SIEMENS End2End-L663.

occ

SUBESTACION SAN LUIS 60 kV

PRUEBAS END TO END L-663

PROTECCION PRINCIPAL - F003

Test Object - Device Settings

Substation/Bay:
Substation: San Luis Substation address: Lima
Bay: Línea L-663 Bay address: Tablero de Linea 663

Device:
Name/description: Protección Principal Manufacturer: Simens
Device type: 7SL86 Device address: F003
Serial/model number: BM1707008845
Additional info 1:
Additional info 2:

Nominal Values:
f nom: 60.00 Hz Number of phases: 3
V nom (secondary): 110.0 V V primary: 60.00 kV
I nom (secondary): 1.000 A I primary: 800.0 A

Residual Voltage/Current Factors:


VLN / VN: 1.732 IN / I nom: 1.000

Limits:
V max: 200.0 V I max: 50.00 A

Debounce/Deglitch Filters:
Debounce time: 3.000 ms Deglitch time: 0.000 s

Overload Detection:
Suppression time: 50.00 ms

Test Object - Overcurrent Parameters

General - Values:
TimeTolAbs: 0.10 s VT connection: n/a
TimeTolRel: 10.00 % CT starpoint connection: n/a
CurrentTolAbs: 0.10 Iref
CurrentTolRel: 5.00 %
Directional: No

Test Object - Distance Settings


System parameters:
Line length: 1.000 Ω Line angle: 75.00 °
PT connection: at line CT starpoint: Dir. line
Impedance correction no
1A/I nom:
Impedances in primary no
values:

Tolerances:
Tol. T rel.: 5.000 %
Tol. T abs. +: 50.00 ms Tol. T abs. -: 0.000 s
Tol. Z rel.: 5.000 % Tol. Z abs.: 50.00 mΩ

Página 1 de 37
SIEMENS End2End-L663.occ

Grounding factor:
kL mag.: 1.000000 kL angle: 0.000000°
Separate arc no
resistance:

Zone Settings:

Hardware Configuration

Test Equipment
Type Serial Number
CMC356 LC626U

Hardware Check
Performed At Result Details
22/01/2018 02:13:54 Passed
p.m.

Analog Outputs
Test Equipment Test Object
Connection
Device Connector Display Name
Terminal
CMC356 V A 1 V L1-E
LC626U 2 V L2-E
3 V L3-E
N
CMC356 V B 1 V(2)-1
LC626U N
CMC356 I A 1 I L1
LC626U 2 I L2
3 I L3
N

Página 2 de 37
SIEMENS End2End-L663.occ

Binary/Analog Inputs
Test Equipment Test Object
Connection
Device Connector Display Name
Terminal
CMC356 1+ Disparo
LC626U 1-
2+ Posición
Cerrado
2-
3+
3-
4+
4-
5+
5-
6+
6-
7+
7-
8+
8-
9+
9-
10+
10-
1
2
N

Binary Outputs
Test Equipment Test Object
Connection
Device Connector Display Name
Terminal
CMC356 1+ Bin. out 1
LC626U 1-
2+ Bin. out 2
2-
3+ Bin. out 3
3-
4+ Bin. out 4
4-
11 Bin. out 5
12 Bin. out 6
13 Bin. out 7
14 Bin. out 8
N

Analog DC Inputs
Test Equipment Test Object
Connection
Device Connector Display Name
Terminal
CMC356 V+ V1
LC626U V-
I+ I1
I-

Caso 1:

Test Settings

Data source:
Página 3 de 37
SIEMENS End2End-L663.occ
Path: D:\PROYECTOS\SIEMENS\END TO END ENERO 2018\END2END 663 SE SAN LUIS - SE
LIMATAMBO\END2END L663\C01\
File: C01 LU.CFG
Info: DIgSILENT PowerFactory

Analog Output:
Name Scale Min max
I L1 :L-663(1):Phase 100.00 % -1.88 A 1.42 A
Current A/Terminal i
I L2 :L-663(1):Phase 100.00 % -13.85 A 19.04 A
Current B/Terminal i
I L3 :L-663(1):Phase 100.00 % -1.30 A 0.84 A
Current C/Terminal i
V L1-E :L-663(1):Phase 100.00 % -89.49 V 93.87 V
Voltage A/Terminal i
V L2-E :L-663(1):Phase 100.00 % -90.69 V 90.68 V
Voltage B/Terminal i
V L3-E :L-663(1):Phase 100.00 % -92.80 V 91.12 V
Voltage C/Terminal i

Binary Output:
Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4

Pre-Playback:
Voltage (L-N): 63.509 V
Current: 1.000 A
Angle Voltage (Fault): 0.00 °
Angle Current: 0.00 °
Duration: 0.000 s

General:
Number of Repetitions: 0x
Time between Repetitions: 100.00 ms
Original Sampling Rate: 960.00 Hz
Maximum Sampling Rate: 10.000 kHz
Sampling Rate Used: 960.00 Hz

Comment

Test Module
Name: OMICRON Advanced TransPlay Version: 3.20
Test Start: 18-ene-2018 14:32:00 Test End: 18-ene-2018 14:32:05
User Name: Manager:
Company:

Test Results

State condition:
Ignore Tnom Tdev- Tdev+ Tdev
No. Name Start Stop Tact [s] Assess
before [s] [s] [s] [s]
o
Assess: + .. Passed x .. Failed o .. Not assessed

Statistics State Condition:


Assess: + .. Passed x .. Failed o .. Not assessed

Reference signal:
Reference Tdev- Tdev+ Tdev
No. Name Ignore before Signal Tact [s] Assess
signal [s] [s] [s]

Página 4 de 37
SIEMENS End2End-L663.occ
o
Assess: + .. Passed x .. Failed o .. Not assessed

Statistics Reference Signal:


Assess: + .. Passed x .. Failed o .. Not assessed

Time Signal:
Assessment no.: 1
Voltages/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100
:L-663(1):Phase Voltage A/Terminal i
:L-663(1):Phase Voltage B/Terminal i
:L-663(1):Phase Voltage C/Terminal i

Currents/A

15

10

5 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-5

-10

-15
:L-663(1):Phase Current A/Terminal i
:L-663(1):Phase Current B/Terminal i
:L-663(1):Phase Current C/Terminal i

Disparo
Posición Cerrado

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8


t/s

Cursor Data
Time Signal Value
Cursor 1 504.24 ms <none> n/a
Cursor 2 2.00 s <none> n/a
C2 - C1 1.49 s n/a

Test State:
Test passed
Caso 2:

Página 5 de 37
SIEMENS End2End-L663.occ

Test Settings

Data source:
Path: D:\PROYECTOS\SIEMENS\END TO END ENERO 2018\END2END 663 SE SAN LUIS - SE
LIMATAMBO\END2END L663\C02\
File: C02 LU.CFG
Info: DIgSILENT PowerFactory

Analog Output:
Name Scale Min max
I L1 :L-663(1):Phase 100.00 % -13.09 A 18.80 A
Current A/Terminal i
I L2 :L-663(1):Phase 100.00 % -13.02 A 18.27 A
Current B/Terminal i
I L3 :L-663(1):Phase 100.00 % -23.29 A 12.56 A
Current C/Terminal i
V L1-E :L-663(1):Phase 100.00 % -89.50 V 93.85 V
Voltage A/Terminal i
V L2-E :L-663(1):Phase 100.00 % -90.68 V 90.68 V
Voltage B/Terminal i
V L3-E :L-663(1):Phase 100.00 % -92.75 V 91.08 V
Voltage C/Terminal i

Binary Output:
Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4

Pre-Playback:
Voltage (L-N): 63.509 V
Current: 1.000 A
Angle Voltage (Fault): 0.00 °
Angle Current: 0.00 °
Duration: 0.000 s

General:
Number of Repetitions: 0x
Time between Repetitions: 100.00 ms
Original Sampling Rate: 960.00 Hz
Maximum Sampling Rate: 10.000 kHz
Sampling Rate Used: 960.00 Hz

Comment

Test Module
Name: OMICRON Advanced TransPlay Version: 3.20
Test Start: 18-ene-2018 14:49:00 Test End: 18-ene-2018 14:49:04
User Name: Manager:
Company:

Test Results

State condition:
Ignore Tnom Tdev- Tdev+ Tdev
No. Name Start Stop Tact [s] Assess
before [s] [s] [s] [s]
o
Assess: + .. Passed x .. Failed o .. Not assessed

Statistics State Condition:


Assess: + .. Passed x .. Failed o .. Not assessed

Página 6 de 37
SIEMENS End2End-L663.occ

Reference signal:
Reference Tdev- Tdev+ Tdev
No. Name Ignore before Signal Tact [s] Assess
signal [s] [s] [s]
o
Assess: + .. Passed x .. Failed o .. Not assessed

Statistics Reference Signal:


Assess: + .. Passed x .. Failed o .. Not assessed

Time Signal:
Assessment no.: 1
Voltages/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100
:L-663(1):Phase Voltage A/Terminal i
:L-663(1):Phase Voltage B/Terminal i
:L-663(1):Phase Voltage C/Terminal i

Currents/A

15
10
5
0
-5 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
t/s
-10
-15
-20
-25
:L-663(1):Phase Current A/Terminal i
:L-663(1):Phase Current B/Terminal i
:L-663(1):Phase Current C/Terminal i

Disparo
Posición Cerrado

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8


t/s

Cursor Data
Time Signal Value
Cursor 1 501.07 ms <none> n/a
Cursor 2 2.00 s <none> n/a
C2 - C1 1.50 s n/a

Página 7 de 37
SIEMENS End2End-L663.occ

Test State:
Test passed
Caso 3:

Test Settings

Data source:
Path: D:\PROYECTOS\SIEMENS\END TO END ENERO 2018\END2END 663 SE SAN LUIS - SE
LIMATAMBO\END2END L663\C03\
File: C03 LU.CFG
Info: DIgSILENT PowerFactory

Analog Output:
Name Scale Min max
I L1 :L-663(1):Phase 100.00 % -2.05 A 2.18 A
Current A/Terminal i
I L2 :L-663(1):Phase 100.00 % -0.86 A 14.97 A
Current B/Terminal i
I L3 :L-663(1):Phase 100.00 % -15.23 A 0.90 A
Current C/Terminal i
V L1-E :L-663(1):Phase 100.00 % -89.50 V 93.85 V
Voltage A/Terminal i
V L2-E :L-663(1):Phase 100.00 % -90.68 V 90.68 V
Voltage B/Terminal i
V L3-E :L-663(1):Phase 100.00 % -92.75 V 91.08 V
Voltage C/Terminal i

Binary Output:
Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4

Pre-Playback:
Voltage (L-N): 63.509 V
Current: 1.000 A
Angle Voltage (Fault): 0.00 °
Angle Current: 0.00 °
Duration: 0.000 s

General:
Number of Repetitions: 0x
Time between Repetitions: 100.00 ms
Original Sampling Rate: 960.00 Hz
Maximum Sampling Rate: 10.000 kHz
Sampling Rate Used: 960.00 Hz

Comment

Test Module
Name: OMICRON Advanced TransPlay Version: 3.20
Test Start: 18-ene-2018 15:01:00 Test End: 18-ene-2018 15:01:05
User Name: Manager:
Company:

Test Results

State condition:
Ignore Tnom Tdev- Tdev+ Tdev
No. Name Start Stop Tact [s] Assess
before [s] [s] [s] [s]

Página 8 de 37
SIEMENS End2End-L663.occ
o
Assess: + .. Passed x .. Failed o .. Not assessed

Statistics State Condition:


Assess: + .. Passed x .. Failed o .. Not assessed

Reference signal:
Reference Tdev- Tdev+ Tdev
No. Name Ignore before Signal Tact [s] Assess
signal [s] [s] [s]
o
Assess: + .. Passed x .. Failed o .. Not assessed

Statistics Reference Signal:


Assess: + .. Passed x .. Failed o .. Not assessed

Time Signal:
Assessment no.: 1
:L-663(1):Phase Current A/Terminal i/A

10

0
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
-5 t/s

-10

-15

:L-663(1):Phase Current B/Terminal i/A

10

0
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
-5 t/s

-10

-15

:L-663(1):Phase Current C/Terminal i/A

10

0
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
-5 t/s

-10

-15

Página 9 de 37
SIEMENS End2End-L663.occ

:L-663(1):Phase Voltage A/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

:L-663(1):Phase Voltage B/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

:L-663(1):Phase Voltage C/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

Disparo
Posición Cerrado

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8


t/s

Cursor Data
Time Signal Value
Cursor 1 0.00 s <none> n/a
Cursor 2 2.00 s <none> n/a
C2 - C1 2.00 s n/a

Test State:
Test passed
Caso 4:

Test Settings

Página 10 de 37
SIEMENS End2End-L663.occ

Data source:
Path: D:\PROYECTOS\SIEMENS\END TO END ENERO 2018\END2END 663 SE SAN LUIS - SE
LIMATAMBO\END2END L663\C04\
File: C04 LU.CFG
Info: DIgSILENT PowerFactory

Analog Output:
Name Scale Min max
I L1 :L-663(1):Phase 100.00 % -0.88 A 12.74 A
Current A/Terminal i
I L2 :L-663(1):Phase 100.00 % -2.52 A 2.99 A
Current B/Terminal i
I L3 :L-663(1):Phase 100.00 % -14.66 A 8.10 A
Current C/Terminal i
V L1-E :L-663(1):Phase 100.00 % -89.50 V 93.85 V
Voltage A/Terminal i
V L2-E :L-663(1):Phase 100.00 % -90.77 V 90.73 V
Voltage B/Terminal i
V L3-E :L-663(1):Phase 100.00 % -92.75 V 91.08 V
Voltage C/Terminal i

Binary Output:
Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4

Pre-Playback:
Voltage (L-N): 63.509 V
Current: 1.000 A
Angle Voltage (Fault): 0.00 °
Angle Current: 0.00 °
Duration: 0.000 s

General:
Number of Repetitions: 0x
Time between Repetitions: 100.00 ms
Original Sampling Rate: 960.00 Hz
Maximum Sampling Rate: 10.000 kHz
Sampling Rate Used: 960.00 Hz

Comment

Test Module
Name: OMICRON Advanced TransPlay Version: 3.20
Test Start: 18-ene-2018 15:10:00 Test End: 18-ene-2018 15:10:04
User Name: Manager:
Company:

Test Results

State condition:
Ignore Tnom Tdev- Tdev+ Tdev
No. Name Start Stop Tact [s] Assess
before [s] [s] [s] [s]
o
Assess: + .. Passed x .. Failed o .. Not assessed

Statistics State Condition:


Assess: + .. Passed x .. Failed o .. Not assessed

Reference signal:

Página 11 de 37
SIEMENS End2End-L663.occ

Reference Tdev- Tdev+ Tdev


No. Name Ignore before Signal Tact [s] Assess
signal [s] [s] [s]
o
Assess: + .. Passed x .. Failed o .. Not assessed

Statistics Reference Signal:


Assess: + .. Passed x .. Failed o .. Not assessed

Time Signal:
Assessment no.: 1
:L-663(1):Phase Current A/Terminal i/A

10.0
7.5
5.0
2.5
0.0
-2.5 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
t/s
-5.0
-7.5
-10.0
-12.5
-15.0

:L-663(1):Phase Current B/Terminal i/A

10.0
7.5
5.0
2.5
0.0
-2.5 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
t/s
-5.0
-7.5
-10.0
-12.5
-15.0

:L-663(1):Phase Current C/Terminal i/A

10.0
7.5
5.0
2.5
0.0
-2.5 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
t/s
-5.0
-7.5
-10.0
-12.5
-15.0

Página 12 de 37
SIEMENS End2End-L663.occ

:L-663(1):Phase Voltage A/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

:L-663(1):Phase Voltage B/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

:L-663(1):Phase Voltage C/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

Disparo
Posición Cerrado

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8


t/s

Cursor Data
Time Signal Value
Cursor 1 0.00 s <none> n/a
Cursor 2 2.00 s <none> n/a
C2 - C1 2.00 s n/a

Test State:
Test passed
Caso 5:

Test Settings

Página 13 de 37
SIEMENS End2End-L663.occ

Data source:
Path: D:\PROYECTOS\SIEMENS\END TO END ENERO 2018\END2END 663 SE SAN LUIS - SE
LIMATAMBO\END2END L663\C05\
File: C05 LU.CFG
Info: DIgSILENT PowerFactory

Analog Output:
Name Scale Min max
I L1 :L-663(1):Phase 100.00 % -0.80 A 0.82 A
Current A/Terminal i
I L2 :L-663(1):Phase 100.00 % -0.42 A 0.42 A
Current B/Terminal i
I L3 :L-663(1):Phase 100.00 % -0.42 A 0.42 A
Current C/Terminal i
V L1-E :L-663(1):Phase 100.00 % -89.50 V 93.85 V
Voltage A/Terminal i
V L2-E :L-663(1):Phase 100.00 % -90.68 V 90.68 V
Voltage B/Terminal i
V L3-E :L-663(1):Phase 100.00 % -92.75 V 91.08 V
Voltage C/Terminal i

Binary Output:
Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4

Pre-Playback:
Voltage (L-N): 63.509 V
Current: 1.000 A
Angle Voltage (Fault): 0.00 °
Angle Current: 0.00 °
Duration: 0.000 s

General:
Number of Repetitions: 0x
Time between Repetitions: 100.00 ms
Original Sampling Rate: 960.00 Hz
Maximum Sampling Rate: 10.000 kHz
Sampling Rate Used: 960.00 Hz

Comment

Test Module
Name: OMICRON Advanced TransPlay Version: 3.20
Test Start: 18-ene-2018 15:22:00 Test End: 18-ene-2018 15:22:04
User Name: Manager:
Company:

Test Results

State condition:
Ignore Tnom Tdev- Tdev+ Tdev
No. Name Start Stop Tact [s] Assess
before [s] [s] [s] [s]
o
Assess: + .. Passed x .. Failed o .. Not assessed

Statistics State Condition:


Assess: + .. Passed x .. Failed o .. Not assessed

Reference signal:

Página 14 de 37
SIEMENS End2End-L663.occ

Reference Tdev- Tdev+ Tdev


No. Name Ignore before Signal Tact [s] Assess
signal [s] [s] [s]
o
Assess: + .. Passed x .. Failed o .. Not assessed

Statistics Reference Signal:


Assess: + .. Passed x .. Failed o .. Not assessed

Time Signal:
Assessment no.: 1
:L-663(1):Phase Current A/Terminal i/mA

600
400
200 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0
-200
-400
-600
-800

:L-663(1):Phase Current B/Terminal i/mA

600
400
200 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0
-200
-400
-600
-800

:L-663(1):Phase Current C/Terminal i/mA

600
400
200 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0
-200
-400
-600
-800

Página 15 de 37
SIEMENS End2End-L663.occ

:L-663(1):Phase Voltage A/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

:L-663(1):Phase Voltage B/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

:L-663(1):Phase Voltage C/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

Disparo
Posición Cerrado

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8


t/s

Cursor Data
Time Signal Value
Cursor 1 0.00 s <none> n/a
Cursor 2 2.00 s <none> n/a
C2 - C1 2.00 s n/a

Test State:
Test passed
Caso 6:

Test Settings

Página 16 de 37
SIEMENS End2End-L663.occ

Data source:
Path: D:\PROYECTOS\SIEMENS\END TO END ENERO 2018\END2END 663 SE SAN LUIS - SE
LIMATAMBO\END2END L663\C06\
File: C06 LU.CFG
Info: DIgSILENT PowerFactory

Analog Output:
Name Scale Min max
I L1 :L-663(1):Phase 100.00 % -0.88 A 0.88 A
Current A/Terminal i
I L2 :L-663(1):Phase 100.00 % -0.87 A 0.86 A
Current B/Terminal i
I L3 :L-663(1):Phase 100.00 % -0.92 A 0.88 A
Current C/Terminal i
V L1-E :L-663(1):Phase 100.00 % -89.50 V 93.85 V
Voltage A/Terminal i
V L2-E :L-663(1):Phase 100.00 % -90.68 V 90.68 V
Voltage B/Terminal i
V L3-E :L-663(1):Phase 100.00 % -92.75 V 91.08 V
Voltage C/Terminal i

Binary Output:
Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4

Pre-Playback:
Voltage (L-N): 63.509 V
Current: 1.000 A
Angle Voltage (Fault): 0.00 °
Angle Current: 0.00 °
Duration: 0.000 s

General:
Number of Repetitions: 0x
Time between Repetitions: 100.00 ms
Original Sampling Rate: 960.00 Hz
Maximum Sampling Rate: 10.000 kHz
Sampling Rate Used: 960.00 Hz

Comment

Test Module
Name: OMICRON Advanced TransPlay Version: 3.20
Test Start: 18-ene-2018 15:29:00 Test End: 18-ene-2018 15:29:04
User Name: Manager:
Company:

Test Results

State condition:
Ignore Tnom Tdev- Tdev+ Tdev
No. Name Start Stop Tact [s] Assess
before [s] [s] [s] [s]
o
Assess: + .. Passed x .. Failed o .. Not assessed

Statistics State Condition:


Assess: + .. Passed x .. Failed o .. Not assessed

Reference signal:

Página 17 de 37
SIEMENS End2End-L663.occ

Reference Tdev- Tdev+ Tdev


No. Name Ignore before Signal Tact [s] Assess
signal [s] [s] [s]
o
Assess: + .. Passed x .. Failed o .. Not assessed

Statistics Reference Signal:


Assess: + .. Passed x .. Failed o .. Not assessed

Time Signal:
Assessment no.: 1
:L-663(1):Phase Current A/Terminal i/A

0.6
0.4
0.2
-0.0
-0.2 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
t/s
-0.4
-0.6
-0.8
-1.0

:L-663(1):Phase Current B/Terminal i/A

0.6
0.4
0.2
-0.0
-0.2 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
t/s
-0.4
-0.6
-0.8
-1.0

:L-663(1):Phase Current C/Terminal i/A

0.6
0.4
0.2
-0.0
-0.2 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
t/s
-0.4
-0.6
-0.8
-1.0

Página 18 de 37
SIEMENS End2End-L663.occ

:L-663(1):Phase Voltage A/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

:L-663(1):Phase Voltage B/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

:L-663(1):Phase Voltage C/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

Disparo
Posición Cerrado

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8


t/s

Cursor Data
Time Signal Value
Cursor 1 0.00 s <none> n/a
Cursor 2 2.00 s <none> n/a
C2 - C1 2.00 s n/a

Test State:
Test passed
Caso 7:

Test Settings

Página 19 de 37
SIEMENS End2End-L663.occ

Data source:
Path: D:\PROYECTOS\SIEMENS\END TO END ENERO 2018\END2END 663 SE SAN LUIS - SE
LIMATAMBO\END2END L663\C07\
File: C07 LU.CFG
Info: DIgSILENT PowerFactory

Analog Output:
Name Scale Min max
I L1 :L-663(1):Phase 100.00 % -0.92 A 0.87 A
Current A/Terminal i
I L2 :L-663(1):Phase 100.00 % -7.13 A 11.81 A
Current B/Terminal i
I L3 :L-663(1):Phase 100.00 % -11.44 A 6.75 A
Current C/Terminal i
V L1-E :L-663(1):Phase 100.00 % -89.50 V 93.85 V
Voltage A/Terminal i
V L2-E :L-663(1):Phase 100.00 % -90.68 V 90.71 V
Voltage B/Terminal i
V L3-E :L-663(1):Phase 100.00 % -92.75 V 91.08 V
Voltage C/Terminal i

Binary Output:
Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4

Pre-Playback:
Voltage (L-N): 63.509 V
Current: 1.000 A
Angle Voltage (Fault): 0.00 °
Angle Current: 0.00 °
Duration: 0.000 s

General:
Number of Repetitions: 0x
Time between Repetitions: 100.00 ms
Original Sampling Rate: 960.00 Hz
Maximum Sampling Rate: 10.000 kHz
Sampling Rate Used: 960.00 Hz

Comment

Test Module
Name: OMICRON Advanced TransPlay Version: 3.20
Test Start: 18-ene-2018 15:34:00 Test End: 18-ene-2018 15:34:04
User Name: Manager:
Company:

Test Results

State condition:
Ignore Tnom Tdev- Tdev+ Tdev
No. Name Start Stop Tact [s] Assess
before [s] [s] [s] [s]
o
Assess: + .. Passed x .. Failed o .. Not assessed

Statistics State Condition:


Assess: + .. Passed x .. Failed o .. Not assessed

Reference signal:

Página 20 de 37
SIEMENS End2End-L663.occ

Reference Tdev- Tdev+ Tdev


No. Name Ignore before Signal Tact [s] Assess
signal [s] [s] [s]
o
Assess: + .. Passed x .. Failed o .. Not assessed

Statistics Reference Signal:


Assess: + .. Passed x .. Failed o .. Not assessed

Time Signal:
Assessment no.: 1
:L-663(1):Phase Current A/Terminal i/A

10.0
7.5
5.0
2.5 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0.0
-2.5
-5.0
-7.5
-10.0
-12.5

:L-663(1):Phase Current B/Terminal i/A

10.0
7.5
5.0
2.5 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0.0
-2.5
-5.0
-7.5
-10.0
-12.5

:L-663(1):Phase Current C/Terminal i/A

10.0
7.5
5.0
2.5 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0.0
-2.5
-5.0
-7.5
-10.0
-12.5

Página 21 de 37
SIEMENS End2End-L663.occ

:L-663(1):Phase Voltage A/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

:L-663(1):Phase Voltage B/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

:L-663(1):Phase Voltage C/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

Disparo
Posición Cerrado

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8


t/s

Cursor Data
Time Signal Value
Cursor 1 0.00 s <none> n/a
Cursor 2 2.00 s <none> n/a
C2 - C1 2.00 s n/a

Test State:
Test passed
Caso 8:

Test Settings

Página 22 de 37
SIEMENS End2End-L663.occ

Data source:
Path: D:\PROYECTOS\SIEMENS\END TO END ENERO 2018\END2END 663 SE SAN LUIS - SE
LIMATAMBO\END2END L663\C08\
File: C08 LU.CFG
Info: DIgSILENT PowerFactory

Analog Output:
Name Scale Min max
I L1 :L-663(1):Phase 100.00 % -17.30 A 17.54 A
Current A/Terminal i
I L2 :L-663(1):Phase 100.00 % -17.24 A 17.00 A
Current B/Terminal i
I L3 :L-663(1):Phase 100.00 % -0.40 A 0.40 A
Current C/Terminal i
V L1-E :L-663(1):Phase 100.00 % -89.50 V 93.85 V
Voltage A/Terminal i
V L2-E :L-663(1):Phase 100.00 % -90.68 V 90.68 V
Voltage B/Terminal i
V L3-E :L-663(1):Phase 100.00 % -92.75 V 91.08 V
Voltage C/Terminal i

Binary Output:
Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4

Pre-Playback:
Voltage (L-N): 63.509 V
Current: 1.000 A
Angle Voltage (Fault): 0.00 °
Angle Current: 0.00 °
Duration: 0.000 s

General:
Number of Repetitions: 0x
Time between Repetitions: 100.00 ms
Original Sampling Rate: 960.00 Hz
Maximum Sampling Rate: 10.000 kHz
Sampling Rate Used: 960.00 Hz

Comment

Test Module
Name: OMICRON Advanced TransPlay Version: 3.20
Test Start: 18-ene-2018 15:44:00 Test End: 18-ene-2018 15:44:04
User Name: Manager:
Company:

Test Results

State condition:
Ignore Tnom Tdev- Tdev+ Tdev
No. Name Start Stop Tact [s] Assess
before [s] [s] [s] [s]
o
Assess: + .. Passed x .. Failed o .. Not assessed

Statistics State Condition:


Assess: + .. Passed x .. Failed o .. Not assessed

Reference signal:

Página 23 de 37
SIEMENS End2End-L663.occ

Reference Tdev- Tdev+ Tdev


No. Name Ignore before Signal Tact [s] Assess
signal [s] [s] [s]
o
Assess: + .. Passed x .. Failed o .. Not assessed

Statistics Reference Signal:


Assess: + .. Passed x .. Failed o .. Not assessed

Time Signal:
Assessment no.: 1
:L-663(1):Phase Current A/Terminal i/A
15

10

5 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-5

-10

-15

:L-663(1):Phase Current B/Terminal i/A


15

10

5 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-5

-10

-15

:L-663(1):Phase Current C/Terminal i/A


15

10

5 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-5

-10

-15

Página 24 de 37
SIEMENS End2End-L663.occ

:L-663(1):Phase Voltage A/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

:L-663(1):Phase Voltage B/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

:L-663(1):Phase Voltage C/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

Disparo
Posición Cerrado

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8


t/s

Cursor Data
Time Signal Value
Cursor 1 0.00 s <none> n/a
Cursor 2 2.00 s <none> n/a
C2 - C1 2.00 s n/a

Test State:
Test passed
Caso 9:

Test Settings

Página 25 de 37
SIEMENS End2End-L663.occ

Data source:
Path: D:\PROYECTOS\SIEMENS\END TO END ENERO 2018\END2END 663 SE SAN LUIS - SE
LIMATAMBO\END2END L663\C09\
File: C09 LU.CFG
Info: DIgSILENT PowerFactory

Analog Output:
Name Scale Min max
I L1 :L-663(1):Phase 100.00 % -0.40 A 0.40 A
Current A/Terminal i
I L2 :L-663(1):Phase 100.00 % -8.31 A 13.11 A
Current B/Terminal i
I L3 :L-663(1):Phase 100.00 % -12.75 A 7.95 A
Current C/Terminal i
V L1-E :L-663(1):Phase 100.00 % -89.50 V 93.85 V
Voltage A/Terminal i
V L2-E :L-663(1):Phase 100.00 % -90.68 V 90.68 V
Voltage B/Terminal i
V L3-E :L-663(1):Phase 100.00 % -92.75 V 91.08 V
Voltage C/Terminal i

Binary Output:
Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4

Pre-Playback:
Voltage (L-N): 63.509 V
Current: 1.000 A
Angle Voltage (Fault): 0.00 °
Angle Current: 0.00 °
Duration: 0.000 s

General:
Number of Repetitions: 0x
Time between Repetitions: 100.00 ms
Original Sampling Rate: 960.00 Hz
Maximum Sampling Rate: 10.000 kHz
Sampling Rate Used: 960.00 Hz

Comment

Test Module
Name: OMICRON Advanced TransPlay Version: 3.20
Test Start: 18-ene-2018 15:49:00 Test End: 18-ene-2018 15:49:05
User Name: Manager:
Company:

Test Results

State condition:
Ignore Tnom Tdev- Tdev+ Tdev
No. Name Start Stop Tact [s] Assess
before [s] [s] [s] [s]
o
Assess: + .. Passed x .. Failed o .. Not assessed

Statistics State Condition:


Assess: + .. Passed x .. Failed o .. Not assessed

Reference signal:

Página 26 de 37
SIEMENS End2End-L663.occ

Reference Tdev- Tdev+ Tdev


No. Name Ignore before Signal Tact [s] Assess
signal [s] [s] [s]
o
Assess: + .. Passed x .. Failed o .. Not assessed

Statistics Reference Signal:


Assess: + .. Passed x .. Failed o .. Not assessed

Time Signal:
Assessment no.: 1
:L-663(1):Phase Current A/Terminal i/A

10.0
7.5
5.0
t/s
2.5 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0.0
-2.5
-5.0
-7.5
-10.0
-12.5

:L-663(1):Phase Current B/Terminal i/A

10.0
7.5
5.0
t/s
2.5 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0.0
-2.5
-5.0
-7.5
-10.0
-12.5

:L-663(1):Phase Current C/Terminal i/A

10.0
7.5
5.0
t/s
2.5 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0.0
-2.5
-5.0
-7.5
-10.0
-12.5

Página 27 de 37
SIEMENS End2End-L663.occ

:L-663(1):Phase Voltage A/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

:L-663(1):Phase Voltage B/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

:L-663(1):Phase Voltage C/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

Disparo
Posición Cerrado

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8


t/s

Cursor Data
Time Signal Value
Cursor 1 0.00 s <none> n/a
Cursor 2 2.00 s <none> n/a
C2 - C1 2.00 s n/a

Test State:
Test passed
Caso 10:

Test Settings

Página 28 de 37
SIEMENS End2End-L663.occ

Data source:
Path: D:\PROYECTOS\SIEMENS\END TO END ENERO 2018\END2END 663 SE SAN LUIS - SE
LIMATAMBO\END2END L663\C10\
File: C10 LU.CFG
Info: DIgSILENT PowerFactory

Analog Output:
Name Scale Min max
I L1 :L-663(1):Phase 100.00 % -8.52 A 11.98 A
Current A/Terminal i
I L2 :L-663(1):Phase 100.00 % -1.81 A 0.89 A
Current B/Terminal i
I L3 :L-663(1):Phase 100.00 % -2.44 A 1.51 A
Current C/Terminal i
V L1-E :L-663(1):Phase 100.00 % -89.50 V 93.85 V
Voltage A/Terminal i
V L2-E :L-663(1):Phase 100.00 % -90.68 V 90.68 V
Voltage B/Terminal i
V L3-E :L-663(1):Phase 100.00 % -92.75 V 91.08 V
Voltage C/Terminal i

Binary Output:
Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4

Pre-Playback:
Voltage (L-N): 63.509 V
Current: 1.000 A
Angle Voltage (Fault): 0.00 °
Angle Current: 0.00 °
Duration: 0.000 s

General:
Number of Repetitions: 0x
Time between Repetitions: 100.00 ms
Original Sampling Rate: 960.00 Hz
Maximum Sampling Rate: 10.000 kHz
Sampling Rate Used: 960.00 Hz

Comment

Test Module
Name: OMICRON Advanced TransPlay Version: 3.20
Test Start: 18-ene-2018 15:56:00 Test End: 18-ene-2018 15:56:04
User Name: Manager:
Company:

Test Results

State condition:
Ignore Tnom Tdev- Tdev+ Tdev
No. Name Start Stop Tact [s] Assess
before [s] [s] [s] [s]
o
Assess: + .. Passed x .. Failed o .. Not assessed

Statistics State Condition:


Assess: + .. Passed x .. Failed o .. Not assessed

Reference signal:

Página 29 de 37
SIEMENS End2End-L663.occ

Reference Tdev- Tdev+ Tdev


No. Name Ignore before Signal Tact [s] Assess
signal [s] [s] [s]
o
Assess: + .. Passed x .. Failed o .. Not assessed

Statistics Reference Signal:


Assess: + .. Passed x .. Failed o .. Not assessed

Time Signal:
Assessment no.: 1
:L-663(1):Phase Current A/Terminal i/A

10.0
7.5
5.0
2.5 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0.0
-2.5
-5.0
-7.5

:L-663(1):Phase Current B/Terminal i/A

10.0
7.5
5.0
2.5 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0.0
-2.5
-5.0
-7.5

:L-663(1):Phase Current C/Terminal i/A

10.0
7.5
5.0
2.5 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0.0
-2.5
-5.0
-7.5

Página 30 de 37
SIEMENS End2End-L663.occ

:L-663(1):Phase Voltage A/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

:L-663(1):Phase Voltage B/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

:L-663(1):Phase Voltage C/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

Disparo
Posición Cerrado

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8


t/s

Cursor Data
Time Signal Value
Cursor 1 0.00 s <none> n/a
Cursor 2 2.00 s <none> n/a
C2 - C1 2.00 s n/a

Test State:
Test passed

Caso 11:

Test Settings

Página 31 de 37
SIEMENS End2End-L663.occ

Data source:
Path: D:\PROYECTOS\SIEMENS\END TO END ENERO 2018\END2END 663 SE SAN LUIS - SE
LIMATAMBO\END2END L663\C11\
File: C11 LU.CFG
Info: DIgSILENT PowerFactory

Analog Output:
Name Scale Min max
I L1 :L-663(1):Phase 100.00 % -8.21 A 11.76 A
Current A/Terminal i
I L2 :L-663(1):Phase 100.00 % -8.16 A 11.37 A
Current B/Terminal i
I L3 :L-663(1):Phase 100.00 % -14.54 A 7.90 A
Current C/Terminal i
V L1-E :L-663(1):Phase 100.00 % -89.50 V 93.85 V
Voltage A/Terminal i
V L2-E :L-663(1):Phase 100.00 % -90.68 V 90.69 V
Voltage B/Terminal i
V L3-E :L-663(1):Phase 100.00 % -92.75 V 91.08 V
Voltage C/Terminal i

Binary Output:
Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4

Pre-Playback:
Voltage (L-N): 63.509 V
Current: 1.000 A
Angle Voltage (Fault): 0.00 °
Angle Current: 0.00 °
Duration: 0.000 s

General:
Number of Repetitions: 0x
Time between Repetitions: 100.00 ms
Original Sampling Rate: 960.00 Hz
Maximum Sampling Rate: 10.000 kHz
Sampling Rate Used: 960.00 Hz

Comment

Test Module
Name: OMICRON Advanced TransPlay Version: 3.20
Test Start: 18-ene-2018 16:05:00 Test End: 18-ene-2018 16:05:04
User Name: Manager:
Company:

Test Results

State condition:
Ignore Tnom Tdev- Tdev+ Tdev
No. Name Start Stop Tact [s] Assess
before [s] [s] [s] [s]
o
Assess: + .. Passed x .. Failed o .. Not assessed

Statistics State Condition:


Assess: + .. Passed x .. Failed o .. Not assessed

Reference signal:

Página 32 de 37
SIEMENS End2End-L663.occ

Reference Tdev- Tdev+ Tdev


No. Name Ignore before Signal Tact [s] Assess
signal [s] [s] [s]
o
Assess: + .. Passed x .. Failed o .. Not assessed

Statistics Reference Signal:


Assess: + .. Passed x .. Failed o .. Not assessed

Time Signal:
Assessment no.: 1
:L-663(1):Phase Current A/Terminal i/A

10.0
7.5

5.0
2.5 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0.0
-2.5

-5.0
-7.5

:L-663(1):Phase Current B/Terminal i/A


10
8
6
4
t/s
2 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0
-2
-4
-6
-8

:L-663(1):Phase Current C/Terminal i/A

5.0
2.5
0.0
-2.5 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
t/s
-5.0
-7.5
-10.0
-12.5
-15.0

Página 33 de 37
SIEMENS End2End-L663.occ

:L-663(1):Phase Voltage A/Terminal i/V


80
60
40
20 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0
-20
-40
-60
-80

:L-663(1):Phase Voltage B/Terminal i/V


80
60
40
20 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0
-20
-40
-60
-80

:L-663(1):Phase Voltage C/Terminal i/V

75

50

25

0
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
-25 t/s

-50

-75

-100

Disparo
Posición Cerrado

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8


t/s

Cursor Data
Time Signal Value
Cursor 1 0.00 s <none> n/a
Cursor 2 2.00 s <none> n/a
C2 - C1 2.00 s n/a

Test State:
Test passed
Caso 12:

Test Settings

Página 34 de 37
SIEMENS End2End-L663.occ

Data source:
Path: D:\PROYECTOS\SIEMENS\END TO END ENERO 2018\END2END 663 SE SAN LUIS - SE
LIMATAMBO\END2END L663\C12\
File: C12 LU.CFG
Info: DIgSILENT PowerFactory

Analog Output:
Name Scale Min max
I L1 :L-663(1):Phase 100.00 % -7.87 A 10.45 A
Current A/Terminal i
I L2 :L-663(1):Phase 100.00 % -7.94 A 10.36 A
Current B/Terminal i
I L3 :L-663(1):Phase 100.00 % -12.91 A 7.87 A
Current C/Terminal i
V L1-E :L-663(1):Phase 100.00 % -90.25 V 93.85 V
Voltage A/Terminal i
V L2-E :L-663(1):Phase 100.00 % -91.36 V 91.37 V
Voltage B/Terminal i
V L3-E :L-663(1):Phase 100.00 % -92.75 V 91.87 V
Voltage C/Terminal i

Binary Output:
Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4

Pre-Playback:
Voltage (L-N): 63.509 V
Current: 1.000 A
Angle Voltage (Fault): 0.00 °
Angle Current: 0.00 °
Duration: 0.000 s

General:
Number of Repetitions: 0x
Time between Repetitions: 100.00 ms
Original Sampling Rate: 960.00 Hz
Maximum Sampling Rate: 10.000 kHz
Sampling Rate Used: 960.00 Hz

Comment

Test Module
Name: OMICRON Advanced TransPlay Version: 3.20
Test Start: 18-ene-2018 16:31:00 Test End: 18-ene-2018 16:31:05
User Name: Manager:
Company:

Test Results

State condition:
Ignore Tnom Tdev- Tdev+ Tdev
No. Name Start Stop Tact [s] Assess
before [s] [s] [s] [s]
o
Assess: + .. Passed x .. Failed o .. Not assessed

Statistics State Condition:


Assess: + .. Passed x .. Failed o .. Not assessed

Reference signal:

Página 35 de 37
SIEMENS End2End-L663.occ

Reference Tdev- Tdev+ Tdev


No. Name Ignore before Signal Tact [s] Assess
signal [s] [s] [s]
o
Assess: + .. Passed x .. Failed o .. Not assessed

Statistics Reference Signal:


Assess: + .. Passed x .. Failed o .. Not assessed

Time Signal:
Assessment no.: 1
:L-663(1):Phase Current A/Terminal i/A

7.5
5.0
2.5
0.0
-2.5 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
t/s
-5.0
-7.5
-10.0
-12.5

:L-663(1):Phase Current B/Terminal i/A

7.5
5.0
2.5
0.0
-2.5 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
t/s
-5.0
-7.5
-10.0
-12.5

:L-663(1):Phase Current C/Terminal i/A

7.5
5.0
2.5
0.0
-2.5 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
t/s
-5.0
-7.5
-10.0
-12.5

Página 36 de 37
SIEMENS End2End-L663.occ

:L-663(1):Phase Voltage A/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

:L-663(1):Phase Voltage B/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

:L-663(1):Phase Voltage C/Terminal i/V

75

50

25 t/s
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0

-25

-50

-75

-100

Disparo
Posición Cerrado

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8


t/s

Cursor Data
Time Signal Value
Cursor 1 496.64 ms <none> n/a
Cursor 2 1.00 s <none> n/a
C2 - C1 505.95 ms n/a

Test State:
Test passed

Página 37 de 37