Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Specification: Constant Current Discharge Characteristics: A (25)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

HT12-100(12V100Ah)

Specification
Cells Per Unit 6
Voltage Per Unit 12
Nominal Capacity 100Ah@10hour-rate to 1.80V per cell @25℃
Weight Approx. 34.0 Kg (Tolerance±2.0%)
Internal Resistance Approx. 5 mΩ
Terminal F5(M8)/F12(M8)
Max. Discharge Current 1000A (5 sec)
HT series is High-temperature series battery
Design Life 15 years (Float charging) with 15 years design life in float service. It
Recommended Maximum Charging meets with IEC, JIS, BS and YDT standards.
30 A With advanced AGM valve regulated
Current
technology and high purity raw material, the
C3 75.3AH
C5 86.5AH
HT series battery maintains high consistency
Reference Capacity C10 100.0AH for better performance and reliable standby
C20 105.8AH service life. It is designed for using under high
13.6 V~13.8 V @ 25℃ temperature conditions.
Standby Use Voltage
Temperature Compensation: -3mV/℃/Cell
14.6 V~14.8 V @ 25℃
Cycle Use Voltage
Temperature Compensation: -4mV/℃/Cell
Discharge: -20℃~60℃
Operating Temperature Range Charge: -10℃~60℃
Storage: -20℃~60℃
Normal Operating Temperature Range 35℃±5℃
RITAR Valve Regulated Lead Acid (VRLA) batteries can
be stored for up to 6 months at 25℃ and then recharging
Self Discharge is recommended. Monthly Self-discharge ratio is less
than 3% at 25℃.Please charge batteries before using.

Container Material A.B.S. UL94-HB, UL94-V0 Optional.

Dimensions
328 172
Φ16 Length 328±2mm (12.9 inches)
M8
Width 172±2mm (6.77 inches)
Height 215±2mm (8.46 inches)
5

Total Height 220±2mm (8.66 inches)


Terminal Value
220
215

39.5

M5 6~7 N*m
M6 8~10 N*m
M8 10~12 N*m
265
F12 Terminal Unit: mm

Constant Current Discharge Characteristics : A (25℃)


F.V/Time 10MIN 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HR
1.60V 233.4 179.5 104.9 61.6 36.9 26.5 21.6 18.2 12.3 10.6 5.47
1.65V 226.4 174.8 102.6 60.4 36.3 26.2 21.3 18.0 12.2 10.5 5.42
1.70V 217.3 168.6 99.6 58.9 35.6 25.7 20.9 17.7 12.0 10.4 5.36
1.75V 205.5 160.5 95.6 56.9 34.7 25.1 20.5 17.3 11.8 10.2 5.29
1.80V 190.4 150.2 90.4 54.3 33.4 24.3 19.8 16.8 11.5 10.0 5.18
1.85V 171.5 137.1 83.8 51.0 31.8 23.2 19.0 16.2 11.1 9.68 5.05
Constant Power Discharge Characteristics : WPC (25℃)
F.V/Time 10MIN 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HR
1.60V 403 318 193 117 71.0 51.4 42.0 35.6 24.3 21.2 10.9
1.65V 401 317 192 116 70.4 51.1 41.7 35.4 24.2 21.1 10.9
1.70V 389 308 187 113 69.3 50.3 41.1 34.9 23.9 20.8 10.8
1.75V 375 298 182 110 67.7 49.3 40.3 34.3 23.5 20.5 10.6
1.80V 353 282 174 106 65.6 47.8 39.2 33.4 23.0 20.0 10.4
1.85V 324 261 163 100 62.8 45.9 37.8 32.2 22.2 19.4 10.2
(Note) The above characteristics data are average values obtained within three charge/discharge cycle not the minimum values.
HT12-100(12V100Ah)
Discharge Characteristics Curve Charge Characteristic Curve For Standby Use
Temperature:25℃(77℉) Temperature:25℃(77℉)
(V/cell)
120 0.14 2.40
2.16 Charge Volume

Charge Voltage (VPC)


Charge Current (CA)
Terminal Voltage (v )

100 0.12 Charge Voltage 2.30

Charge Volume (%)


2.00

80 0.10 2.20
1.84
0.1C 0.05C
1.68
0.25C 0.17C 60 0.06 2.10
0.55C After 50% Discharge
3C 2C 1C After 100% Discharge
1.52 40 0.04 2.00

1.36 20 0.02 1.90


Charge Current
0
1 2 4 6 8 10 20 40 60 2 4 6 8 10 20 0 0.00 1.80
min h 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28

Discharge Time Charging Time(h)

Cycle Life In Relation To Depth Of Discharge Relationship Between Charging Voltage And Temperature
2.70
120

100 2.60

Charge Voltage (v )
Cycle use
80 2.43~2.47VPC@25℃
Capacity(%)

2.50

60
100% 80% 30%
DOD DOD DOD 2.40
40

2.30
20
Float charging
2.27~2.30VPC@25℃
0 2.20
200 400 600 800 1000 1200 1400
-20 -10 0 10 20 30 40 50

Number of Cycles Temperature (℃)

Temperature Effects On Capacity Storage Characteristics


120 100

100 0℃
0 .1 C A 80
Capacity (% )

Capacity (% )

80 0 .2 C A
60
10℃
60
20℃
1 .0 C A 40
40℃ 30℃
40
2 .0 C A
3 .0 C A 20
20

0 0
-20 -10 0 10 20 30 40 50 0 2 4 6 8 10 12 14 16 18 20 22 24
Temperature (℃) Storage Time(months)

Effect Of Temperature On Long Term Life Life Characteristics Of Standby Use


Testing conditions: float charging Temperature: 25℃(77℉)
20
120
Lift Expectancy (y ears)

16 100

80
12
Capacity(%)

60
8
40

4
20

0 0
0 10 20 30 40 50 0 3 6 9 12 15 18
Temperature(℃) Life expectancy (years)

(Note) All above information shall be changed without prior notice, Ritar reserves the right to explain and update the latest information.

SHENZHEN RITAR POWER CO.,LTD. Add: 10th Floor, Tower C, 1st Building, Software Industry Base, No.81, Xuefu Road, Nanshan District, Shenzhen,
Guangdong, China 518057
URL: www.ritarpower.com Tel: +86-755-33981668/83475380 Fax: +86-755-83475180 E-mail: sales@ritarpower.com Version 17A-0