Foundation Check: Considering The Whole Area

The document summarizes a foundation check calculation for a proposed 8-story building at Jeddah Airport. Floor loads were calculated based on architectural drawings. Total building load was determined to be 168,530 kN. Spread over a 1006 sqm raft foundation, pressure on soil is 167.4 kPa, less than the allowable 200 kPa based on geotech report. Therefore, a raft foundation without piling is sufficient to safely carry the building loads. Isolated column footing sizes were also checked and found adequate with areas of 37.8 sqm and 15.9 sqm for interior and exterior columns respectively.

Uploaded by

rey
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
163 views

Foundation Check: Considering The Whole Area

The document summarizes a foundation check calculation for a proposed 8-story building at Jeddah Airport. Floor loads were calculated based on architectural drawings. Total building load was determined to be 168,530 kN. Spread over a 1006 sqm raft foundation, pressure on soil is 167.4 kPa, less than the allowable 200 kPa based on geotech report. Therefore, a raft foundation without piling is sufficient to safely carry the building loads. Isolated column footing sizes were also checked and found adequate with areas of 37.8 sqm and 15.9 sqm for interior and exterior columns respectively.

Uploaded by

rey
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 4

Project Name: Ministry of Housing: Jeddah Airport

Structural Element: Footing


SAUDI ARABIAN PARSONS Subject: Foundation Check- Page:
LTD
Cals by: Harish/Roy Checked By: Date: Jul-18
Foundation Check : Considering the Whole Area
Load calculation for Jeddah Airport site Building:
As per the architecture drawing sent by developer the building is G+7+Roof
(total 8 rcc slabs) structure.

Calculation of Floor Area


Gross Area (Typical Floor) (A) = 1078.6 Sq.m
Area of Skylight (B) = 43.4 Sq.m
Net Area (A-B) = 1035.2 Sq.m
No. Floors = 8 Floors
Total Loaded Area = 8281.6 Sq.m

Calculation of Area Load


Slab Selfweight 200 mm thick = 5.00 kN/sq.m (kPa)
Partition = 1.00 kPa
False Ceiling = 0.50 kPa
Floor Finish = 1.20 kPa
Wall Load = 6.00 kPa
Beam Weight = 1.40 kPa
Col + Wall = 1.40 kPa
Live Load = 2.00 kPa
Total Area Load = 18.50 kPa

Total Load of all floor (P) = 153209.6 kN


with Allowances (add 10%) = 168530.56 kN

Area of Raft Considered (A) = 1006.51 Sq.m

Pressure Exerted by Building on Soil = P/A = 167.4 kPa


Allowable Soil Bearing
Based on Approved Geotech Report = 200 kPa > 167.4 kPa

Conclusion:
There is no need to go for piling as raft foundation is sufficient to carry the load safely to soil.

Raft Area :
1006.51 Sq.m

Typical Floor
1078.6 Sq.m

Skylight Area
43.4 Sq.m
Project Name: Ministry of Housing: Jeddah Airport
Structural Element: Footing
SAUDI ARABIAN PARSONS Subject: Foundation Check- Page:
LTD
Cals by: Harish/Roy Checked By: Date: Jul-18
Foundation Check : Considering the Whole Area
Project Name: Ministry of Housing - Jeddah Airport
Structural Element: Footing
SAUDI ARABIAN PARSONS Subject: Foundation Check- Page:
LTD
Cals by: Checked By: Date: Jul-18
Foundation Check For Isolated Footing
Column Load
Interior Column Tributary Area Considered = 48 Sq.m
No. of Floors = 8 Floors
Live Load = 2 KPa
SDL (Finishes, MEP Allowances) = 3 KPa
Dead Loads
Slab = 200 x 24 = 4.8 KPa
Allowance for CMU = 6 KPa
= 15.8 KPa = 758.4 KN

Columns = 1100 x 300 x 3.5 x 24 = 27.72 KN


Allowance for Beams = 300 x 500 x 20 x 24 = 72 KN

Total Service Load (DL + SDL + LL) = 858.12 KN


Total Loads x Number of Floors = 6865 KN
10% Increase (Allowance) = 7551 KN

Considered Soil Bearing Capacity = 200 KPa


Footing Area = 37.757 Sq.m
Length = 6.1 m

Exterior Column Tributary Area Considered = 18.9 Sq.m


No. of Floors = 8 Floors
Live Load = 2 KPa
SDL (Finishes, MEP Allowances) = 3 KPa
Dead Loads
Slab = 200 x 24 = 4.8 KPa
Allowance for CMU = 6 KPa
= 15.8 KPa = 298.62 KN

Columns = 1100 x 300 x 3.5 x 24 = 27.72 KN


Allowance for Beams = 300 x 500 x 10 x 24 = 36 KN

Total Service Load (DL + SDL + LL) = 362.34 KN


Total Loads x Number of Floors = 2899 KN
10% Increase (Allowance) = 3189 KN

Considered Soil Bearing Capacity = 200 KPa


Footing Area = 15.943 Sq.m
Length = 4.0 m
Project Name: Ministry of Housing - Jeddah Airport
Structural Element: Footing
SAUDI ARABIAN PARSONS Subject: Foundation Check- Page:
LTD
Cals by: Checked By: Date: Jul-18
Foundation Check For Isolated Footing