SECTION 23 05 41
NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT
23 05 41 - 1
12-06M
23 05 41 - 2
12-06M
material, such as, furniture. This allowance may not be taken after
occupancy. The room attenuating effect is defined as the difference
between sound power level emitted to room and sound pressure level
in room.
4. In absence of specified measurement requirements, measure equipment
noise levels three feet from equipment and at an elevation of maxi-
mum noise generation.
//C. Seismic Restraint Requirements:
1. Equipment:
a. All mechanical equipment not supported with isolators external to
the unit shall be securely anchored to the structure. Such
mechanical equipment shall be properly supported to resist a
horizontal force of // 50 // 20 // percent of the weight of the
equipment furnished.
b. All mechanical equipment mounted on vibration isolators shall be
provided with seismic restraints capable of resisting a
horizontal force of // 100 // 50 // percent of the weight of the
equipment furnished.
2. Piping: Refer to specification Section 23 05 11, COMMON WORK RESULTS
FOR HVAC and STEAM GENERATION.
3. Ductwork: Refer to specification Section 23 31 00, HVAC DUCTS AND
CASINGS.
D. Allowable Vibration Tolerances for Rotating, Non-reciprocating Equip-
ment: Not to exceed a self-excited vibration maximum velocity of 5 mm
per second (0.20 inch per second) RMS, filter in, when measured with a
vibration meter on bearing caps of machine in vertical, horizontal and
axial directions or measured at equipment mounting feet if bearings are
concealed. Measurements for internally isolated fans and motors may be
made at the mounting feet.
23 05 41 - 3
12-06M
1.4 SUBMITTALS
A. Submit in accordance with specification Section 01 33 23, SHOP
DRAWINGS, PRODUCT DATA, and SAMPLES.
B. Manufacturer's Literature and Data:
1. Vibration isolators:
a. Floor mountings
b. Hangers
c. Snubbers
d. Thrust restraints
2. Bases.
//3. Seismic restraint provisions and bolting.//
4. Acoustical enclosures.
C. Isolator manufacturer shall furnish with submittal load calculations
for selection of isolators, including supplemental bases, based on
lowest operating speed of equipment supported.
//D. Seismic Requirements: Submittals are required for all equipment an-
chors, supports and seismic restraints. Submittals shall include
weights, dimensions, standard connections, and manufacturer's
certification that all specified equipment will withstand seismic
Lateral Force requirements as shown on drawings.//
1.5 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification to the
extent referenced. The publications are referenced in the text by the
basic designation only.
B. American Society of Heating, Refrigerating and Air-Conditioning
Engineers, Inc. (ASHRAE):
2009 ...................Fundamentals Handbook, Chapter 7, Sound and
Vibration
C. American Society for Testing and Materials (ASTM):
A123/A123M-09...........Standard Specification for Zinc (Hot-Dip
Galvanized) Coatings on Iron and Steel Products
A307-07b................Standard Specification for Carbon Steel Bolts
and Studs, 60,000 PSI Tensile Strength
D2240-05(2010)..........Standard Test Method for Rubber Property -
Durometer Hardness
D. Manufacturers Standardization (MSS):
SP-58-2009..............Pipe Hangers and Supports-Materials, Design and
Manufacture
23 05 41 - 4
12-06M
23 05 41 - 5
12-06M
23 05 41 - 6
12-06M
23 05 41 - 7
12-06M
23 05 41 - 8
12-06M
23 05 41 - 9
12-06M
23 05 41 - 10
02-01-15
EQUIPMENT ON GRADE 20FT FLOOR SPAN 30FT FLOOR SPAN 40FT FLOOR SPAN 50FT FLOOR SPAN
BASE ISOL MIN BASE ISOL MIN BASE ISOL MIN BASE ISOL MIN BASE ISOL MIN
TYPE TYPE DEFL TYPE TYPE DEFL TYPE TYPE DEFL TYPE TYPE DEFL TYPE TYPE DEFL
REFRIGERATION MACHINES
ABSORPTION --- D 0.3 --- SP 0.8 --- SP 1.5 --- SP 1.5 --- SP 2.0
PACKAGED HERMETIC --- D 0.3 --- SP 0.8 --- SP 1.5 --- SP 1.5 R SP 2.5
OPEN CENTRIFUGAL B D 0.3 B SP 0.8 --- SP 1.5 B SP 1.5 B SP 3.5
RECIPROCATING:
ALL --- D 0.3 --- SP 0.8 R SP 2.0 R SP 2.5 R SP 3.5
PUMPS
CLOSE UP TO --- --- --- --- D,L, --- --- D,L, --- --- D,L, --- --- D,L, ---
COUPLED 1-1/2 W W W W
HP
2 HP --- --- --- I S 0.8 I S 1.5 I S 1.5 I S 2.0
&
OVER
T-1
12-06M
EQUIPMENT ON GRADE 20FT FLOOR SPAN 30FT FLOOR SPAN 40FT FLOOR SPAN 50FT FLOOR SPAN
BASE ISOL MIN BASE ISOL MIN BASE ISOL MIN BASE ISOL MIN BASE ISOL MIN
TYPE TYPE DEFL TYPE TYPE DEFL TYPE TYPE DEFL TYPE TYPE DEFL TYPE TYPE DEFL
LARGE Up to --- --- --- --- S 0.75 --- S 1.50 --- S 1.50 --- --- NA
INLINE 25 HP
26 HP --- --- --- --- S 1.0 --- S 1.50 --- S 2.50 --- --- NA
THRU
30 HP
UP TO --- --- --- --- D,L, --- --- D,L, --- --- D,L, --- --- D,L, ---
10 HP W W W W
BASE 15 HP I S 1.0 I S 1.0 I S 2.0 I S 2.0 I S 2.0
MOUNTED THRU
40 HP
50 HP I S 1.0 I S 1.0 I S 2.0 I S 2.5 I S 2.5
&
OVER
ROOF FANS
ABOVE OCCUPIED AREAS:
5 HP & OVER --- --- --- CB S 1.0 CB S 1.0 CB S 1.0 CB S 1.0
CENTRIFUGAL FANS
UP TO 50 HP:
UP TO 200 RPM B N 0.3 B S 2.5 B S 2.5 B S 3.5 B S 3.5
201 - 300 RPM B N 0.3 B S 2.0 B S 2.5 B S 2.5 B S 3.5
301 - 500 RPM B N 0.3 B S 2.0 B S 2.0 B S 2.5 B S 3.5
501 RPM & OVER B N 0.3 B S 2.0 B S 2.0 B S 2.0 B S 2.5
T-2
12-06M
EQUIPMENT ON GRADE 20FT FLOOR SPAN 30FT FLOOR SPAN 40FT FLOOR SPAN 50FT FLOOR SPAN
BASE ISOL MIN BASE ISOL MIN BASE ISOL MIN BASE ISOL MIN BASE ISOL MIN
TYPE TYPE DEFL TYPE TYPE DEFL TYPE TYPE DEFL TYPE TYPE DEFL TYPE TYPE DEFL
60 HP & OVER:
UP TO 300 RPM B S 2.0 I S 2.5 I S 3.5 I S 3.5 I S 3.5
301 - 500 RPM B S 2.0 I S 2.0 I S 2.5 I S 3.5 I S 3.5
501 RPM & OVER B S 1.0 I S 2.0 I S 2.0 I S 2.5 I S 2.5
COOLING TOWERS
UP TO 500 RPM --- --- --- --- SP 2.5 --- SP 2.5 --- SP 2.5 --- SP 3.5
501 RPM & OVER --- --- --- --- SP 0.75 --- SP 0.75 --- SP 1.5 --- SP 2.5
INTERNAL COMBUSTION ENGINES
UP TO 25 HP I N 0.75 I N 1.5 I S 2.5 I S 3.5 I S 4.5
30 THRU 100 HP I N 0.75 I N 1.5 I S 2.5 I S 3.5 I S 4.5
125 HP & OVER I N 0.75 I N 1.5 I S 2.5 I S 3.5 I S 4.5
AIR HANDLING UNIT PACKAGES
SUSPENDED:
UP THRU 5 HP --- --- --- --- H 1.0 --- H 1.0 --- H 1.0 --- H 1.0
7-1/2 HP & OVER:
UP TO 500 RPM --- --- --- --- H, 1.5 --- H, 2.5 --- H, 2.5 --- H, 2.5
THR THR THR THR
501 RPM & OVER --- --- --- --- H, 0.8 --- H, 0.8 --- H,TH 0.8 --- H,TH 2.0
THR THR R R
T-3
12-06M
EQUIPMENT ON GRADE 20FT FLOOR SPAN 30FT FLOOR SPAN 40FT FLOOR SPAN 50FT FLOOR SPAN
BASE ISOL MIN BASE ISOL MIN BASE ISOL MIN BASE ISOL MIN BASE ISOL MIN
TYPE TYPE DEFL TYPE TYPE DEFL TYPE TYPE DEFL TYPE TYPE DEFL TYPE TYPE DEFL
FLOOR MOUNTED:
UP THRU 5 HP --- D --- --- S 1.0 --- S 1.0 --- S 1.0 --- S 1.0
7-1/2 HP & OVER:
UP TO 500 RPM --- D --- R S, 1.5 R S, 2.5 R S, 2.5 R S, 2.5
THR THR THR THR
501 RPM & OVER --- D --- --- S, 0.8 --- S, 0.8 R S, 1.5 R S, 2.0
THR THR THR THR
HEAT PUMPS
ALL --- S 0.75 --- S 0.75 --- S 0.75 CB S 1.5 --- --- NA
CONDENSING UNITS
ALL --- SS 0.25 --- SS 0.75 --- SS 1.5 CB SS 1.5 --- --- NA
IN-LINE CENTRIFUGAL AND VANE AXIAL FANS, FLOOR MOUNTED: (APR 9)
UP THRU 50 HP:
UP TO 300 RPM --- D --- R S 2.5 R S 2.5 R S 2.5 R S 3.5
301 - 500 RPM --- D --- R S 2.0 R S 2.0 R S 2.5 R S 2.5
501 - & OVER --- D --- --- S 1.0 --- S 1.0 R S 2.0 R S 2.5
60 HP AND OVER:
301 - 500 RPM R S 1.0 R S 2.0 R S 2.0 R S 2.5 R S 3.5
501 RPM & OVER R S 1.0 R S 2.0 R S 2.0 R S 2.0 R S 2.5
T-4
12-06M
NOTES:
1. Edit the Table above to suit where isolator, other than those shown, are used, such as for seismic restraints and
position limit stops.
2. For suspended floors lighter than 100 mm (4 inch) thick concrete, select deflection requirements from next higher span.
3. For separate chiller building on grade, pump isolators may be omitted.
4. Direct bolt fire pumps to concrete base. Provide pads (D) for domestic water booster pump package.
5. For projects in seismic areas, use only SS & DS type isolators and snubbers.
6. For floor mounted in-line centrifugal blowers (ARR 1): use "B" type in lieu of "R" type base.
7. Suspended: Use "H" isolators of same deflection as floor mounted.
T-5