GUIDELINES FOR DOMESTIC WATER METER INSTALLATION IN METER ROOM

All domestic water meters in high rise (6 storied and higher) residential and commercial buildings
shall be arranged in groups and housed inside the water meter rooms as shown in standard
drawing PEW-STD-AMI-003. The meter rooms shall be used solely for water meter installation to
protect them against exposure to undue external interferences. No other service installations will
be allowed in the water meter room. Meter should not be installed in the basement of the building,
pump room or in underground meter chambers.
A. WATER METER ROOM REQUIREMENTS:

Water meter room shall comply with the following requirements:


1. Meter Room in high rise buildings shall be located in each floor of the building and adjacent to
the Electricity Meter Room.
2. The size and shape of the water meter room shall be determined based on the number of
water meter to be installed and minimum size of the water meter room shall be 1500mm length
x 1000mm depth x 3000mm height.
3. The meter room door shall have minimum 800mm width and 2000mm height.
4. The water meter room shall be designed to arrange water meters as groups in one layer with
sufficient clearance for installation and maintenance of meters.
5. Meter room shall be located in common area for safe, free and uninterrupted access.
6. Install a 25mm dia. PVC conduit with pulling spring between the water meter rooms from the
highest floor to ground floor to lay interconnecting cable for meter communication and Install
junction boxes, Trunking and associated fittings in every floors as described in Section C.
7. There shall be provision of adequate drainage inside the meter room to remove flushed water
during installation and maintenance of the meter.
8. Meter room flooring shall be clear from obstacles and shall be even, rigid and not slippery.
9. Meter room level shall be lower than (min.100mm) the passage or other floor areas so that
water from the meter room should not flow to the passage, other floor areas and elevators/lifts.
10. There shall be sufficient ventilation and illumination inside the meter room.
11. A waterproof 13 Amp. Power socket shall be provided in the meter room.
12. All electrical fittings in the water meter room shall be waterproof.
13. A permanent Notice/Warning plate “Landlord/Customer is not allowed to install any other
devices in the water meter room and also not allowed to do any modification to meter
connection, pipes and fittings without written permission from DEWA” in Arabic and English
language shall be affixed inside the meter room.
14. The ‘DEWA Water Meter Room’ plate in Arabic and English language shall be affixed on the
door and meters shall be accessible to DEWA staff at any time.
15. Detailed shop drawing, elevation plans of the meter rooms with dimensions, including the width
and height of entrances shall be submitted for DEWA approval before commencement of work.
16. No plumbing work shall commence inside the meter room before the plumbing proposal is
inspected and approved by DEWA.

Page: 1 of 4
B. METER INSTALLATION AND ASSOCIATED PLUMBING WORKS REQUIREMENTS:

All plumbing work shall be performed in accordance with all local codes, ordinances, laws and
regulations; and as recommended by BS EN 12056-2:2000 and BS 8000, Part 13, 14 and 15.
Piping shall be installed not to obstruct room entrance or passageways and rigidly anchored to
walls with suitable wall brackets. Meter and associated piping works shall be in line with the
dimension mentioned in the typical installation Drawing PEW-STD-AMI-003

The following practice shall be adopted in plumbing work for meter room:-

1. The fittings at the meter position should facilitate easy installation and removal of the water
meter without the need to work on other pipes. All-time maintenance of the meters shall be
taken into account while installing new meters.
2. Pipes, Valves, PRV, NRV and other fittings used for meter connection shall be high quality,
heavy duty, non-toxic, non-corrosive material approved by DEWA.
3. Pipe size for ½” meter installation shall be ½” to 1” maximum and for 1” meter installation shall
be 1” to 2” maximum.
4. ½” meter can deliver up to 10,000 gallons water in 24 hours and 1” meter can deliver up to
20,000 gallons in 24 hours, approximately.
5. Consumer must have water storage tank equivalent to 24 hours’ consumption for residential
premises and storage equivalent to 48 hours’ consumption for labour accommodation and
other high consumption premises.
6. The pipework at the meter position should be securely fixed to support the weight of the water
meter and to resist any torsion, bending and tension during the installation and removal of the
meter.
7. The meter shall be installed on a straight length of pipe the same diameter as the meter and
equivalent in length to 3 times the meter dia. at the inlet and 2 times dia. at the outlet.
8. Isolation valves shall be installed upstream and downstream the meter to stop water flow from
both directions and a stop cock shall be installed prior to the meter for locking/ disconnection of
supply to the meter.
9. In addition to this a main isolation valve shall be installed on the main pipe inlet in the meter
room to isolate the supply in case of pipe breakages to avoid flooding.
10. Main isolation valve shall be provided for every group of five meters in order to sectionalize the
group of meters during maintenance without affecting other group of meters.
11. Both valves shall be fully open while the meter is in service and no control of flow shall be
made by regulating the inlet and outlet valves.
12. A threaded joint/union shall be provided after the meter to make length adjustments for meter
connection in accordance with the meter length.
13. Meters shall be installed at a height of 1200mm from the finished floor/ground level. The
clearance between the back plate of meter and the wall plane shall be 200mm and the entire
meter group must be adjusted as a single layer. Multiple layers and different elevations of
meters are not permitted in the water meter room.

Page: 2 of 4
14. Suitable size single header supply lines are to be considered in plumping design for each
meter room, multiple or parallel header lines are not allowed in one room.
15. Sufficient space (at least 200mm.) shall be provided between and around water meters to
permit installation, reading, servicing and removal of the meters.
16. Water meter and its associated fittings/pipes shall not be part of electrical earthing.
17. No water pump shall be installed upstream or downstream the meter and sudden variation of
flow/pressure shall be avoided.
18. Maximum pressure at the meter inlet shall not exceed 2 bar, PRV and Pressure Gauge shall
be installed, at least 1 mtr. before the meter, to achieve the required pressure.
19. Meter shall be easily accessible for reading - without the use of mirror, ladder etc.
20. Meter installation guidelines shall strictly be followed while installing the meter.
21. Meter shall be installed in accordance with the arrows shown on the body of the meter and
register shall be arranged in the most convenient position for reading.
22. The meter room shall be suitable for the Technician to stand straight and remove/refix the
meter easily.
23. Prepare As-built drawings showing the pipelines to the meter and after meter to the customer
pipe connection to their storage tank and the PVC Conduit from meter to the building’s LV
room for communication cabling and submit to DEWA.
24. A/c. No. & Flat No. plates shall be affixed on wall immediately adjacent to the meter (not on the
meter) for identification.
25. DEWA is responsible for the supply and installation of water meters for new connections.
Meters are installed either by DEWA staff or Contractors acting on behalf of DEWA. Customers
and property developers are responsible for supply and installation of all ancillary fittings and
pipe-work beyond the meter in accordance with relevant DEWA specifications and standard
drawings.

C. WATER METER COMMUNICATION NETWORK INSTALLATION REQUIREMENTS :

1. Install 25mm dia. PVC conduit vertically between the water meter rooms from the highest floor
to lowest floor for interconnecting communication cable for Smart water meters. Install PVC
junction boxes at 25m interval (if the length exceeds 25m) and corner portions with pulling
spring so as to provide ease of access to cable circuits throughout the route. The JB shall be a
two way PVC JB for easiness of cabling pulling.
2. In the water meter room (each floor), install 50X50 mm PVC trunk horizontally on the wall
surface behind the back plate of the meter by utilizing the achieved clearance of 165mm. The
trunk shall be single piece securely fixed and aligned at an elevation of 1600 mm from the
finished floor level and installed with proper end caps.
3. PVC trunk shall be installed with PVC PG-7 glands equal to the number of Water Meters in the
Water Meter room.
4. PVC trunk shall be of high quality complying with BS4607 and of rectangular cross-section of
which one side is removable.
5. All PVC conduits, trunks, glands and coupling accessories must comply with BS 4607 and be
suitable for the ambient conditions expected. It shall be corrosion resistant.

Page: 3 of 4
6. The external and internal surface of pipes shall be clean, smooth and virtually free from
grooves or other indentations or projections. The smoothness of the internal surface of the pipe
shall be such that the pulling through of the cables in long lengths shall be facilitated without
risk of damage to the exterior surface of the cable. The ends of conduit, trunk and cable tray
shall be provided with bushes or other finished ends such that cables do not sustain damage
during installation or throughout the life of the Installation and must be suitably sealed against
the ingress of water.
7. PVC conduits shall be clamped at every 1 meter interval using suitable and safe fixtures. The
connection of conduit to JB shall be done with proper couplings/adaptors.
8. Provide an IP65, PVC Junction Box of dimension150X150X100mm for up to 10 Water Meters
and 200X150X100mm for up to 25 Water Meters in water meter room on each floor with DIN
rail for fixing the water meter communication interfacing units.
9. The Junction Boxes shall be mounted on the wall planes inside the meter room at an elevation
of 1800mm from the finished floor level and minimum 500mm away from the nearest water
meters.
10. PVC trunk behind the meters shall be connected to the Junction Box through 25mm PVC
conduit by using proper couplings/adaptors. The PVC conduit shall have soft bends and proper
mounting. There shall be one connection for up to 10 water meters and two connections for up
to 25 water meters.
11. A heavy duty GI conduit of 25 mm dia. shall be provided between the ground floor water meter
room and LV room (or the water meter room on the floor nearest to LV room) with pulling
spring for interconnecting meter communication cable with data concentrator. Install pulling
junction boxes in every 25 meters interval and corner portions. The connection of GI conduit
shall be done with proper GI couplings.
12. Install an IP56 GI Junction Box of dimension150X150X50mm at suitable position on the wall
inside LV room at an elevation of 1600mm from the finished floor level. This shall be connected
with the GI conduit mentioned above.
13. As built drawing of the communication installation shall be submitted for approval.
14. Sample Installation of AMI Smart Water Meter and Communication Network is displayed at
DEWA Sustainable Building Al Quoz, Smart Metering Office as a guideline for the Developers,
Landlords, Consultants and Contractors to finalize their design drawings and to submit for
DEWA approval before commencement of construction.

Reference Drawing: PEW-STD-AMI-003