E Tool and Corrigo Web (User Manual)
E Tool and Corrigo Web (User Manual)
E Tool and Corrigo Web (User Manual)
User manual
DISCLAIMER
The information in this manual has been carefully checked and is believed to be correct. Regin however, makes no warranties
as regards the contents of this manual and users are requested to report errors, discrepancies or ambiguities to Regin, so that
corrections may be made in future editions. The information in this document is subject to change without prior notification.
The software described in this document is supplied under licence by Regin and may be used or copied only in accordance
with the terms of the licence. No part of this document may be reproduced or transmitted in any form, in any fashion,
electronically or mechanically, without the express, written permission of Regin.
COPYRIGHT
AB Regin. All rights reserved.
TRADEMARKS
Corrigo E, E tool, EXOdesigner, EXOreal, EXOline, EXO4, EXO4 Web Server, Optigo, Regio and Regio tool are registered
trademarks of AB Regin.
Windows, Windows 2000, Windows XP, and Windows Server 2003 are registered trademarks of Microsoft Corporation.
Some product names mentioned in this document are used for identification purposes only and may be the registered
trademarks of their respective companies.
This manual covers E tool for both heating (E tool Heating), ventilation (E tool Ventilation) and
boiler control (E tool Boiler).
This manual is designed to be an aid during installation and use of E tool. It describes all the
functions unique to the program. The Corrigo E control parameters however are not described here.
For detailed information on these, please see the manual for the controller and application in
question.
News
From version 3.1, the access level System has changed name to Admin, see page 8.
Regin Building Access, (Android application): From version 3.0-1-06 of the ventilation application
and version 3.0-1-02 of the heating application, you can communicate with the controller from an
Android phone. This is done via an application (app) which is free of charge and can be ordered
from Regin or downloaded from Google Play. There are two applications, one for ventilation and
one for heating. See chapter 13 for more information.
To install and run E tool you need a PC running Windows 2000, Windows XP, Windows Vista or
Windows 7.
To run Corrigo Web, you need Internet Explorer 7.0 or later and Java.
To communicate with a Corrigo you need a special communication cable, E-Cable.
E tool is delivered as a self-installing program on a CD, or can be downloaded from Regin’s website
(www.regin.se).
Load the CD and follow the on-screen instructions, or download the program folder from
www.regin.se. Unzip the folder and run the setup.exe file, which you will find in the unzipped
folder.
E tool Heating, E tool Ventilation and E tool Boiler are Windows-based PC-programs for
configuration and maintenance of the various Corrigo E series controllers.
E tool has not been designed with the intention of being a full SCADA program.
The installation program will have placed a Corrigo E tool folder in the Programs folder in the Start
menu. This folder contains the links to E tool Heating, E tool Ventilation and E tool Boiler.
To start either program, click on the Start button at the lower left hand corner of the display. Then
click on Programs, the folder Corrigo E tool and finally the program you wish to run.
To avoid having to go through the Start folder, you can create a shortcut on the desktop by pointing
at the program name, click and hold the right hand mouse button and drag the program name from
the folder onto the desktop. Release the button and click on "Create shortcut here".
On start-up E tool will automatically search for any controller connected to the computer and
connect to it if it is of a type suitable to the program being loaded. If no suitable Corrigo controller
is found the program will start offline.
E tool always starts with a box where you enter which Corrigo model you are using. The Overview
folder is also displayed. Make sure that you enter the correct model, or strange things may occur in
the control and alarm handling.
The menu bar has five drop-down menus; File, Edit, View, Tools and Help.
5.1 File
These items are used to handle configuration files. The data describing a configuration can be saved
as a file. Any number of different configurations can be saved, the only limit being available disk
space. The file will have a .vtc extension for ventilation, .htc for heating and .btc for boiler control
and needs about 22 kb of disk space. The files are pure text files and can be opened using regular
editing programs like Notepad or WordPad.
New
New will open a new unnamed file. A box appears where you choose the model of your Corrigo. If
you are unsure which model you are using, you will find the article number on the right short side of
the controller. Make sure that you choose the correct model. If you load an incorrect model in a
Corrigo, unexplainable alarms etc. may appear since certain functions can be activated that are not
visible in the present model.
Open
Opens a saved file.
Save
Saves the current file to disk. If the file is unnamed you will be prompted for a name.
Save as
Saves the current file to disk using a new name of your choice.
Read only
This item can normally be ignored. Should you for some reason open two instances for the same file
one of them will be marked as Read only to prevent data conflict.
Print
Will give a printed list showing all the configuration settings of the present file.
5.2 Edit
The edit menu only contains one item:
Delete
Delete is only used in conjunction with Holiday periods. Use delete to remove assigned periods.
5.3 View
The view menu contains one item.
Refresh
E tool is not a dynamic program. If a parameter value is changed in a connected Corrigo, for
example a temperature, the corresponding value in E tool will not automatically be updated. The E
tool user must initiate reading of parameter values from the controller.
Update initiates a reading of all dynamic parameters from the connected controller. The display is
updated with the new values.
When you change between display tabs, an update is automatically initiated.
Alternatively, the Update button in the Toolbar (see Toolbar below) or the F5 key on the computer
keyboard can be used.
You can choose to auto refresh pictures with dynamic values, i.e. an automatic finger that presses
F5 at settable intervals. See ”Options” on page 9.
If the controller revision is older than the E tool revision, you are asked what you want to do to
make them compatible. See section 9.
Upgrade operating system for web server (only shown for Corrigo
Web)
Unless the Corrigo is brand new it is advisable to upgrade the TCP/IP operating system.
Log on
Corrigo E has four different log-on levels, 1, 2, 3 and 5.
5 is the basic level with the lowest access, 3 is the operator level giving more access, 2 is the service
level giving even more access and 1 is the Admin level with full access.
E tool only uses the levels Normal, Operator and Admin.
As default Corrigo comes with the following passwords for the different levels:
Admin 1111
Service 2222
Operator 3333
Normal 5555
Should you try to perform an operation which requires a higher access level than the one you have,
you will be prompted to change log-on level.
Log off
Is only active if you are logged on as Operator or Admin. Enables log-off to the basic level.
Change password
Is only active if you are logged on as Operator or Admin. Permits change of the password for the
present log-on level.
To be able to load new default passwords, change LoadDiaPassWordVisible from ”No” to ”Yes”.
Change ”1111”, ”2222” and ”3333” to the values you want the levels Admin, Service and Operator
to have. ”4444” is not used by Corrigo and ”5555” for basic level should not be changed.
Save the vtc-file.
Start E tool and import the file. When downloading parameters to the Corrigo, a checkbox is shown
which you can check if you want the passwords to be downloaded.
Creates a real time chart. Up to four parameters of your choice can be logged. The chosen
parameters are listed at the bottom of the screen together with information on colour, which of the
vertical scales it is referring to and latest recorded value. The chart has left and right vertical scales
with individually settable ranges. The horizontal timeline can be changed so that the chart window
can show longer or shorter intervals. Using the scrollbar at the bottom of the chart you can scroll
along the timeline to show any position since the recording started. Values are recorded every 5
seconds. All recorded values can be saved to a textfile for later use in, for example, a spread-sheet
program.
Several sessions of the real-time chart can be run at the same time if you wish to study more than
four parameters.
The chart cannot be saved. On exiting all values and settings are lost.
Export
Exports all recorded values to a .txt file. The values are tab-separated for easy import to, for
example, Excel. Each line of the text file contains the values from one recording together with the
time for the recording. Recorded data are saved for approximately 24 hours.
Add curves
A click on this button reveals a list of all Corrigo parameters that can be displayed in the chart.
Choose up to 4 parameters.
Show nodepoints
A marker can be displayed on each curve at the point of each recording.
Show cursor
Displays a vertical line on the chart display. The cursor can be moved along the timeline. When the
cursor is active, instead of showing the latest recorded values in the parameter list, the values at the
cursor position are displayed. In this way you can check back on earlier record values.
Go to home
Home position is the chart position where you have the "recording pens" close to the right hand
edge of the chart. If you have scrolled back along the timeline you can use this button to jump back
to normal position.
Pause
Pauses the chart. The "paper" stops scrolling and no new curve segments are added. Data
acquisition continues, however, and new readings are saved every 5 seconds. Press Pause again and
all the saved readings will be added to the chart.
Options
Set various options.
Time scale
Sets the time width of the chart display.
The parameter list shows the parameters assigned to the chart. To remove a parameter, right-click
on it and choose remove.
To change which of the right / left scales the parameter curve is referring to, right-click and choose
properties or double-click with the left mouse-button.
Notes
Gives access to a notepad area. Any text written here is saved together with the configuration file. If
you make a printout of the configuration the notepad text is included in the printout.
Options
Permits the setting of some program parameters.
You can choose to auto refresh pictures with dynamic values, i.e. an automatic finger that presses
F5 at settable intervals.
Log-on timeout
After inactivity for longer than the set time the log-on level will be set to 5.
Number of decimals
Sets the number of decimals displayed. All calculations however, are always done with full
precision.
Lock configuration
Blocks access to the configuration tab.
Communication
Setting of the communication between E tool and controller.
Which communication is suggested depends on which Corrigo model has been loaded into E tool at
start-up. Serial communication is suggested for all models except Corrigo Web.
Check that the suggested Com port corresponds to the Com port which the computer has assigned to
E-cable. You can see which Com port has been assigned in the Control panel / System / Device
Manager / Ports (COM & LPT).
If you have opened E tool with a Corrigo Web, you can choose if the communication should take
place via E-cable (serial) or via the TCP/IP port.
3. Static IP address
In this case, the static IP address of the controller is specified.
This configuration is most suitable for networks without a DHCP Server. You can also use it if you
do not trust the network services completely, as it is the communication that has the best
qualification to work when servers etc. do not. As long as routers and switches work well, this
configuration alternative will work.
The following requirements have to be fulfilled: The EXOline-TCP port, 26486, must be open from
the controller to the main computer. This is especially important when the communication passes
through a firewall.
You get the static IP address, Net Mask and Default Gateway from the network administrator.
5.5 Help
Gives access to help texts and revision information.
By placing the cursor over a tool icon a tool tip will be displayed giving a short description of the E
tool.
All the E tools except for Refresh have been described in the menu bar description above.
7.1 General
The contents of the various folders depend on which of the programs E tool Heating or E tool
Ventilation you are running and also on which Corrigo model, E28, E15 or E8 the program has been
configured for.
Therefore the contents will not be described in detail here.
Items in a folder that somehow belong together are grouped. Group names are displayed in bold.
The groups are normally shown expanded, that is that all the items in the group are displayed,
headed by the group name. A group can be compressed to show only the group name by clicking on
the box with a - (minus) to the left of the group name. For a compressed group the box will contain
a +. Click on it to expand the group.
Setting values
Many of the folders contain settable values. If you pass the cursor over such a value a text box (tool
tip) will be displayed showing the permitted value interval.
If you have a Corrigo connected you must download a value to the Corrigo for it to become active.
Downloading can be done in several ways:
Right-click on any single item and choose Load parameters. This will download only that single
parameter.
Right-click on a group name and choose Load parameters. This will download all parameters in
the chosen group.
Click on the Load all parameters button on the E toolbar.
Click on Tools on the Menu bar and choose Load all parameters.
These last two methods will, as the name implies, download all parameters to the Corrigo.
You can also synchronize parameters following the same rules as above but choose Synchronize
parameters. A useful tool to compare the settings in the Corrigo with the settings in E tool.
It is also possible to reset parameters to default values by right-clicking and choosing Reset
parameters to default values.
The major part of the Overview folder displays a process diagram. The diagram is a static bitmap
illustration that can be edited using, for example Paint. Any number of different diagrams can be
saved. Which diagram is displayed is governed by the setting of the parameter Process picture in
the System subfolder in the configuration folder.
Down the left-hand edge of the Overview folder there is a list of the most important control
parameters. To update the values, press F5 or click on the refresh button in the E tool bar. You can
choose to auto refresh pictures with dynamic values, i.e. an automatic finger that presses F5 at
settable intervals. See Options on page 9.
Displays consumption values for energy meter, heat water meter and cold water meter. The values
are calculated using pulse constants that are set in the submenu Pulse constants in the configuration
folder.
Alarm categories
Corrigo has three alarm categories, Sum alarm A, Sum alarm B and Sum alarm C.
A and B alarms will activate the digital outputs A-alarm and B-alarm respectively if configured.
Both will activate the Sum alarm output if configured.
C alarms are internal only.
C alarms need not be acknowledged. Once they reset, they automatically return to normal status.
Alarms can be shown according to class: A, B, C or All classes, and according to status: Normal,
Blocked, Acknowledged, Returned, Alarm active and All statuses.
The alarm text, including any possible space, may not consist of more than 38 characters. These will
be distributed on 2 rows of 19 characters each. If a word in the text goes over the 19th position, the
whole word will be moved to the second row. To avoid this you can add a hyphen in the 19th
position, thereafter space and then the rest of the word.
Example: ”Sensor error Relative Humidity supply air” consists of 40 characters, but since the third
word goes over the 19th position, the following will be shown in the display:
Sensor error
Relative Humidity su
9 Sept 08:52 Class B
7.6 Inputs/Outputs
E tool Ventilation
Here you set the daily running periods.
If single-speed fans have been configured there is only one set of daily schedules.
If two-speed or pressure controlled fans have been configured there will be two sets of daily
schedules. One for normal running speed and one for reduced speed.
For each day there are two periods.
Should the running periods for normal and reduced speed overlap, normal speed will take
precedence.
The 8th day, Holiday, governs the activity on all days marked as holidays in the holiday schedule,
see below.
The schedules for Timer channel output 1…5 dictate the activation of the corresponding digital
output signal.
To deactivate a period, set the time to 00:00 – 00:00.
To run the unit 24 hours a day, set the time to 00:00 – 24:00.
Note: An interval cannot exceed over midnight. For example, if you want to configure a period from
18:00 to 02:00 , you have to divide it into two periods: Day 1 18:00 – 24:00 and day 2 00:00 –
02:00.
Holiday schedule
Up to 24 separate holiday periods can be configured. A holiday period can be anything from one
day up to 365 consecutive days.
To create a holiday period, click on the button at the right hand end of the line Add holiday period.
7.8 Settings
Controller settings
Setting of the control parameters.
Parameter setting-interval endpoint values and default value are displayed if you place the cursor
over a parameter value.
Changes must be downloaded to the controller in order to take effect.
To download, right-click on a parameter name or a parameter group name and choose Load
parameters, or click on Load all parameters in the E toolbar or the E tool menu.
However, if you change the text to: “Sensor error RH supply air”, you will get:
Sensor error RH
Supply air
9 Sept 08:52 Class B
In this menu you can take manual command of most controller functions. Very useful for testing
purposes.
Setting functions to manual command will generate alarms to ensure that control is returned to
Auto.
In this menu all changes are instantly downloaded to any attached controller, it is not necessary to
run Load parameters for changes to take effect.
This folder contains all the configuration parameters for the Corrigo. Since the contents are very
diverse, the folder has been divided into sub-folders. These are accessed by clicking on the buttons
in the left-hand button-list. For detailed information on these, please see the manual for the
controller in question.
From version 3.0, one/two expansion units can be connected to Corrigo E. This requires a controller
with two ports. Any Corrigo E model can be used as expansion unit. However, since the display will
not show anything, a Corrigo E without display is normally selected.
Set ”Function port 2” to ”Expansion units” and choose under Configuration/System which
controllers you want to connect. Connect them thereafter to the computer. Depending on what has
been configured, ”Initiate Expansion unit 1” and/or ”Initiate Expansion unit 2” will be shown under
Tools. This initiation function is used for Corrigo E models which are not factory loaded with
version 3.0.
For controllers that are factory loaded with version 3.0, you can select ”Expansion unit 1” or
”Expansion unit 2” under Application choices in the controller. In this case, E tool is not required to
set the controller as an expansion unit.
After initiating the expansion controllers and configuring the program, all Corrigo E units are
connected. Then the master unit is connected to the computer via port 1 for the configuration to be
loaded. The controller is configured in the same way as described in chapter 8.
E tool should always be updated with the latest program revision. If you are using the latest revision
of E tool and connect it to a Corrigo E with an older program revision, E tool will give a warning
and offer two alternatives.
One alternative is to temporarily downgrade E tool to a revision corresponding to the revision in the
controller. All the settings in the controller will remain intact and the controller will keep its
revision.
The other alternative is to upgrade the controller to the same revision as E tool. This will cause the
Corrigo-unit to temporarily stop working. Any previous settings will be permanently lost.
Take the following actions to avoid having to configure again:
Start E tool and connect it to the controller. When asked, choose to downgrade E tool to the
controller’s revision.
Select Synchronize all parameters in the menu Tools. Then select Update tools. E tool should now
contain an exact copy of the configuration in the controller. Select Save as in the menu File and save
the configuration under a suitable name.
Close E tool. Then open it again and choose to reload the controller with a new revision.
After reloading, open the saved configuration file, synchronize all parameters and the select Update
the controller. The controller should now have the latest revision and be configured as it was before
the upgrade. Make sure that the settings of the parameters that were not available in the old revision
have suitable values.
IP network
An IP network is a cluster of cables and devices, where an equipment with one IP address can
communicate with any other IP addressed equipment. Internet is one network, and when your home
computer connects to the Internet, you become part of the Internet.
Subnet
Networks are divided into subnets, which are linked with routers. Routers need some kind of map
of the network (or at least of the closest subnets, and somewhere to send everything else). A
computer only needs to know the address of the closest router. A local switched Ethernet network is
one subnet. Routers can have several Ethernet ports for different Ethernet networks, or maybe an
Ethernet port and an ADSL connection.
IP address
Each computer or network connected controller has an IP address consisting of four numbers
between 0 and 255, which makes up a total of 32 bits.
Subnet mask
Each computer or network connected controller also has a subnet mask consisting of 32 bits.
Example
If the IP address is 192.0.2.73 and the subnet mask is 255.255.255.0, then the subnet addresses are
from 192.0.2.0 up to 192.0.2.255, and 192.0.2.73 is your address on the subnet. Sometimes the
subnet mask is specified by the number of bits used (always starting at the beginning of the subnet
mask). The subnet is then 192.0.2.0/24, and the IP address and the subnet mask can also be
specified together: 192.02.73/24.
Default Gateway
Each computer and each controller using TCP/IP communication must know the IP address to the
router that goes out from its subnet. The IP address of this router is usually called the default
gateway. All traffic that shall be sent out of your own subnet is sent to the default gateway.
DNS name
The computer or the controller must know the address of the equipment it is going to communicate
with. This can be given as an IP address or a DNS name. DNS is a name service which can translate
hierarchical names like exohuvuddator.regin.se to an IP address. Several DNS servers are
part of the system, but you only have to know the IP address to one of them.
Dynamic IP addresses
The use of dynamic addresses presents a problem when other equipments try to contact the
equipment, as the dynamic addresses are unknown in advance and are subject to change. To be able
to contact equipment using dynamic addresses, your equipment need to use DNS, which also has to
be updated when the dynamic address is changed via DHCP. This is commonly used in corporate
networks and for Windows computer. However, most Internet Service Providers and several types
of EXO controllers do not support the DNS update via DHCP, and must therefore use a static IP
address.
Black addresses
There is a shortage of IP addresses on the Internet and organizations are encouraged to use internal
IP addresses on internal networks. Different companies may use the same address series, as their
internal work computers never really need to connect directly to each other. This kind of addressing
is called private or black addressing.
Reserved addresses
The following addresses are reserved for private nets:
192.168.0.0 - 192.168.255.255
172.16.0.0 - 172.31.255.255
10.0.0.0 - 10.255.255.255
See also: RFC1918, Address Albcatton for Private Internets [Online document], [cited Nov 29
2005], Available HTTP: http://www.ietf.org/rfc/rfc1918.txt
White addresses
Addresses that are unique on the Internet are called public or white adresses. More information of
the use of IP addresses can be found on RFC3330, Special-use, IPv4 addresses,
http://www.ietf.org/rfc/rfc3330.txt
NAT
Firewalls can act as agents for computers with private IP addresses, when they are searching the
Internet for information. A connection from a computer with a black IP address is transformed into
a connection from the firewall (which has a public IP address) to the Internet server. The Internet
server may then return the information to the firewall which forwards it to the computer with the
black address. This is called NAT or masquerading.
NAT router
You can also have a NAT router to forward traffic from the white net to a computer on the black
net. This is accomplished by letting traffic to a specific TCP port or UDP port to be forwarded to an
IP address on the black net.
EXO controllers
There are Internet Service Providers that target, e.g. housing co-operatives, offering only private
dynamic addresses. EXO controllers with a TCP/IP port can manage controllers connected this way,
provided that the main computer has a static or a DNS registered public address. The EXO system
can also manage the reverse condition, and allows a main computer with a private address to contact
controllers with public addresses.
10.5 Tunnels
PC – black network
A tunnel can also be created between a single computer and a private network. Nowadays, it is
common for travelling salesmen to connect their mobile stations via GPRS and the Internet, and
then connect to the company network using a tunnel. The same technology can be used by the duty
technician to work with the ÉXO4 work station from his home, from the service vehicle or similar.
11.1 Connection
The controller must be connected to a static, white IP address. The following connection methods
have been tested for Corrigo Web:
Connection directly to an ADSL/cable modem
Connection to a router, which in turn is connected to an ADSL/cable modem
Corrigo Web has not been tested with all Internet suppliers.
If the Corrigo is to be located behind a router with a built-in firewall, the router must be configured.
The router should have a fixed white IP address. Then it must find the Corrigo, either by sending an
IP address to the controller or by giving the Corrigo’s MAC address. Thereafter, all incoming traffic
on Ports 80 and 26486 should be NAT routed to the Corrigo’s black IP address. See the router
manual for this.
Ports 80 and 26486 on the internet modem must also be open for incoming traffic.
This webserver technology is built into the Corrigo and is based on the fact that the Corrigo has an
integrated webserver. Using NAT-routing, you can also connect more than one web server behind
the same white IP.
A Corrigo E can handle max. 5 connections from E tool, EXO4 and Internet Explorer at a time.
Then go to Tools/Load Web-site to the Controller to load the unit with the new setting. If using a
third Corrigo, it can for example be set to communicate EXOline on port 26001.
34 Chapter 11 Corrigo Web (only E tool Ventilation and Heating) E tool manual
The example below visualises the communication routes in a router which has been set to NAT
routing to two Corrigo. The same pattern is followed if the number of Corrigo units is three, four,
five, and so on.
White IP
If you (as in the example) want to access the unit with black IP, 192.168.0.30, in the web browser of
the client computer, you must enter the white IP or DNS of the router followed by ”:81” in the
address field of the web browser. Then the web server in the Corrigo will send back information on
the layout of the website to the client computer (through the same NAT routing). It will also open a
Java application in the client computer which, among other things, controls the EXOline
communication.
The router settings in the example may differ depending on the manufacturer. See the example
below for guidance.
E tool manual Chapter 11 Corrigo Web (only E tool Ventilation and Heating) 35
11.3 Configuration of the webservers
As before, all configuration of the controller parameters takes place via E tool or directly in the
display. No configuration can be done via the webserver. For configuration of the controller, see the
previous chapters in this manual or the manuals for Corrigo E heating and ventilation respectively.
If the configuration of the controller’s parameters is changed, the website is automatically
downloaded to the webserver. You only need to refresh the website if the settings for the website
are changed.
IP settings
Here you choose if the Corrigo should have a static IP address or if the DHCP server should give it
a dynamic IP address.
If the TCP/IP port uses fixed IP and you have given the e-mail server’s network name, you must
also enter a DNS server under Use the following IP settings. The TCP/IP port can then translate the
network name into an IP address. If DHCP is used, this will take place automatically.
DNS name
The Corrigo can be connected to a DNS name, for example: DNS name: Corrigoweb, Domain:
regin.se. The controller’s IP address will then be connected to the DNS name Corrigoweb.regin.se.
36 Chapter 11 Corrigo Web (only E tool Ventilation and Heating) E tool manual
Encrypted communication
The encryption is used to prevent other users in the TCP/IP network from connecting to the Corrigo
via E tool.
The password is only used when you want to reach the Corrigo via E tool. If you loose the
password, the controller must be cleansed and reloaded.
Headline Web-site
Here you can write a headline which should be shown on the first page when you surf to the Corrigo
website.
E tool manual Chapter 11 Corrigo Web (only E tool Ventilation and Heating) 37
Link, Heading
Up to four different links to small pdf files or other Internet sites can be added to the website. Note:
The total size of the pdf files and the process picture must not be over 150 kB. Under Link1,
Heading you write the heading for Link 1, under Link2, Heading you write the heading for Link 2
and so on. The heading must not contain any space. Instead of for example AB Regin, you must
write AB_Regin. This is the default setting for Heading 4.
Link
Under Link 1 you write the address to the pdf file or Internet site.
Process picture
The picture that is chosen here will be shown in the Overview folder on the web. The picture should
be in jpg format or similar because of the lack of storage space.
E-mail
Here you give the e-mail address to which an alarm should be sent, as well as the titel and subject of
the message.
After making the above settings and downloading the settings to the TCP/IP card, the only thing that
remains is to download all the settings to the webserver in the Corrigo. You do this by selecting
Tools/Load Web-site to the Controller.
38 Chapter 11 Corrigo Web (only E tool Ventilation and Heating) E tool manual
11.5 Log on to the website
This is how the login page for the Corrigo looks when it is published on the web.
In the box Password, you log on using the password you have entered under TCP/IP, WEB-site and
E-mail settings.
All values written in blue can be changed. As soon as a value has been changed and you have
pressed Enter, the value is downloaded to the Corrigo.
E tool manual Chapter 11 Corrigo Web (only E tool Ventilation and Heating) 39
Real time charts in Corrigo Web
A new feature, introduced from version 3.0 and on, is the option to handle real-time charts in the
website. The operator may use the “Copy to clipboard” command in order to copy the values
currently displayed in the diagram (as tab-separated text, TSV). This text may then be pasted into,
for instance, Excel.
When the Copy to clipboard command is excecuted, a dialogue window is opened in which the
resolution for the values about to be copied can be selected. The following alternatives are
available: 1 hour, 15 minutes, 1 minute and 5 seconds. The most suitable alternative is pre-chosen in
consideration to the current interval in the diagram.
When copying takes place, a title row is first created, followed by a row for every period (using the
selected resolution) for the time range and signals currently displayed in the diagram.
The title row consists of a date, followed by the titles of the various signals with units (within
parenthesis).
The additional rows consist of a time, followed by values for the various signals (with the
configured amount of decimals but with no units).
Date, times and decimal points are written in a national format, in accordance with the settings of
the computer running the web browser.
For time periods for which values are missing (or are not applicable), the value will be empty
strings.
Example
2008-05-22 Outdoor temperature (°C) Supply temperature (°C)
12:23:00 17.3 25.6
12:24:00 17.7 25.6
12:25:00 18.2 25.6
40 Chapter 11 Corrigo Web (only E tool Ventilation and Heating) E tool manual
Chapter 12 Regin Building Access – Mobile
application
12.1 Introduction
Regin Building Access is a general application for the operating system Android which can be used
for an operator to access a Corrigo at a time via TCP/IP (via e.g. a mobile network or a Wi-Fi
network). Once connected, you can view values, alarms, documents, etc. from the Corrigo in the
form of lists.
The application is intended to be run on Android phones, however can also be run on Internet
tablets. Regin Building Access is published on Google Play for simple downloading.
The application is available for Corrigo E Ventilation and Corrigo E Heating, however currently not
for Corrigo E Boiler.
The Android application is free of charge and can either be downloaded from Google Play or
ordered from Regin. To use the application, Corrigo E…-WEB must be connected to the Internet, or
a local WiFi network (router with wireless communication).
The menu language is Swedish or English, in the future the application will also be available in
other languages. If the phone language is Swedish, the menus will automatically be displayed in
Swedish.
Import connections
Import a ready-made connection received in an SMS from another phone.
Add a connection
Opens a dialogue box in which you can create a new connection.
Exit
Exit the application.
If you have already added a Corrigo and want to add another Corrigo, press the menu button on the
mobile. The following page will be shown:
The buttons Search, Import and Connect To have the same function as described above.
Settings
Opens a dialogue box where you can make various general settings such as size, communication
interval, start page, etc.
More
Opens a menu with the below options.
Add a connection
Opens a page where you can create a new connection (more detailed description in the section The
connections page).
Edit
Opens an existing page in which you can edit the properties of the selected connection.
Send
Opens a dialogue box from which you can send the selected connection in an SMS to another
phone.
Log
Opens a new page where you can view any errors.
About
Version.
The connections (and other settings) are stored in a local file in the device. Each connection has the
following properties which are accessed by pressing the menu button, then More and Edit:
Icon
The connection icon on the connections page. You can choose between a number of predefined
icons included in the application.
Network address
The Corrigo network address (IP or DNS).
Password
Password for communication with the Corrigo.
Auto connect
Checkbox which indicates that the application should automatically connect to this Corrigo when
started. If the box is already checked for another connection when checking it, it will automatically
be unchecked for the other connection.
TCP port
The TCP port number that should be used to communicate EXOline with the Corrigo. Default:
26486.
Config. URL
The network address or URL from which the configuration files are to be obtained. Default: The
Corrigo network address.
AB Regin
Head office
Box 116, S-428 22 Kållered, Phone: +46 31 720 02 00 info@regin.se
Sweden Fax: +46 31 720 02 50 www.regin.se