Gs33j60e10-01en Afv30d
Gs33j60e10-01en Afv30d
Gs33j60e10-01en Afv30d
[Release 6]
n GENERAL
This GS covers the hardware specifications of the
Field Control Unit (FCU) which is the core of the
control function of the Field Control Station (FCS).
n STANDARD SPECIFICATIONS
For the installation specifications and the environmental
conditions common to the systems, refer to “Integrated
Production Control System CENTUM VP System
Overview” (GS 33J01A10-01EN).
Note: When option code /HKU is specified, a FCU fault [19-inch Rack Mountable Type FCU]
contact is output from the House Keeping Unit
(HKU).
l No. of Node Units Connectable
l Communication Interface Max. 13/FCU
Vnet/IP Interface: Dual-redundant The total number of ESB Bus Node Units (ANB10)
and Optical ESB Bus Node Units (ANB11) that can
For more details, refer to "Integrated Prodction be connected to FCU are 13 or less.
Control Systrm CENTUM VP System Overview" (GS
33J01A10-01EN) l Module Configuration
Power Supply Module (PW481, PW482, or PW484):
l HKU Interface (Option) 2 modules for dual-redundant
When option code /HKU is specified, a FCU configuration.
fault contact is output from the HKU. Also, the Processor Module (CP471 or CP461):
environmental conditions of the cabinet connected via 2 modules for dual-redundant
the HK bus and optical ESB bus can be monitored and configuration.
the operating status of the HKU can be displayed on A dual-redundant configuration is enabled
the HIS. System alarms can also be displayed. by using 2 identical modules with same
model code (CP471 or CP461).
I/O Module (*1): Max. 8
l System Configuration
This is a configuration example of an FCU and node units, and an ESB bus (including optical ESB bus) that connects
them.
Dual-redundant Vnet/IP
FCU:
Field Control
Unit
Dual-redundant
ESB bus
TM1 FUSE RL1 CN1 (PSU-L) TM2 100-120V AC
READY
CN2 (PSU-R)
Dual-redundant
Optical cable
Dual-redundant
ESB bus
ESB Bus
Node Unit
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 33J60E10-01EN Feb. 1, 2015-00
<<Contents>> <<Index>> 3
n LIMITATIONS OF INSTALLATION AND NOTICES FOR INSTALLATION
For installing I/O modules in AFV30S or AFV30D, the quantity and allocation are limited.
Also, when installing a node unit to the dedicated cabinet, there are limitations of installation under the ambient
operating temperature conditions.
When modules with built-in barriers are installed in AFV30, an insulating partition kit (Part No. T9083ND) must be
installed.
For details, please refer to “FIO System Overview” (GS 33J60A10-01EN) and “Installation Guidance”
(TI 33J01J10-01EN).
n EXTERNAL DIMENSIONS
Unit: mm
482.6
207
8.75 465.1
150.6 20.4
21.3 440
221.3
146
265.9
44.5
31.75
Nominal Tolerances :
Nominal tolerance is ± 0.8 mm for the dimensions of 0.5 mm or more and 120 mm or less, and the combined nominal
tolerance is ± 1.5 mm.
The nominal tolerance is in accordance with JEM 1459 for the dimensions over 120 mm.
SOFTWARE REQUIREMENT
n
A software license is required for AFV30 separately. For details, refer to the GS “VP6F1700 Control Function
for Field Control Station (for AFV30/ AFV40)” (GS 33J15C10-01EN) and “VP6F3100 Project I/O License” (GS
33J15A10-01EN).
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 33J60E10-01EN Feb. 1, 2015-01
<<Contents>> <<Index>> 4
STANDARD ACCESSORIES
n
The FCU is delivered with the following standard accessories.
Parts Names Parts Numbers Quantity Remarks
Insulating bush S9049PM 8 Accessory
Description
Model AFV30S Field Control Unit (for FIO, 19-inch Rack Mountable)
-A Standard type (for CP471) (*1) (*2)
-S Standard type (for CP461) (*3)
3 Dual-redundant Vnet/IP, single power supply
4 Dual-redundant Vnet/IP, dual-redundant power supply
1 Always 1
1 100 - 120 V AC power supply (*4)
2 220 - 240 V AC power supply (*4)
4 24 V DC power supply (*4)
Suffix
Codes 0 Basic type (*5)
1 With ISA Standard G3 option (*5)
5 Basic type with no explosion protection
6 With ISA Standard G3 option and no explosion protection
E Basic type with explosion protection
F With ISA Standard G3 option and explosion protection
LFS1700 Control function for field control station
1
(for AFV30/AFV40, Vnet/IP and FIO) (for CP461) (*6)
2 Always 2 (R6.01 or later)
/HKU With HKU interface (*7)
Option
/ATDOC Explosion Protection Manual (*8)
Codes
/MRN With Marine Standards (*2)
Note: The existing AFV30S-S1 for CENTUM VP R5 can be used with CENTUM VP R6.01 or later.
*1: CP471 runs with CENTUM VP R6.05 or later version of Control Function for Field Control Station. CP471 can be combined
with the style code S3 or later of ESB bus coupler module EC401. See GS 33J60E30-01EN.
*2: Select the option code “/MRN” if AFV30S with marine standard is required. Combination of the suffix code “-A” and the
option code “/MRN” is inhibit.
*3: Shipped with CP461. Also CP471 is usable. Replacement from CP461 to CP471 is prohibited to perform by a user.
Replacement work must be done by the service engineer authorized by Yokogawa Electric Corporation. CP471 can be
combined with the style code S3 or later of ESB bus coupler module EC401. See GS 33J60E30-01EN.
*4: To meet the safety standards and EMC standards, the unit must be installed in a keyed metallic cabinet.
*5: These suffix codes are applicable to only AFV30S-S. They are no longer available.
*6: This suffix code is acceptable to only AFV30S-S and CENTUM VP R5.
*7: When used in combination with ACUKT, specify this option code “/HKU.”
*8: Select the option code “/ATDOC” to follow the ATEX Directive for use in potentially explosive atmospheres.
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 33J60E10-01EN Feb. 13, 2018-00
<<Contents>> <<Index>> 5
Duplexed Field Control Unit
Description
Model AFV30D Duplexed Field Control Unit (for Vnet/IP and FIO, 19-inch Rack Mountable)
-A Standard type (for CP471) (*1) (*2)
-S Standard type (for CP461) (*3)
4 Dual-redundant Vnet/IP, dual-redundant power supply
1 Always 1
1 100 - 120 V AC power supply (*4)
2 220 - 240 V AC power supply (*4)
4 24 V DC power supply (*4)
Suffix 0 Basic type (*5)
Codes
1 With ISA Standard G3 option (*5)
5 Basic type with no explosion protection
6 With ISA Standard G3 option and no explosion protection
E Basic type with explosion protection
F With ISA Standard G3 option and explosion protection
LFS1700 Control function for field control station
1
(for AFV30/AFV40, Vnet/IP and FIO) (for CP461) (*6)
2 Always 2 (R6.01 or later)
/HKU With HKU interface (*7)
Option
/ATDOC Explosion Protection Manual (*8)
Codes
/MRN With Marine Standards (*2)
Note: The existing AFV30D-S1 for CENTUM VP R5 can be used with CENTUM VP R6.01 or later.
*1: CP471 runs with CENTUM VP R6.05 or later version of Control Function for Field Control Station. CP471 can be combined
with the style code S3 or later of ESB bus coupler module EC401. See GS 33J60E30-01EN.
*2: Select the option code “/MRN” if AFV30D with marine standard is required. Combination of the suffix code “-A” and the
option code “/MRN” is inhibit.
*3: Shipped with a pair of CP461. Also a pair of CP471 is usable. Replacement from CP461 to CP471 is prohibited to perform
by a user. Replacement work must be done by the service engineer authorized by Yokogawa Electric Corporation. CP471
can be combined with the style code S3 or later of ESB bus coupler module EC401. See GS 33J60E30-01EN.
*4: To meet the safety standards and EMC standards, the unit must be installed in a keyed metallic cabinet.
*5: These suffix codes are applicable to only AFV30D-S. They are no longer available.
*6: This suffix code is acceptable to only AFV30D-S and CENTUM VP R5.
*7: When used in combination with ACUKT, specify this option code “/HKU.”
*8: Select the option code “/ATDOC” to follow the ATEX Directive for use in potentially explosive atmospheres.
APPLICABLE STANDARDS
n
Refer to the GS “Integrated Production Control System CENTUM VP System Overview (GS 33J01A10-01EN).”
ORDERING INFORMATION
n
Specify model and suffix codes.
For selecting the right products for explosion protection, please refer to TI 33Q01J30-01E without fail.
TRADEMARK
n
• CENTUM and Vnet/IP are registered trademarks of Yokogawa Electric Corporation.
• Other company and product names appearing in this document are trademarks or registered trademarks of their
respective holders.
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 33J60E10-01EN Feb. 13, 2018-00
Subject to change without notice.