Chillers Brochure
Chillers Brochure
Chillers Brochure
Applications
• Laser Technology • Coating Systems • Food & Beverage
Features inlcude:
• Removable tank & condenser • Full frontal access for easy maintenance
Maximum Efficiency
Maximum efficiency can be achieved through the energy saving components to reduce
power consumption.
Features include:
• Compliant scroll compressor ( ICEP007 & above ) • Economic design
Precision Control
Advanced onboard control unit helps to control the water temperature.
Features include:
• Low water velocity • Adjustable programming (ICEP015 & above)
Reliable Operation
Sullair Water Chillers offer an all-in-one package capable of operating continuously in all
conditions of varying applications. They can accept water inlet temperatures up to 30C and
can deliver outlet temperatures down to 0C, capable of achieving as much as 15C difference in
temperatures.
Features include:
• Condenser pre-filter (ICEP007 & above) • Extensively tested for quality assurance
ground.
Specifications
Correction factors
1. At water in/out temperature = 20/15 °C, glycol 0 %, either 25 °C ambient temperature (air-cooled models) or 25 °C condenser water inlet temperature with 35°C
condensing temperature (water-cooled models).
2. At water in/out temperature = 12/7 °C, glycol 0 %, 32 °C ambient temperature (air-cooled models).
3. Referred to axial fan version in free field conditions at a distance of 10m from unit, measured on condenser side, 1m from ground.
C) Glycol % 0 10 20 30 40 50
correction factor (f3) 1 0,99 0,98 0,97 0,96 0.94
D) Condenser water inlet temp. °C 20 25 30 35 40 N/A
(water-cooled models)
correction factor (f4) 1,05 1 0,95 0,9 0,85 N/A
To obtain the required cooling capacity multiply the value at nominal conditions by the above correction factors (i.e. cooling capacity = Pxf1xf2xf3xf4, where P is the cooling
capacity at conditions (1)). Sullair Water Chillers, in their standard configuration, can operate up to ambient temperatures of max 45 °C and min. 5 °C and water temperatures of
max 30 °C inlet and min. 0 °C outlet. The above correction factors are approximative: for a precise selection or higher capacities, refer to Sullair’s Sales Specialist.