme- III, Fusible plug loops shall be divided into two sub-groups, one for
Cellar Deck and other for Main Deck (corresponding to two fire water deluge
networks, one Cellar Deck and other for Main Deck). These two sub-groups of
Fusible plug loops shall be provided with individual loop charging facility.
4.2.1.3.5.6 Manually operated ESD valves shall be provided on the pneumatic loop generated
from Pneumatic Panel (Refer Spec. no.- MR / OD / INST / FS / 3501). ESD valves
shall be installed at strategic locations all over the platform adjacent to each FSD
valves. ESD valves shall be BLACK in color.
a) Fire alarm.
b) Platform Abandonment.
4.2.1.4.2 Manual alarm stations for fire alarm shall be located throughout all areas of the
platform, especially at exits and in the main equipment rooms. These stations shall be
located at easily accessible, well lighted, conspicuous areas and located no more than
30 meters apart.
4.2.1.4.3 Manual alarm stations- platform abandonment shall be located adjacent to each
survival craft.
4.2.1.4.4 All manual alarm stations shall require a double action to activate the alarm. They
shall be the break-glass, pushbutton type.
OFFSHORE FUNCTIONAL SPECIFICATION VOL No III
DESIGN SECTION FOR FIRE & GAS DETECTION
MUMBAI REGION SYSTEM REV No 1
4.2.1.4.5 Each unit shall be surface mounted at a height of 1.4 meters and shall be provided
with a striker connected to the station by a chain.
4.2.1.4.6 Each unit shall be wired to the F&G control system in the Control Room.
4.2.1.4.7 The manual alarm stations- Fire alarm shall be red in colour & manual alarm stations-
Platform abandonment shall be black in colour.
4.2.1.5.1.1 The Flashing alarm beacons shall be direct ignition, Xenon type. Flashing alarm
beacons shall be powered from 24 V DC, -ve earthed supply.
4.2.1.5.1.2 The Flashing alarm beacons shall have flashing speed of 60 flashes per minute.
b) Flashing alarm beacons shall be located at Helideck and Mezzanine Deck for
visibility to personnel approaching the platform via Helicopter or sea.
b) Flashing alarm beacons shall be located at each deck covering all the areas of
the platform. In addition these beacons shall also be located inside enclosures
(such as Enclosure building of Gas Turbines, etc) with high noise environment
and shall be visible 3600.
4.2.1.5.2.1 Field sounder shall be electronic type, and shall be powered from a 24 V DC, -ve
earthed supply.
4.2.1.5.2.2 Field sounder shall be provided for audible alarm for confirmed HC-H2 / H2S gas
release.
OFFSHORE FUNCTIONAL SPECIFICATION VOL No III
DESIGN SECTION FOR FIRE & GAS DETECTION
MUMBAI REGION SYSTEM REV No 1
4.2.1.5.2.3 Field sounder shall be located near personnel rest room on Main deck of the platform.
4.2.1.5.3.2 Methane, and Hydrogen Calibration gas shall be supplied. Sufficient quantity of
calibration gas shall be supplied to enable complete calibration, testing, inspection of
all sensing heads
4.2.1.5.4 Extinguishant
4.2.1.5.4.1 Areas protected by extinguishant shall have warning lights and alarms, both on the
inside and outside of the enclosure that will be activated prior to and during the
release of extinguishant.
4.2.1.5.4.2 Two lights shall be provided apart from a blue flashing strobe. One of the lights shall
be used to indicate “Extinguishant release imminent” and the other to indicate “Do
Not Enter – Extinguishant Released”.
4.2.1.5.4.3 The release of the extinguishant shall be indicated on the F&G panel and the DCS.
4.2.1.5.4.4 A manual release station and a lockable inhibit valve shall be provided at the entrance
to the protected area.
4.2.2.1 GENERAL
4.2.2.1.1 The F&G Control components shall be located in safe area on the platform.
4.2.2.2.1 Fire & Gas detection system panel for Scheme- I shall constitute the following:
a) There shall not be any separate Fire & Gas detection system panel in Scheme-
I.
b) Control & other auxiliary components like logic relays, auxiliary relays, power
distribution for detectors-flashing alarm beacons-sounders, etc shall be housed
in Telemetry Interface Cabinet (TIC) installed in the SAFE area.
OFFSHORE FUNCTIONAL SPECIFICATION VOL No III
DESIGN SECTION FOR FIRE & GAS DETECTION
MUMBAI REGION SYSTEM REV No 1
c) For confirmed HC, H2 & H2S gas release separate SPDT volt free contacts
shall be provided for RTU connection.
d) Fire & Gas system shall be interfaced with Pneumatic Shutdown panel to
confirm to SAFE (Safety Analysis and Function Evaluation) Table
requirements.
4.2.2.2.2 The Fire & Gas detection system panel for Scheme- II shall constitute the following:
a) Gas detector Controller / Monitor Cards, Logic & auxiliary relays, power
distribution scheme, hooter mounted on a separate panel in SAFE area.
b) For confirmed HC, H2 & H2S gas release separate SPDT volt free contacts
shall be provided for RTU connection.
c) Fire & Gas system panel shall be interfaced with Pneumatic Shutdown panel
to confirm to SAFE chart requirements.
f) The modules shall be plug-in type permitting the removal of the modules
without disturbing the system wiring. Each module shall have a maximum of
4 channels (one detector per channel) per modules. Gas/Fire circuit shall be so
designed that any channel can be put out of service for repair, without
affecting the other.
(v) Indicator LEDs for the following: Malfunction warning for each channel,
Power on, Calibration mode, Test mode, Low alarm for each channel,
High alarm / trip for each channel.
(vi) Alarm Contact: For each detector, module shall be able to generate
minimum 2 independently adjustable (adjustable over entire range of
detection) SPDT relays for each alarm level for the purpose of alarming
& logic solving.
4.2.2.2.3 The Fire & Gas detection system panel for Scheme- III shall constitute the following:
a) Fire & Gas detection system panel for Scheme- III shall be PLC-based
providing independent automatic control. PLC shall be provided as per
Functional Specification No. MR / OD / INST / FS / C 101.
b) Fire & Gas detection system panel shall be interfaced with the following
systems of the platform to confirm to SAFE table requirements (refer Basic
Bid Work also):
- ESD system.
- Pneumatic Panel
- Unit Control Panels for package items (such as Gas Turbines, Process gas
compressors, etc)
- Paging system for alarm tones
- Flashing Beacons & Sounders
- Extinguishant systems
- HVAC System
- Deluge panel
- Diesel and electric fire pumps
- DCS for graphic displays
c) Besides PLC related cabinets other main components of Fire & Gas Detection
system panel shall be:
removal and replacement from the panel front via individual snap out
windows or a swing out hinged door on which all windows are mounted.
Minimum critical alarms to be provided are given below:
e) Matrix Panel: Matrix panel shall provide graphic status of Fire & Gas
Detection system & Fire suppression system area-wise for the entire platform.
- Low HC
- High HC
- Low H2S
- High H2S
- Low H2
- High H2
- Flame
- Heat
- Smoke
- Manual Alarm Call point- Fire Alarm.
- Manual Alarm Call point- Platform abandonment.
OFFSHORE FUNCTIONAL SPECIFICATION VOL No III
DESIGN SECTION FOR FIRE & GAS DETECTION
MUMBAI REGION SYSTEM REV No 1
- Fusible Plug
- Extinguishant- Inhibited.
- Extinguishant- Auto.
- Extinguishant- Manual.
- Extinguishant- Initiated.
- Extinguishant- Released.
- Extinguishant- Pressure & Weight loss.
- Deluge- Valve open.
- Deluge- Valve closed.
- Deluge- Pressure.
- System Fault.
- Abandon platform.
- Gas alarm.
- Fire alarm.
- Manual ESD.
- Manual FSD (Separate for ‘Cellar’ deck and ‘Main’ deck).
- FWP: Start.
- FWP: Stop.
- Diesel Transfer Pump: Start.
- Diesel Transfer Pump: Stop.
- Diesel supply valve: Open.
- Diesel supply valve: Close.
- Pushbutton- Mute.
- Pushbutton- Accept.
- Pushbutton- Reset.
- Buzzer.
(iv) All annunciator components except the alarm horn and auxiliary
contact relays shall be mounted integrally in a protective enclosure.
Mounting clamps which present a flat surface to the front panel face
shall be provided for panel mounting the assembly. All connections
(i.e. trouble contact, speaker, test, acknowledge and test-push-buttons)
shall be made on screw type terminals. Sufficient spares terminals
shall be provided to accommodate all spares/future alarm point in the
display. Access shall be provided to allow checking and/or changing
the wiring to these terminal strips.
4.2.2.2.4 The Fire & Gas detection system panel shall be freestanding, self-supporting cubicle
type, fully enclosed construction made of CRCA sheet. The contractor shall be
responsible for matching this panel with the other panels of Control room.
4.2.2.2.5 Plates shall be cut on Squaring shear to ensure tight flush joints when bolted together.
All sharp edges and corners shall be smoothened off to protect personnel. The final
assembly shall be free of buckles, warps, dents or blemishes. Steel strips stock shall
be edge welded to the back of the panel from face above and below the cut-outs as
required to ensure a rigid, self supporting structure. In order to reduce the loading on
the panel face, channel or equivalent support shall be run horizontally beneath the
module cases/shelves to provide rear support. The finished panel frame work shall be
of sufficient strength to allow transportation and lifting by a crane, with all
instrumentation installed without causing buckling or deflection. Each panel section
shall have four (4) removable lifting lugs at the top to facilitate handling.
4.2.2.2.6 Hinges shall be full-length type. Doorframes shall be formed in the enclosure to
ensure that the doors fit tightly all around. Doors latches shall be the flush-mounted,
3-point type with recessed chrome-plated handles. An installed clearance will be
maintained inside the panels to allow for door opening and access the equipment.
Doors shall open outwards of the panel.
4.2.2.2.7 The enclosure and its internal equipment arrangement shall be designed to provide
adequate cooling of panel hardware by natural convection alone. Louvers shall be
provided on the top of enclosures for air circulation purposes along with exhaust fans,
as required.
4.2.2.2.8 All sheet and structural steel shall be vapour degreased after shearing, cutting and
forming and prior to welding. Welded construction shall be used throughout, except
OFFSHORE FUNCTIONAL SPECIFICATION VOL No III
DESIGN SECTION FOR FIRE & GAS DETECTION
MUMBAI REGION SYSTEM REV No 1
where specifically noted otherwise. All welds shall be continuous on the pieces being
joined. Skip welding is not acceptable.
4.2.2.2.9 Proper precautions shall be taken to prevent material warpage during the welding
process. All welded surfaces shall be thoroughly brushed chipped and ground to
provide a clean, smooth surface.
4.2.2.2.10 The entire steel structure is to be sand blasted, phosphatized and painted with two
coats of sealing primer on surfaces. The final finish shall be a minimum of three
coats of non-glossy Admiralty Grey epoxy paint on exterior surface and pale cream
on interior surface. The fabricator shall supply separately one (1) Kilogram of paint
for touch up.
4.2.2.2.11 Panel cutout sizes, instrument supports and stabilizers and panel reinforcements shall
be strictly in accordance with the instrument manufacturer's recommendations.
Cutouts shall not be made with flame production devices.
4.2.2.2.12 Sufficient access shall be provided for all instruments via cable duct/trays to allow
checking and/or changes to the wiring to the instrument case.
4.2.2.2.13 Auxiliary Equipment: All rear of panel equipment (terminal blocks, auxiliary relays,
solid state logic cards, etc.) shall be physically located off the exterior walls of the
panel by means of suitable mounting brackets/plates welded to the wall prior to
finishing and painting. Drilling and tapping the outside walls of the enclosure for
mounting internal equipment is prohibited. The auxiliary equipment shall be located
and arranged for easy access, for calibration and maintenance. It shall not be
necessary to remove any item in order to gain access to check or remove any other
item. All cable runs shall be grouped, routed and secured to provide a neat
appearance and prevent interference with the operation and maintenance of auxiliary
equipment. Auxiliary relays, if used shall be of the plug-in enclosed type.
4.2.2.2.14 Electrical Construction: The installed electrical equipment component parts and
associated wiring in the panel shall be in accordance with the practices outlined in
NEC, latest edition, for non-hazardous area. The panel itself shall meet the
requirement for NEMA-1 (General purpose in door) electrical enclosure.
4.2.2.2.15 Cables from field shall enter through bottom of the panel through multi-cable transits.
4.2.2.2.16 Cable glands are to be provided in panel to clamp the incoming/outgoing cables.
Glands shall be of Double Compression type and nickel-plated brass. Gland plates
shall be provided to facilitate cable gland installation.
4.2.2.2.17 The 24V DC main power supply feeder to the box shall be protected by a suitably
sized circuit breaker with manual trip lever. The breaker shall be housed in a suitable
OFFSHORE FUNCTIONAL SPECIFICATION VOL No III
DESIGN SECTION FOR FIRE & GAS DETECTION
MUMBAI REGION SYSTEM REV No 1
surface mounted enclosure. All components shall be suitable for 24V DC ± 10%.
Power distribution to controllers and associated group of auxiliary relays circuits shall
be via fused terminals with a blown fuse indicator, and input/output fuse status alarm.
4.2.2.2.18 Panel Ground and signal ground shall be separate. Signal ground shall be provided
for circuit grounds of Electronic instruments, Detector Circuit shields, Drain wire of
cable shields, I.S. Barrier earth etc. For this purpose an insulated ground bus bar 25
mm wide x 6 mm thick of copper material shall be provided which shall run along the
entire panel length. Ground wiring shall be directly connected to the ground bus bar
by means of suitable wire lugs. Intermediate terminals are not allowed. This ground
bus bar shall be provided with grounding terminals at both ends. Terminals shall be
compression type suitable for AWG No. 4 copper ground cable. The same shall be
provided on each panel structure for panel grounding.
4.2.2.2.19 The panel shall be designed such that field wiring from remote sensing head for Fire
& Gas may be terminated directly on the associated detection controller input
terminals, rather than interposing field wiring terminal blocks. All gas and fire
detection circuits shall be grounded as per recommendations of the manufacturer and
good engineering practices. All the detector circuit shields shall be grounded at the
same point as the signal circuit.
4.2.2.2.21 Suitably sized Terminals shall be provided for terminating main power supply cable.
The size shall be decided by the Contractor.
4.2.2.2.22 Internal Fluorescent lighting, working on 110V AC, 60 Hz shall be installed within
the panel to provide adequate lighting for maintenance of equipments. An On/Off
control switch shall be provided for this purpose in a surface mounted enclosure near
both the panel doors. The lighting fixtures must not interfere with doors or other
equipment, which must be accessible and space shall be provided for bulb
replacement. Thermal insulation must be provided, if necessary to prevent excessive
temperature rise in the panel surface of mounted equipment.
4.2.2.2.23 All major shut down alarms shall be repeated for output to a remote telemetry unit
(RTU). These outputs shall be in the form of SPDT volt free contacts and shall be
terminated separately in the panel at a convenient central location for further
connection.
OFFSHORE FUNCTIONAL SPECIFICATION VOL No III
DESIGN SECTION FOR FIRE & GAS DETECTION
MUMBAI REGION SYSTEM REV No 1
4.3.1.1 General
4.3.1.1.1 The Contractor shall produce a set of Cause and Effect diagrams during the design
stage reflecting the proposed location / action for review by the Company. Cause and
Effect diagram diagrams shall be as per API RP 14C requirements together with the
requirements of this specification.
4.3.1.1.2 All shutdown interlock and alarm circuits shall be designed to operate in a fail-safe
mode.
4.3.1.1.3 Fire & Gas logics shall be designed to de-energize to actuate gas / fire shutdown
interlock.
4.3.1.1.4 Alarms-
a) In addition to signaling on the F&G matrix and alarm annunciator, fire and gas
detection shall result in separate and distinct audible and visual alarms at Control
room / equipment enclosure room / field area. (Scheme- III)
c) For gas detection, distinct visual and audible alarms in the Control room shall be
provided for the two levels of detection. (Scheme- III)
d) Silencing of audible alarms shall not deactivate visual alarms until detection falls
below the alarm level.
e) Visual and audible alarms shall be different for each level of detection. (Scheme-
III)
f) Fire & Gas Detection system shall be suitably interfaced with platform DCS. DCS
shall have an over view graphic for each F&G zone. The graphic shall display
individual detector analogue value, alarm and fault status, and deluge valve and
extinguishant release status. A separate graphic will display the fire water pumps
run and fault status and fire water pressure. (Scheme- III)
OFFSHORE FUNCTIONAL SPECIFICATION VOL No III
DESIGN SECTION FOR FIRE & GAS DETECTION
MUMBAI REGION SYSTEM REV No 1
4.3.1.1.5 Detector Voting: Confirmed fire or gas-release shall be indicated by the following:
4.3.1.1.6 Distinct platform audio-alarm shall be provided for confirmed HC-H2 gas release,
confirmed H2S gas release, confirmed fire through paging system. Dry volt Free
Contacts shall be provided for the input signals.
4.3.1.1.8 All remote gas/fire alarm outputs shall be provided through paging system.
4.3.1.2.1 The control actions to be initiated upon fire and / or gas detection on wellhead-
platform are as follows:
Note: FSD (Fire Shut down) shall open deluge valves & activate fire water network.
4.3.1.3.1 The control actions to be initiated upon fire and / or gas detection on process platform
are as follows:
1. Alarm on DCS, Annuciators and Paging system, Indication on Fire & Gas
matrix.
4. Initiate ESD.
Note: FSD (Fire Shut Down) shall open blowdown valves and shall start firewater
pumps.
ESD (Emergency Shut Down) shall close all ESD valves, trip the main
generator set and start the emergency generator.
4.4.1 In Scheme- III installed spares shall be as per Spec. no. MR / OD / INST / FS / C101,
‘Functional specification for PLC’.
4.4.2 For installation, testing, commissioning of Fire & Gas detection system vendor shall
recommend and provide all the necessary spares. These spares shall be properly &
separately packaged with clear marking- ‘Commissioning Spares’.
4.4.3 Vendor shall include along with the proposal a separate priced list of recommended
spare parts for two years normal operation and maintenance. This list should take into
account related factors of ‘Fire & Gas detection system’ reliability, effect of
downtime upon normal operation & safety and availability of servicing facilities.
OFFSHORE FUNCTIONAL SPECIFICATION VOL No III
DESIGN SECTION FOR FIRE & GAS DETECTION
MUMBAI REGION SYSTEM REV No 1
4.5 Material
4.5.1.1 The Fire & Gas detectors shall have SS 316 sensor body housing material.
4.5.1.2 Enclosure for sensor electronics shall be copper-free marine grade Aluminum suitable
for offshore marine environment.
5.1 The protection requirements for the components of the Fire and Gas Detection System
shall in general be as per clause no. 3.6.4.4 of Instrumentation Design Criteria.
5.2 The fixed gas detectors shall be provided with manufacturer-approved rain hoods.
Shop fabricated rain hoods shall not be used.
5.3 The portable gas detectors shall be intrinsically safe for use in Class I, Division I,
Group B, C, D- T3 hazardous area.
6.1 The installation requirements for the components of the Fire and Gas Detection
System shall in general be according to clause 3.6.4.6 of Instrumentation Design
Criteria.
6.2 All detectors shall be installed such that they are easily accessible from a walkway or
access platform for calibration and maintenance. Where this is not possible, test tube
connections for detector calibration shall be provided.
6.3 All field equipment shall be readily accessible without the need to move other items
or equipment, except ceiling and floor tiles in the case of concealed detectors.
6.4 All components of the fire & gas detection system panel, which require regular
maintenance and / or monitoring, shall be easily accessible to the operations and
maintenance personnel with minimum wiring removal and no special tools.
7.1 Inspection category of Fire & Gas detection system is B. Equipment / items shall be
inspected by company representative only at final stages as per project finalized
documents viz. Purchase specification (s), applicable project documents, vendor
documents at vendor’s works, in addition to stage inspection by contractor and / or
third party inspection agency.
7.2 Calibration, inspection and testing requirements shall in general be as per clause
3.6.4.7 of Instrumentation Design Criteria. However, for specific requirements this
specification shall also be followed.
7.3 Prior to shipment from vendor’s works vendor shall carry out 100 percent testing of
hardware and software of Fire & Gas detection system.
7.4 After finalisation of testing procedures Vendor / Contractor shall notify to the
company one month before the scheduled date of testing of Fire & Gas detection
system.
7.5 Vendor / contractor shall provide complete documentation and facilities including
consumables to allow testing of Fire & Gas detection system.
7.6 The minimum requirements for testing of Fire & Gas detection system shall be:
e) Wiring check- visual check (type, size, segregation ferruling, etc), continuity test,
insulation test.
h) Functional check: Flame detectors- Each detector shall be subjected to testing and
shall be powered for a minimum of 2 hrs before testing.
j) Other field devices including Flashing beacons, sounder, etc shall be tested for
their functions.
k) Test all shutdowns in accordance with the ‘Cause and Effects diagrams’.
l) For ‘Loop testing / acceptance’ testing, ‘Panel’ inspection / testing, etc refer to
‘Design Criteria- Instrumentation’.
m) Fire & Gas detection system shall be subjected to elaborate ‘Factory Acceptance
Test’ (FAT) at vendor’s works. After successful installation system shall under-go
‘Site Acceptance Test’. For ‘Scheme- III’ vendor / contractor shall also refer to
Spec.no. MR / OD / INST / FS / C101, ‘Functional Specifications for PLC’.
n) The Contractor shall demonstrate the design life and overall system availability.
Full details of the operating design life of all major components that will be
subjected to planned maintenance / replacement during the life of the package,
shall be provided by the Contractor.
7.7 Responsibility of proper installation, site testing, commissioning of Fire & Gas
detection system shall be with the contractor. However, Fire & Gas detection system
vendor shall provide all the necessary assistance, supervision services, etc for
successful installation, site testing, commissioning of the system.
a) All fixed gas sensors shall be capable of direct calibration at the sensor head by
one person from deck level or from a fixed platform, without the need to open the
detector enclosure.
b) A kit shall be provided for detector calibration and testing. Tubing to conduct
sample to the sensor head shall be provided.
d) Calibration of all detectors shall be possible either from remote location or via
hand-held calibration tool, without disconnection of any equipment or cables. On-
OFFSHORE FUNCTIONAL SPECIFICATION VOL No III
DESIGN SECTION FOR FIRE & GAS DETECTION
MUMBAI REGION SYSTEM REV No 1
e) Gas detectors installed inside HVAC ducts shall be provided with collecting cones
and a facility to calibrate the gas detectors externally from the ducts without
disturbing the installation.
a) Kits for testing and calibrating the fire detectors shall be provided.
b) All fire sensors shall be capable of direct calibration at the sensor head by one
person from deck level or from a fixed platform.
8.1 The Contractor shall submit complete QA / QC plans for the proposed Fire & Gas
detection system for Company’s review.
8.2 The vendor, and his sub-vendor, shall operate a quality system satisfying the
applicable provisions of ISO 9000 (series). A detailed quality plan shall be provided
with the bid.
8.3 The company reserves the right to carry out quality and technical review at both
vendor’s and sub-vendor’s works.
9.0 DOCUMENTATION
9.2 Specifically for Fire & Gas Detection system following minimum documents shall be
submitted:
Type of
S.N. Document Name
Document
Following documents shall be generated by the contractor and shall be included in
main DCI of the project. These documents shall be provided to the vendor to aid
design & engineering of Fire & Gas detection system.
1 F & G detectors, other field devices layouts. FR
2 Cause & Effect diagrams. FR
3 System I / O listing / point configuration database FI
OFFSHORE FUNCTIONAL SPECIFICATION VOL No III
DESIGN SECTION FOR FIRE & GAS DETECTION
MUMBAI REGION SYSTEM REV No 1
Notes:
FR For ONGC Review
FI For ONGC Information
OFFSHORE FUNCTIONAL SPECIFICATION VOL No III
DESIGN SECTION FOR FIRE & GAS DETECTION
MUMBAI REGION SYSTEM REV No 1
9.3 For other PLC related documents refer to Spec .no. MR / OD / INST / FS / C101
9.4 Purchase specification shall cover all the details as indicated in ‘Design Criteria-
Instrumentation’. Beside these details indicative formats of the documents 6, 7, 9, &
18 (typical only for each type of detector, field devices, etc.) shall also be
incorporated in the proposal / purchase specification.
10.1 Tagging & Nameplate requirements shall in general be according to clause 3.6.6.1 of
Instrumentation Design Criteria.
10.2 For the purpose of tagging field devices including detectors, manual alarm stations,
flashing beacons, sounders, etc following philosophy shall be used:
11.1 Review and approval of purchase specification shall in general be according to clause
3.6.6.3 of Instrumentation Design Criteria.
11.2 F & G detection system related detail engineering documents categorization shall be
as per Cl. No. 9 (including its sub-clauses) of this specifications.
13.1 The components of the Fire and Gas Detection System shall be prepared for shipment
in accordance to clause 3.6.6.5 of Instrumentation Design Criteria.
14.1 Receipt and storage of the components of the Fire and Gas Detection System shall be
in accordance to clause 3.6.6.6 of Instrumentation Design Criteria.