Some applications may require using only one or two modes to provide
the appropriate system control. This is achieved by setting the gain of
undesired control outputs to zero. A PID controller will be called a PI, PD, P or
I controller in the absence of the respective control actions. PI controllers are
particularly common, since derivative action is very sensitive to
measurement noise, and the absence of an integral value may prevent the
system from reaching its target value due to the control action.
2.0 RESULT AND DISCUSSION
No.4
FIC11 & FIC12
PB2 : 100%
TI2 : 6 seconds
TD2 : 0 seconds
SV2 at FIC11 : 3m3/hr
SV2 at FIC12 : 2.5 m3/hr
FIC11
PB2 : 150%
TI2 : 6 seconds
TD2 : 0 seconds
SV2 : 3 m3/hr,
(Test disturbance)
No.7
PB2 : 100%
No.8
PB2 : 200%
PB2 : 150%
TI2 : 9 seconds
TD2 : 0 seconds
PB2 : 2%
PB2 : 20%
PB2 : 40%
PB2 : 60%
To study the responses from different PID settings in the flow control,
two systems have been used. The inflow system is using LIC/FIC11 and the
outflow system is using TIC11/FIC12. First at all, the tank T12 is filled with
water till it reaches the overflow Drain pipe outlet (D).
The experiment results were shown in the graph of figure 1. When the
experiment started, four difference color lines were shown on the paper by
the chart recorder. First, the red color line indicates the water level in the
tank T12, green color line indicates inflow, blue color line indicates the
outflow and the purple color line indicates the temperature. By referring the
purple color line in the graph printed by the chart recorder, the line is linear;
therefore the temperature in the system remains constant through the whole
process.
The Proportional (P) and Integral (I) control is set into FIC11 and FIC12
by using the trial PID values for both controllers, that is PB2= 150%, TI2= 6s
and TD2= 0s. (PI action controller.) The first disturbance is observed when
the inflow set point was 5m3/hr which is specified at point 1.The disturbance
that presence can be detected by moderate oscillation and the damping
pattern of green line.
Meanwhile, when the outlet flow rate which was changed to 4.5m3/hr,
the blue line was increased steadily to its steady state in a monotonic
pattern, which was no any oscillation. This is shown at point 2. As a result,
the respond of inflow was a sinusoidal response whereas outflow was a first
order step response. Both inflow and outflow increased gradually which then
led to the rise of water level in tank T12. The red line moved upward as
shown in the graph indicates that the water level in T12 is rise due to the
increased of water inflow. Gradually, the response would reach a new steady
point. However, it would be take some time to reach the new steady point.
When the inflow and outflow are nearly steady with slight oscillations
about the set points, the inflow and outflow were set to 3.0m3/hr and
2.5m3/hr respectively (point 3) in the auto mode. This disturbance caused
the inflow and outflow decreased to the values of the new set points in a
negative step change response. This is because the controller had detected
that the values of the controlled/process variables are much higher than the
new set points.
As the system was achieved steady state, the PID control was change
value of PB2 from 150% to 100% with the inflow and the outflow were
increased to 5.0m3/hr and 4.5m3/hr respectively (indicated point 4). There
was an increment due to the increased of flow with the outflow shown a
slower response. When the inflow and the outflow were adjusted to 3.0m3/hr
and 2.5m3/hr, the chart showed a decrement pattern with an over damp
oscillation.
The pattern of the curve of PB2 = 100% is almost similar to the pattern
of the curve of PB2 = 150%. This verify that PB = 150% has no significant
difference with PB = 100%. This slight difference is due to the slightly
difference in Kc.
When the inflow and outflow were increased to 5.0m3/hr and 4.5m3/hr
respectively (indicated point 5), the green and blue lines increased to new
set points but the outflow line shown a slower response. After a period of
time the inflow will approach the new set point. When the inflow and outflow
were reduce to 3.0m3/hr and 2.5m3/hr, the lines decreased until it stabled
and reached the new set point. The level in the tank increased to its
maximum value and became stable at this value.
After the system achieved steady state, the outflow was set at
2.5m3/hr, PB2 = 150%, TI2 = 6 seconds and TD2 = 0 seconds. Therefore, the
blue line remained at a constant value. At point 6(a), the inflow was
increased to 3.5m3/hr and decreased to 3.0m3/hr. The result indicated that
the changes were due to a step input since the graph didn’t show an
oscillation pattern.
Next, the by-pass valve was opened for 5 seconds (indicated point
6(b)), the inflow was increased in a sudden and dropped drastically when the
valve was closed.
Also, the response for the water level decreased severely due to the
shutting of valve and gradually increased after a while. At point 6(c), the MV
was step increased by 10% manually and the result showed the inflow
increased and formed a small overshoot.
When the three steps 1(a), 1(b) and 1(c) are repeated with different
values of PB2 = 100% and 200% in the disturbance test for the inflow
loop(indicated point 7 & 8), we observed The chart recorder shows the same
pattern of responses with small oscillation and no significant oscillation
amplitude difference for both PB2 values.
Once the system became stable, the PB2 was set back to 150% and
TD2 at 0 second but the T12 was set at 9 seconds. The same results were
observed instead of the third step (indicated point 9). The system could not
go back to the previous steady set point at 3.0m3/hr when MV is increased by
10%. Instead, an offset is observed. Proportional controller cannot eliminate
the error completely, but there will be an offset between the output and the
set point. In this case, the derivative does not take place, since TD2 = 0.
Therefore the offset persists.
When a disturbance is applied to the set point, the flow rate changed
drastically. But when PB2 was set higher and higher until 60%, the oscillation
was become smaller (indicated point 13).
Thus, the critical value for PB2 is around 60%. Here, the value of Kc is
the limiting proportionality of the proportional controller. Any K c value over
this limiting value will results an unstable response. The time to reach steady
state will also increase as Kc increase.
Finally, we re-adjusted the PB2 value to 150% (indicated point 14), TI2
at 6 seconds and TD2 at 0 second. This setting brought the system to PID
system. Vigorous oscillation was obtained as the inflow was disturbed by
opening/closing the by-pass valve of pump P12. The derivative action gives
the controller the capability to anticipate where the process is heading. The
amount of anticipation is decided by the value of TD. Right now, this
controller not only can integrate the error, but also calculate the rate of
error. Thus, it is a more efficient controller. The oscillation dampened a little
when the test at point 6 was applied but became stabilize in a quick time. In
reality, time should be given more to observe the reduction of the oscillation.
3.0 CONCLUSION AND RECOMMENDATIONS
The other disadvantage of PID control is the control action will not take
place when there is a steady error. As for a steady error, de/dt is 0, thus
control action will not take place. On the other hand, the proportional
controller (P) is the simplest because the only tuning parameter is the PB but
they carry an offset in the controlled variable and do not provide the
required control. A large value of TI is not suitable in process control as the
time for the integral control to take action is too long. An error could be
larger and larger until it saturated if given enough time. Since there is
defection for proportional-integral controller, the presence of derivative in PI
controller will result in a better control. Though causing more oscillations, the
derivative can handle a drastic change (de/dt is large).