910 KW, Tier 3, Chilled Water, 15400 FT: Reference Design 9)
910 KW, Tier 3, Chilled Water, 15400 FT: Reference Design 9)
910 KW, Tier 3, Chilled Water, 15400 FT: Reference Design 9)
2
910 kW, Tier 3, Chilled Water, 15400 ft
Facility Power
The facility power system supplies power to all of the critical and non-critical
components within the data center. The architecture used in this electrical
design is a dual path with 2N UPS and N+1 generators. Switching between
generator power and utility is achieved using a programmable logic controller
(PLC). A 3200 amp bus feeds PZ4 electrical and mechanical switchboards. In
the electrical room, UPSs are configured down-stream of the switchboards.
Two Symmetra MW units configured to 2N redundancy provide 1200 kW of
critical power to the IT room with 6 minutes of runtime. Valve regulated lead
acid (VRLA) batteries are housed in an isolated battery room. Two Galaxy 5000
UPS units configured to 2N redundancy provide 72 kW of power to the pumps in
DESIGN OPTIONS
the facility cooling system. Additional low-voltage transformers are included in
This reference design can be modified as
the design to support lighting and other building loads. The power distribution
follows without a significant effect on the architecture from the electrical room to the IT space utilizes a combination of LV
design’s performance attributes: panels and InfraStruxure power distribution units (PDUs). The facility power
system is designed to support additional peripheral devices like fire panels,
Add StruxureWare Power Monitoring access control systems, and environmental monitoring and control devices.
Expert Power meters in the electrical path monitor power quality and allow for
Provision for load bank predictive maintenance & diagnostics of the system. These meters also
Change UPS batteries integrate with StruxureWare Power Monitoring Expert.
Add/change standby generator options: Every component in this design is built and tested to the applicable ANSI,
Location NEMA, UL or IEEE standards.
Tank size Further design details and schematics are available in the engineering package.
Fuel type
Utility
3200A, 480V, 65kA
Name Value Unit
Utility
AC AC
Total amps (main bus) 3200 A
3200A, 480V, 65kA 3200A, 480V, 65kA
Input voltage (main bus) 480 V
2000A, 480V, 65kA 2000A, 480V, 65kA
Switchboard kAIC 65 kA
72 kW 1200kW
Symmetra SSW
72 kW 1200kW
Symmetra SSW
Power path Dual
Galaxy Galaxy
5000 MW 1200kW 5000 MW 1200kW
400A, LOAD 400A, LOAD Generator redundancy N+1
480V, BANK 480V, BANK
65kA 2000A, 480V, 65kA 65kA 2000A, 480V, 65kA
IT space UPS capacity 1200 kW
IT space UPS redundancy 2N
© 2013 Schneider Electric. All rights reserved.
4x CHW Pumps
14x PDU Feeds
to IT Space
4x CHW Pumps 14x PDU Feeds
to IT Space
IT space UPS runtime @ rated load 6 minutes
Facility Cooling
The mechanical design utilizes chilled water as the primary medium for heat
dissipation. The architecture consists of dual chilled water loops. The cooling
system contains two 1196 kW water-cooled chillers in a 2N redundant
configuration. Water-side economization is achieved with a plate & frame heat
exchanger to save energy during favorable outdoor conditions.
In order to extend availability of chilled water during a power outage, redundant
7000 gallon water storage tanks provides 7 minutes of continuous cooling.
The piping architecture of the mechanical system feeds row-based InRow RC
CRAHs in the IT space. It also feeds room-based CRAHs in the electrical and
battery rooms. More information on the cooling configuration is provided in the
IT space section of this document.
DESIGN OPTIONS This design is instrumented to work with StruxureWare Cooling Monitoring
Expert.
This reference design can be modified as
Further design details such as dimensions, equipment placement, temperature
follows without a significant effect on the
set points, pipe sizing, flow rates, and pressure drops are available in the
design’s performance attributes:
engineering package.
Add StruxureWare Cooling
Monitoring Expert
CW supply
© 2013 Schneider Electric. All rights reserved.
Primary loop pumps VFD to IT space
VFD System
VFD Dirt/air
Strainers bypass
separator
Chiller
VFD
VFD
Heat
Exchanger
Expansion
Tower Tower
tank Secondary loop
City Water
pumps
VFD
Thermal Storage
CW supply
Primary loop pumps VFD to IT space
VFD System
VFD Dirt/air
Strainers bypass
separator
Chiller
VFD
VFD
Heat
Exchanger
IT Space
The IT capacity of this design is 910 kW. The design is highly scalable and
adaptable; it can be configured to support IT loads within a range. Smaller
starting loads as low as 200 kW can be supported by making adjustments such
as reducing the number of IT pods or decreasing the quantity of UPS modules.
Likewise, this design can be used as a baseline for larger loads as high as 2730
kW by using a step and repeat approach to the design. This flexibility drives
efficiency and defers capital expenditure until needed.
The IT space design specifies all of the physical infrastructure systems, as well
as their physical arrangement/spacing, required to meet the overall design’s
performance attributes. This includes racks, PDUs, rack power distribution,
DESIGN OPTIONS cooling units, and airflow management systems.
This reference design can be modified as Each pair of rows (pod) within the IT space can be “stepped and repeated” in a
follows without a significant effect on the standardized and predictable manner. This enables right-sizing of power and
design’s performance attributes: cooling that scales with IT growth. Each pod supports an average power
density of 6.5 kW per rack. All the pods are outfitted with integrated power and
Add environmental and security cooling distribution.
management Each pod is powered by floor mount factory-configured power distribution units
Change rack options (tall, (PDUs). Every rack is configured with a metered rack-mount PDU to enable
wide, deep)
remote monitoring of the units for efficiency and capacity management.
Change power distribution options
Rack PDU type (basic, Each pod is cooled by N+1 redundant chilled water-based InRow RC CRAHs
switched) that control the supply of cool air by monitoring temperature variation at the rack
Add StruxureWare Data Center level.
Expert
The security of the room is maintained at multiple points. At the rack level,
access is controlled by a door lock and sensor. At the room level, security
cameras are utilized for monitoring.
Row A Row B
P R C R C R R C R R C R R C R R C R R C R C R P
P/A-2/Z1 R/A-3/Z1 C/
A-4/
Z1
R/A-5/Z1 C/
A-6/
Z1
R/A-7/Z1 R/A-8/Z1 C/
A-9/
Z1
R/A-10/Z1 R/A-11/Z1 C/
A-
12/
Z1
R/A-13/Z1 R/B-1/Z2 C/
B-2/
Z2
R/B-3/Z2 R/B-4/Z2 C/
B-5/
Z2
R/B-6/Z2 R/B-7/Z2 C/
B-8/
Z2
R/B-9/Z2 C/
B-
10/
Z2
R/B-11/Z2 P/B-12/Z2
IT ROOM ATTRIBUTES
G
Gap
Row C Row D
R C R R C R R C R C R R C R C R R C R R C R
R/C-1/Z1 C/
C-2/
Z1
R/C-3/Z1 R/C-4/Z1 C/
C-5/
Z1
R/C-6/Z1 R/C-7/Z1 C/
C-8/
Z1
R/C-9/Z1 C/
C-
10/
Z1
R/C-11/Z1 P
P/C-12/Z1
P
P/D-1/Z2
R/D-2/Z2 C/
D-3/
Z2
R/D-4/Z2 C/
D-5/
Z2
R/D-6/Z2 R/D-7/Z2 C/
D-8/
Z2
R/D-9/Z2 R/D-10/Z2 C/
D-
11/
Z2
R/D-12/Z2
Row G
G
Gap
Row H
Input voltage 480 V
R C R R C R R C R C R R C R C R R C R R C R
P P
Supply voltage to IT 120 / 208 V
R/G-1/Z4 C/ R/G-3/Z4 R/G-4/Z4 C/ R/G-6/Z4 R/G-7/Z4 C/ R/G-9/Z4 C/ R/G-11/Z4 R/H-2/Z3 C/ R/H-4/Z3 C/ R/H-6/Z3 R/H-7/Z3 C/ R/H-9/Z3 R/H-10/Z3 C/ R/H-12/Z3
G-2/ G-5/ G-8/ G- P/G-12/Z4 P/H-1/Z3 H-3/ H-5/ H-8/ H-
Z4 Z4 Z4 10/ Z3 Z3 Z3 11/
Z4 Z3
Row J
P
P/J-2/Z5
R
R/J-3/Z5
C
C/J-
R
R/J-5/Z5
C
C/J-
R
R/J-7/Z5
R
R/J-8/Z5
C
C/J-
R
R/J-10/Z5
R
R/J-11/Z5
C
C/J-
R
R/J-13/Z5
Row K
R
R/K-1/Z6
C
C/
R
R/K-3/Z6
R
R/K-4/Z6
C
C/
R
R/K-6/Z6
R
R/K-7/Z6
C
C/
R
R/K-9/Z6
C
C/
R
R/K-11/Z6
P
P/K-12/Z6
Average density 6.5 kW/rack
4/ 6/ 9/ 12/ K-2/ K-5/ K-8/ K-
Z5 Z5 Z5 Z5 Z6 Z6 Z6 10/
Z6
Row L
G
Gap
Row M
Number of racks 140 racks
R C R R C R R C R C R R C R C R R C R R C R
R/L-1/Z5 C/L- R/L-3/Z5 R/L-4/Z5 C/L- R/L-6/Z5 R/L-7/Z5 C/L- R/L-9/Z5 C/L- R/L-11/Z5 P P R/M-2/Z6 C/ R/M-4/Z6 C/ R/M-6/Z6 R/M-7/Z6 C/ R/M-9/Z6 R/M-10/Z6 C/ R/M-12/Z6
2
IT floor space 6700
2/ 5/ 8/ 10/ M- M- M- M-
P/L-12/Z5 P/M-1/Z6
© 2013 Schneider Electric. All rights reserved.
ft
Z5 Z5 Z5 Z5 3/ 5/ 8/ 11/
Z6 Z6 Z6 Z6
Row N Row P
P
P/N-2/Z9
R
R/N-3/Z9
C
C/
N-4/
R
R/N-5/Z9
C
C/
N-6/
R
R/N-7/Z9
R
R/N-8/Z9
C
C/
N-9/
R
R/N-10/Z9
R
R/N-11/Z9
C
C/
N-
R
R/N-13/Z9
R
R/P-1/Z10
C
C/
P-2/
R
R/P-3/Z10
R
R/P-4/Z10
C
C/
P-5/
R
R/P-6/Z10
R
R/P-7/Z10
C
C/
P-8/
R
R/P-9/Z10
C
C/
P-
R
R/P-11/
Z10
P
P/P-12/Z10
Single or dual cord Dual
Z9 Z9 Z9 12/ Z10 Z10 Z10 10/
Z9 Z10
Row Q
G
Gap
Row S Row T
P
P/S-2/Z7
R
R/S-3/Z7
C
C/
S-4/
Z7
R
R/S-5/Z7
C
C/
S-6/
Z7
R
R/S-7/Z7
R
R/S-8/Z7
C
C/
S-9/
Z7
R
R/S-10/Z7
R
R/S-11/Z7
C
C/
S-
12/
Z7
R
R/S-13/Z7
R
R/T-1/Z8
R
R/T-2/Z8
C
C/T-
3/
Z8
R
R/T-4/Z8
R
R/T-5/Z8
R
R/T-6/Z8
R
R/T-7/Z8
C
C/T-
8/
Z8
R
R/T-9/Z8
P
P/T-10/Z8 CRAC/CRAH redundancy N+1
G
Gap
Row U
R
R/U-1/Z7
C
C/
R
R/U-3/Z7
R
R/U-4/Z7
C
C/
R
R/U-6/Z7
R
R/U-7/Z7
C
C/
R
R/U-9/Z7
C
C/
R
R/U-11/Z7 P
Row V
P
R
R/V-2/Z8
R
R/V-3/Z8
C
C/
R
R/V-5/Z8
R
R/V-6/Z8
R
R/V-7/Z8
C
C/
R
R/V-9/Z8
R
R/V-10/Z8
Containment type None
U-2/ U-5/ U-8/ U- P/U-12/Z7 P/V-1/Z8 V-4/ V-8/
Z7 Z7 Z7 10/ Z8 Z8
Z7
Design Attributes
OVERVIEW Value Unit
Target availability Tier 3 Tier
Annualized PUE at 100% load 1.49 / 1.62 / 1.40
Data center IT capacity 910 kW
2
IT & facility floor space 15400 ft
Average density 6.5 kW/rack
FACILITY POWER Value Unit
Total amps (main bus) 3200 A
Input voltage (main bus) 480 V
Switchboard kAIC 65 kA
Power path Dual
Generator redundancy N+1
IT space UPS capacity 1200 kW
IT space UPS redundancy 2N
IT space UPS runtime @ rated load 6 minutes
IT space UPS output voltage 480 V
Facility cooling UPS capacity 72 kW
Facility cooling UPS redundancy 2N
Facility cooling UPS runtime @ rated load 12 minutes
FACILITY COOLING Value Unit
Total cooling capacity 1196 kW
Input voltage 480 V
Heat rejection medium Chilled water
Mechanical redundancy 2N
Outdoor heat exchange Water-cooled chiller with cooling tower
Coolant supply temperature 46 F
Coolant return temperature 56 F
Storage tank size 7000 gallons
Ride-through time 7 minutes
Economizer type Water-side
Good design and quality construction alone do not ensure a highly available &
efficient data center. Data centers require on-going monitoring and management to
ensure the facility lives up to its design intent. StruxureWare for Data Centers is a
software management suite designed to collect and manage data about a data
center’s assets, resource use, and operational status throughout the life cycle of the
facility. This information is then distributed, integrated, and applied in ways that help
managers optimize the data center’s performance and meet IT, business, and
service-oriented goals. From IT assets to racks, rows, rooms and buildings,
StruxureWare for Data Centers delivers the right information to the right users at the
right time.
Control level: Experts, on site or remotely, can control process performance and
ensure business continuity in real time, while tracking energy consumption in a highly
critical and secure environment.
Operations level: Functional managers can optimize operations, energy, and assets
through smart analytical tools, often spanning multiple sites.
Enterprise level: C-level executives can drive their sustainability strategy efficiently,
choosing the best scenario that meets their business objective to conserve
enterprise-wide resources.
StruxureWare for Data Centers allows for flexibility when requirements and
implementation strategies change over time. StruxureWare software applications
and suites simplify integration time, improve reliability, enhance visibility to energy
information, and streamline operational efficiency.
>
© 2013 Schneider Electric. All rights reserved.
Demo:
Visit www.apc.com/software to learn more about StruxureWare for Data Centers!
Bill of materials
One-line schematics
> Click here to register to receive the Engineering Package for this design, or email
ReferenceDesigns@Schneider-Electric.com.