ABB ZX1.2 SwitchgearDS 2448 ZX1.2 en
ABB ZX1.2 SwitchgearDS 2448 ZX1.2 en
ABB ZX1.2 SwitchgearDS 2448 ZX1.2 en
2
Gas-insulated medium
voltage switchgear
ZX1.2
High level cable termination compartment
8 Safety first
Partitioned single busbar system for transformer and distribution
1 systems with a raised cable termination point for ease of cable
15 assembly from the rear. The parameters extend up to 40 kV,
up to 31.5 kA and up to 2500 A for the switching devices and
2 busbars.
14 3
All the switching devices can be remote controlled, and as an
4 option mechanically interlocked. Both combined protection and
13 control units and pure protection devices are used. The plug-
12 5
in busbar technology without bolted joints permits simple and
11
therefore safe installation. Furthermore, the disconnector in the
10 busbar compartment permits fully unrestricted decoupling of
6 the outgoing feeder side. The level of operator safety, already
successfully confirmed by the IAC classification AFL(R) 31.5 kA
4
1s, can be even further enhanced by pressure relief channelled
outside the building.
7
Configuration opportunities
Together with incoming and outgoing feeder panels with
9 8 circuit-breakers for various rated currents and thus various
panel widths (400, 600 and 800 mm), panel variants for
sectionalizers, pure disconnector and metering panels round
off the range. Sectionalizer and coupler panels also offer
Feeder 2000 A
busbar voltage measurement as an integrated function.