Design of Cantileaver Toe Wall (H 3.0m)
Design of Cantileaver Toe Wall (H 3.0m)
Design of Cantileaver Toe Wall (H 3.0m)
33.69 0.300 m
Y
3.000 m
2.050 m 0.450 m
0.450 m
3.000 m X
2
Surcharge Load = 10 kN/m
3
Soil Density = 18 kN/m
3
Concrete Density = 25 kN/m
Structural analysis shall be done according to the coulomb wedge
method.
W1+Q-Cw
F1
Sliding Angle,θ1 44.0 51.3 46.0
Active Earth Pressure kN 165.38 135.06 171.23
W2+Q
R2
R2
SLS ULS
Maximum Bearing Pressure σ 84.59 103.41
BS 5400-4
= 2
1990 0.15x 30 x 1000 x 389
Equ. 2 = 681 kNm > 93.4
Hence section is Singly Reinforcement
5.057𝑀𝑢
𝑧 = 0.5𝑑 1 + 1 −
𝑓𝑐𝑢 𝑏𝑑2
z = 378.6 mm
0.95d = 0.95 x 389
= 369.6 < 378.6
Therefore z = 369.6 mm
As*fy = f 'ct* Ac
Page 55
Reference Calculation Output
-6
єsh = 275 x 10 x 0.90 x 0.60 x 1.00
-6
= 148.5 x 10
For distribution, φ= 12 mm
2
As= 564.02 mm < As,prov = 754
Hence satisfies the Shrinkage & Temperature Reinforcement requirement
= 0.79 mm < 12 mm
Hence Deflection is OK
BS 5400-4
= 2
1990 0.15x 30 x 1000 x 389
Equ. 2 = 681 kNm > 12.21
Hence section is Singly Reinforcement
z = 387.7 mm
0.95d = 0.95 x 389
= 369.6 < 387.7
Therefore z = 369.6 mm
𝑀𝑢
Required reinforcement area 𝐴𝑠 = 0.87𝑓𝑦 𝑧
= 12.21 x 10^6
0.87 x 500 x 369.6
2
= 76 mm
BS 5400-4 Minimum reinforcement required = 0.15% bd
1990 = 0.15% x 1000 x 389
2
Cl 5.8.4.1 = 584 mm
BS 5400-4 Hence 𝐴𝑠,𝑟𝑒𝑞 = 584 mm2 T 12 @
2
1990 Provide T 12 @ 150 , 𝐴𝑠,𝑝𝑟𝑜𝑣 = 754 mm 150 mm
EXTENSION OF SOUTHERN EXPRESSWAY (ESE)
BS 5400-4
1990 Check for Shear
Cl 5.4.4
Shear Force at toe = 47.40 kN
2
Maximum Shear Stress at toe = 0.122 N/mm < 4.8 N/mm2
= < 0.75 𝑓𝑐𝑢
2
Hence OK 4.1079 N/mm
Page 58
Reference Calculation Output
Reinforcement Design for Toe Wall Base Heal
Maximum Sagging ULS Bending Moment, BMuls = 145.8 kNm
BS 5400-4
1990 Consider 1000mm length section, b = 1000 mm
Table 5,6 Assume, Cover = 55 mm
Bar dia meter = 16 mm
Effective Depth, d = 450 -16 /2 - 55
= 387 mm
BS 5400-4
= 2
1990 0.15x 30 x 1000 x 387
Equ. 2 = 674 kNm > 146
Hence section is Singly Reinforcement
Mu ,Maximum flexural capacity of a singly reinforced section
BS 5400-4
1990
Equ. 1
Equ.5 z, Lever arm
5.057𝑀𝑢
𝑧 = 0.5𝑑 1 + 1 −
𝑓𝑐𝑢 𝑏𝑑2
6
z = 0.5x 387 1+ 1 -5.057 x 146 x10^
30 x 1000 x 387 2
z = 370.4 mm
0.95d = 0.95 x 387
= 367.7 < 370.4
Therefore z = 367.7 mm
𝑀𝑢
Required reinforcement area 𝐴𝑠 = 0.87𝑓𝑦 𝑧
= 146 x 10^6
0.87 x 500 x 367.7
2
= 911 mm
BS 5400-4
1990 Check for Shear
Cl 5.4.4
Shear Force at Heal = 106.98 kN
2
Maximum Shear Stress at heal = 0.275 N/mm < 4.8 N/mm2
= < 0.75 𝑓𝑐𝑢
2
Hence OK 4.1079 N/mm
60
Reference Calculation Output
Shrinkage & Temperature Reinforcement
As*fy = f 'ct* Ac
-6
Fig. 14 kL = 275 x 10 (for 70% relative humidity)
Fig. 11 kC = 0.90 (for W/C ratio-0.5, cement content - 300)
Fig. 12 ke = 0.60 (for effective thickness 250)
kj = 1.00 (for long term)
-6
єsh = 275 x 10 x 0.90 x 0.60 x 1.00
-6
= 148.5 x 10
2
Single face reinforcement for thermal cracking As = 70.50 φ mm
For main reinforcement, φ= 16 mm
2
As= 1128 mm < As,prov = 1340
Hence satisfies the Shrinkage & Temperature Reinforcement requirement
EXTENSION OF SOUTHERN EXPRESSWAY (ESE)
DESIGN OFFICE Designed
For distribution, φ= 12 mm
2
As= 846.03 mm > As,prov = 754
Hence satisfies the Shrinkage & Temperature Reinforcement requirement
Summary of reinforcement
Toe Wall