Refrigeration IIAR 4 PR1
Refrigeration IIAR 4 PR1
Refrigeration IIAR 4 PR1
Approved by
the American
National
Standards
Institute
Xxxx x, 201x
(Revision D).
Metric Policy
The IIAR metric policy for ANSI standards, bulletins and all IIAR publications is to use the common
engineering “inch-pound” (IP) unit system as the primary unit of measure, and the International
System of Units (SI), as defined in United States National Institute of Standards and Technology
Special Publication 330 “The International System of Units,” for secondary units.
Normative/Informative Elements
This standard includes both Normative (required) and Informative (advisory) language. The bodies
of the standard and labeled appendices are Normative. The forward, notes, and any appendices
labeled Informative are non-mandatory. Informative material shall never be regarded as a
requirement.
Notice
The information contained in this Standard has been obtained from sources believed to be reliable.
However, it should not be assumed that all acceptable methods or procedures are contained in this
document, or that additional measures may not be required under certain circumstances or conditions.
The Standards Committee and Consensus Body that approved the Standard were balanced to assure
that individuals from competent and concerned interests have had an opportunity to participate. The
proposed Standard was made available for review and comment for additional input from industry,
academia, regulatory agencies and others.
The IIAR does not “approve” or “endorse” any products, services or methods. This document
should not be used or referenced in any way which would imply such approval or endorsement.
Note that the various codes and regulations referenced in this document may be amended from time
to time and it should be assumed that the versions referenced herein are the versions of such codes
and regulations in effect at the time of the publication of this Standard.
The IIAR uses its best efforts to promulgate Standards for the benefit of the public in light of
available information and accepted industry practices. However, the IIAR does not guarantee, certify,
or assume the safety or performance of any products, components or systems tested, installed, or
operated in accordance with IIAR’s Standards or that any tests conducted under its Standards will be
nonhazardous or free from risk.
(Edit upon approval from ANSI): This is a proposed Standard issued for public notice-and-comment
under consensus procedures accredited by the American National Standards Institute. It is not a
final standard and shall not be used in place of an American National Standard.
Copyright
This document may not, in whole or in part, be reproduced, copied or disseminated, entered into or stored in
a computer database or retrieval system, or otherwise utilized without the prior written consent of the
IIAR.
Copyright © 201x by
INTERNATIONAL INSTITUTE OF AMMONIA REFRIGERATION
All Rights Reserved
Foreword
(Informative)
This document is a standard for the installation of closed-circuit ammonia mechanical refrigeration systems.
Additional requirements may be necessary because of particular circumstances, project specifications or
other jurisdictional considerations. Note that this standard does not constitute a comprehensive detailed
technical design manual and should not be used as such.
The standard is intended to be a reference document covering the minimum requirements for specific
aspects of closed-circuit ammonia mechanical refrigeration systems to supplement existing IIAR refrigeration
standards and refrigeration standards issued by other organizations such as ASHRAE, ASME and ANSI.
At the time of publication of this revision of the standard, the IIAR Standards Review Committee had the
following members:
Table of Contents
Section 1 Purpose ............................................................................................................................. 1
Section 2 Scope ................................................................................................................................. 1
Section 3 Definitions .......................................................................................................................... 2
Section 4 References ........................................................................................................................ 2
Section 5 General Requirements ...................................................................................................... 4
Section 6 Compressors .................................................................................................................... 5
Section 7 Condensers....................................................................................................................... 5
Section 8 Evaporators ...................................................................................................................... 7
Section 9 Pressure Vessels.............................................................................................................. 7
Section 10 Pipe and Valve Installation ............................................................................................. 8
Section 11 Components and Controls Installation ........................................................................ 10
Section 12 Insulation ....................................................................................................................... 11
Section 13 Testing of Installation ................................................................................................... 11
Section 14 Sources of References (Informative) .......................................................................... 14
Appendix A (Normative) Minimum Values for Leak Test Pressure – NH3 .................................... 15
Appendix B (Informative) Insulation for Refrigeration Systems ................................................... 15
Section 1
Purpose
The purpose of this standard is to provide minimum requirements for the installation of closed-circuit ammonia
mechanical refrigeration systems and overpressure device piping when used in conjunction with a closed-
circuit ammonia refrigeration system.
Section 2
Scope
This standard shall apply only to closed-circuit refrigeration systems utilizing ammonia as the refrigerant and
overpressure device piping when used in conjunction with a closed-circuit ammonia mechanical
refrigeration system.
2.1 This is a standard for the installation of closed-circuit ammonia mechanical refrigeration systems and is not
intended to supplant existing safety codes.
In cases where the jurisdictional authority has specific code requirements that are more stringent than those herein,
that authority shall prevail.
2.3 This standard does not apply to ammonia absorption refrigeration systems.
Section 3
Definitions
Section 4
References
4.1.1.2 ASME B31.5, 2013, Refrigeration Piping and Heat Transfer Components.
4.1.1.3 ASME Boiler and Pressure Vessel Code Section IX, 2013, Welding and Brazing
Qualifications.
4.1.2.2 ASTM A105/A105M-03, Standard Specification for Carbon Steel Forgings for Piping
Applications;
4.1.2.3 ASTM A106/A106M-04b Standard Specification for Seamless Carbon Steel Pipe
for High- Temperature Service;
4.1.2.4 ASTM A120-84, Specification for Pipe, Steel, Black and Hot-Dipped Zinc-Coated (Galvanized)
Welded and Seamless for Ordinary Uses (Withdrawn 1987, replaced by ASTM A53
[ref.4.1.2.1]);
4.1.2.5 ASTM A181/A181M-01, Standard Specification for Carbon Steel Forgings, for General-
Purpose Piping;
4.1.2.6 ASTM A193/A193M-04c, Standard Specification for Alloy-Steel and Stainless Steel Bolting
Materials for High-Temperature Service;
4.1.2.7 ASTM A234/A234M-04, Standard Specification for Piping Fittings of Wrought Carbon
Steel and Alloy Steel for Moderate and High Temperature Service;
4.1.2.8 ASTM A307-04, Standard Specification for Carbon Steel Bolts and Studs, 60,000 PSI Tensile
Strength;
4.1.2.9 ASTM A312/A312M-04b, Standard Specification for Seamless, Welded, and Heavily Cold
Worked Austenitic Stainless Steel Pipes;
4.1.2.10 ASTM A320/A320M-04, Standard Specification for Alloy-Steel and Stainless Steel Bolting
Materials for Low-Temperature Service;
4.1.2.11 ASTM A333/A333M-04a, Standard Specification for Seamless and Welded Steel Pipe
for Low-Temperature Service;
4.1.2.12 ASTM A403/A403M-04, Standard Specification for Wrought Austenitic Stainless Steel
Piping Fittings;
4.1.2.13 ASTM A420/A420M-04, Standard Specification for Piping Fittings of Wrought Carbon
Steel and Alloy Steel for Low-Temperature Service;
4.1.2.14 ASTM A575-96, Standard Specification of Steel Bars, Carbon, Merchant Quality, M Grades;
4.1.2.15 ASTM A707/A707M-02, Standard Specification for Forged Carbon and Alloy Steel
Flanges for Low-Temperature Service.
4.1.3 American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc. (ASHRAE),
ANSI/ASHRAE Standard 15-2010, Safety Standard for Mechanical Refrigeration.
4.1.4 National Fire Protection Association (NFPA), NFPA Standard 70, National Electric Code (NEC),
2013.
4.1.5 U.S. Department of Transportation (US DoT), 49 CFR Part 172, Hazardous Materials Regulations,
2013.
4.1.6 International Safety Equipment Association (ISEA), ANSI/ISEA Z358.1, World Safety Standard for
Emergency Eyewash and Shower Equipment, 2009.
4.2.3 Occupational Safety and Health Administration (OSHA), U.S. Department of Labor, Governing
editions:
4.2.5 Manufacturers Standardization Society of the Valve and Fittings Industry (MSS), ANSI/
MSS Standard Practice SP 58-2009, Pipe Hangers and Supports, Selection and Application.
4.2.6 American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE), 2010
ASHRAE Handbook — Refrigeration, System Practices for Ammonia Refrigerant, Chapter 2, Page
2.8.
Section 5
General Requirements
5.1.1 Installation shall be executed by individuals who through experience and training have been
taught the skills necessary to safely receive, transport, mount and fit refrigeration equipment,
piping and components in a manner so as to assemble a complete refrigeration system and not
harm themselves, others, or the structure in which the equipment is to be installed.
5.1.1.1 Individuals who are in training or others who do not have these skills may participate in
the installation provided they are closely supervised by those listed in Section 5.1.1.
5.2.1 All individuals participating in the installation shall be properly and adequately trained in all
applicable safety procedures prior to participating in the installation.
5.2.2 All individuals participating in the installation shall be properly and adequately equipped with
all necessary personnel protective equipment (PPE) for their protection and safety devices for
the protection of others working in their immediate area.
5.3 Materials
5.3.1 General
All materials used in the installation of the equipment designated in Sections 6 –11 shall be suitable for
ammonia refrigerant (per Section 4) at the coincident temperature and pressure to which the component shall be
subjected. No materials shall be used that will deteriorate because of the presence of ammonia refrigerant or
lubricating oil, or a combination of both, or any normal contaminant such as air or water. Where external
surfaces of the equipment are exposed to the corrosive effects of air, water or other media, such exposed
materials must be suitable for the application.
5.3.2 Metallic Materials
Cast iron, malleable iron, nodular iron, steel, cast steel, and alloy steel shall meet ASME B31.5-2013
(ref.4.1.1.2) or Section VIII, Division 1, ASME Boiler and Pressure Vessel Code (ref.4.1.1.1), as applicable.
5.3.2.1 Zinc, copper, and copper alloys shall not be used in contact with or for containment of ammonia.
Copper-containing anti-seize and/or lubricating compounds shall not be used in contact with
ammonia piping. Copper as a component of brass alloys may be used for bearings or other non-
refrigerant containment uses.
5.3.2.2 Other metallic materials, such as aluminum, aluminum alloys, lead, tin, and lead-tin alloys may be
used if they conform to Section 5.3.1. Where tin and tin-lead alloys are used, the alloy composition
shall be suitable for the temperatures of application.
EXAMPLE: Typical uses would be tubing, valves, gaskets, packing, and joint compounds.
5.3.3 Non-Metallic Materials
5.4.1 All equipment, pipe, fittings, valves and components shall be positioned to insure that
appropriate service clearances are provided.
5.4.2 Where equipment, pipe, fittings, valves and components are supported by the roof or ceiling
structure, the structure shall be designed to support the weight of all suspended piping, equipment and
components and be adequate enough to handle seismic conditions expected.
5.4.3 Foundations and supports for equipment shall be of noncombustible construction and capable of
supporting loads imposed by such units. Manufacturer’s recommendations shall be considered.
EXCEPTION: It shall be permissible to use pressure treated wood or synthetic bases or
“sleepers” under pipe stand bases to protect the roof from damage or between the pipe and stand (e.g.
shims).
5.4.4 Refrigeration piping or components with cold surfaces shall be properly insulated and conditioned to
prevent or mitigate condensation and shall not be located over electrical equipment.
EXCEPTION: Where the potential for condensation or drips above the electrical equipment cannot be
avoided, the electrical equipment shall be adequately protected.
Section 6
Compressor Installation
6.1 Compressors
This section applies to compressors which are utilized in closed-circuit ammonia refrigerating systems.
6.1.1 All exposed rotating components (e.g., shafts, belts, pulleys, flywheels, couplings) shall be
protected with screens or guards in accordance with approved safety standards [ref.4.2.3.1].
6.1.2 The compressor(s) shall be installed only where the building structure is designed to provide
adequate strength and rigidity to the compressor(s).
6.1.3 Foundations and supports for compressor units and other equipment shall not impede
drainage to floor drains.
6.1.4 All machinery shall be mounted in such a manner as to prevent excessive vibration from being
transmitted to the building structure or to the connected equipment. Isolation materials such as
rubber are permissible between the foundation and equipment.
6.1.5 Electrical equipment and wiring shall be installed in accordance with the NFPA Standard 70:
National Electrical Code (NEC) (ref.4.1.4).
Section 7
Condenser Installation
7.1 Condensers
This section applies to air cooled, water cooled, plate type, plate and frame type and evaporative type refrigerant
condensers which are applied to closed-circuit ammonia refrigerating systems.
7.1.1 All exposed rotating components (e.g., shafts, belts, pulleys, flywheels, couplings) shall be protected
with screens or guards in accordance with approved safety standards [ref.4.2.3.1].
7.1.2 The condenser(s) shall be installed only where the building structure is designed to provide
adequate strength and rigidity to house and support the condenser(s).
7.1.3 All machinery shall be mounted in such a manner as to prevent excessive vibration from being
transmitted to the building structure, or to connected equipment. Isolation materials such as rubber
are permissible between the foundation and equipment.
7.1.4 Electrical equipment and wiring shall be installed in accordance with the NFPA Standard 70:
National Electrical Code (NEC) (ref.4.1.4).
Section 8
Evaporator Installation
8.1 Evaporators
This section applies to forced air evaporator coils, shell and tube evaporators, plate type and plate and frame
evaporators which are applied to closed-circuit ammonia refrigerating systems.
8.1.1 All exposed rotating components (e.g., shafts, belts, pulleys, flywheels, couplings) shall be
protected with screens or guards in accordance with approved safety standards [ref.4.2.3.1].
8.1.2 The evaporator(s) shall be installed only where the building structure is designed to provide
adequate strength and rigidity to house and support all evaporator(s). Where appropriate seismic
bracing may be required.
8.1.3 All machinery shall be mounted in such a manner as to prevent excessive vibration from
being transmitted to the building structure, or to connected equipment. Isolation materials such
as rubber are permissible between the structural support or foundation and equipment.
8.1.4 Electrical equipment and wiring shall be installed in accordance with the applicable edition of
the NFPA Standard 70: National Electrical Code (NEC) (ref.4.1.4).
Section 9
This section applies to high pressure and low pressure vessels which are applied for use in closed-circuit
ammonia refrigerating systems.
EXCEPTION:
Application design pressures for refrigerant-containing pressure vessels incorporated into other
equipment which exceed Section 9.1 minimum shall prevail.
EXAMPLE: Pressure vessel shells of shell and tube evaporators.
9.1.1 The pressure vessel(s) shall be installed only where the building structure is designed to
provide adequate strength and rigidity to house and support the pressure vessels for any
operating condition that may occur..
9.1.2 Where the pressure vessel(s) is supported by the roof or ceiling structure, the structure shall
be designed to support the weight of all suspended piping and equipment.
9.1.3 Electrical equipment and wiring shall be installed in accordance with the applicable edition of
the NFPA Standard 70: National Electrical Code (NEC) (ref.4.1.4).
Section 10
Pipe and Valve Installation
10.1 General
This section applies to pipe, fittings and valves for use in closed-circuit ammonia refrigerating systems.
10.1.1 The pipe, fittings and valves shall only be installed where the building structure is designed
to provide adequate strength and rigidity to house and support all compressors, accumulators,
pumps and other equipment.
10.1.2 Where pipe, fittings and valves are supported by the roof or ceiling structure, the structure
shall be designed to support the weight of all suspended piping and equipment.
10.1.3 Valves shall not be aggressively forced (e.g. beyond safe and reasonable force) to open or
close.
10.1.4 Hot tap tie-ins are a last resort option. Hot Tapping, if necessary, shall follow the hot tap
equipment manufacturer procedures and be performed by a qualified and trained service firm.
10.2 The piping materials, whether fabricated in a shop or as a field erection, shall comply with ASME
B31.5-2013, Refrigeration Piping [ref.4.1.1.2], except where noted.
10.3 Pipe
10.3.1 Pipe shall be new, clean and free of rust, scale, sand and dirt.
10.3.2 Where ½” and smaller pipe must be used, it is recommended that the use be limited to short
runs and/or to instrumentation. Where the use of ½” and smaller pipe is required in the
engineering design, it shall be adequately supported and/or protected to prevent damage. See
Section 10.5.3 for Threaded Joints.
NOTE:
Refer to ANSI/IIAR 3-2012 (ref.4.1.7.3) for the manufacturing design performance requirements of
ammonia refrigeration valves and strainers.
10.4.1 Valves shall be oriented in accordance with the respective manufacturer’s specification or as
shown on the drawings.
10.4.2 Valve gasket materials shall match valve manufacturer’s specifications, be compatible with
ammonia and of the thickness specified. Flange bolts shall be torqued as indicated in the valve
manufacturer’s installation documents.
10.4.3 Strainers shall be fitted with provision for refrigerant removal to facilitate maintenance.
10.4.4 Shut-off valves used to isolate equipment, control valves, controls or other components from other
parts of the system for the purpose of maintenance or repair shall be capable of being locked out per the
facility’s “Lock Out / Tag Out” procedure (ref.4.2.3.5).
Valves (or flange sets) with specialized tightening requirements shall be installed according to manufacturer’s
instructions.
10.5.1 Piping joints shall be supported and in alignment such that the joint assembly does not induce
distortion and stress.
10.5.2 Flanges
10.5.2.1 The mating surfaces of the gasketed joints shall be parallel, aligned and perpendicular to the
pipe axis, in good condition and free of debris and corrosion.
10.5.2.3 Nuts, bolts, cap screws and washers shall meet manufacturer’s requirements for the
application. Bolt threads shall extend completely through the mating nut.
10.5.3.1 Thread compound used in threaded joints shall be suitable for service in an ammonia
refrigerating system.
10.5.3.2 Threaded joints that require seal welding shall be made up without any thread compound.
10.5.3.3 Threaded joints shall not be used for refrigerant piping larger than 2”.
10.5.5 Special care shall be taken during fabrication and assembly to assure that the inside of the
7
Copyright © 201x International Institute of Ammonia Refrigeration. All Rights Reserved.
ANSI/IIAR 4-201x Revision D
Installation of Closed-Circuit Ammonia Mechanical Refrigeration Systems
10.5.5.1 Pipe and system components shall be properly stored during installation to prevent
contaminants from getting inside the system.
10.5.5.3 Cutting and welding procedures should be developed to keep the inside of the piping
system clean.
Section 11
Components and Controls Installation
This section applies to components and controls applied for use in closed-circuit ammonia refrigeration
systems.
11.1.1 All exposed rotating components (e.g., shafts, belts, pulleys, flywheels, couplings) shall be
protected with screens or guards in accordance with approved safety standards [ref.4.2.3.1].
11.1.2 The refrigerant pump(s) shall be installed only where the building structure is designed to
provide adequate strength and rigidity to house and support the pump(s).
11.1.3 Where refrigerant pump(s) are supported by the roof or ceiling structure, the structure shall be
designed to support the weight of all suspended piping and equipment.
11.1.4 Foundations and supports for refrigerant pump(s) and other equipment shall be of
noncombustible construction and capable of supporting loads imposed by such units.
Manufacturer’s recommendations shall be considered.
11.1.5 All machinery shall be mounted in such a manner as to prevent excessive vibration from being
transmitted to the building structure, or to connected equipment. Isolation materials such as
rubber are permissible between the foundation and equipment.
11.1.6 Refrigeration piping attached to a refrigerant pump(s) which could cause condensation or drips
shall not be located over electrical equipment.
11.1.7 Electrical equipment and wiring shall be installed in accordance with NFPA Standard 70:
National Electrical Code (NEC) (ref.4.1.4).
11.1.8 Suction lines, low-temperature liquid lines, accumulators, surge drums and similar cold surfaces
shall be insulated to mitigate and control condensation.
EXCEPTION:
Surfaces where condensation or ice could form in valve groups or in equipment shall be permitted to
be left un-insulated to accommodate access for service, provided the adjacent insulation has its’
vapor retarder sealed to the piping or equipment.
11.2 Visual Liquid Level Indicators: Bull’s- Eyes, tubular glass and flat “armored glass”
linear sight glasses/sight columns
11.2.1 Visual Liquid Level Indicators constructed using Bull’s-Eye type indicator(s)
11.2.1.1 All visual liquid level indicators shall be inspected prior to installation. Any indicator found to
have a scratch, chip or any defect shall be discarded.
7
Copyright © 201x International Institute of Ammonia Refrigeration. All Rights Reserved.
ANSI/IIAR 4-201x Revision D
Installation of Closed-Circuit Ammonia Mechanical Refrigeration Systems
11.2.1.3 The glass component of the indicator shall not be allowed to come into contact with any metal
or hard surfaces when assembling.
11.2.1.5 Gaskets used shall be those recommended by the manufacturer of the visual liquid level
indicator.
11.2.1.6 The retaining ring shall be installed as per the specification provided by the manufacturer.
11.2.2 Visual Liquid Level Indicators constructed of tubular glass and flat “armored glass”
11.2.2.1 Linear liquid level indicators (sight columns) shall be fitted with internal check-type shut-
off valves (e.g. ball flow check). This type of site glass shall also have robust protection
against accidental breakage 360 degrees around the glass tube, over the full length of the
tube.
Section 12
Insulation
This section applies to components and controls applied for use in closed-circuit ammonia refrigeration
systems.
12.1 All refrigerant lines which operate slightly above or below dew point shall be insulated to prevent or
mitigate condensation.
12.1.1 All exterior refrigerant lines shall have a thickness determined to minimize heat gain into the
refrigerant within the piping, according to good engineering practice.
12.1.2 All interior refrigerant lines which operate slightly above or below the corresponding dew
point shall be properly insulated and conditioned to prevent or mitigate condensation.
12.1.3 Surfaces where condensation or ice could form in valve groups or in equipment shall be permitted to
be left un-insulated to accommodate access for service, provided the adjacent insulation has its
vapor retarder sealed to the piping or equipment.
Section 13
Testing of Installation
13.1.1 Upon complete installation of or revision to a closed-circuit ammonia refrigeration system, the
system or affected part shall be tested for leaks before charging.
This field leak testing program for closed-circuit ammonia refrigerating systems is designed to assure a tight
system which will operate without any appreciable loss of refrigerant.
13.1.2.1 Valve off and isolate from any test pressures all refrigeration compressors, liquid pumps,
pressure switches and pressure transducers.
13.1.2.2 Remove all safety pressure relief devices and cap or plug the openings.
13.1.2.3 Open all solenoid, pressure-regulating, check or other control devices by means of their manual
lifting stems.
13.1.2.4 Open all other valves except those leading to the atmosphere.
13.1.2.5 Cap, plug, or lock shut all valves and devices leading to the atmosphere.
7
Copyright © 201x International Institute of Ammonia Refrigeration. All Rights Reserved.
ANSI/IIAR 4-201x Revision D
Installation of Closed-Circuit Ammonia Mechanical Refrigeration Systems
Section 14
Sources of References (Informative)
1. American National Standards Institute (ANSI) 25 West 43rd Street, 4th Floor
New York, NY 10036
www.ansi.org
2. American Petroleum Institute (API) 1220 L Street NW
Washington, DC 20005-4070
www.api.org
3. American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc. (ASHRAE) 1791 Tullie
Circle, N.E.
Atlanta, GA 30329
www.ashrae.org
4. American Society of Mechanical Engineers (ASME)
ASME International
Three Park Avenue
New York, NY 10016-5990
www.asme.org
5. American Society of Testing and Materials (ASTM)
ASTM International
100 Barr Harbor Drive
P.O. Box C700
West Conshohocken, PA 19428-2959
www.astm.org
6. International Institute of Ammonia Refrigeration (IIAR)
1001 N. Fairfax St., Suite 503
Alexandria, VA 22314-1797
www.iiar.org
Appendix A (Normative)
Minimum Values for Leak Test Pressure – NH3
Appendix B (Informative)
Insulation for Refrigeration Systems
Chapter 7 of the IIAR Piping Handbook [ref.4.2.2.1] covers insulation systems operating on below-
ambient temperature piping systems ranging from +50°F to –100°F for piping, fittings, valves, vessels,
equipment and
heat exchangers typically used in industrial refrigeration systems.
B.1 Purpose
The purpose of the insulation system is to conserve energy by preventing heat infiltration, preventing
condensation or ice formation, and minimizing corrosion.
The success of an insulation system for cold piping depends upon four factors: proper pipe preparation,
correct refrigeration and insulation system design, adequate insulation thickness, and proper installation
of the insulation and related materials such as vapor retarders, sealants, and protective jacketing. It is
critical to maintain the integrity of the vapor retarder system. The insulating system must be regularly
maintained
and inspected after installation.
B.2 Fundamentals of Insulation
Heat is a form of energy, always moving from a higher to a lower temperature.
There are three types of heat transfer:
conduction, through direct thermal contact between a hotter and a colder material, convection,
through natural or forced circulation of air or a fluid, and radiation, through exchange of the infrared
energy naturally given off by every object. Poor heat conductors are good insulation products. Water is a
good conductor of heat. Water and water vapor are the prime enemy of an insulation system.
Equipment or piping operating either steadily or cyclically at or above freezing (such as hot gas
defrost systems) may experience significant corrosion problems. Pipe legs or instruments protruding into
ambient-temperature areas may corrode faster than cold, insulated pipe mains.
Some areas of a piping system are more susceptible to corrosion than others. Where the risk of
corrosion is elevated, apply a primer-
paint coating system. The higher-risk areas include (but are not limited to) all pipe welds, control
valve groups, areas around pump bases or control columns, evaporator coil headers,
oil pots, valves, unions and flanges or any termination of insulation.
The insulation itself should be a low thermal conductivity material with low water vapor
permeability and it should provide moisture resistance. The types of insulation commonly used in
industrial refrigeration are: extruded polystyrene insulation, cellular glass, polyisocyanurate
insulation (The terms polyisocyanurate (PIR) and polyurethane (PU) are frequently used
interchangeably. The two products use the same raw materials, in different ratios) and closed-cell
phenolic.
Use a joint sealant on all insulations operating
at below-ambient conditions. The sealant should be resistant to liquid water and to water vapor and be
able to bond to the specific insulation surface. Use low-permeance insulation materials
and a continuous, effective vapor retarder system.
Jacketing on insulated refrigeration piping protects the insulation and vapor retarder from damage.
Store insulation in a cool, dry location and protect it from the weather before and during application.
Install vapor retarders and weather barriers over dry insulation.
Finish all welding and other hot work, as well as all pressure testing, before installing pipe insulation.
The surfaces to be insulated should be free from all oil, grease, loose scale, rust and foreign matter and
must be dry and free from frost. Complete site touch-up of shop coating (including preparation and
painting at field welds) before insulating. For insulation and insulation accessories, use specific
manufacturer instructions.