RTHD SVX01G en - 08302016 PDF
RTHD SVX01G en - 08302016 PDF
RTHD SVX01G en - 08302016 PDF
and Maintenance
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing
of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.
RTHD-SVX01G-EN 3
Table of Contents
Model Number . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Fused-disconnect switches or circuit
breakers. . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Unit Nameplate . . . . . . . . . . . . . . . . . . . . . . . 6
Compressor Nameplate . . . . . . . . . . . . . . . . 6 Module Connections for Interconnecting
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Model Number Descriptions . . . . . . . . . . . . . . 7 AFD Drive (Optional) . . . . . . . . . . . . . . . . . . .46
Unit Model Number . . . . . . . . . . . . . . . . . . . . 7 AFD Drive Installation . . . . . . . . . . . . . . . .46
Compressor Model Number . . . . . . . . . . . . 8 AFD Drive Programming . . . . . . . . . . . . . .47
General Information . . . . . . . . . . . . . . . . . . . . . 9 Communications Interface . . . . . . . . . . . . . .49
Unit Description . . . . . . . . . . . . . . . . . . . . . . . 9 LonTalk Interface (LCI-C) . . . . . . . . . . . . . .49
Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . 14 BACnet Interface (BCI-C) . . . . . . . . . . . . . .49
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Modbus Remote Terminal Unit Interface .49
Inspection Checklist . . . . . . . . . . . . . . . . . 14
Operating Principles . . . . . . . . . . . . . . . . . . . . .50
Loose Parts Inventory . . . . . . . . . . . . . . . 14 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Refrigeration Cycle . . . . . . . . . . . . . . . . . . . .50
Installation Requirements . . . . . . . . . . . . . . 15 Refrigeration Circuits . . . . . . . . . . . . . . . . . .50
Dimensions and Weights . . . . . . . . . . . . . . . . 16 Compressor and Motor . . . . . . . . . . . . . . . . .50
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . 16 Evaporator and Condenser . . . . . . . . . . . . .50
Unit Weights . . . . . . . . . . . . . . . . . . . . . . . . . 16 Oil Management . . . . . . . . . . . . . . . . . . . . . .51
Service Clearances . . . . . . . . . . . . . . . . . . . . 18 Unit-Mounted Starter . . . . . . . . . . . . . . . . . .51
Installation Mechanical . . . . . . . . . . . . . . . . . . 19 Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Location Requirements . . . . . . . . . . . . . . . . 19 UC800 Specifications . . . . . . . . . . . . . . . . . .52
Sound Considerations . . . . . . . . . . . . . . . 19 Wiring and Port Descriptions . . . . . . . . . .52
Foundation . . . . . . . . . . . . . . . . . . . . . . . . 19 Communication Interfaces . . . . . . . . . . . .53
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . 19 Rotary Switches . . . . . . . . . . . . . . . . . . . . .53
Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . 19 LED Description and Operation . . . . . . . .53
Water Drainage . . . . . . . . . . . . . . . . . . . . . 19 Tracer AdaptiView™ TD7 Display . . . . . . . .53
Access Restrictions . . . . . . . . . . . . . . . . . 19 Operator Interface . . . . . . . . . . . . . . . . . . .53
Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Home Screen . . . . . . . . . . . . . . . . . . . . . . .54
Lifting Procedure . . . . . . . . . . . . . . . . . . . 23 Viewing Chiller Operating Modes . . . . . .54
Unit Leveling . . . . . . . . . . . . . . . . . . . . . . . 26 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
Isolation Pads . . . . . . . . . . . . . . . . . . . . . . 26 Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
Water Piping . . . . . . . . . . . . . . . . . . . . . . . 31 Equipment Settings . . . . . . . . . . . . . . . . .59
Freeze Protection . . . . . . . . . . . . . . . . . . . . . 37 Service Settings . . . . . . . . . . . . . . . . . . . . .61
Installation Electrical . . . . . . . . . . . . . . . . . . . . 38 Display Settings . . . . . . . . . . . . . . . . . . . .61
General Recommendations . . . . . . . . . . . . 38 Viewing the Settings Screen . . . . . . . . . .61
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . 38 Cleaning the Display . . . . . . . . . . . . . . . . .63
Standard Units with Wye-Delta Starter . 38 Security Settings . . . . . . . . . . . . . . . . . . . .63
Units with AFD Option . . . . . . . . . . . . . . . 39 Disabling/Enabling Security . . . . . . . . . . .63
Installer-Supplied Components . . . . . . . . . 39 Tracer® TU . . . . . . . . . . . . . . . . . . . . . . . . . . .65
4 RTHD-SVX01G-EN
Table of Contents
RTHD-SVX01G-EN 5
Model Number
Nameplates of typical unit model number and the coding system for
each.
The Optimus™ unit nameplates are applied to the exterior Each position, or group of positions, in the model number
of the Control Panel. A compressor nameplate is located is used to represent a feature. For example, in the first
on the compressor. When the unit arrives, compare all table, position 08 of the unit model number, Unit Voltage,
nameplate data with ordering, submittal, and shipping contains the letter “F”. An F in this position means that the
information. unit voltage is 460/60/3.
Unit Model Number. An example of a typical unit
Unit Nameplate model number (M/N) is:
See Figure 1 for a typical unit nameplate. The unit RTHD UB1F XG0U AB1A 2LAL B1A2 LALA VXQX EXAA
nameplate provides the following information: AXY1 76DC XT52 XXXX XXH
• Unit model and size description. Model number digits are selected and assigned in
• Unit serial number. accordance with the definitions as listed in “Unit Model
Number,” p. 7.
• Identifies unit electrical requirements.
• Lists correct operating charges of R-134a and Compressor Nameplate
refrigerant oil.
• Lists unit test pressures. The compressor nameplate provides the following
information:
• Identifies installation, operation and maintenance and
service data literature. • Compressor model number. See “Compressor Model
Number,” p. 8.
• Lists drawing numbers for unit wiring diagrams.
• Compressor electrical characteristics.
Model Number Coding System • Utilization range.
The model numbers for the unit and the compressor are • Recommended refrigerant.
composed of numbers and letters that represent features
of the equipment. Shown in the following table is a sample
6 RTHD-SVX01G-EN
Model Number Descriptions
Unit Model Number
Digits 1 - 4 – Chiller Model Digits 14,15 – Evaporator Digit 24 – Condenser Water
RTHD= Water-Cooled Optimus™ Chiller B1 = B1 Evaporator Passes
B2 = B2 Evaporator 2 = 2 Pass
Digit 5 – Manufacturing C1 = C1 Evaporator
Location C2 = C2 Evaporator Digit 25 – Condenser Water
U = Water Chiller Business Unit, D1 = D1 Evaporator Connection
Pueblo, CO USA D2 = D2 Evaporator L = Left Hand
D3 = D3 Evaporator R = Right Hand
Digits 6, 7 – Compressor Frame D4 = D4 Evaporator
B1 = B1 Compressor D5 = D5 Evaporator Digit 26 – Condenser
B2 = B2 Compressor D6 = D6 Evaporator Connection Type
C1 = C1 Compressor E1 = E1 Evaporator A = Standard Grooved Pipe
C2 = C2 Compressor F1 = F1 Evaporator C = Marine
D1 = D1 Compressor F2 = F2 Evaporator S = Special
D2 = D2 Compressor G1 = G1 Evaporator
D3 = D3 Compressor (50 hz only) G2 = G2 Evaporator Digit 27 – Condenser Waterside
E3 = E3 Compressor (50 hz only) G3 = G3 Evaporator Pressure
Digits 8 – Unit Power Supply Digit 16 – Evaporator Tube Type L = 150 psi (10.5 bar)
A = 200V/60Hz/3Ph power H = 300 psi (21 bar)
A = Enhanced fin copper (all fluids)
C = 230V/60Hz/3Ph power W = Enhanced fin copper (water only) Digit 28 – Condenser Leaving
D = 380V/60Hz/3Ph power Water Temperature
F = 460V/60Hz/3Ph power Digit 17 – Evaporator Water Pass
H = 575V/60Hz/3Ph power Configuration A = Standard
R = 380V/50Hz/3Ph power 2 = 2 Pass Digit 29 – Refrigerant Isolation
T = 400V/50Hz/3Ph power 3 = 3 Pass Valves
U = 415V/50Hz/3Ph power 4 = 4 Pass
X = No Refrigerant Isolation Valves
Digit 9 – Specials Digit 18 – Evaporator Water V = With Refrigerant Isolation Valves
X = No Specials Connection Digit 30 – Oil Cooler
Historical information: L = Left Hand
C = Specials denoted elsewhere X = Without Oil Cooler
R = Right Hand C = With Oil Cooler
S = Specials not denoted elsewhere
Digit 19 – Evaporator Digit 31 – Thermal Insulation
Digit 10, 11 – Design Sequence
Connection Type X = No Insulation
** = Factory assigned
A = Standard Grooved Pipe Q = Factory Installed Insulation
Digit 12 – Agency Listing Historical information:
S = Special
Digit 32 – Acoustic Insulation
X = No Agency Listing
U = UL Listed to US and Canadian X = No Insulation
Digit 20 – Evaporator Water Historical information:
Safety Standard
A = IBC Seismically Rated Side Pressure A = Standard Attenuator
B = UL/Canadian and IBC L = 150 psi (10.5 bar) Digit 33 – Label and Literature
C = OSHPD Seismically Rated H = 300 psi (21 bar)
Language
D = UL/Canadian and OSHPD Digit 21, 22 – Condenser
Historical information: C = Spanish
3 = CCC - Chinese Compulsory Code B1 = B1 Condenser E = English
B2 = B2 Condenser F = French
Note: Digit 12 selections A, B, C & D are D1 = D1 Condenser
special order only. D2 = D2 Condenser
Digit 34 – Safety Devices
Digit 13 – Pressure Vessel Code E1 = E1 Condenser X = Standard
E2 = E2 Condenser Digit 35 – Factory Charge
A = ASME Pressure Vessel Code
E3 = E3 Condenser
C = Canadian Code A = Factory Refrigerant Charge
E4 = E4 Condenser
D = Australian Code (R-134a)
E5 = E5 Condenser
L = Chinese Code-Imported Pressure B = Factory Nitrogen Charge
F1 = F1 Condenser
Vessel
Historical information:
F2 = F2 Condenser Digit 36 – Shipping Package
F3 = F3 Condenser A = No Skid (Standard)
S = Special
G1 = G1 Condenser B = Shrink Wrap
G2 = G2 Condenser C = Skid
G3 = G3 Condenser D = Skid + Shrink Wrap
Digit 23 – Condenser Tube Type Historical information:
J = Special
A = Enhanced Fin Copper - 0.028”
B = Smooth Bore Copper
C = Smooth Bore CuNi
D = Enhanced Fin Copper - 0.025”
RTHD-SVX01G-EN 7
Model Number Descriptions
8 RTHD-SVX01G-EN
General Information
Unit Description
The RTHD units are single compressor, helical-rotary type, Figure 2 through Figure 4 show typical Optimus™ units
water-cooled liquid chillers designed for installation and their components. Water inlet and outlet openings are
indoors. Each unit is a completely assembled, hermetic covered before shipment. The oil tank is factory charged
package that is factory-piped, wired, leak-tested, with the proper amount of refrigeration oil. The unit can be
dehydrated, charged (optional), and tested for proper factory charged with refrigerant.
control operation before shipment.
Figure 2. Component location — Optimus™ wye-delta starter (front view)
TD7 Interface
Relief Valves
Oil Sump
Condenser
Evaporator Water Outlet
Liquid Level
Sensor
(a) Component locations shown in Figure 2 are the same for units with optional AFD.
RTHD-SVX01G-EN 9
General Information
Unit Nameplate
Relief Valves (On side of starter/control panel)
EXVs
Evaporator
Water Inlet
Condenser
Service Valves Oil Sump
(With Refrigerant Isolation (The oil distribution system is located between
Valve Option Only) the condenser and the evaporator.)
(a) Optional AFD is not shown. See Figure 3, p. 9 for location of optional AFD.
10 RTHD-SVX01G-EN
General Information
RTHD-SVX01G-EN 11
General Information
12 RTHD-SVX01G-EN
General Information
RTHD-SVX01G-EN 13
Pre-Installation
Inspection
When the unit is delivered, verify that it is the correct unit 46 psig at 50oF), call a qualified service organization
and that it is properly equipped. and the appropriate Trane sales office.
Inspect all exterior components for visible damage. Report Note: Pressure will be approximately 20 psig if shipped
any apparent damage or material shortage to the carrier with the optional nitrogen charge.
and make a “unit damage” notation on the carrier’s
delivery receipt. Specify the extent and type of damage
found and notify the appropriate Trane Sales Office.
Do not proceed with installation of a damaged unit without
sales office approval.
Inspection Checklist
To protect against loss due to damage incurred in transit,
complete the following checklist upon receipt of the unit.
• Inspect the individual pieces of the shipment before
accepting the unit. Check for obvious damage to the
unit or packing material.
• Inspect the unit for concealed damage as soon as
possible after delivery and before it is stored.
Concealed damage must be reported within 10 days
after receipt.
• If concealed damage is discovered, stop unpacking the
shipment. Do not remove damaged material from the
receiving location. Take photos of the damage, if
possible. The owner must provide reasonable
evidence that the damage did not occur after delivery.
• Notify the carrier’s terminal of the damage
immediately, by phone and by mail. Request an
immediate, joint inspection of the damage with the
carrier and the consignee.
• Notify the Trane sales representative and arrange for
repair. Do not repair the unit, however, until damage is
inspected by the transportation representative.
Storage
If the chiller is to be stored more than one month prior to
installation, observe the following precautions:
• Do not remove the protective coverings from the
electrical panel.
• Store the chiller in a dry, secure area.
• At least every three months, attach a gauge and
manually check the pressure in the refrigerant circuit.
If the refrigerant pressure is below 71 psig at 70oF (or
14 RTHD-SVX01G-EN
Pre-Installation
Installation Requirements
A list of the contractor responsibilities typically associate
with the unit installation process is provided in Table 4.
RTHD-SVX01G-EN 15
Dimensions and Weights
Unit Dimensions
See unit submittals for specific unit dimensions and water
connection locations.
Unit Weights
Table 5. Weights — standard units (wye-delta starter)
16 RTHD-SVX01G-EN
Dimensions and Weights
RTHD-SVX01G-EN 17
Dimensions and Weights
Service Clearances
Notes:
• Required vertical clearance above unit is 36” (914 mm). • If the room configuration requires a variance to the
There should be no piping or conduit located over the clearance dimensions, contact your Trane sales office
compressor motor. representative.
• Maximum clearances are given. Some units
configurations may require less clearance than others
in the same category.
Tube Removal
Clearance
(Either End)
3’-0” (914mm)
EDE, DDE, CDE, BBB: Service Clearance
108” (2743mm) (Opposite
Tube Removal)
EFF, DFF, CEF, BCD:
126” (3200mm)
(a) Optional AFD is not shown. See Figure 3, p. 13 for location of optional AFD.
18 RTHD-SVX01G-EN
Installation Mechanical
Location Requirements Ventilation must be adequate to maintain an ambient
temperature lower than the following:
Sound Considerations Wye-Delta Starter Units: 104°F (40°C)
Note: See Trane Engineering Bulletin Sound Ratings and AFD Unit Option: 104°F (40°C)
Ventilation
The unit produces heat even though the compressor is
cooled by the refrigerant. Make provisions to remove heat
generated by unit operation from the equipment room.
RTHD-SVX01G-EN 19
Installation Mechanical
C B
= C.G.
X
D A
Y
(a) Optional AFD is not shown. See Figure 3, p. 13 for location of optional AFD. Lifting weights and center of gravity measurements are shown for both unit
configurations in tables below.
20 RTHD-SVX01G-EN
Installation Mechanical
RTHD-SVX01G-EN 21
Installation Mechanical
22 RTHD-SVX01G-EN
Installation Mechanical
Lifting Procedure
B
E D C
Anti-rolling
Cable
Eyelet or M16
Anti-rolling Internal Thread
Cable
F (min)
Lifting
Holes Starter Controls
44.5mm dia typ
Condenser Evaporator
Unit Model Number Location
(a) Optional AFD is not shown. See Figure 3, p. 13 for location of optional AFD. Rigging information is same for wye-delta or AFD units.
RTHD-SVX01G-EN 23
Installation Mechanical
24 RTHD-SVX01G-EN
Installation Mechanical
RTHD-SVX01G-EN 25
Installation Mechanical
10. Remove the shipping brackets from the bottom sides shell to level the unit. Unit should be level to within 1/
of the oil separator(s). See Figure 11. 4” (6.35 mm) over its length.
Figure 11. Oil separator shipping bracket 3. Place the level on the evaporator shell tube sheet
support to check side-to-side (front-to-back) level.
Adjust to within 1/4” (6.35 mm) of level front-to-back.
Note: The evaporator MUST be level for optimum heat
transfer and unit performance.
4. Use full-length shims to level the unit.
Durometer: 50 ± 5 Durometer: 40 ± 5
0.31 0.31
Durometer: 55± 5
Typical Elastomeric
Isolation Pad
0.31
B
A
(hidden leg)
D
C
NOTE: Level unit to 1/4” (6.25mm)
across length and width.
Pads extend the full
width of the legs
26 RTHD-SVX01G-EN
Installation Mechanical
RTHD-SVX01G-EN 27
Installation Mechanical
28 RTHD-SVX01G-EN
Installation Mechanical
RTHD-SVX01G-EN 29
Installation Mechanical
30 RTHD-SVX01G-EN
Installation Mechanical
Water Piping
Figure 13. Typical water piping setup
Cond Water
Shutoff Ref Valve (Opt)
Shutoff
Valves Relief Relief
Valves Isolation
Valve Valve
Isolation Valves
Manifold Manifold
Valves
Cond
Water
Evap Flow
Water
Flow
Flow Pressure
Flow Switch Differential
Pressure Switch Gauge
Thermometers
Differential Thermometers
Gauge
RTHD-SVX01G-EN 31
Installation Mechanical
OUT
OUT
IN IN
2 Pass Evap Connection
Configuration
COND EVAP (left or right hand)
Depending on Water Inlet
OUT
OUT
IN
IN
3 Pass Evap Connection
Configuration
COND EVAP (left or right hand)
Depending on Water Inlet
32 RTHD-SVX01G-EN
Installation Mechanical
RTHD-SVX01G-EN 33
Installation Mechanical
34 RTHD-SVX01G-EN
Installation Mechanical
minimum shown on the pressure drop curves. Follow the Relief valve discharge setpoints and capacities rates are
manufacturer’s recommendations for selection and given in Table 10. Once the relief valve has opened, it will
installation procedures. General guidelines for flow switch re-close when pressure is reduced to a safe level.
installation are outlined below. Note: Once opened, relief valves may have tendency to
• Mount the switch upright, with a minimum of 5 pipe leak and must be replaced.
diameters straight, horizontal run on each side.
• Do not install close to elbows, orifices or valves. Figure 17. Relief valve location
Note: The arrow on the switch must point in the direction
of the water flow. Relief
Valves
• To prevent switch fluttering, remove all air from the
water system
Note: The UC800 provides a 6-second time delay on the
flow switch input before shutting down the unit on
a loss-of-flow diagnostic. Contact a qualified
service organization if nuisance machine
shutdowns persist.
• Adjust the switch to open when water flow falls below
nominal. See “General Information,” p. 9, general data
tables for minimum flow recommendations for
specific water pass arrangements. Flow switch Evaporator Shell
contacts are closed on proof of water flow.
RTHD-SVX01G-EN 35
Installation Mechanical
36 RTHD-SVX01G-EN
Installation Mechanical
Freeze Protection
For unit operation in a low temperature environment, glycol solution strengths are contained in Table 12 as
adequate protection measures must be taken against follows:
freezing. Adjusted settings and recommended ethylene
Table 12. Low refrigerant temperature, ethylene glycol, and freeze protection settings
DDE, EDE, CBC(b) DFF, EFF, CDE, BCD, BBB, CFF(b) DGG, EGG, CEF(b)
Chilled Low Rfgt Low Rfgt Solution Low Rfgt
Water Leaving Temp Rec % Solution Temp Rec % Freeze Temp Rec % Solution
Setpt Wtr Temp Cutout(c) Ethylene Freeze Cutout(c) Ethylene Point Cutout(c) Ethylene Freeze
(F)(a) Cutout (F) (F) Glycol Point (F) (F) Glycol (F) (F) Glycol Point (F)
40 34 28.6 0 32.0 28.6 0 32.0 28.6 0 32.0
39 33 27.2 2 30.6 27.6 1 31.3 27.9 0 32.0
38 32 25.7 4 29.1 26.5 3 30.1 27.2 2 31.1
37 31 24.2 6 27.6 25.4 5 28.9 26.5 3 30.2
36 30 22.7 8 26.1 24.2 6 27.7 25.7 4 29.3
35 29 21.1 11 24.5 23.0 8 26.4 24.9 6 28.3
34 28 20.2 12 23.6 22.1 10 25.5 24.0 7 27.4
33 27 19.2 13 22.6 21.1 11 24.5 23.0 8 26.4
32 26 18.1 15 21.5 20.1 12 23.5 22.0 10 25.4
31 25 17.0 16 20.4 18.8 14 22.2 20.6 12 24.0
30 24 15.9 17 19.3 17.6 15 21.0 19.3 13 22.7
29 23 14.8 18 18.2 16.6 16 20.0 18.4 14 21.8
28 22 13.6 20 17.0 15.5 17 18.9 17.4 15 20.8
27 21 12.4 21 15.8 14.4 18 17.8 16.4 16 19.8
26 20 11.2 22 14.6 13.3 20 16.7 15.4 17 18.8
25 19 9.9 23 13.3 12.1 21 15.5 14.3 19 17.7
24 18 8.6 24 12.0 10.9 22 14.3 13.2 20 16.6
23 17 7.3 25 10.7 9.7 23 13.1 12.1 21 15.5
22 16 5.9 26 9.3 8.4 24 11.8 10.9 22 14.3
21 15 4.5 27 7.9 7.1 25 10.5 9.7 23 13.1
20 14 3.1 28 6.5 5.8 26 9.2 8.5 24 11.9
19 13 1.6 30 5.0 4.4 27 7.8 7.3 25 10.7
18 12 0.1 31 3.5 3.1 29 6.5 6.0 27 9.4
17 11 -1.4 32 2.0 1.6 30 5.0 4.7 28 8.1
16 10 -2.9 33 0.5 0.2 31 3.6 3.3 29 6.7
15 9 -4.5 33 -1.1 -1.3 32 2.1 2.0 30 5.4
14 8 N/A 34 -2.8 -2.8 33 0.6 0.6 31 4.0
13 7 N/A 35 -4.4 -4.3 34 -0.9 -0.8 32 2.6
12 6 N/A 36 -6.1 N/A 34 -2.5 -2.3 33 1.1
11 5 N/A 37 -7.8 N/A 35 -4.1 -3.8 34 -0.4
10 4 N/A 38 -9.6 N/A 36 -5.7 -5.3 34 -1.9
(a) Column “Chilled Water Setpoint” becomes “Actual Leaving Solution Temperature” for ice-making.
(b) See unit model number digits 6, 14, 21
(c) “N/A” means chiller is not to be applied at leaving evaporator water temperatures, which results in the LRTC setting below those shown in the table.
RTHD-SVX01G-EN 37
Installation Electrical
General Recommendations Important: Do not allow conduit to interfere with other
components, structural members or
As you review this manual, keep in mind that: equipment. Control voltage (115V) wiring in
• All field-installed wiring must conform to National conduit must be separate from conduit
Electric Code (NEC) guidelines, and any applicable carrying low voltage (<30V) wiring. To
state and local codes. Be sure to satisfy proper prevent control malfunctions, do not run
equipment grounding requirements per NEC. low voltage wiring (<30 V) in conduit with
• Compressor motor and unit electrical data is listed on conductors carrying more than 30 volts.
the chiller nameplate.
• All field-installed wiring must be checked for proper Electrical Data
terminations, and for possible shorts or grounds.
• For proper electrical component operation, do not Standard Units with Wye-Delta Starter
locate the unit in areas exposed to dust, dirt, corrosive See “Electrical Data Table Information,” p. 39. Electrical
fumes, or excessive humidity. If any of these component sizing should be based on actual jobsite
conditions exist, corrective action must be taken. operating conditions. This factor can be obtained through
Notes: the use of TOPSS™.
• Always refer to wiring diagrams shipped with chiller or
unit submittal for specific electrical schematic and Table 13. Compressor motor electrical data (60 Hz) —
connection information. standard units (wye-delta starter)
• All conduit must be long enough to allow compressor RLA @
and starter removal. Compressor Voltage Max LRA LRA
Code(a) (b) Max kW kW(c) (Wye) (Delta)
WARNING 200 174 557 970 3103
Proper Field Wiring and Grounding 230 174 484 818 2617
Failure to follow code could result in death or serious 460 174 241 400 1280
injury. All field wiring MUST be performed by qualified 575 174 193 329 1053
personnel. Improperly installed and grounded field 200 249 812 1173 3634
wiring poses FIRE and ELECTROCUTION hazards. To
230 249 698 936 2901
avoid these hazards, you MUST follow requirements
for field wiring installation and grounding as described C1, C2 380 249 421 558 1727
in NEC and your local/state electrical codes. 460 249 349 469 1453
575 249 279 375 1162
WARNING 200 329 1047 1690 5477
38 RTHD-SVX01G-EN
Installation Electrical
amperes (RLA), locked rotor wye amperes (LRA) and 447 - 549 6663
expected inrush for the Wye-delta configurations are 0 - 197 2555
shown. 198 - 241 2949
Although the terms “LRA” and “expected inrush” are often 380V 50 Hz 242 - 292 3764
400V 50 Hz
used interchangeably, the distinction applied here is that 293 - 367 4109
415V 50 Hz
LRA is the rated inrush for the motor, but expected inrush
368 - 446 5129
is that allowed by the starter, based on the specific
447 - 549 6663
configuration. Selecting starters in the Wye-delta
configuration lowers expected inrush vs. the Delta (or Note: AFD input amps are shown in the RLA field of the unit nameplate.
RTHD-SVX01G-EN 39
Installation Electrical
Power Supply Wiring All power supply wiring must be sized and selected
accordingly by the project engineer in accordance with
NEC Table 310-16.
WARNING All wiring must comply with local codes and the National
Proper Field Wiring and Grounding Electrical Code. The installing (or electrical) contractor
must provide and install the system interconnecting
Required! wiring, as well as the power supply wiring. It must be
Failure to follow code could result in death or serious properly sized and equipped with the appropriate fused
injury. All field wiring MUST be performed by qualified disconnect switches.
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To The type and installation location(s) of the fused
avoid these hazards, you MUST follow requirements disconnects must comply with all applicable codes.
for field wiring installation and grounding as described
in NEC and your local/state electrical codes.
NOTICE:
Use Copper Conductors Only!
WARNING Failure to use copper conductors could result in
equipment damage as unit terminals are not designed
Hazardous Voltage w/Capacitors! to accept other types of conductors.
Failure to disconnect power and discharge capacitors
before servicing could result in death or serious injury. See Figure 19 for electrical installation panel locations.
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives
or other energy storing components provided by Trane
or others, refer to the appropriate manufacturer’s
literature for allowable waiting periods for discharge of
capacitors. Verify with an appropriate voltmeter that all
capacitors have discharged.
For additional information regarding the safe discharge
of capacitors, see PROD-SVB06A-EN.
Figure 19. Electrical Installation
6.1” x 14.6” (156x370mm)
opening for incoming line voltage
Evaporator
Condenser
40 RTHD-SVX01G-EN
Installation Electrical
Water Pump Power Supply 3. Connect the phase sequence indicator leads to the line
power terminal block (or the unit mounted disconnect)
Provide power supply wiring with fused disconnect for
as follows:
both the chilled water and condenser water pumps.
Phase Seq. Lead 1TB1 Terminal
Compressor Motor Phase Sequencing
Black (Phase A) L1
Always verify that proper rotation of the compressor is Red (Phase B) L2
established before the machine is started. Proper motor
Yellow (Phase C) L3
rotation requires confirmation of the electrical phase
sequence of the power supply. The motor is internally
4. Turn power on by closing the unit supply power
connected for clockwise rotation with incoming power
disconnect switch.
supply phased A, B, C.
5. Read the phase sequence on the indicator. The “ABC”
Units with Optional AFD. indicator on the face of the phase indicator will glow if
phase is “ABC”.
NOTICE:
Equipment Damage! WARNING
• Do not change AFD phase rotation to Hazardous Voltage w/Capacitors!
counterclockwise. Failure to disconnect power and discharge capacitors
• Do not enable phase reversal protection. before servicing could result in death or serious injury.
Disconnect all electric power, including remote
Changing default clockwise phase rotation or enabling disconnects before servicing. Follow proper lockout/
phase reversal protection could prevent proper chiller tagout procedures to ensure the power cannot be
operation or cause equipment damage. inadvertently energized. For variable frequency drives
or other energy storing components provided by Trane
AFD must be set with phase rotation clockwise (default or others, refer to the appropriate manufacturer’s
from factory), and phase reversal protection DISABLED. literature for allowable waiting periods for discharge of
capacitors. Verify with an appropriate voltmeter that all
All Units. To confirm the correct phase sequence (ABC), capacitors have discharged.
use a Model 45 Associated Research Phase indicator or
equivalent. For additional information regarding the safe discharge
of capacitors, see PROD-SVB06A-EN.
Voltages generated in each phase of a polyphase
alternator or circuit are called phase voltages. In a three- 6. If “CBA” indicator glows instead, open unit main
phase circuit, three sine wave voltages are generated, power disconnect and switch two line leads on the line
differing in phase by 120 electrical degrees. The order in power terminal block (or the unit mounted disconnect).
which the three voltages of a three-phase system succeed Re-close main power disconnect and recheck phasing.
one another is called phase sequence or phase rotation.
7. Reopen the unit disconnect and disconnect the phase
This is determined by the direction of rotation of the
indicator.
alternator. When rotation is clockwise, phase sequence is
usually called “ABC,” when counterclockwise, “CBA.” Electrical Connections
This direction may be reversed outside the alternator by Proper starter/control panel line-side lug sizes are
interchanging any two of the line wires. It is this possible specified on the unit submittals. These lug sizes must be
interchange of wiring that makes a phase sequence compatible with conductor sizes specified by the electrical
indicator necessary if the operator is to quickly determine engineer or contractor.
the phase rotation of the motor.
For recommended field connection lug sizes (RTHD
Correcting Improper Electrical Phase Sequence. starters) see unit submittal.
Proper compressor motor electrical phasing can be quickly Circuit Breakers and Non-Fused Disconnect
determined and corrected before starting the unit. If using Switches
an Associated Research Model 45 Phase Sequence
Indicator, follow this procedure:
(Factory Installed Option)
1. Press the STOP button to insure the unit will not Units that are ordered with factory installed circuit
attempt to start the compressor. breakers or non-fused disconnect switches ship with the
handle in the control panel. The handle must be installed
2. Open the electrical disconnect or circuit protection prior to starting the unit.
switch that provides line power to the line power
terminal block in the control panel (or to the unit- The operating mechanism is already pre-installed on the
mounted disconnect). Disconnect/ Circuit Breaker frame.
The hole locations and shafts lengths have already been
cut, and the shaft already installed.
RTHD-SVX01G-EN 41
Installation Electrical
WARNING WARNING
Hazardous Voltage w/Capacitors! Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors Failure to disconnect power and discharge capacitors
before servicing could result in death or serious injury. before servicing could result in death or serious injury.
Disconnect all electric power, including remote Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/ disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives inadvertently energized. For variable frequency drives
or other energy storing components provided by Trane or other energy storing components provided by Trane
or others, refer to the appropriate manufacturer’s or others, refer to the appropriate manufacturer’s
literature for allowable waiting periods for discharge of literature for allowable waiting periods for discharge of
capacitors. Verify with an appropriate voltmeter that all capacitors. Verify with an appropriate voltmeter that all
capacitors have discharged. capacitors have discharged.
For additional information regarding the safe discharge For additional information regarding the safe discharge
of capacitors, see PROD-SVB06A-EN. of capacitors, see PROD-SVB06A-EN.
1. Attach the handle and gasket to the enclosure door and Important: WHEN EVACUATING THE CHILLER’S
secure with the four bolts, lock washers and nut as REFRIGERANT SYSTEM, ALWAYS HAVE
shown in Figure 20. Tighten to 75 in-Lbs. THE MAIN POWER DISCONNECT/CIRCUIT
Note: There is an additional Lexan spacer on the handle, BREAKER OPENED.
not shown in the Figure 20. Do not remove. Even when the compressor is not running,
voltage is present at the compressor motor
terminals, providing the potential for
Figure 20. Handle on door current to flow through a low impedance
path.
1/4-20 Hex Nut (4)
1/4” Lockwasher (4)
NOTICE:
Gasket Equipment Damage!
When removing refrigerant for the chiller, both the
condenser and chilled water pump must be operating
Lock
Plate to avoid freeze up.
NOTICE:
Motor Damage!
Fully disconnect all power sources before pumpdown
or evacuation procedures and ensure disconnects
cannot be closed while chiller is in a vacuum. Failure to
Cut Away of
Enclosure Door do so could cause motor damage.
Handle Plate
Sealing Washer (4) As the chiller is evacuated below atmospheric pressure,
(Used with 4 & 4X the dielectric strength (resistance to arcing) of the gaseous
Enclosures Only) atmosphere is significantly reduced. Because the SCRs are
1/4-20 x 1 Square Neck Bolt (4) connected “inside the delta,” three of the motor terminals
are connected directly to the line voltage. An “arc over”
Handle
can occur between motor terminals under conditions seen
2. Check that when the enclosure door is closed, the in the evacuation process. If this occurs the circuit breaker
handle interlocks with the shaft in all handle positions (or other external protective devices) will trip in response
except RESET/OPEN. To open the enclosure door when to high fault currents, and motor damage may also occur.
the breaker is in the ON position, rotate the screw slot To avoid motor damage, verify chiller fully disconnected
on the handle plate counter -clockwise. Verify from all power sources before beginning
operation. pumpdown or evacuation procedures, and use proper
lockout/tagout procedures to make sure the disconnect
cannot be accidentally closed while the chiller is in a
vacuum.
42 RTHD-SVX01G-EN
Installation Electrical
RTHD-SVX01G-EN 43
Installation Electrical
pump relay. This diagnostic is automatically reset if flow is Reset Ratio calculation:
established at any later time. The Reset Ratio on the User Interface is displayed as a
Note: This diagnostic would never automatically reset if percentage. To use it in the above equation it must be
UC800 was in control of the condenser pump converted to its decimal form.
through its condenser pump relay since it is Reset Ratio percent / 100 = Reset Ratio decimal
commanded off at the time of the diagnostic. It
could however reset and allow normal chiller Example of converting Reset Ratio:
operation if the pump was controlled from some If the Reset Ratio displayed on the User Interface is 50%
external source.
then use (50/100) = 0.5 in the equation.
Chilled Water Reset (CWR) Abbreviations used in equations:
The controller will reset the chilled water temperature • TOD = Outdoor Air Temp
setpoint based on either return water temperature, or
• TWE = Evap Entering Water Temp
outdoor air temperature. The Return Reset option is
standard, Outdoor Reset is optional. • TWL = Evap Leaving Water Temp
The following is selectable: Programmable Relays (Alarm and Status) -
• RESET TYPE Setpoint. Optional
This can be set to: DISABLE, CONSTANT, RETURN or UC800 provides a flexible alarm or chiller status indication
OUTSIDE AIR. The MP shall not permit more than one to a remote location through a hard wired interface to a dry
type of reset to be selected. contact closure. Four relays are available for this function,
• RESET RATIO Setpoints. and they are provided (generally with a Quad Relay Output
For outdoor air temp. reset, both positive and negative LLID) as part of the Alarm Relay Output Option.
reset ratios will be allowed. The events/states that can be assigned to the
• START RESET Setpoints. programmable relays are listed in the following table.
• MAXIMUM RESET Setpoints.
The maximum resets shall be with respect to the Table 16. Chiller events/status descriptions
chilled water setpoint. Event/State Description
When the chiller is running, if any type of CWR is enabled, This output is true whenever there is any active
the controller will step the CWS toward the desired CWS' diagnostic that requires a manual reset to clear,
(based on the below equations and setup parameters) at a Alarm - Latching that affects the Chiller, the Circuit, or any of the
Compressors on a circuit. This classification does
rate of 1 degree F every 5 minutes until the Active CWS not include informational diagnostics.
equals the desired CWS'. When the chiller is not running
This output is true whenever there is any active
the CWS will be fully reset immediately (within one diagnostic that could automatically clear, that
minute). The chiller will then start at the Differential to Start affects the Chiller, the Circuit, or any of the
value above a fully reset CWS or CWS' for Outdoor, Return, Alarm - Auto Reset Compressors on a circuit. This classification does
not include informational diagnostics. If all of the
and Constant Return Reset. auto resetting diagnostics were to clear, this output
would return to a false condition.
Equations for calculating CWR
This output is true whenever there is any
Equation used to get Degrees of Reset: diagnostic effecting any component, whether
Alarm latching or automatically clearing. This
Outdoor Air: classification does not include informational
diagnostics.
Degrees of Reset =
Reset Ratio * (Start Reset - TOD) This output is true whenever there is any
Warning informational diagnostic affecting any component,
Return Reset: whether latching or automatically clearing.
Degrees of Reset = This output is true whenever the chiller has been
running in one of the Unloading types of limit
Reset Ratio * (Start Reset - (TWE - TWL)) modes (Condenser, Evaporator, Current Limit or
Constant Return: Phase Imbalance Limit) continuously for the last 20
minutes. A given limit or overlapping of different
Degrees of Reset = limits must be in effect continuously for 20 minutes
prior to the output becoming true. It will become
100% * (Design Delta Temp - (TWE - TWL))
Chiller Limit Mode false, if no Unload limits are present for 1 minute.
To obtain Active CWS from Degrees of Reset: The filter prevents short duration or transient
repetitive limits from indicating. The chiller is
Active CWS = Degrees of Reset + Previous CWS considered to be in a limit mode for the purposes
of front panel display and annunciation, only if it is
Note: Previous CWS can either be Front Panel, BAS, or fully inhibiting loading by virtue of being in either
External the “hold” or “forced unload” regions of the limit
control, excluding the “limited loading region”.
44 RTHD-SVX01G-EN
Installation Electrical
Table 16. Chiller events/status descriptions (continued) Note: A “panic” stop (similar to “emergency” stop) can
be manually commanded by pressing the STOP
Event/State Description
button twice in a row, the chiller will immediately
The output is true whenever any compressors are shut down, but without creating a latching
started or running on the chiller and false when no
compressors are either starting or running on the
diagnostic.
Compressor
chiller.
Running
This status may or may not reflect the true status
Soft Loading
of the compressor in Service Pumpdown if such a Soft loading will prevent the chiller from going to full
mode exists for a particular chiller.
capacity during the pull-down period.
This relay output is energized anytime the chiller is
running in one of the following modes; Ice Making The UC800 control system has two soft loading algorithms
Mode or Condenser Pressure Limit Control Mode running all of the time. They are capacity control soft
continuously for the duration specified by the
Chiller Head loading and current limit soft loading. These algorithms
Chiller Head Relief Relay Filter Time. The Chiller
Pressure Relief introduce the use of a Filtered Chilled Water Setpoint and
Head Relief Relay Filter Time is a service setpoint.
Request Relay
The relay output is de-energized anytime the a Filtered Current Limit Setpoint. After the compressor has
chiller exits all above modes continuously for the been started, the starting point of the filtered chilled water
duration specified by the same Chiller Head Relief
Relay Filter Time. setpoint is initialized to the value of the Evap Leaving
Water Temperature. The filtered current limit setpoint is
The UC800 Service Tool (Tracer® TU) is used to install and initialized to the value of the Current Limit Softload
assign any of the above listed events or status to each of Starting Percent. These filtered setpoints allow for a stable
the four relays provided with this option. pull-down that is user adjustable in duration. They also
eliminate sudden transients due to setpoint changes
The default assignments for the four available relays are
during normal chiller operation.
listed below.
Three settings are used to describe the behavior of soft
Table 17 Programmable relays loading. The setup for softloading can be done using
Tracer® TU.
LLID
Software • Capacity Control Softload Time: This setting controls
Relay Output the time constant of the Filtered Chilled Water
LLID Name Designation Name Default Setpoint. It is settable between 0 and 120 min.
Status Relay 4, Head Pressure Relief • Current Limit Control Softload Time: This Setting
Relay 0
J2-1,2,3 Request
controls the time constant of the Filtered Current Limit
Status Relay 3, Chiller Limit Mode Setpoint. It is settable between 0 and 120 minutes.
Operating Relay 1
J2-4,5,6 Relay
Status • Current Limit Softload Starting Percent: This setting
Programmable Chiller Alarm Relay
Status Relay 2, controls the starting point of the Filtered Current Limit
Relays Relay 2 (latching or
J2-7,8,9
nonlatching) Setpoint. It is adjustable from 40 for RTHD to 100
Status Relay 1, Compressor Running percent RLA.
Relay 3
J2-10,11,12 Relay
External Base Loading - Optional
Emergency Stop Primarily for process control requirements, base loading
The UC800 provides auxiliary control for a customer provides for immediate start and loading of a chiller up to
specified/installed latching trip out. When this customer- an externally or remotely adjustable current limit setpoint
furnished remote contact is provided, the chiller will run without regard to differential to start or stop, or to leaving
normally when the contact is closed. When the contact water temperature control. This allows the flexibility to
opens, the unit will trip off on a manually resettable prestart or preload a chiller in anticipation of a large load
diagnostic. This condition requires manual reset at the application. It also allows you to keep a chiller on line
chiller switch on the front of the control panel. between processes when leaving water temperature
control would normally cycle the unit.
External Auto/Stop When the base loading option is installed through TD7 it
If the unit requires the external Auto/Stop function, the will be controllable through TD7/Tracer® TU, External
installer must provide leads from the remote contacts to Hardware Interface or Tracer (if Tracer is installed). Order
the proper terminals of the LLID on the control panel. for precedence for all setpoints, TD7/Tracer® TU, then
The chiller will run normally when the contacts are closed. External then Tracer from lowest to highest priority. If one
When the contact opens, the compressor(s), if operating, of the higher priority setpoints drops out due to a bad
will go to the RUN:UNLOAD operating mode and cycle off. sensor or communication loss then base loading shall go
Unit operation will be inhibited. Re-closure of the contacts to the next lowest priority of command and setpoint. The
will permit the unit to automatically return to normal command settings and control setpoints associated with
operation. base loading are explained below.
RTHD-SVX01G-EN 45
Installation Electrical
If the input is configured as a 2 - 10 Vdc: • ‘Trane Drive Utility’ for configuration and tracking
% Load = 7.5 * (Vdc Input) + 25 See Service Manual BAS-SVM01A-EN for more
information.
Ice Making Contact - Optional
UC800 accepts a contact closure input to initiate Ice AFD Drive Installation
Building. When in the ice building mode, the compressor The AFD drive is manufactured with a jumper installed
will be fully loaded (not given a low setpoint) and will between terminal 12 (+24Vdc source) and terminal 37
continue to operate until the ice contacts open or the (Safe Stop digital input). This jumper must be removed
return water temperature reaches the Ice Termination prior to unit operation. See Figure 21 for view of jumper as
Setpoint. If terminated on return setpoint, UC800 will not it would be installed on drive from manufacturer.
allow chiller to restart until ice making contact is opened.
46 RTHD-SVX01G-EN
Installation Electrical
Important:
Table 18. Non-compressor specific parameter settings
• For factory provided AFD units, verify jumper has
been removed. ID Description Setting
• For field installed drives, remove jumper shown in 0-03 Region Settings North American
Figure 21. 0-20 Display Line 1.1 Small DC Link Voltage
0-22 Display Line 1.3 Heatsink Temp.
AFD Drive Programming 0-24 Display Line 3 Large Analog Input 53
0-40 [Hand on] Key on LCP Disabled
NOTICE:
0-41 [Off] Key on LCP Disabled
Equipment Damage! 0-60 Main Menu Password 999
• Do not change AFD phase rotation to 0-61 Access to Main Menu w/o Password Read Only
counterclockwise.
1-03 Torque Characteristics Compressor Torque
• Do not enable phase reversal protection. 1-71 Start Delay 0s
Changing default clockwise phase rotation or enabling 1-73 Flying Start Disabled
phase reversal protection could prevent proper chiller
1-78 Compressor Start Max Speed [Hz] 20Hz
operation or cause equipment damage.
1-79 Compressor Start Max Time to Trip 10s
Field replacement drives must be programmed via the 1-87 Trip Speed Low [Hz] 25Hz
keypad interface. Program non-compressor specific 3-02 Min Reference 30Hz
parameters first in sequential order (Table 18), followed by 3-41 Ramp 1 Ramp up Time 10s
compressor specific parameters (see Table 19) in
3-42 Ramp 1 Ramp Down Time 10s
sequential order.
3-82 Starting Ramp Up Time 5s
4-10 Motor Speed Direction Clockwise
4-12 Motor Speed Low Limit [Hz] 30Hz
4-18 Current Limit Max
5-02 Terminal 29 Mode Output
5-12 Terminal 27 Digital Input Coast Inverse
5-31 Terminal 29 Digital Output Alarm
5-40 Function Relay 1 No Operation
6-10 Terminal 53 Low Voltage 2V
6-14 Terminal 53 Low Ref./Feedb. Value 30Hz
6-50 Terminal 42 Output Power 4-20mA
14-00 Switching Pattern SFAVM
14-03 Overmodulation Off
14-10 Mains Failure [4] Kinetic Back-Up
14-12 Function at Mains Imbalance Derate
14-21 Automatic Restart Time 8s
14-50 RFI Filter Off
14-51 DC Link Compensation On
14-60 Function at Over Temperature Derate
14-61 Function at Inverter Overload Derate
14-62 Inv. Overload Derate Current 75%
RTHD-SVX01G-EN 47
Installation Electrical
E3
Motor
Parameters B1/B2 Motor Frame C1/C2 Motor Frame D1/D2/D3/E3 Motor Frame Frame
460/ 400/ 380/ 575/ 460/ 400/ 380/ 575/ 460/ 400/ 380/ 575/ 400/
ID Description 60 50 60 60 60 50 60 60 60 50 60 60 50
Motor Power
1-21 233 194 233 233 334 280 334 334 441 375 441 441 403
(hp)
Motor Voltage
1-22 460 400 380 575 460 400 380 575 460 400 380 575 400
(V)
Motor
1-23 Frequency 60 50 60 60 60 50 60 60 60 50 60 60 50
(Hz)
Motor Current
1-24 241 233 291 193 349 349 421 279 455 455 549 367 488
(A)
Motor Nominal
1-25 3512 2921 3512 3512 3531 2938 3531 3531 3535 2943 3535 3535 2943
Speed (rpm)
Stator
1-30 Resistance 0.0303 0.0303 0.0213 0.0430 0.0201 0.0201 0.0138 0.0308 0.0122 0.0122 0.0087 0.0197 0.0122
(ohms)
Rotor
1-31 Resistance 0.0257 0.0257 0.0179 0.0365 0.0146 0.0146 0.0103 0.0227 0.0091 0.0091 0.0066 0.0144 0.0091
(ohms)
Main
1-35 Reactance 5.3684 5.3684 3.9634 8.0570 3.005 3.005 2.1972 4.8857 2.8882 2.8882 2.1848 4.8553 2.8882
(ohms)
Iron Loss
1-36 Resistance 188.388 188.388 142.836 280.73 152.612 152.612 116.132 243.61 125.549 125.549 90.188 193.85 125.549
(ohms)
Maximum
3-03 Reference 60 50 60 60 60 50 60 60 60 50 60 60 50
(Hz)
Motor Speed
4-14 High Limit 60 50 60 60 60 50 60 60 60 50 60 60 50
(Hz)
Terminal 53
High Ref./
6-15 60 50 60 60 60 50 60 60 60 50 60 60 50
Feedback
Value (Hz)
Switching
14-01 Frequency 3 3 3 2 3 3 3 2 3 3 3 2 3
(kHz)
Voltage at
14-11 391 340 323 489 391 340 323 489 391 340 323 489 340
Main Fault (V)
(a) Compressor frame size is shown in model number digits 6 and 7.
48 RTHD-SVX01G-EN
Installation Electrical
Communications Interface
LonTalk® Interface (LCI-C)
UC800 provides an optional LonTalk® Communication
Interface (LCI-C) between the chiller and a Building
Automation System (BAS). An LCI-C LLID shall be used to
provide “gateway” functionality between a LonTalk
compatible device and the Chiller. The inputs/outputs
include both mandatory and optional network variables as
established by the LONMARK® Functional Chiller Profile
8040.
Note: For more information see ACC-SVN100*-EN.
RTHD-SVX01G-EN 49
Operating Principles
This section describes the overall operating principles of the compressor to discharge pressure conditions.
the Optimus™ water chiller. Simultaneously, lubricant is injected into the compressor.
An oil management system provides an almost oil-free
General refrigerant to the shells to maximize heat transfer
performance, while providing lubrication and rotor
Optimus™ units are single-compressor water-cooled sealing to the compressor. The lubrication system ensures
liquid chillers. These units are equipped with unit- long compressor life and contributes to quiet operation.
mounted starter/control panels.
Immediately following the compression process the
The basic components are: lubricant and refrigerant are effectively divided using an
• Unit-mounted panel containing UC800 controller and oil separator.
input/output LLIDs The oil-free refrigerant vapor enters the condenser at State
• Helical-rotary compressor Pt. 2. Condensing is accomplished in a shell-and-tube heat
exchanger where refrigerant is condensed on the shell
• Evaporator
side and water flows internally in the tubes. Cooling tower
• Electronic expansion valve water, circulating through the condenser tubes, absorbs
• Water-cooled condenser with integral subcooler heat from this refrigerant and condenses it.
• Oil supply system As the refrigerant leaves the bottom of the condenser
(State Pt. 3), it enters an integral subcooler where it is
• Oil cooler (application dependent)
subcooled before traveling to the electronic expansion
• Related interconnecting piping valve (State Pt. 4). The pressure drop created by the
• AFD (optional) expansion process vaporizes a portion of the liquid
refrigerant.
Refrigeration Cycle The resulting mixture of liquid and gaseous refrigerant
then enters the Evaporator Distribution system (State Pt.
The refrigeration cycle can be described using the 5). The flash gas from the expansion process is internally
pressure-enthalpy diagram shown in Figure 22. Key State routed to compressor suction, and while the liquid
Points are indicated on the figure and are referenced in the refrigerant is distributed over the tube bundle in the
discussion following. evaporator.
50 RTHD-SVX01G-EN
Operating Principles
copper with lands at all tube sheets. All tube sheets are
made of carbon steel. Tubes are mechanically expanded
into tube sheets and mechanically fastened to tube
supports. Evaporator tubes are 1.0- inch (25.4 mm)
diameter and condenser tubes are 0.75-inch (19.05 mm)
diameter. All tubes can be individually replaced.
Shells are carbon steel plate. The evaporator and
condenser are designed, tested, and stamped in
accordance with ASME Code for refrigerant-side/ working-
side pressure of 200 psig (13.8 bars).
All water pass arrangements are available with grooved
connections (150 or 300 psig waterside working pressure).
All connections may be either right- or left-handed.
Waterside shall be hydrostatically tested at 1.5X design
working pressure.
Oil Management
The unit is configured with an oil management system that
ensures proper oil circulation throughout the unit. The key
components of the system include an oil separator, oil
filter, oil sump and oil sump heater. An optional oil cooler
is installed when the unit is used for high condensing
temperature or low evaporator temperature conditions.
Unit-Mounted Starter
A unit-mounted starter and control panel is provided on
every chiller. Microprocessor-based unit control modules
(Tracer® UC800) provide for accurate chilled water control
as well as monitoring, protection and adaptive limit
functions. The “adaptive” nature of the controls
intelligently prevents the chiller from operating outside of
its limits, or compensates for unusual operating
conditions, while keeping the chiller running rather than
simply tripping due to a safety concern. When problems
do occur, diagnostic messages assist the operator in
troubleshooting.
RTHD-SVX01G-EN 51
Controls
Overview UC800 Specifications
Optimus™ RTHD units utilize the following control/ This section covers information pertaining to the UC800
interface components: controller hardware.
• Tracer® UC800 Controller
Wiring and Port Descriptions
• Tracer AdaptiView™ TD7 Operator Interface
Figure 23 illustrates the UC800 controller ports, LEDs,
rotary switches, and wiring terminals. The numbered list
following Figure 23 corresponds to the numbered callouts
in the illustration.
2 3 4 5
6 6
7
8
9
10
10 11
11
Front View Bottom View
52 RTHD-SVX01G-EN
Controls
Communication Interfaces
Table 20. LED behavior
There are four connections on the UC800 that support the
communication interfaces listed. See Figure 23, p. 52 for LED UC800 Status
the locations of each of these ports. Powered. If the Marquee LED is green solid, the
UC800 is powered and no problems exist.
• BACnet® MS/TP
Low power or malfunction. If the Marquee LED is
• MODBUS™ Slave Marquee LED red solid, the UC800 is powered, but there are
• LonTalk™ using LCI-C (from the IPC3 bus) problems present.
• Comm 4 using TCI (from the IPC3 bus) Alarm. The Marquee LED blinks Red when an alarm
exists.
Rotary Switches The TX LED blinks green at the data transfer rate
when the UC800 transfers data to other devices on
There are three rotary switches on the front of the UC800 LINK, MBUS, the link.
controller. Use these switches to define a three-digit IMC The Rx LED blinks yellow at the data transfer rate
address when the UC800 is installed in a BACnet or when the UC800 receives data from other devices on
the link.
MODBUS system (e.g., 107, 127, etc.).
The LINK LED is solid green if the Ethernet link is
Note: Valid addresses are 001 to 127 for BACnet and 001 connected and communicating.
Ethernet Link
to 247 for MODBUS. The ACT LED blinks yellow at the data transfer rate
when data flow is active on the link.
LED Description and Operation Service
The Service LED is solid green when pressed. For
qualified service technicians only. Do not use.
There are 10 LEDs on the front of the UC800. Figure 24
shows the locations of each LED and Table 20, p. 53 Important: Maintain at least 6” between low-voltage
describes their behavior in specific instances. (<30V) and high voltage circuits to prevent
control malfunctions, do not run low
Figure 24. LED locations voltage wiring (<30 V) in conduit with
conductors carrying more than 30 volts.
Marquee
Tracer AdaptiView™ TD7 Display
Operator Interface
Information is tailored to operators, service technicians,
and owners. When operating a chiller, there is specific
information you need on a day-to-day basis—setpoints,
limits, diagnostic information, and reports. Day-to-day
operational information is presented at the display.
Logically organized groups of information— chiller modes
of operation, active diagnostics, settings and reports put
information conveniently at your fingertips.
Operator Display Boot Screen Display Loading Data Home Screen, Auto Mode
RTHD-SVX01G-EN 53
Controls
Home Screen Note: You can also access the Chiller Operating Modes
screen from the chiller status button in the upper
The home screen (Table 26) provides the most frequently left corner of the screen.
needed chiller status information on “touch targets” (the
entire white rectangular areas) for each chiller component. Figure 27. Chiller operating modes
Touching any touch target displays a screen containing
more chiller status information related to each
component.
The chiller is not running and cannot run without intervention. Further information is provided
Stopped
by the sub-mode:
Local Stop Chiller is stopped by TD7 Stop button command– cannot be remotely overridden.
Chiller is stopped by the TD7 Panic Stop (by pressing Stop then Immediate Shutdown in succession) –
Immediate Stop
previous shutdown was manually commanded to shutdown immediately.
Diagnostic Shutdown – Manual Reset The chiller is stopped by a diagnostic that requires manual intervention to reset.
The chiller is currently being inhibited from starting (and running*), but may be allowed to start
Run Inhibit if the inhibiting or diagnostic condition is cleared. Further information is provided by the sub-
mode:
Diagnostic Shutdown – Auto Reset The entire chiller is stopped by a diagnostic that may automatically clear.
54 RTHD-SVX01G-EN
Controls
RTHD-SVX01G-EN 55
Controls
Alarms
Figure 28. Alarm screen
You can use the display to view alarms and to reset them.
Alarms are communicated to the display immediately
upon detection.
56 RTHD-SVX01G-EN
Controls
regardless of type, machine or circuit. The scrollable list Editing a Custom Report
will be sorted by time of occurrence.
You can edit the custom report by adding, removing, or re-
“Alarms” Key Behavior: order data as follows:
• Alarm Shutdown (immediate) has occurred: Flash red 1. On the Custom Report screen, touch Edit. The Edit
• Alarm Shutdown (normal) has occurred: Flash yellow Custom Report screen appears.
• Informational warning is present: Flash blue 2. Add, remove, or re-order as follows:
No alarms present: Default button color, not flashing a. To add an item to the custom report, touch it. It
responds by changing to blue. You can use the
Reports arrows to scroll through the rest of the items that
can be added to the custom report. Then touch Add
You can use the TD7 display to view a variety of reports
to move the selected item to the box on the right
and to create and edit a custom report. All reports contain
side of the screen.
live data that refreshes every 2–5 seconds.
b. To remove an item from the custom report, touch it.
Viewing the Reports Screen It responds by changing to blue. You can use the
Touch the Reports button in the main menu area (Figure 4) arrows to scroll through the rest of the items that
to view the Reports screen. The Reports screen contains can be removed from the custom report. Then touch
the following buttons: Remove to move the selected item to the box on the
left side of the screen.
• Custom Report1
c. To re-order items in the custom report, touch it. It
• Custom Report2 responds by changing to blue. Use the arrows to
• Custom Report3 change the order of a highlighted item.
• Evaporator 3. To save and view your edited custom report, touch
• Condenser Save.
RTHD-SVX01G-EN 57
Controls
Table 23. Report evaporator screen items Figure 33. Report compressor screen
58 RTHD-SVX01G-EN
Controls
Equipment Settings
You can use the TD7 display to monitor and change a
variety of equipment settings.
Viewing the Settings Screen
Touch the Settings button in the main menu area (see
Figure 26, p. 54) to view the Settings screen. Equipment
Settings identifies a column of buttons located on the
To change an equipment setting, follow this procedure:
screen (see the outlined column in Figure 35). The buttons
are: 1. Touch one of the button in the Equipment Settings
column on the Settings screen, such as Chiller Settings.
• Chiller Settings
The corresponding screen appears (in this case, the
• Feature Settings Chiller Settings screen).
• Chiller Water Reset 2. Touch the button that shows the equipment setting you
• Manual Control Settings want to change. A screen that allows you to change the
equipment setting appears. There are two types of
Each of these buttons provide access to a screen that
these screens:
contains additional buttons related to each topic. This
section provides detailed information about these a. For screens with button selections (Figure 37),
screens. touch the button that represents the setting you
want. The button becomes shaded, and a Save
Figure 35. Setting screen button appears at the bottom of the screen.
b. For screens with numerical keypads (Figure 38),
touch the appropriate numbers to change the
current value. The new value appears above the
keypad.
3. Touch Save to complete the change. The current value
is updated in the upper left side of the screen,
demonstrating that the change has been
communicated to the Tracer® UC800 controller. The
screen you were previously viewing appears.
RTHD-SVX01G-EN 59
Controls
• When you enter a new number, the value in the New Return Reset Ratio XXX %
value field is deleted and replaced with the new entry. Return Start Reset XXX.X °F / °C
• The backspace (arrow) key deletes the characters you Return Maximum Reset XXX.X °F / °C
previously entered. Outdoor Reset Ratio XXX %
• If the keypad is used to enter a setpoint that is out of Outdoor Start Reset XXX.X °F / °C
range, an error dialog will appear when you touch the Outdoor Maximum Reset XXX.X °F / °C
Save button. Mode Overrides
• Keypads that allow negative numbers have positive Evap Water Pump (Auto, On) Auto Text
and negative number (+/-) keys. Cond Water Pump (Auto, On) Auto Text
60 RTHD-SVX01G-EN
Controls
Service Settings Each button provide access to a screen that is related to the
button name.
Setpoints on the Service Settings screen are only intended
for use by experienced service personnel. Setpoints Viewing and Changing Display Preferences
include security, if enabled. On the Settings screen, touch Display Preferences to view
The Service Settings screen is found through Chiller a screen containing these buttons (see Figure 29):
Settings, and includes a warning message for the user. • Date Format
• Date Separator
Figure 39. Warning message
• Time Format
• Unit System
• Pressure Units
• Number Format
Display Settings
You can use the Tracer AdaptiView™ display to change the
format of the information that appears on the display, and
to clean the touch screen.
RTHD-SVX01G-EN 61
Controls
Date Format . Use the Date Format screen to choose 1. Touch the button that identifies the language you
from the following date formats: prefer.
• MMDDYYYY (default) 2. Touch Save to confirm your selection and to return to
the Settings screen.
• YYYYMMDD
• DDMMYYYY Figure 44. Date and time screen
Date Separator . Use the Date Separator screen to
choose from the following date formats:
• None
• Slash (default)
• Hyphen
Time Format . Use the Time Format screen to choose
from the following time formats:
• 12 hour (default)
• 24 hour
Units System . Use the Display Units screen to choose
from the following display units:
• SI The current date and time for the display is expressed as
the current value. The current value appears below the
• Inch-Pounds (default)
center line on the screen.
Pressure Units . Use the Pressure Units screen to Above the center line, the following date and time
choose from the following pressure units: attributes appear:
• kPaA (default if “SI” is chosen for display units) • Month
• kPaG • Day
• PSIA (default if “Inch-Pound” is chosen for display • Year
units)
• Hour
• PSIG
• Minute
Number Format .
• AM/PM
• 1000000.0
To change the date or time:
• 1000000,0
1. Touch the square presenting the attribute you want to
change. The square becomes highlighted.
Figure 43. Language page
2. Touch the up or down arrow key on the screen until the
your desired selection appears. Repeat the process for
any other attributes you want to change.
3. Touch Save to confirm your selection and return to the
Settings screen.
Note: Alternately, fields can be edited by touching the
highlighted square a second time to access a
keypad.
62 RTHD-SVX01G-EN
Controls
Cleaning the Display 3. Touch Save. The Settings screen appears with a Log
out button, in addition to the Security button.
On the Settings screen, touch Clean Display to disable the Figure 46. Security screen - disable
Tracer AdaptiView™ display screen for 5 seconds after
finger is removed. This process allows screen cleaning
without it responding to touch. During this time, the screen
is black with a number in the center that counts down the
seconds. After 5 seconds, the Settings screen re-appears.
Security Settings
If security if enabled, the Tracer AdaptiView™ display
requires that you log in with a four-digit security PIN to
make setting changes that are protected by security. This
feature prevents unauthorized personnel from doing so.
There are two levels of security, each allowing specific
changes to be made.
You can view all data without logging in. The log-in screen
appears only when you try to change a setting that is
protected by security, or when you touch the Log in button
Logging In
from the Settings screen.
There are two levels of security:
Disabling/Enabling Security • Security Level 1 allows users to change a limited group
The Tracer AdaptiView™ display gives you the ability to of secure settings. The default security PIN is 1111.
disable or enable the security feature that allows a user to • Security Level 2 allows users to change all secure
log in and log out. settings. The default security PIN is 7123.
To disable security, you must be logged in: A technician must use the Tracer® TU service tool to define
1. From the Settings screen, touch the Security button. a different PIN, or to recall a PIN that has been forgotten.
The Security screen appears (Figure 46). When defining a PIN in Tracer® TU, the technician enters
a 4-digit PIN that corresponds with the desired level of
Note: If you are logged out, the Log in screen appears.
security.
2. Touch the Disable button. The button becomes shaded.
To log in:
3. Touch Save. The Settings screen appears with only the
1. Touch the Log in button. The Log in screen appears
Security button visible. The Log in/Logout button is
(Figure 47).
gone.
2. Use the keypad to enter your PIN.
To enable security:
a. The PIN is a four-digit number, which was
1. From the Settings screen, touch the Security button.
configured for your system with the Tracer® TU
The Security screen appears (Figure 46).
service tool.
2. Touch the Enable button. The button becomes shaded.
b. As you enter the number, the PIN remains hidden
by asterisks.
Note: If you enter an invalid PIN, an error message
appears on the Log in screen.
RTHD-SVX01G-EN 63
Controls
3. Touch Save.
a. If you viewed the Log in screen from touching Log
in on the Settings screen, the Settings screen
appears with a Log out button on it.
b. If the Log in screen appeared when you tried to
change a setting, you return to that setting screen.
Note: The PIN is valid until 30 minutes of inactivity
passes, or until you log out.
Logging Out
To log out:
1. Touch the Log out button. A confirmation screen
appears (Figure 49).
2. Touch Yes to confirm that you want to log out. The
Settings screen appears with a Log in button on it.
64 RTHD-SVX01G-EN
Controls
Tracer® TU
Tracer® TU (non-Trane personnel, contact your local Trane Tracer® TU is designed to run on a customer’s laptop,
office for software) adds a level of sophistication that connected to the Tracer AdaptiView™ control panel with a
improves service technician effectiveness and minimizes USB cable. Your laptop must meet the following hardware
chiller downtime.TheTracer AdaptiView™ control’s and software requirements:
operator interface is intended to serve only typical daily • 1 GB RAM (minimum)
tasks. The portable PC-based service-tool software,
Tracer® TU, supports service and maintenance tasks. • 1024 x 768 screen resolution
Tracer® TU serves as a common interface to all Trane® • Ethernet 10/100 LAN card
chillers, and will customize itself based on the properties of • Available USB 2.0 port
the chiller with which it is communicating.Thus, the
• Microsoft® Windows® 7 Enterprise or Professional
service technician learns only one service interface.
operating system (32-bit or 64-bit) or Windows 8.1.
The panel bus is easy to troubleshoot using LED sensor
Important: Tracer® TU V8.6 was the final release to
verification. Only the defective device is replaced.Tracer®
support Windows XP. Beginning with
TU can communicate with individual devices or groups of
Tracer® TU V9.0, you will need to migrate to
devices.
Windows 7 or Windows 8.1 operating
All chiller status, machine configuration settings, system.
customizable limits, and up to 100 active or historic
Notes:
diagnostics are displayed through the service-tool
software interface. • Tracer® TU is designed and validated for this minimum
laptop configuration. Any variation from this
LEDs and their respective Tracer® TU indicators visually configuration may have different results. Therefore,
confirm the availability of each connected sensor, relay, support for Tracer® TU is limited to only those laptops
and actuator. with the configuration previously specified.
For more information, see TTU-SVN01*-EN Tracer® TU
Getting Started Guide.
RTHD-SVX01G-EN 65
Pre-Start
Upon completion of installation, complete the Optimus™
RTHD Installation Completion Check Sheet and Request
for Trane Service checklist in chapter “Log and Check
Sheets,” p. 95.
Important: Start-up must be performed by Trane or an
agent of Trane specifically authorized to
perform start-up and warranty of Trane
products. Contractor shall provide Trane (or
an agent of Trane specifically authorized to
perform start-up) with notice of the
scheduled start-up at least two weeks prior
to the scheduled start-up.
66 RTHD-SVX01G-EN
Start-Up and Shutdown
Important: Initial unit commissioning start-up must be 3. The unit will start normally, provided the following
performed by Trane or an agent of Trane conditions exist:
specifically authorized to perform start-up a. The UC800 receives a call for cooling and the
and warranty of Trane products. Contractor differential-to-start is above the setpoint.
shall provide Trane (or an agent of Trane
specifically authorized to perform start-up) b. All system operating interlocks and safety circuits
with notice of the scheduled start-up at least are satisfied.
two weeks prior to the scheduled start-up.
Extended Unit Shutdown
Unit Start-Up 4. Perform the normal unit stop sequence using the
<Stop> key.
NOTICE:
Note: Do not open starter disconnect switch. This must
Equipment Damage! remain closed to provide control power from the
Ensure that the compressor and oil sump heaters have control power transformer to the oil sump heater.
been operating properly for a minimum of 24 hours 5. Verify chilled water and condenser water pumps are
before starting. Failure to do so could result in
equipment damage. cycled off. If desired, open disconnect switches to the
pumps.
If required, once the system has been operating for 6. Drain condenser piping and cooling tower, if desired.
approximately 30 minutes and has become stabilized, 7. Remove the drain and vent plugs from the condenser
complete the remaining start-up procedures, as follows: headers to drain the condenser.
1. Check evaporator and condenser refrigerant pressures 8. Verify that the Crank Case heater is working.
under Refrigerant Report on the AdaptiView ™TD7. The
9. Once the unit is secured, perform the maintenance
pressures are referenced to sea level (14.6960 psia).
identified in the following sections.
2. Check EXV sight glasses after sufficient time has
elapsed to stabilize the chiller. The refrigerant flow past
sight glasses should be clear. Bubbles in the
Seasonal Unit Start-Up Procedure
refrigerant indicate either low refrigerant charge or 1. Close all valves and re-install the drain plugs in the
excessive pressure drop in the liquid line or a stuck evaporator and condenser heads.
open expansion valve. A restriction in the line can
sometimes be identified by a noticeable temperature 2. Service the auxiliary equipment according to the start-
differential between the two sides of the restriction. up/maintenance instructions provided by the
Frost will often form on the line at this point. See respective equipment manufacturers.
“General Information,” p. 9 for proper refrigerant 3. Vent and fill the cooling tower, if used, as well as the
charges. condenser and piping. At this point, all air must be
Important: A clear sight glass alone does not mean that removed from the system (including each pass). Close
the system is properly charged. Also check the vents in the evaporator chilled water circuits.
system subcooling, liquid level control and 4. Open all valves in the evaporator chilled water circuits.
unit operating pressures. 5. If the evaporator was previously drained, vent and fill
If chiller is limited by any limiting conditions, contact local the evaporator and chilled water circuit. When all air is
Trane service organization for more information. removed from the system (including each pass), install
the vent plugs in the evaporator water boxes.
Temporary Shutdown And NOTICE:
Restart Equipment Damage!
To shut down for a short time, use the following procedure: Ensure that the oil sump heaters have been operating
for a minimum of 24 hours before starting. Failure to do
1. Press the STOP key on the Adaptiview TD7. The so may result in equipment damage.
compressors will continue to operate and an
operational pumpdown cycle will be initiated. 6. Check the adjustment and operation of each safety and
2. UC800 pump control will turn off the pump (after a operating control.
minimum 1 min. delay) when the STOP key is pressed 7. Close all disconnect switches.
and automatically restart the pump when the unit
starts normally. 8. Refer to the sequence for daily unit startup for the
remainder of the seasonal startup
RTHD-SVX01G-EN 67
Start-Up and Shutdown
Sequence of Operation
This section will provide basic information on chiller • The text in the circles is the visible top level operating
operation for common events. With microelectronic mode displayed on Tracer™ AdaptiView.
controls, ladder diagrams cannot show today’s complex • The shading of each software state circle corresponds
logic, as the control functions are much more involved to the shading on the time lines that show the state the
than older pneumatic or solid state controls. chiller is in.
Adaptive control algorithms can also complicate the exact There are five generic states that the software can be in:
sequence of operations. This section illustrates common
control sequences. • Power Up
• Stopped
Software Operation Overview
• Starting
The Software Operation Overview shown in Figure 51 is a
• Running
diagram of the five possible software states. This diagram
can be though of as a state chart, with the arrows and • Stopping
•
RTHD Sequence Of
Operation Overview:
Power
Stopped Up
Stopped
Run Inhibit
ed Co Sta r
rm mm t
onfi own and
C utd
Sh
Auto
Stopping Fast Restart or Satisfied Setpoint Auto
Preparing to Shut Down Waiting to Start
Shutting Down Starting Compressor
Stop Command or Diagnostic
Sto
pC
om
ma art
Dia nd St
gn ed
os nfirm
tic Running Co
Running
Running - Limit
Timelines
• The time line indicates the upper level operating mode, • Boxes indicate control actions such as turning on
as it would be viewed on the Tracer AdaptiView™. relays, or pulsing compressor load or unload
• The shading color of the cylinder indicates the solenoids.
software state. • Smaller cylinders under the main cylinder indicate
• Text in parentheses indicates sub-mode text as viewed diagnostic checks.
on Tracer AdaptiView™. • Text outside a box or cylinder indicates time based
• Text above the time line cylinder is used to illustrate functions.
inputs to the Main Processor. This may include user • Solid double arrows indicate fixed timers.
input to the Tracer AdaptiView™ Touch screen, control • Dashed double arrows indicate variable timers.
inputs from sensors, or control inputs from a Generic
BAS.
68 RTHD-SVX01G-EN
Start-Up and Shutdown
Power Up
The Power up chart shows the respective TD7 screens state independent of the last mode. If the last mode before
during a power up of the main processor. This process power down was ‘Auto’, the transition from ‘Stopped’ to
takes from 30 to 50 seconds depending on the number of ‘Starting’ occurs, but it is not apparent to the user.
installed Options. On all power ups, the software model
will always transition through the ‘Stopped’ Software
Figure 52. Sequence of events: power up diagram
Black Screen
Operator Display Boot Screen Display Loading Data Home Screen, Auto Mode
RTHD-SVX01G-EN 69
Start-Up and Shutdown
Power Up to Starting
The Power up to starting diagram shows the timing from • Power up Start Delay setpoint set to 0 minutes
a power up event to energizing the compressor. The • Adjustable Stop to Start Timer set to 5 seconds
shortest allowable time would be under the following
conditions: • Need to cool
• No motor restart inhibit The above conditions would allow for a minimum power
up to starting compressor time of 95 seconds.
• Evaporator and Condenser Water flowing
Figure 54. Sequence of events: power up to starting
Last Mode Call for
Was Auto Cooling
Enforce Power Up Enforce 'Cond Pmp (6 Second Filter) (0 to 30 mins) (0 to 300 Sec) (0 to 2 mins)
Start Delay Timer Strt Delay'
(0 to 30 mins) (0 to 300 Sec)
70 RTHD-SVX01G-EN
Start-Up and Shutdown
Stopped to Starting
The stopped to starting diagram shows the timing from a • Power up Start Delay Timer has expired
stopped mode to energizing the compressor. The shortest • Adjustable Stop to Start Timer has expired
allowable time would be under the following conditions:
• Need to cool
• No motor restart inhibit
The above conditions would allow the compressor to start
• Evaporator and Condenser Water flowing in 60 seconds.
Figure 55. Sequence of events: stopped to starting
Chiller Mode Call for
Set to Auto Cooling
Stopped
Or Waiting Waiting Waiting Waiting Waiting Starting
Auto Compressor
Run to Start to Start to Start to Start to Start
Inhibit
Confirm Evaporator Enforce Restart Confirm Condenser Condense r Enforce 'Cprsr Confirm Presence of Oil
Water Flow Inhibit Timer Water Flow Water Pump Strt Delay' With Optical Oil Sensor
(6 Second Filter) (0 to 30 mins) (6 Second Filter) Pre-Run (0 to 300 Sec) (0 to 2 mins)
Starting Wye-Delta
The Starting Wye-Delta shows the order of operation for this type of starter.
Figure 56. Sequence of events: Starting wye-delta
Energize Stop and Start
Relays
Starting Compressor
Starting Compressor Starting Compressor
Compressor Running
Starting Compressor
Starter Contactor Integrity Test Transition Starter to Delta
in Wye
Max Accel Timer
(6 to 64 Seconds)
Arm/Run Command to Starter Module
RTHD-SVX01G-EN 71
Start-Up and Shutdown
Starting AFD
The Starting AFD shows the order of operation for this type of starter.
Figure 57. Sequence of events: starting AFD
Accelerating
Compressor
(1 Second) (6 to 64 Seconds (Default 7 sec))
Waiting
To Start
Starting Compressor Running Running
Running
The Running Diagram shows a typical running sequence.
Figure 58. Sequence of events: running
Starter
Status is Enter Exit
‘Running’ Limit Mode Limit Mode
'
72 RTHD-SVX01G-EN
Start-Up and Shutdown
Satisfied Setpoint
The Satisfied Setpoint diagram shows the normal transition from Running to shutting down due to the Evap Leaving water
temp falling below the differential to stop setpoint.
Figure 59. Sequence of events: satisfied setpoint
Satisfied Setpoint
Energize Unload
Open EXV Close EX V
Solenoid
Pre-Position EX V
De-Energize Condenser to 38% Open for
Water Pump Relay Next Start
De-Energize
Compressor
RTHD-SVX01G-EN 73
Start-Up and Shutdown
Local Stop EXV Closed and Evap Pump Off Delay Complete
Normal Latching Diagnostic Stopped
Normal Non-Latching Diagnostic
Tracer Stop
Run Inhibit
External Auto-Stop
Stopped
Preparing or
Running Shutting Down Shutting Down
to Shutdown Run Inhibit
Open EXV
De-Energize Condenser
Water Pump Relay
Energize Unload
Solenoid for 60 mins
74 RTHD-SVX01G-EN
Start-Up and Shutdown
Run Inhibit
Running Shutting Down Shutting Down Shutting Down or
Stopped
De-Energize
Close EX V
Condenser Water Pump
Energize Unload
Solenoid for 60 mins
De-Energize Evaporator
Water Pump Relay
Evap Pump Off Delay Time (0-30 Minutes)
Open EXV
De-Energize
Compressor
Energize Condenser
Water Pump Relay
Energize Unload
Solenoid
Confirm Condenser Water Flow
Within 20 minutes
Enforce Power Up Start Delay Enforce Restart Inhibit Time r (6 Sec Filter)
(0 to 30 mins) (0 to 30 mins)
Confirm No
Compressor Currents
Within 0-30 Seconds
De-Energize Condenser
Water Pump Relay
RTHD-SVX01G-EN 75
Start-Up and Shutdown
Running Running
Running Running Running
(Unit is Building Ice) (Ice to Normal Transition)
De-Energize
Compressor
76 RTHD-SVX01G-EN
Start-Up and Shutdown
No Load Start
This diagram shows a pre-start sequence with the Start Sequence Type set to 'No Load'.
Figure 65. Sequence of events: no load start
Removal of all of the following:
External Stop
Local Stop Evap Leaving Water
Tracer/BAS Stop Temp Above the Diff to
Stop
Stopped
Or Waiting Waiting Waiting Waiting Waiting Starting
Auto Compressor
Run to Start to Start to Start to Start to Start
Inhibit
Confirm Evaporator Enforce Restart Confirm Condenser Condenser Enforce 'Cprsr Confirm Presence of Oil
Water Flow Inhibit Timer Water Flow Water Pump Strt Delay' With Optical Oil Sensor
(6 Second Filter) (0 to 30 mins) (6 Second Filter) Pre-Run (0 to 300 Sec) (0 to 2 mins)
Limit Conditions
UC800 will automatically limit certain operating parameters during startup and run modes to maintain optimum chiller
performance and prevent nuisance diagnostic trips. These limit conditions are noted in Table 28.
Condition Description
The chiller, circuit, and compressor are currently running, but the operation of the chiller/compressor is being actively
Running- limited
limited by the controls. Further information is provided by the sub-mode.
Condenser Pressure
The circuit is experiencing condenser pressures at or near the condenser limit setting. The compressor will be unloaded
Limit
to prevent exceeding the limits.
Low Evaporator
The circuit is experiencing saturated evaporator temperatures at or near the Low Refrigerant Temperature Cutout setting.
Refrigerant
The compressors will be unloaded to prevent tripping.
Temperature Inhibit
Capacity Limited by
The circuit is experiencing low refrigerant liquid levels and the EXV is at or near full open. The compressor will be unloaded
Low
to prevent tripping.
Liquid Level
The compressor is running and its capacity is being limited by high currents. The current limit setting is 100% RLA (to
Current Limit
avoid overcurrent trips).
Phase Unbalance
The compressor is running and its capacity is being limited by excessive phase current unbalance.
Limit
RTHD-SVX01G-EN 77
Maintenance
• Clean all water strainers in both the chilled and
condensing water piping systems.
WARNING
• Measure and log the subcooling and superheat.
Hazardous Voltage w/Capacitors! • See “Refrigerant and Oil Charge Management,” p. 78.
Failure to disconnect power and discharge capacitors If chiller measurements vary significantly from values
before servicing could result in death or serious injury. listed in Table 29 and Table 30, p. 79, problems may
Disconnect all electric power, including remote exist with refrigerant and oil charge levels. Contact
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be local Trane service.
inadvertently energized. For variable frequency drives
or other energy storing components provided by Trane Annual
or others, refer to the appropriate manufacturer’s Shut down the chiller once each year to check the
literature for allowable waiting periods for discharge of following:
capacitors. Verify with an appropriate voltmeter that all
capacitors have discharged. • Perform all weekly and monthly maintenance
procedures.
For additional information regarding the safe discharge
of capacitors, see PROD-SVB06A-EN. • Have a qualified laboratory perform an oil analysis to
determine system moisture content and acid level.
This section describes the basic chiller preventive Important: Due to the hygroscopic properties of the
maintenance procedures, and recommends the intervals POE oil, all oil must be stored in metal
at which these procedures should be performed. Use of a containers. The oil will absorb water if
periodic maintenance program is important to ensure the stored in a plastic container.
best possible performance and efficiency from a Stealth™
chiller. • Contact Trane service to leak check the chiller, inspect
safety controls, and inspect electrical components for
Use an Operator Log (see “Log and Check Sheets,” p. 95) deficiencies.
to record an operating history for unit. The log serves as a
valuable diagnostic tool for service personnel. By • Inspect all piping components for leakage and/or
observing trends in operating conditions, an operator can damage. Clean out any in-line strainers.
anticipate and prevent problem situations before they • Clean and repaint any areas that show signs of
occur. corrosion.
If unit does not operate properly during inspections, see • Inspect vent piping of all relief valves for presence of
“Diagnostics,” p. 83. refrigerant to detect improperly sealed relief valves.
Contact Trane service if unusual conditions are
Recommended Maintenance observed.
• Inspect the condenser tubes for fouling. Clean if
Weekly necessary. See “Cleaning the Condenser,” p. 79.
While the unit is running in stable conditions: • Check to make sure that the oil sump heater is working.
• Log the chiller. Scheduling Other Maintenance
• Check evaporator and condenser pressures with
• Use a nondestructive tube test to inspect the
gauges and compare to the reading on the Tracer
condenser and evaporator tubes at 3-year intervals.
AdaptiView™ TD7 or Tracer® TU service too. Pressure
readings should fall within operating ranges specified Note: It may be desirable to perform tube tests on these
in Table 29 and Table 30, p. 79. If chiller measurements components at more frequent intervals, depending
vary significantly from values listed in Table 29 and upon chiller application. This is especially true of
Table 30, p. 79, problems may exist with refrigerant critical process equipment.
and oil charge levels. Contact local Trane service. • Depending on chiller duty, contact Trane service
Note: Optimum condenser pressure is dependent on organization to determine when to conduct a complete
condenser water temperature, and should examination of the unit to determine the condition of
equal saturation pressure of refrigerant at a the compressor and internal components.
temperature 2 to 5F above that of leaving
condenser water at full load. Refrigerant and Oil Charge Management
Proper oil and refrigerant charge is essential for proper
Monthly unit operation, unit performance, and environmental
• Review operating log. protection. Only trained and licensed service personnel
should service the chiller.
78 RTHD-SVX01G-EN
Maintenance
Table 29 and Table 30 list baseline measurements for Mechanical Cleaning Procedure
Optimus™ units running at AHRI standard operating
Mechanical tube cleaning this method is used to remove
conditions. If chiller measurements vary significantly from
sludge and loose material from smooth-bore condenser
values listed below, problems may exist with refrigerant
tubes.
and oil charge levels. Contact Trane service.
RTHD-SVX01G-EN 79
Maintenance
80 RTHD-SVX01G-EN
Maintenance
Oil Sump Level Check 1. Run the unit fully unloaded for approximately 20
minutes.
Running the chiller at minimum load is the best for the
quickest return of oil to the separator and sump. The 2. Cycle the compressor off line.
machine still needs to sit for approximately 30 minutes
before the level is taken. At minimum load, the discharge
superheat should be highest. The more heat in the oil as it NOTICE:
lays in the sump, the more refrigerant will boil off in the Equipment Damage!
sump and leave more concentrated oil.
Never operate the compressor with the sightglass
The oil level in the oil sump can be measured to give an service valves opened. Severe oil loss will occur. Close
indication of the system oil charge. Follow the procedures the valves after checking the oil level. The sump is
below to measure the level. above the condenser and it is possible to drain the oil.
RTHD-SVX01G-EN 81
Maintenance
82 RTHD-SVX01G-EN
Diagnostics
Diagnostic Name and Source: Name of Diagnostic and in the table below, it will be displayed only as
its source. Note that this is the exact text used in the User “Informational Warning” as long as no circuit or chiller
Interface and/or Service Tool displays. shutdown results. If there is a shutdown and special action
Affects Target: Defines the “target” or what is affected defined in the table, then the Tracer® TU Diagnostics Page
by the diagnostic. Usually either the entire Chiller, or a display will indicate the shutdown type only.
particular Circuit or Compressor is affected by the Persistence: Defines whether or not the diagnostic and
diagnostic (the same one as the source), but in special its effects are to be manually reset (Latched), or can be
cases functions are modified or disabled by the diagnostic. either manually or automatically reset when and if the
None implies that there is no direct affect to the chiller, sub condition returns to normal (Nonlatched).
components or functional operation. Active Modes [Inactive Modes]: States the modes or
Note: Tracer® TU does not support the display of certain periods of operation that the diagnostic is active in and, as
targets on its Diagnostics pages although the necessary, those modes or periods that it is specifically
functionality implied by this table is supported. “not active” in as an exception to the active modes. The
Targets such as Evap Pump, Ice Mode, Heat Mode, inactive modes are enclosed in brackets, [ ]. Note that the
Chilled Water Reset, External Setpoints etc. – are modes used in this column are internal and not generally
displayed as simply “Chiller” even though they do annunciated to any of the formal mode displays.
not imply a chiller shutdown – only a compromise Criteria: Quantitatively defines the criteria used in
of the specific feature. generating the diagnostic and, if nonlatching, the criteria
Severity: Defines the severity of the above effect. for auto reset.
Immediate means immediate shutdown of the affected Reset Level: Defines the lowest level of manual
portion, Normal means normal or friendly shutdown of the diagnostic reset command which can clear the diagnostic.
affected portion, Special Action means a special action or The manual diagnostic reset levels in order of priority are:
mode of operation (limp along) is invoked, but without Local or Remote. For example, a diagnostic that has a reset
shutdown, and Info means an Informational Note or level of Remote, can be reset by either a remote diagnostic
Warning is generated. Design Note: Tracer® TU does not reset command or by a local diagnostic reset command.
support display of “Special Action”, on its Diagnostics
pages, so that if a diagnostic has a special action defined
Starter Diagnostics
RTHD-SVX01G-EN 83
Diagnostics
84 RTHD-SVX01G-EN
Diagnostics
RTHD-SVX01G-EN 85
Diagnostics
86 RTHD-SVX01G-EN
Diagnostics
RTHD-SVX01G-EN 87
Diagnostics
88 RTHD-SVX01G-EN
Diagnostics
RTHD-SVX01G-EN 89
Diagnostics
90 RTHD-SVX01G-EN
Diagnostics
Communication Diagnostics
Notes:
• The following communication loss diagnostics will not LLIDs, such as the Quad Relay LLID, have more than
occur unless that input or output is required to be one functional output associated with it. A comm loss
present by the particular configuration and installed with such a multiple function board, will generate
options for the chiller. multiple diagnostics. Refer to the Chiller's wiring
• Communication diagnostics (with the exception of diagrams to relate the occurrence of multiple
“Excessive Loss of Comm” are named by the communication diagnostics back to the physical LLID
Functional Name of the input or output that is no boards that they have been assigned to (bound).
longer being heard from by the Main Processor. Many
Table 36. Communication diagnostics
Active Modes
[Inactive Reset
Diagnostic Name Affects Severity Persistence Modes] Criteria Level
Loss of comm with 20% or more of the llids configured
for the system has been detected. This diagnostic will
Excessive Loss of Comm Chiller Immediate Latch All suppress the callout of all subsequent comm loss Remote
diagnostics. Check power supply(s) and power
disconnects – troubleshoot LLIDS buss using Tracer TU
Comm Loss: Slide Valve Continual loss of communication between the MP and
Chiller Normal Latch All Remote
Unload the Functional ID has occurred for a 30 second period.
Comm Loss: Slide Valve Continual loss of communication between the MP and
Chiller Normal Latch All Remote
Load the Functional ID has occurred for a 30 second period.
Comm Loss: External Auto/ Continual loss of communication between the MP and
Chiller Normal Latch All Remote
Stop the Functional ID has occurred for a 30 second period.
Comm Loss: Emergency Continual loss of communication between the MP and
Chiller Normal Latch All Remote
Stop the Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and
Comm Loss: External Ice the Functional ID has occurred for a 30 second period.
Normal Latch All Remote
Building Command Chiller shall revert to normal (non-ice building) mode
regardless of last state.
Continual loss of communication between the MP and
Comm Loss: Ice Building the Functional ID has occurred for a 30 second period.
Normal Latch All Remote
Status Relay Chiller shall revert to normal (non-ice building) mode
regardless of last state.
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Info and
Comm Loss: Outdoor Air Note that if this diagnostic occurs, Chiller shall remove
Chiller Special Latch All Remote
Temperature any OA Chilled Water Reset, if it was in effect and if
Action
Tracer OA was unavailable. Apply slew rates per Chilled
Water Reset spec
Comm Loss: Evap Leaving Continual loss of communication between the MP and
Normal Latch All Remote
Water Temp the Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and
Info and the Functional ID has occurred for a 30 second period.
Comm Loss: Evap Entering
Special Latch All Chiller shall remove any Return or Constant Return Remote
Water Temp
Action Chilled Water Reset, if it was in effect. Apply slew rates
per Chilled Water Reset spec.
Comm Loss: Condenser Continual loss of communication between the MP and
Info Latch All Remote
Leaving Water Temp the Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and
Info and
Comm Loss: Condenser the Functional ID has occurred for a 30 second period.
Special Latch All Remote
Entering Water Temp If chiller running, and condenser water regulating valve
Action
option installed, force valve to 100% flow.
Comm Loss: Cprsr Continual loss of communication between the MP and
Immediate Latch All Remote
Discharge Rfgt Temp the Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and
Info and the Functional ID has occurred for a 30 second period.
Comm Loss: Ext Chilled/Hot
Special Latch All Chiller shall discontinue use of the External Chilled Remote
Water Setpoint
Action Water Setpoint source and revert to the next higher
priority for setpoint arbitration
RTHD-SVX01G-EN 91
Diagnostics
Active Modes
[Inactive Reset
Diagnostic Name Affects Severity Persistence Modes] Criteria Level
Continual loss of communication between the MP and
Info and the Functional ID has occurred for a 30 second period.
Comm Loss: Ext Current
Special Latch All Chiller shall discontinue use of the External Current Remote
Limit Setpoint
Action limit setpoint and revert to the next higher priority for
Current Limit setpoint arbitration
Comm Loss: High Pressure Continual loss of communication between the MP and
Chiller Normal Latch All Remote
Cutout Switch the Functional ID has occurred for a 30 second period.
Comm Loss: Evaporator Continual loss of communication between the MP and
Immediate Latch All Remote
Water Flow Switch the Functional ID has occurred for a 30 second period.
Comm Loss: Condenser Continual loss of communication between the MP and
Chiller Immediate Latch All Remote
Water Flow Switch the Functional ID has occurred for a 30 second period.
Comm Loss: Evaporator Continual loss of communication between the MP and
Chiller Normal Latch All Remote
Rfgt Pressure the Functional ID has occurred for a 30 second period.
Comm Loss: Condenser Continual loss of communication between the MP and
Chiller Normal Latch All Remote
Rfgt Pressure the Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and
Comm Loss: Oil Pressure Chiller Normal Latch All Remote
the Functional ID has occurred for a 30 second period.
Comm Loss: Oil Return Gas Continual loss of communication between the MP and
Chiller Normal Latch All Remote
Pump Fill the Functional ID has occurred for a 30 second period.
Comm Loss: Oil Return Gas Continual loss of communication between the MP and
Chiller Normal Latch All Remote
Pump Drain the Functional ID has occurred for a 30 second period.
Comm Loss: Oil Loss Level Continual loss of communication between the MP and
Chiller Normal Latch All Remote
sensor Input the Functional ID has occurred for a 30 second period.
Comm Loss: Master Oil Line Continual loss of communication between the MP and
Normal Latch All Remote
SV the Functional ID has occurred for a 30 second period.
Comm Loss: Evaporator Continual loss of communication between the MP and
Info Latch All Remote
Water Pump Relay the Functional ID has occurred for a 30 second period.
Comm Loss: Condenser Continual loss of communication between the MP and
Info Latch All Remote
Water Pump Relay the Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and
Comm Loss: SSS/AFD Fault Info Latch All Remote
the Functional ID has occurred for a 30 second period.
Comm Loss: Refrigerant Continual loss of communication between the MP and
Chiller Info Latch All Remote
Monitor Input the Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and
Info and
Comm Loss: Ext Base the Functional ID has occurred for a 30 second period.
Special Latch All Remote
Loading Setpoint The external base load setpoint input is removed from
Action
the arbitration to establish the Base Loading Setpoint.
Continual loss of communication between the MP and
Info and
Comm Loss: Ext Base the Functional ID has occurred for a 30 second period.
Special Latch All Remote
Loading Command The external base load input is removed from the
Action
arbitration to enable Base Loading.
Comm Loss: Evaporator Continual loss of communication between the MP and
Chiller Normal Latch All Remote
Rfgt Liquid Level the Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and
Comm Loss: Starter Chiller Immediate Latch All Local
the Functional ID has occurred for a 30 second period.
Comm Loss: Electronic Continual loss of communication between the MP and
Normal Latch All Remote
Expansion Valve 1 the Functional ID has occurred for a 30 second period.
Comm Loss: Electronic Continual loss of communication between the MP and
Normal Latch All Remote
Expansion Valve 2 the Functional ID has occurred for a 30 second period.
Starter Comm Loss: Main Starter has had a loss of communication with the MP for
Chiller Immediate Latch All Local
Processor a 15 second period.
Info and Continual loss of communication between the MP and
Comm Loss: Local BAS
Chiller Special Latch All the Functional ID has occurred for a 30 second period. Remote
Interface
Action Use the last values sent from BAS
Comm Loss: Op Status Continual loss of communication between the MP and
Chiller Info Latch All Remote
Programmable Relays the Functional ID has occurred for a 30 second period.
Comm Loss: Compressor % Continual loss of communication between the MP and
Chiller Info Latch All Remote
RLA Output the Functional ID has occurred for a 30 second period.
92 RTHD-SVX01G-EN
Diagnostics
Active Modes
[Inactive Reset
Diagnostic Name Affects Severity Persistence Modes] Criteria Level
Comm Loss: Cond Rfgt Continual loss of communication between the MP and
Normal All Remote
Pressure Output the Functional ID has occurred for a 30 second period.
Comm Loss: Cond Head Continual loss of communication between the MP and
Chiller Immediate Latch All Remote
Press Cntrl Output the Functional ID has occurred for a 30 second period.
Comm Loss: AFD speed Continual loss of communication between the MP and
Chiller Immediate Latch All Remote
signal output the Functional ID has occurred for a 30 second period.
Comm Loss: AFD output Continual loss of communication between the MP and
Chiller Immediate Latch All Remote
power input the Functional ID has occurred for a 30 second period.
Comm Loss: External Hot Warning Continual loss of communication between the MP and
Chiller Info All Remote
Water Command Reset the Functional ID has occurred for a 30 second period.
Description
Operator Display Message //Troubleshooting
• Ethernet cable not connected between display and UC800.
• UC800 not powered.
Communication Lost with UC800
• UC800 has an invalid configuration – Download a valid configuration
• UC800 is in Binding View. When exit Binding View, select ‘Restart’ on this message.
• Ethernet cable not connected between display and UC800.
• UC800 not powered.
Display Failed to Establish Communication • UC800 just has the backup application running as received from the vendor. Download CTV
application software.
• UC800 has an invalid configuration – Download a valid configuration
• The display is low on memory, and needs to re-start. Select Yes to restart. Selecting Yes will not
Display is about to Restart
affect the UC800 operation. Only the Operator Display is reset.
File Not Found Update UC800 software with Tracer TU.
Screen partially populated.
Valid configuration is not present. Download a configuration.
Auto and Stop button graphics display, no text.
Screen Unresponsive TU is downloading software. Wait till download is complete.
• Most likely this UC800 has only the backup application. Download the latest UC 800 software
build.
• This could also mean that the UC800 does not have a valid configuration. Download a
The Page Cannot be found
configuration to it.
• Cycle power to the OD and UC800.
• UC could be in binding view. If so, get it out of binding view by navigating to another screen in TU.
UC800 Configuration is Invalid Update the UC800 configuration with TU.
RTHD-SVX01G-EN 93
Wiring
Table 38 and Table 39 provide lists of field wiring
diagrams, electrical schematics and connection diagrams
for the Optimus™ units. The complete unit wiring package
is documented in RTHD-SVE01*-EN. A laminated wiring
diagram kit is also shipped with each RTHD unit.
To determine the specific electrical characteristics of a
particular chiller, see the nameplates mounted on the
units.
Drawing Description
2311-1975 Schematic
2311-1977 Component Location
2311-1976 Field Wiring
2311-0023 Field Layout
94 RTHD-SVX01G-EN
Log and Check Sheets
The operator log and check sheet are included for use as
appropriate, for installation completion verification before
Trane start-up is scheduled, and for reference during the
Trane start-up.
Where the log or check sheet also exists outside of this
publication as standalone literature, the literature order
number is also listed.
• Optimus™ RTHD Installation Completion Check Sheet
and Request for Trane Service (RLC-ADF005*-EN)
• Chiller Settings
• Operator Log
RTHD-SVX01G-EN 95
Log and Check Sheets
96 RTHD-SVX01G-EN
Optimus™ Model RTHD Chiller
Installation Completion Check Sheet and Request for Trane Service
Important: A copy of this completed form must be submitted to the Trane service agency that will be responsible for the start-
up of the chiller. Start-up will NOT proceed unless applicable items listed in this form have been satisfactorily
completed. See unit IOM RTHD-SVX01*-EN for detailed installation instructions.
Important: Start-up must be performed by Trane or an agent of Trane specifically authorized to perform start-up of Trane®
products. Contractor shall provide Trane (or an agent of Trane specifically authorized to perform start-up) with
notice of the scheduled start-up at least two weeks prior to the scheduled start-up.
Important: It is required that heaters are energized for a minimum of 24 hours prior to start up. Therefore, chiller
should have power for this amount of time before Trane Service arrives to do start-up.
1. Screw Chiller
Installation meets foundation requirements.
In place and piped.
Isolation pads installed.
2. Piping
Note: See bulletin RLC-PRB015*-EN for piping installation considerations affecting sound.
Chilled water piping connected to:
Evaporator
Air handling units
Pumps
Flow switch or flow proving device installed (if not factory provided)
Strainer installed and cleaned
Condenser and heat recovery condenser (as applicable) piping connected to:
Condenser
Pumps
Flow switch or flow proving device installed (if not factory provided)
Cooling tower
Heating loop (as applicable)
Make-up water connected to cooling tower
Water supply connected to filling system
Does unit have freeze inhibitor? If unit has freeze inhibitor:
Verify type and concentration correct per unit submittal
Calculate and record freeze point of the solution: _____________________________
Systems filled
Pumps run, air bled from system
Strainer installed in entering water piping (evaporator and condenser) and cleaned
Relief valve ventilation piping installed (if applicable)
RLC-ADF005C-EN 1
4. Gauges, thermometers, and air vents
Installed on both sides of evaporator
Installed on both sides of condenser and heat recovery condenser (as applicable)
5. Wiring
Wire size per submittal and NEC 310-16.
Full power available
External interlocks (flow switch, pumps auxiliary, etc.)
Chilled water pump (connected and tested)
Condenser water pump (connected and tested)
Cooling tower fan rotation checked
Heat recovery condenser water pump (as applicable)
115 Vac power available for service tools as required
All controls installed and connected
6. Testing
Dry nitrogen available for pressure testing
Trace gas amounts of R-134a available for leak testing, if necessary
9. Heaters
Energize oil sump and compressor heaters and verify they are operational using a temperature probe.
If unit was factory charged (model number digit 35 = A), energize heaters for 24 hours prior to start up.
Important: It is required that heaters are energized for a minimum of 24 hours prior to start up.
Therefore, chiller should have power for this amount of time before Trane Service arrives
to do start-up.
If unit has nitrogen charge (model number digit 45 = 1), contact Trane Service for unit charging prior to start-up.
2 RLC-ADF005C-EN
Note: Additional time required to properly complete the start-up and commissioning, due to any incompleteness of the
installation, will be invoiced at prevailing rates.
This is to certify that the Trane® equipment has been properly and completely installed, and that the applicable items listed above
have been satisfactorily completed.
Important: It is required that the chiller heaters are energized for a minimum of 24 hours prior to start up. Therefore, the chiller
should have power for this amount of time before Trane Service arrives to do start-up of the equipment.
In accordance with your quotation and our purchase order number __________________, we will therefore require the presence
of Trane service on this site, for the purpose of start-up and commissioning, by __________________ (date).
Note: Minimum two-week advance notification is required to allow scheduling of the chiller start-up.
A copy of this completed from must be submitted to the Trane Service Office that will be responsible for start-up of chiller.
RLC-ADF005C-EN 3
Ingersoll Rand (NYSE:IR) advances the quality of life by creating comfortable, sustainable and efficient environments.
Our people and our family of brands—including Club Car®, Ingersoll Rand®, Thermo King® and Trane®—work together
to enhance the quality and comfort of air in homes and buildings; transport and protect food and perishables; and
increase industrial productivity and efficiency. We are a global business committed to a world of sustainable progress
and enduring results. For more information, visit www.ingersollrand.com.
Ingersoll Rand has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
Settings
Settings Tab
Chiller
Front Panel Chilled Water Setpt (F)
Front Panel Current Limit Setpt (RLA)
Differential to Start (F)
Differential to Stop (F)
Setpoint Source
Feature Settings
Chilled Water Reset
Return Reset Ratio
Return Start Reset
Return Maximum Reset
Outdoor Reset Ratio
Outdoor Start Reset
Outdoor Maximum Reset
Mode Overrides
Evap Water Pump
Cond Water Pump
Expansion Valve Control
Slide Valve Control
Service Pumpdown
Display Settings
Date Format
Date
Time Format
Time of Day
Keypad/Display Lockout
Display Units
Pressure Units
Language Selection
Operator Log
Chiller Log
Run Time
Main Tab 15 min 30 min 1 hr
Chiller Mode
Evap Ent/Lvg Water Temp
Cond Ent/Lvg Water Temp
Active Chilled Water Setpoint (F)
Average Line Current (%RLA)
Active Current Limit Setpoint (%RLA)
Software Type
Software Version
Reports Tab
Evaporator
Evap Entering Water Temperature (F)
Evap Leaving Water Temperature (F)
Evap Sat Rfgt Temp (F)
Evap Rfgt Pressure (psia)
Evap Approach Temp (F)
Evap Water Flow Switch Status
Expansion Valve Position (%)
Expansion Valve Position Steps
Evap Rfgt Liquid Level (in)
Condenser
Cond Entering Water Temperature (F)
Cond Leaving Water Temperature (F)
Cond Sat Rfgt Temp (F)
Cond Rfgt Pressure (psia)
Cond Approach Temp (F)
Cond Water Flow Switch Status
Cond Head Pressure Ctrl Command (%)
Compressor
Compressor Starts
Compressor Run Time
System Rfgt Diff Pressure (psid)
Oil Pressure (psia)
Compressor rfgt Discharge Temp (F)
Discharge Superheat (F)
% RLA L1 L2 L3 (%)
Amps L1 L2 L3 (Amps)
Volts AB BC CA
Ingersoll Rand (NYSE:IR) advances the quality of life by creating comfortable, sustainable and efficient environments.
Our people and our family of brands—including Club Car®, Ingersoll Rand®, Thermo King® and Trane®—work together
to enhance the quality and comfort of air in homes and buildings; transport and protect food and perishables; and
increase industrial productivity and efficiency. We are a global business committed to a world of sustainable progress
and enduring results. For more information, visit www.ingersollrand.com.
Ingersoll Rand has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.