INTELLIGENT DIGITAL DISPLAY TEMPERATURE OPERATION PRECAUTIONS

XMT-6000 CONTROLLER Before cleaning the instrument, check that the power is turned off.

INSTRUCTION MANUAL Remove stains on the display unit using a soft cloth or tissue paper.

Before using this product, please carefully read this manual for its correct use. In addition, after reading the As the display unit is easily scratched, do not scrub or touch it with a hard object.

manual keep it available easily anytime. Do not operate the front key with a pointed object such as a ballpoint pen or screwdriver, as this may scratch or

damage the key.

1.PRODUCT CHECK
! WARNING This instrument is applicable for the machines or equipments of injection molding, extrusion, bottle manufacture,

food, packaging, printing and also can be used for controlling the temperature of the equipments of thermostats,
 Wiring precautions
dryness, heat treatment of metal and so on.
—If failure or error of this instrument could result in a critical accident of the system, install an external
The PID parameters of this instrument can be set up automatically, so it is an intelligent instrument and its
protection circuit to prevent such an accident.
employ is vary convenient. This instrument is the optimal replacements of the electronic pointer controller and
—In order to prevent instrument damage or failure, protect the power line and the input/output lines from high
simulated digital display temperature instrument recently.
currents by using fuses with appropriate ratings.
This instrument satisfies the requirements of the standard of the Q/SQG01-1999 intelligent digital display
 Power supply
controller.
—In order to prevent instrument damage or failure, supply power of the specified rating from 85VAC to
Check whether the delivered product is as specified by referring to the following model code list.
264VAC.—In order to prevent electric shock or instrument failure, do not turn on the power supply until all of

the wiring is completed.


XMT □-□□□□ □ □ □—□
 In order to prevent fire, explosion or instrument damage never use this instrument at a location where
① ②③④⑤ ⑥ ⑦ ⑧ ⑨
inflammable or explosive gases or vapor exist.
1 Panel Dimensions(mm) ⑤ Type of Input
 Never touch the inside of the instrument.
D:96×96 1: Thermocouple signal
—In order to prevent electric shock or burns, never touch the inside of the instrument. Only “YATAI” service
E:72×72 2: Thermo-resistance signal (RTD input)
engineers can touch the inside of the instrument to check the circuit or to replace parts. High voltage and high
F:96×48(Vertical form);F(H):48×96(Horizontal form) ⑥Type of Output
temperature sections inside the instrument are extremely dangerous!
G:48×48 No: Relay contact (Maximum 3A)
 Never modify the instrument.
②Type of Display V: Logic output for SSR
—In order to prevent accident or instrument failure, never modify the instrument.
6: Double rows display A: Relay contact (Maximum 16A)
 Maintenance
③Type of control action B: Relay contact (Maximum 16A)
—In order to prevent electric shock, burns or instrument failure, only “YATAI” service engineers may replace
0: On-off action Relay ⑦Type of calibration
parts.
3: Time proportion action ⑧Lower limit of the span
—In order to use this instrument continuously and safely, conduct periodic maintenance. Some parts used in this
4: On-off PID action with auto-tuning ⑨Upper limit of the span
instrument have a limited service life and may deteriorate with time.
7: Single phase zero-across pulse PID action with auto-tuning <Accessories>
④On-off position Alarm Mounting bracket: 2 pieces 3.1 Wiring cautions
0: No alarm Instruction manual: 1 copy (1) For thermocouple input, use the specified compensation wire.

1: High alarm (XMTD, XMTF zero-across pulse output, logic level output and all models of XMTG have no this function) (2) For RTD input, use leads with low resistance and having no resistance differences among the 3 leads.

(3) Conduct input signal wiring away from instrument power, electric equipment power and load lines to

2.MOUNTING avoid noise induction.

3.2 Terminals' configuration


2.1 Mounting cautions
( 1 ) Terminals for Model: XMTD-6011, 6311, 6411, 6012, 6312, 6412 and XMTF-6011, 6311, 6411, 6012,
(1) environmental condition
6312, 6412 (96×96) (96×48)
Ambient pressure:86~106kPa。 2.3 Dimensions
220VAC
Ambient temperature:0~50℃。
(9)
Ambient humidity:45~85%RH。
(10)

(11)
(2) Following cautions must be kept in mind while H h
(12)
mounting:
(13)
Rapid changes in ambient temperature, which
(14)
may cause condensation. B L
(15) - Load
Corrosive or inflammable gases. B b’
(16) +
Direct vibration or shock to the mainframe.
(2)Terminals for Model (with SSR): XMTD-6401V, 6401V, 6302V, 6402V and XMTF-6301V, 6401V,
Water, oil, chemicals, vapor or steam splashes. Panel hole:
6302V, (96×96) (96×48)
Excessive dust, salt or iron particles.
220VAC
Excessive induction noise, static electricity, h’
(9)
magnetic fields or noise.
(10)
Direct airflow from an air conditioner.
(11) - ~
Should be used indoors where the system is not
(12) + ~
exposed to direct sunlight. mm
(13) SSR
Heat to be accumulated radiation heat. Type H×B h×b×L h’ ×b’
(14)
XMTD 96×96 92×92×100 (92+1) ×(92+1)
(15) - Load
XMTE 72×72 68×68×100 (68+1) ×(68+1)
(16) +
XMTF 96×48 92×44×100 (92+1) ×(44+1)

XMTF(H) 48×96 44×92×100 (44+1) ×(92+1)


(3)Terminals for Model (with bi-directional thyristor): XMTD-6701, 6702 and XMTF-6701, 6702 (96×96) (96×48)
XMTG 48×48 44×44×100 (44+1) ×(44+1)
220VAC

(9) (9)
3.WIRING (10) (10)
(11) (11) (1) (7)

(12) (12) (2) (8)

(13) thyristor (3) (9) (5)

(14) (4) (10) (6)

(15) - Load thyristor (5) (11) -

(16) + (6) (12) +

XMTE-6701M;6702M

Load

(4) Terminals for Model: XMTE-6011, 6311, 6411, 6012, 6312, 6412 (72×72) (7) Terminals for Model: XMTG-6001, 6401, 6002,6302, 6402 (48×48)

220VAC 220VAC

(1) (6)

(2) (7)

(1) (7) (3) (8)

(2) (8) (4) (9) +

(3) (9) (5) (10) -

(4) (10) Load

(5) (11) -

(6) (12) +

(8) Terminals for Model (with SSR): XMTG-6301V, 6401V, 6302V, 6402V(48×48)

Load

(5) Terminals for Model (with SSR): XMTE-6301V, 6401V, 6302V, 6402V(72×72) 220VAC

220VAC (1) (6)

(2) (7)

(1) (7) (3) (8)

(2) (8) ~ + (4) (9) +

(3) (9) SSR ~ - (5) (10) -

(4) (10)

~ + (5) (11) - Load

SSR ~ - (6) (12) +

(9) Terminals for Model (with bi-directional thyristor): XMTG-6701,6702(48×48)

Load

(6) Terminals for Model (with bi-directional): XMTE-6701,6702 (72×72) 220VAC

220VAC (1) (6)


(2) (7)
4.OPERATION
(3) (8)

thyristor (4) (9) +


4.1 Sequence to pick up the functions of the instrument
(5) (10) -

Power on
Load

Power supply voltage:


Upper row displays code(Sn),lower Row
198 to 242 VAC (Including power supply voltage variation)(50Hz)
displays type No. (Display input type)
Control output rated:

Relay contact output: 240 VAC, 3A(Resistive load)


Upper row: Input high limit, lower row
Voltage output:0 to 12 VDC (Load resistance 600Ω or more)
input low limit(Display input Lange) Automatically turn over after 4 seconds displaying
3.3 Configuration of the Instrument Panel
①Measured value (PV)display unit (Red)
Upper row displays process value, lower Automatically return over when not press any key over 1 minute
Displays measured value (PV).
row displays set value(Standard mode)
PV Displays various characters depending on the

instrument.
Press function key Upper row displays setting code (SP,St), lower row
① ②Set value (SV)display unit (Green)
displays set value(Update the setting mode )
Displays set value (SV)

SP ② Displays various each parameter set value depending


Press function over 4 seconds Upper row displays function code (AL…), Lower row displays
on the instrument.
control parameters(Changing the control parameters)
③Indication lamps

AT OUT ALM ③ Auto-tuning(AT)lamp [Green]. Flashes during


Example:Input: Thermocouple E, 0~400℃.When turn on power, display:
auto-tuning execution.

Control output lamps [Green](OUT)turned on


1 PV PV
when outputs operate

Alarm output lamp (ALM)[Red] turned on when

output operate
SP SP (Standard display mode)
④ Function key

Used for displaying the change and confirm of the

④ ⑤ ⑥ parameters

⑤、⑥ Adjusting key to change the digital code and/or the key to express entering the auto-tuning state

. Used for adjusting the digital code displayed or entering the auto-tuning state.
Code Sn Type Input signal Type Range(℃) 100.0 Alarm. For on-off controller, On-off control
dF
0 S E 0~600 ℃ and alarm adopted Same value.

1 B K 0~1300 Upper limit alarm for AL 0, low


Thermocouple Alarm point -19991999
Type 2 K S 0~1600 Limit alarm for AL 0. The state of 50
AL (Setting) ℃
Output turn over automatically.
of 3 E B 200~1800

input 6 Pt100 Pt100 -200.0~2.000 Control

7 Pt100 RTD Pt100 -200~500 Period 1100 Relay output ≮≮20s,SSR and thyristor 20

8 Cu50 Cu50 -50.0~150.0 T ( On heating second output≮≮3s continuous output,1s. 2

side)

The delay
When the measuring value increases
time 13600
4.2 The detail description for every function to the alarm value, after Ct time the 0
If upper row displays “OVER” the sensor is in open circuit or the input signal excesses the range Ct fof alarm second
alarm relay output acts.
of measurement. output

The method for changing set value: Proportional


When “P” is large, the proportional
Press  key the high row displays SP. Press or key,the low row displays the needed value. Again press  key, return to the standard Band 1300
action is small. Only used for heating 30
display mode. P ( On heating ℃
side.
The method for changing control parameter: side)

Press  key over 4 seconds, the high row displays the parameter display code. Press  or  key the low row displays the needed parameter Integral

value. Again press  key over 4 seconds, Time 13600 When “I” is large, the integral action
240
return to the standard display mode. (If not press any key over 1 minute, return to the standard display mode automatically.) I (Re-setting second is small.

Following table lists the function parameters time)

Param Derivative

eter Initial value setting Time 13600 When “D” is large the derivative
Name Setting range Description 60
displa at factory d (Pre second action in large.

y code -setting)

Time The proportion re-setting only used 0:All parameters can be updated.
-99 99.9 Set data lock
Proportion for adjusting the static deviation of 0 02 1:Only SP can be updated. 0
function
rE Re-setting
100100.0℃
The proportional system.
Lc 2:All parameters cannot be updated.

Process Used for correcting the measure 4.3 The function of the controller Auto-tuning
-9999.9
value deviation caused by the sensors and 0 After pressing key 8 seconds the lamp of AT flashes and the auto-tuning process starts; after the end of
rt biasing
100100.0℃
compensation wire of thermocouple auto-tuning the lamp of AT world be turned out. Then a set of PID parameters can be got automatically for

Dead band 0.4100 Dead band for on-off control and 0.4 quickly increasing the process temperature. The controller operates according to this set of PID parameters.
After pressing  key 8 seconds the lamp of AT flashes and the auto-tuning press starts; after the end of auto- When the controller is set as deviation alarm, the actual alarm point will be SP+AL. Example as a controller whose set point SP is

tuning the lamp of AT be turned out. A set of PID parameters can be got automatically for overcoming 200℃. When we set the alarm point AL to be 10℃, then the actual alarm controlled point is at 200.0+10.0=210.0℃. That is to say, if the

temperature overshoot. The controller operates according to this set of PID parameters. process temperature is larger than SP+AL+1/2dF, the alarm relay will be put on and when the process temperature is smaller than SP+AL -

4.4 The sketch map of the function of the controller Auto-tuning 1/2dF, the alarm relay may be put on at 210.5℃ and put off 209.5℃.

W W On the other hand, when we set the AL at -10.0℃, then the actual alarm controlled point is on the value of 200.0-10.0=190.0℃. At

SP SP the same time the state of output is also changed. When the process temperature is smaller than SP+AL-1/2dF, the alarm relay will be put on

and larger than SP+AL-1/2Df the alarm relay will be put off. If dF also be set at 1.0 ℃, then the alarm relay point for putting on is 189.5℃

0.8SP and the point for putting off is 190.5℃. This function not only can be used to low limit alarm but also be used for controlling heating with

large power (needed dual heating elements) to shorten the time of increasing temperature and decrease the overshoot of the system.

When the controller is set as absolute measuring value alarm the actual point of alarm is AL. If AL is set larger than SP the alarm is an

upper limit alarm one. If AL is smaller than SP the alarm is a low limit alarm.

Ct——for setting the delay time of alarm. Ordinary the ct value should be set to zero. When the alarm output is used to the

t t refrigeration compressor, the delay time of alarm ought to longer than 180 seconds..

AT start AT end AT start AT end T──for setting the control period. Ordinarily if the controller using the AC contactor, the control period is ought to set between 20.0~60.0

Press  key to start auto-tuning Press  key to start auto-tuning seconds and if the controller using the solid relay and deadband the control period is ought set between 2.0~10.0 seconds.

P——for setting proportional band. When take place regular oscillation of controlled temperature, the proportional band should be
5. Description of each function
increased and if controlled temperature drifts irregularly we ought to decrease the proportional band.
rE──for re-setting of proportional controller. This function is only used for XMT-8300. Due to the varieties of process power and I──for setting the integral time. When the system takes place regular oscillation ought to increase integral time and if the system
controlled temperature, the static deviation of the system controlled by the proportional controller is caused. Through adjusting the value of controlled can not remove the static deviation in a long time ought to decrease the integral time.
the parameter rE, the static deviation may be decreased even removed. d──for setting the derivative time. Increasing the derivative time can decrease the overshoot of the system.
Example as a equipment with a setting point temperature 200℃. After system have to be stable the controlled temperature is 204.5℃.

That is to say a static deviation of 4.5℃is yielded. Then we can set the rE to -4.5℃. After some time the system can be re-stable at the
Address
controlled temperature about 200℃. Shanghai No.1851 Sichuanbei Road, Shanghai, China
rt──for correcting the measuring value. This function can be used for all the controllers in this series o instrument. The deviations
Tel021-51053127 51053128 Fax : 086-021-51053123
caused from sensor, compensation wire of thermocouple and the controller accuracy can also be decreased even to be removed by adjusting Yatai Instrumentation Co., Ltd. Mail Code: 200081 Email: yatai@yatai.sh.cn
the parameter rt.

Example as the setting value of the controller is 200℃ and the measuring value also is 200℃, but the actual controlled temperature

measured by a high accuracy mercury temperature meter is 201.7 ℃. At that time we can set the parameter rt=1.7℃,then the temperature

displayed as 201.7℃. After a very long controlling time the temperature also be stable at 200℃ that is the same as the value measuring by

the mercury temperature meter.

dF──for setting the dead band of on-off control and alarm. If we set dF=1.0℃, than the output of controller will be changed at 0.5℃

deviated from the setting value of temperature.

AL──for setting the alarm point.