BeyondKneePoint AH 20190418 Web
BeyondKneePoint AH 20190418 Web
BeyondKneePoint AH 20190418 Web
© 2018 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained
for all other uses, in any current or future media, including reprinting/republishing this material
for advertising or promotional purposes, creating new collective works, for resale or
redistribution to servers or lists, or reuse of any copyrighted component of this work in other
works.
This paper was presented at the 71st Annual Conference for Protective Relay Engineers and can
be accessed at: https://doi.org/10.1109/CPRE.2018.8349779.
For the complete history of this paper, refer to the next page.
Revised edition released April 2019
Abstract—Current transformer (CT) saturation, while a fairly understanding of CT saturation must extend beyond the
common occurrence in protection systems, is not often clearly knee point.
understood by protective relay engineers. This paper forgoes the
usual physics equations to describe how CTs saturate in a simple
and intuitive way. We explain the differences between II. CT SATURATION THEORY
symmetrical and asymmetrical saturation and how remanence To understand CT saturation, it is very important to
accumulates in the core of a CT. We then describe the CT understand the basic concept of how CTs work and what is
equivalent circuit and how it results in the familiar CT excitation actually happening when they saturate. This section describes
graph. ANSI ratings of CTs are explained, and we show how to
analyze the performance of CTs using simple equations and tools. what happens in the core of a CT during symmetrical saturation,
Finally, we explain how CT saturation can affect relay operation asymmetrical saturation, and remanence. It then explains how
and show how to detect CT saturation in protective relay event this core activity corresponds to the CT equivalent circuit,
reports. Real-world event reports are presented where correct ANSI voltage ratings, and the familiar CT excitation graph.
relay operation was compromised as a result of incorrect current
values from saturated CTs. A. How CTs Work
In its simplest form, a CT consists of two sets of wire
I. INTRODUCTION windings around an iron core, as shown in Fig. 1. The concept
Current transformer (CT) saturation is not a new topic, and is the same for a window or bushing CT, which consists of a
there have been many papers, books, application guides, and secondary winding around a core, with the primary winding
tutorials written on the subject. Sorting through this vast array being the primary conductor that passes through it.
of information to piece together a complete understanding of Transformers work based on the principle of electromagnetic
the topic is a time-consuming task and may not be realistic with induction. This principle states that an alternating magnetic flux
the schedules and demands placed on many practicing in the presence of a loop of wire induces a voltage across that
engineers. Because of this, engineers’ level of understanding is loop. Magnetic flux is simply the amount of magnetic field
often limited to the familiar CT excitation graph. The following passing through a material such as a transformer core.
is a list of common questions related to CT saturation: When alternating current IP flows in the primary winding of
• Why does a CT saturate (Section II, Subsection B)? a transformer, it generates an alternating magnetic field H,
• What is remanence, and do I have to worry about it which corresponds to an alternating magnetic flux Φ, around
(Section II, Subsection C)? the transformer core. This alternating magnetic flux passes
• What does it mean when a CT is a C800 (Section II, through the secondary winding. What happens next depends on
Subsection F)? the load connected to the secondary winding.
• I have a C800 multiratio CT tapped at 400/5. Is it still If the secondary is connected to a burden, the alternating
a C800 (Section II, Subsection F)? magnetic flux in the core induces an alternating voltage VS
across the secondary winding. This causes a corresponding
• How do I make sure my CT will not saturate for my
alternating current IS to flow in the secondary winding. The
worst-case fault current (Section III)?
alternating current in the secondary creates its own alternating
• The knee point determines the saturation voltage of a
magnetic field and alternating magnetic flux that oppose those
CT, right (Section II, Subsection E)?
created by the primary winding. These primary and secondary
• Will saturated CTs cause my relay to misoperate?
fluxes cancel, leaving a negligible amount of net flux in the
What if they just saturate a little bit (Section V)?
core. This occurs until the core becomes saturated.
• After a misoperation, how do I know if CT saturation If the secondary is open-circuited, the alternating magnetic
was a cause (Section IV)? flux in the core induces a very high alternating voltage VS
• Can modern relays prevent misoperations due to CT across the secondary winding. VS remains on the terminals with
saturation (Section VI)? no secondary current flowing, which is why it is very dangerous
The goal of this paper is to explain CT saturation to the to open-circuit an in-service CT. Because IS cannot flow, it
protective relay engineer and to answer these questions in a cannot create an opposing magnetic field, leaving a net flux in
clear and practical way. As this paper demonstrates, a proper the core equal to the flux created by the primary current.
2
The example in Fig. 3 shows the primary current decreasing saturates. This limit is defined by a symmetrical sine wave with
in magnitude every cycle. The point of this is to show that if a fixed voltage magnitude and fixed area under the curve in
primary current magnitude decreases, the CT is saturated for both the positive and negative directions. As long as the actual
less time. The lower magnitude in the second cycle of Fig. 3 CT waveform does not exceed this positive or negative volt-
generates a weaker magnetic field, requiring less flux density time area, the CT will not saturate. Consider the dc offset of the
to replicate the current correctly. Because fewer magnets are asymmetrical current in Fig. 4. This dc offset will result in an
used, IS reliably replicates IP for a longer time until all the accumulating positive volt-time area that eventually reaches the
magnets are aligned. In the third cycle, the magnitude of IP has maximum that the CT can handle at Point d, where saturation
been lowered to the point that the CT does not saturate and occurs.
replicates current correctly the entire time.
IS
IP
Current
Time
a b c d
IP
Current
Current
measured.
Time
The effect of remanence on CT saturation is shown in Fig. 7.
In this example, the CT is sized to perfectly handle an ac current
signal of a certain magnitude without saturating. In addition,
there is some remanence left over in the core of the CT. Before
Fig. 6. Saturated waveshapes for resistive (a) and resistive-inductive (b)
loads the current is applied, between Points a and b, some of the
magnets in the core are already aligned in the positive direction
C. Remanence because of remanence. Between Points b and c, as IP starts to
If a CT has reached saturation and a switch is opened to flow in the first positive half cycle, the remaining magnets also
remove the primary current, we would expect the magnetic field line up in the positive direction. Because there is a change in
(H) to disappear and the flux density (B) to reduce to zero. flux during this time, the current IS matches IP divided by the
However, flux density does not go to zero when the primary turns ratio. Before the positive half cycle is over, at Point c, all
current stops flowing. When primary current is removed, the the magnets available in the core are lined up in the positive
magnetic field that causes the magnets to change orientation direction and the core has reached saturation. At this point, even
disappears, and the magnets in the core remain in their present though IP continues to flow, there is no more change in flux and
orientation. The magnets will not move again until exposed to VS and IS drop to zero. IS stays at zero until IP begins to flow in
another magnetic field. The amount of flux density remaining the negative direction, reversing the magnetic field and
in the core is called remanence. The fact that the magnets still allowing flux to accumulate in the opposite direction. This
point in the direction they were in when the magnetic field was occurs at Point d, where magnets begin to align in the negative
removed gives the core “memory” (like a permanent magnet). direction and the changing flux allows IS to follow IP again. By
This remanence remains in the core until primary current is the time IP reaches its negative peak at Point e, only half of the
reapplied. If the reapplied current is opposite in polarity from maximum core flux is aligned in the negative direction. This
the original, flux density is created in the opposite direction of allows IS to continue to follow IP until all the magnets are
the prior remanence. aligned in the negative direction, at Point f. Although we have
The example of a switch being opened to remove primary reached maximum flux density again, this is where IP changes
current is exactly what happens when a relay trips a circuit direction and we start accumulating flux in the positive
breaker during a fault. Recall that when a breaker operates, direction.
current is interrupted at a zero crossing. In Section II, IP
Subsection B, we show that for both symmetrical and
IS
asymmetrical currents, there is a positive or negative flux
density in the core when the current zero crossing occurs. This a b c d e f g
flux density can be significant during high-magnitude
asymmetrical current (when a dc transient is present). This
remanence remains in the CTs after the breaker opens and
affects their behavior the next time they are energized.
Remanence can either help or hinder a CT’s performance,
depending on whether the remanence is of the same polarity or
a–b b–c c c–d d–e e–f g
opposite polarity of the next current that the CT measures. It
takes more time for the CT to saturate if the remanence is the Fig. 7. Primary currents, secondary currents, and magnetic dipoles in the
opposite polarity of the current and less time if it is the same core with remanence
polarity. As we can see from this example, saturation as a result of
Examination of the example B-H curve in Fig. 2 shows remanence is short-lived, lasting about half a cycle. Because of
another factor that causes the magnetic core to have remanence. this short saturation time, remanence has little effect on
Note that the curve follows a loop trajectory. The flux density standard protection algorithms and is normally neglected in CT
(B) lags the field intensity (H) as it goes through a power system saturation calculations [4] [5]. Any relaying algorithm that
cycle. This phenomenon is called hysteresis. performs faster than this should include some level of built-in
protection against CT saturation.
5
D. CT Equivalent Circuit when the ZE impedance is large (during normal conditions) and
We can represent the behavior of the C-class CT shown in large when the ZE impedance is small (during saturation). The
Fig. 8a with the simplified equivalent circuit shown in Fig. 8b. current measured by the load (IS) is what is left of the ratio
current (IST) after the error current (IE) is lost through the
(a) Secondary
magnetizing impedance (ZE). Therefore, the current the relay
sees is accurate during times of high ZE impedance (low error
current), and it is much lower than expected during times of low
ZE impedance (high error current). This behavior gives us the
Primary
classic saturation waveform shown in Fig. 3.
Fig. 9, adapted from [6], explains the saturation process in
the time domain. The graph in Quadrant III shows the primary
Fully Distributed Windings current IP being applied to the CT. The graph in Quadrant II
IST RS IS
shows the flux density over time. At time t0, when the CT is
(b)
first energized, the flux density starts to increase from whatever
IE
remanent value was left in the CT at the last de-energization.
Flux density continues to rise in the CT during the positive half
IP VE VS ZB
ZE cycle and decreases during the negative half cycle. Time t3 is
the point of maximum flux density, when the CT is fully
saturated. The graph in Quadrant IV shows the excitation
N1 N2
(error) current over time. We can see that the highest excitation
Fig. 8. Class C CT (a) and Simplified CT equivalent circuit (b) current occurs at the point of maximum flux density. The graph
IP (the primary current), VS (the secondary CT terminal in Quadrant I shows flux density versus excitation current and
voltage), and IS (the secondary load current) are is made up of the intersection of points between the graph in
self-explanatory. N1 and N2 represent the turns ratio of the CT, Quadrant II and the graph in Quadrant IV. The graph in
and the ratio current IST is the primary current divided by this Quadrant I is not time-dependent, but simply shows the amount
ratio. The circuit connected to the secondary of the CT is the of excitation current that is measured for a given flux density.
burden represented by ZB and includes the impedance of the This graph shows that when the flux density is low, the
relay and CT leads. The resistance RS represents the secondary excitation (error) current is low (because ZE is a high value). As
winding resistance of the CT. The magnetizing behavior of the flux density increases and the CT approaches saturation, the
core of the CT is represented by a varying reactance, ZE. This excitation current increases substantially (because ZE is a lower
impedance changes as the CT saturates, resulting in varying value), meaning less current will be available to the burden.
secondary excitation voltage VE and varying exciting branch Notice that the graph in Quadrant I corresponds directly to the
current IE. (Although ZE technically has a real and reactive B-H curve in Fig. 2, where the excitation current IE is
component, most practical CT analysis is close enough when proportional to the magnetic field strength H.
neglecting the angles of the impedances.) The flux density in Fig. 9 is directly proportional to both the
In the CT equivalent circuit in Fig. 8, the constant current flux and the excitation voltage VE. We can therefore interpret
source IP drives the total secondary current IST as determined by the graph in Quadrant I as the instantaneous relationship
the turns ratio. IST is the current that is measured by the load if between VE and IE, and use it to understand the changing
the CT is ideal. However, we must take into account the impedance of the CT excitation branch (ZE). The slope of the
magnetizing behavior of the CT core that is represented by the curve is the ratio of VE/IE, which Ohm’s law allows us to
varying impedance ZE. Because magnetization is nonlinear, characterize as ZE. We can easily visualize that the curve is
different values of impedance (ZE) must be used for different made up of two linear sections and that the knee point is where
states of operation (normal conditions vs. saturated conditions). the two linear sections transition. The steep part of the curve,
We can think of ZE as a varying impedance that changes with where the ratio of VE/IE is high (ZE is high), represents where
flux density. It has a very high value under normal conditions the core is not saturated. This is called the iron-core reactance
and a very low value (basically a short-circuit) when the CT is region of the curve. The flat part of the curve, where the ratio
saturated. The excitation current (IE) is the current that is lost of VE/IE is low (ZE is low), represents where the core is
through the magnetizing branch and corresponds to the CT saturated. This is called the air-core reactance region of the
error. We can also refer to this as “error current.” IE is small curve because the saturated iron core has no better permeability
than air.
6
2) Saturation
The area of saturation is along the low linear slope portion
of the excitation graph, where a small change in VE results in a
very large change in IE. We select a random point on the line in
this region as (IE = 10 A, VE = 496 V) and apply these values to
the equivalent circuit, as shown in Fig. 12. We then solve for
ZE = 49.6 Ω, which is a very small impedance. If we connect a
burden of 4 Ω, we can solve for IS = 124 A and IST = 134 A. We
Fig. 10. Example excitation graph for a C400 CT [7] see that because the error current is so large, the ratio current
(IST) is not very close to the current the load actually sees (IS),
meaning the CT is behaving poorly.
7
increase in current delivered to the load. The definition also of the CT has a much lower terminal voltage at 10 A of error
states that assuming a 5 A nominal CT, 100 A is delivered to a current than the full 2000/5 tap. For multiratio CTs, the voltage
standard burden when VS matches the voltage rating of the CT. rating of a tap is directly proportional to the CT ratio
IEEE defines standard burdens for relaying CTs as 1, 2, 4, and corresponding to the tap divided by the full CT ratio (assuming
8 Ω. Consequently, the standard voltage ratings for 5 A nominal the windings are fully distributed around the core). For
relaying CTs are C100, C200, C400, and C800 (20 times the example, if a C400, 1200/5 CT is operating on a 600/5 tap, the
5 A rated secondary current) [9]. For example, a C400 accuracy voltage rating at 600/5 is calculated as shown in (2).
class on a 5 A CT means that the ratio error will not exceed 600 / 5
VTAP C400 • C200 (2)
10 percent for any current up to 100 A secondary (20 times the 1200 / 5
rated current) as long as the burden does not exceed the 4 Ω
standard burden. This means that the CT supports a voltage of 200 V at 20
From this definition, the voltage rating of a CT defines times rated secondary current of 100 A, which results in a
voltage VS, burden ZB, and current IS in the example shown in standard burden of 2 Ω.
Fig. 13 for a C400, 5 A nominal CT. The definition also tells us A final note on CT ratings and the knee point: notice that the
that at this voltage, the ratio error (IE / IS) is a maximum of knee point of the graph in Fig. 10 is VE = 200, which is half of
10 percent. If we assume this worst case, then IE must equal the ANSI voltage rating of the CT (C400). In fact, 400 V is not
10 A. We can then back-calculate to find IST = 110 A, which is even on the high linear slope portion of the graph. Recall again
the primary current divided by the turns ratio. If we go above that the knee point only shows where the CT behavior starts to
this, we will start getting more than 10 percent error on the become nonlinear, while the ANSI rating defines the point of
output, and the current the connected load reads will not be 10 percent error. The ANSI rating, not the knee point, defines
reliable. Similarly, increasing the burden ZB to a value greater the practical threshold for saturation. Because the knee-point
than the standard burden will also result in an increased error. voltage is normally 46 percent of the saturation voltage, a
When applying CTs, a simple rule of thumb to avoid a popular rule of thumb to avoid saturation is to ensure that the
symmetrical saturation error over 10 percent is to use a burden ANSI rating is twice the terminal voltage developed by the
equal to or less than the standard burden and ensure that the maximum fault current [8]. This ensures operation near the
worst-case secondary fault current is less than 100 A. knee point for the maximum symmetrical fault current.
IST = 110 A RS IS = 100 A
III. ANALYZING CT PERFORMANCE
IE = 10 A
When a CT saturates, it provides distorted information to the
IP VS = 400 V ZB = 4 Ω
connected relay, which can cause the relay to behave
unexpectedly. When selecting a CT for a protective relay
application, it is important to check if the CT saturates for the
levels of fault current that will occur on the system. This section
Fig. 13. Example for a C400, 5 A nominal CT explains an equation that can be used to determine if a CT will
saturate for given fault conditions.
IEEE defines common CT voltage ratings as C100, C200,
C400, and C800. Because the ratings are defined at specific A. CT Steady-State Performance Analysis
voltage levels, not all CTs with the same voltage rating are Equation (3) is the criterion to avoid CT saturation for
created equal. For example, a CT with a terminal voltage of symmetrical fault currents. Real-world faults are rarely
810 V and a CT with a terminal voltage of 1,000 V would both symmetrical, so this equation should never be used practically
be classified as C800. The CT with the excitation graph shown to analyze CT performance. It is explained here and derived in
in Fig. 10 has an excitation voltage of 496 V at an error current Appendix B as a basis for the more practical equation in
of 10 A. To get the terminal voltage VS, we subtract the voltage Section III, Subsection B. Equation (3) can be used to
drop across the secondary winding resistance (RS • 100 A) from determine the maximum allowable fault current for a given
the excitation voltage of 496 V. If the resulting terminal voltage burden or maximum allowable burden for a given fault current.
is over 400 V, we classify the CT as a C400 CT [2]. I FAULT ZB R S
It is important to note that these voltage ratings only apply • 20 (3)
I PRI ZB STD R S
to the full winding ratio of the CT, and tapping down a CT
reduces its accuracy. Because both windings are distributed The terms in (3) are defined as follows:
around the same core, they are each subject to the same flux and IFAULT is the maximum fault current in primary amperes
the voltage induced across every turn of any winding is the for a given fault.
same. That is, the maximum volts per turn the CT can support IPRI is the primary current rating of the CT (e.g., for a
without symmetrical saturation is fixed by the cross-sectional 2000/5 CT, IPRI is 2,000.)
area of the core. If we choose to tap a CT at anything other than ZB is the actual burden of the CT’s secondary circuit.
its full winding, there will be less voltage available at the RS is the internal resistance of the CT secondary winding.
terminals because not all of the available turns are connected to ZB STD is the standard burden of the CT (e.g., for a C800
the load. In Fig. 10, for example, we can see that the 300/5 tap CT, the ZB STD is 8 Ω).
9
ZB includes both the impedance of the connected relay and in less saturation. Therefore, a value over 20 in this equation
the impedance of the leads from the CT to the relay. does not mean that the CT will saturate for that fault current—
Microprocessor-based relays have a negligible burden, but just that it could, assuming the fault current had the worst-case
electromechanical relays do not. The impedance of the leads is dc offset.
determined by the wire gauge, the length of the leads, how the
C. What About Remanence?
CTs are connected, and the fault type. #10 AWG copper wire
has a resistance of 0.9989 Ω per 1,000 feet. Reference [10] There is no way to predict the value of remanence that may
shows how to calculate the resistance of other wire gauges. exist in a CT at a given instant in time. As described in
When using wye-connected CTs and performing the calculation Section II, remanence can either impair or improve the CT
for a single-phase-to-ground fault, a two-way lead burden behavior for a given fault. The worst case is when a fault
should be used because the fault current has to make a full loop produces flux of the same sign as the remanence. In this case,
through the CT circuit (phase and neutral) and back to the relay. the flux change required to saturate the CT equals the difference
When using wye-connected CTs and performing the calculation between the core saturation flux and the remanence.
for a three-phase fault, a one-way lead burden should be used Regardless of how much remanence exists in a CT, recall
because the fault current for a single phase sums with the other from Section II that the effect remanence has on saturation only
two phases at the neutral point of the wye connection and no lasts about half a cycle. Modifications to (5) have been made to
current will flow through the neutral. This is derived in [5], account for the effects of remanence by derating the CT, but
which also shows how to calculate the burden when using delta- they are only valid for the first half cycle of the fault [2]. Using
connected CTs. these modifications to size CTs is unnecessarily conservative
RS, the secondary winding resistance of the CT, is specified and often yields impractically large CTs. Be aware that because
on the CT data sheet. The RS value is directly related to the of the random nature of remanence, even a CT that was properly
resistance of the wire and the number of turns and is therefore sized using (5) may still saturate momentarily. This saturation
dependent on the tap for multiratio CTs. will be short-lived and should have little effect on the
ZB STD is the standard burden of the CT and must be adjusted performance of standard relay algorithms.
if the CT is not tapped at its full ratio. In these instances, the Despite the best intentions, there are certain times when the
standard burden must first be multiplied by the ratio of the tap use of (5) to select CTs that will never saturate becomes an
rating to the full rating. For example, for a C800, 2000/5 CT exercise in futility. One such example is on applications near a
tapped at 1200/5, the standard burden is shown in (4). The generator bus. Here, the X/R ratios and fault current magnitudes
resulting C-rating for the tap would be 4.8 • 100 A = C480. are extremely high, and it is usually impossible to avoid
asymmetrical saturation even with the largest CTs.
800 1, 200 Reference [2] recommends selecting the highest practical rating
ZB STD • 4.8 (4)
20 • 5 2, 000 for the CTs and always matching the CTs on the terminal and
B. CT Transient Performance Analysis neutral sides of the generator to each other (same ANSI voltage
rating, CT ratio, and connected burden). This way, even though
Section II shows that symmetrical fault currents are not the
we know the CTs will saturate, they will saturate in the same
only risk for CT saturation. Fault currents with an exponentially
way and the saturated waveforms will cancel each other out in
decaying dc offset, caused by the X/R ratio of the system, can
the differential calculation. Because not all CTs with the same
produce significant CT saturation. Selecting CTs based only on
voltage rating are created equal, it is important to make sure that
symmetrical fault current is not advised because it ignores the
both CTs have the same excitation curve, knee-point voltage,
risk of heavy CT saturation when the fault current includes dc
and terminal voltage at 10 A of excitation current. See
offset.
Section III, Subsection D for an example illustrating this point.
To account for dc offset, we can improve (3) by including
Another example of not being able to avoid saturation is in
an extra X/R term, resulting in (5) [5]. This extra term is the
low- and medium-voltage switchgear applications, where fault
X/R ratio of the entire Thevenin equivalent of the system, from
currents are high and space requirements force the use of small
the source to the fault, through the particular CT. Equation (5)
and poorly-rated CTs. Refer to [11] and [12] for selection
only considers dc offset from sinusoidal fault current, not offset
criteria for low-voltage applications. For more information on
from nonsinusoidal sources like transformer inrush.
selecting CTs for various protection applications, see [1], [2],
Appendix C gives an example of using (5) to analyze
[7], [10], [13], and [14].
asymmetrical saturation in a CT.
I FAULT ZB R S X D. Transient Performance of Different CTs With the
• 1 20 (5) Same Rating
I PRI ZB STD R S R
To illustrate the point discussed in the previous section about
The initial magnitude of the dc offset that occurs is trying to make sure that the terminal and neutral-end CTs on a
determined by the fault incidence angle, and the time it takes generator differential have the same excitation curve, we can
for the dc offset to decay is determined by the X/R ratio of the look at two different C800 CTs manufactured to two different
system. Equation (5) is quite conservative and assumes a worst- designs. Fig. 14 shows two CTs that are both classified as C800
case, completely offset waveform, which is not often the case because they each deliver 800 V to a standard burden of 8 Ω at
in the real world. Any fault other than the worst case will result 100 A secondary current. The construction of the two CTs,
10
18, 000 A 1.2 Ω + 1 Ω Fig. 16 shows the calculated operate and restraint values for
• • ( 25 + 1) =
57.2 (6)
2, 000 A 8 Ω + 1 Ω a differential relay connected to these two CTs. We can see that
the false differential current reaches over 25 A secondary for
We get the following for the CT in Fig. 14b (larger RS): almost 1.5 cycles. This relay would have to have a fairly high
18, 000 A 1.2 Ω + 2 Ω slope ratio of 40 percent to ride through the transient differential
• • ( 25 + 1) =
74.9 (7) current from these two CTs with the same rating.
2, 000 A 8 Ω + 2 Ω
100
Even though the CT in Fig. 14b has more iron (VE is higher),
90
transiently, (5) predicts that it will saturate more severely.
Current (secondary A)
80
70
(a) IST = 110 A RS = 1 Ω IS = 100 A Restraint
60
IE = 10 A 50
40
30
IP VE = 900 V VS = 800 V ZB = 8 Ω
20
10 Operate
0
0.000 0.017 0.033 0.050 0.067 0.083 0.010
Time (seconds)
(b) IST = 110 A RS = 2 Ω IS = 100 A
Fig. 16. Operate and restraint values from a differential relay connected to
IE = 10 A the CTs in Fig. 14
IP VE = 1000 V VS = 800 V ZB = 8 Ω
E. CT Analysis Tools
Equation (5) shows how to verify if a CT will saturate for a
given fault current and burden. In addition to this equation,
other tools exist to analyze the behavior of a CT or sets of CTs.
Fig. 14. Two C800 CTs, one with more copper and less iron (a) and one
with more iron and less copper (b)
1) CT Saturation Theory and Calculator
Perhaps the most common is the “CT Saturation Theory and
Using a modeling tool like those described in Section III, Calculator,” an Excel® spreadsheet created by the IEEE Power
Subsection E, we can plot the response of both of these CTs and System Relaying Committee (PSRC) [15]. This spreadsheet is
compare the results. Fig. 15 shows the two CTs modeled in a shown in Fig. 17 and is well documented. Using the available
differential circuit, with the differential current being the tutorials, a level of proficiency can be gained in a short period
difference between the two CTs. We can see that the two CTs of time. The necessary inputs are a description of the CT
do indeed perform very similarly except in the second cycle, (e.g., ratio, accuracy class, and so on) and data on the available
where CT B saturates sooner than CT A as the evaluation of (5) fault current and X/R ratio. The calculator allows the settings
predicted. After the second cycle, the CTs have nearly the same and specification engineer to play “what if” scenarios with the
error and the errors mostly cancel (resulting in little differential CT. Being able to adequately predict the CT’s behavior during
current). fault conditions can help form well-reasoned decisions when
creating relay settings.
11
Fig. 17. Simulation in the “CT Saturation Theory and Calculator” spreadsheet for a C400 CT [15]
Fig. 18. Simulation in the “CT Saturation Theory and Calculator” spreadsheet for a C800 CT [15]
3) Two CTs In addition to these tools, other software exists to model the
The authors of [8] developed a program that simulates the transient behavior of CTs—many of which are described in
transient behavior of two CTs in a differential circuit. The [17].
program was originally written in BASIC programming
F. Mitigating Saturation
language, but has since been converted to an executable
program that can be run on a Windows® operating system If any of the analysis in the previous subsections proves that
(shown in Fig. 20). In addition to plotting the output of the CTs, CT saturation is a concern, there are several practical solutions
the program produces ASCII and COMTRADE files that can that can be used to mitigate the situation. The most obvious
be used to play the signals into a relay for testing. solution is to use a CT with a higher accuracy class, but
sometimes these CTs are simply too large physically and do not
fit in the given space requirements. Another option is to reduce
the CT burden by adding another set of CT cables in parallel.
Halving the burden has the same impact on saturation as
doubling the accuracy class. Another option is to use CT taps
to double the turns ratio. This has an even larger impact—the
same as quadrupling the accuracy class. This is because
doubling the turns ratio results in halving the secondary current
as well as doubling the available voltage at the CT terminals to
drive that current through the connected burden. Whenever the
turns ratio is increased, ensure that the currents the relay
measures during normal operation are still high enough that
sensitivity is not lost.
Fig. 20. Two CTs simulation program
13
when analyzing a relay operation, and always download both the B-phase CT is saturated slightly, and in Fig. 25c, there is
raw and filtered event reports after a fault. severe CT saturation on all three phases.
In addition to whether the event report is raw or filtered, it is
a) 20
important to be aware of the sampling rate of the data in the 15
10 2:IA69
event report. Fig. 23 shows CT saturation error between two
Current
5 2:IB69
CTs that only lasts for a quarter cycle but manages to cause a 0 2:IC69
–5
misoperation [21]. This could easily have been missed if the –10
user was looking at a 4 sample-per-cycle event report. It is –15
important to always download the highest resolution data b) 600
400
possible after a fault. 200 1:IA_A
Current
0 1:IB_A
1:IBW –200 1:IC_A
8,000 –400
1:IBX_NEG
–600
Current (A)
4,000 –800
0 c) 600
400
–4,000 200 1:IA
1:IB
Current
0
–8,000 1:IC
25.030581 25.040581 25.050581 –200
–400
1,400 1:IB_SUM –600
Current (A)
1,000 –800
Time
600
200 Fig. 25. Inrush currents with no CT saturation (a), slight CT saturation (b),
–200 and severe CT saturation (c)
25.030581 25.040581 25.050581
Time (s) 2) Look for Frequency Changes
Depending on the level of CT saturation and how long it
Fig. 23. Difference error from CTs lasting for a quarter cycle persists, it may not always be as obvious as what we have seen
B. How to Detect Saturation in an Event Report so far. Light saturation, while capable of still causing relay
To determine if CTs have saturated, relay event reports can misoperations, does not always give us the typical sawtooth
be inspected for several known characteristics. waveforms shown previously. Fig. 26 shows a current
waveform from a saturated CT that might not be immediately
1) Look for the Characteristic Waveform obvious. In cases like this, we can use the fact that saturated
The simplest way to detect CT saturation is to look in the CTs output currents rich in harmonics to our advantage. One
raw event data for the characteristic “sawtooth” current way to detect higher-level harmonics is to look for frequencies
waveforms shown in Fig. 5. Fig. 24 shows a CT that saturated above 60 Hz.
and then recovered during a phase-to-phase fault [22]. This We can detect a change in frequency by using event analysis
waveform is very similar to the textbook cases, and CT software to measure and compare the periods of different parts
saturation should be immediately suspected. of a signal in a raw event report. In Fig. 26, we placed two
100
vertical lines to create a window that starts at one zero crossing
and ends at another zero crossing approximately 1 cycle later.
60
1:ICW2 The software shows that the time period between these two
Current (A)
20
lines is 16.147 ms, which is very close to 16.666 ms (1 cycle,
–20
based on a 60 Hz nominal frequency). This means that the
–60
current signal between these two points in time is almost a true
–100 60 Hz signal and the CT is not experiencing much saturation.
3 4 5 6 7 8 9 10
Cycles
20,000
Fig. 24. C-phase CT saturates and recovers during a phase-to-phase fault 10,000
Realize that the currents the relay sees will vary depending 0
Curren t
inrush, and so on). In general, look for currents to not accurately –20,000
–30,000
follow the waveform expected for the given system conditions.
–40,000
Take the system condition of inrush on a power transformer, for 16.147 ms
example. A relay sees inrush currents when a downstream 12:26:32.97 12:26:32.99
transformer is first energized, and these inrush currents have an Time
expected signature. Fig. 25 shows three examples of event Fig. 26. No frequency distortion exists when the period of a signal is
reports during an inrush condition, each with varying levels of 16.666 ms
CT saturation. Fig. 25a shows an inrush event with no CT Now, we move the time cursors further along the waveform
saturation—this is what inrush is supposed to look like [22]. and compare the results. In Fig. 27, the period between the two
Fig. 25b and Fig. 25c show a different inrush event. In Fig. 25b,
15
zero crossings has decreased to 14.616 ms. This shows that the Just like with frequency changes, CT saturation is not the
signal has a frequency higher than 60 Hz, and it could be a sign only cause of harmonic content in current waveforms. The
that the CT is saturating. inrush condition shown in the previous section also generates
large amounts of harmonic content that the relay will measure.
20,000 Measuring harmonic content is just one method that can be used
10,000 when trying to determine if a CT has saturated.
0
4) Look for a Sudden Loss of DC Offset
Curren t
–10,000
In cases where a fault current contains dc offset, the sudden
–20,000 dissipation of this offset can be a sign that CTs have saturated.
–30,000 Theory and testing that shows why dc disappears from the
–40,000 secondary current when saturation occurs is given in [24].
14.616 ms
Fig. 29 gives an illustration of what a sudden loss in dc offset
12:26:32.99 12:26:33.00
Time
looks like. Normally, we would expect a current with dc offset
to slowly decay along an exponential curve (shown in red in
Fig. 27. Frequency is greater than 60 Hz when the period of a signal is less
Fig. 28). We can see that the waveform follows the exponential
than 16.666 ms
curve for the first 2–3 cycles, at which point the dc offset
This same technique can be applied to filtered event reports completely goes away and the waveform is symmetrical around
to a certain extent. When a saturated waveform gets passed the 0 axis. If there is rapid dissipation of dc offset in a raw event
through the cosine filter, there is some distortion in the output report, suspect CT saturation.
compared with when a nonsaturated waveform gets passed
4,000
through. For example, the angle of the filtered current phasor
will start to go in the leading direction. It is important to note 2,000
that distortion in a filtered waveform may not be the result of
0
CT saturation—that is just one possible cause. Step changes in
Curren t
134.4199 (rms)
60 4.61%
120 Hz
currents on the delta side of the transformer. We also suspect
40 4.1226 (rms)
Second Harmonic this to be a false residual current because we would not expect
120 Hz
20 Second Harmonic zero-sequence current to exist on the high side of the delta
0 connection for this fault. Note that only unexpected residual
0 120 240 360 0 120 240 360 current (calculated by the relay as the sum of all three phase
Hz Hz
CTs or wired into a relay input in a residual connection) is a
Fig. 28. Second-harmonic content of current waveform when CT is not sign of CT saturation—unexpected neutral current through a
saturated (a) and is saturated (b) core-balanced CT is not. Whenever CT saturation is suspected
from filtered event reports, the raw data should be downloaded
to verify.
16
–2
currents experienced saturation around the 670 ms point in the
80
IAW2
fault data, causing distortion and a difference from Winding 2.
40
0 IBW2
5ICW2 The magnitudes of the differential signals resulting from the
–40 saturation on Winding 1 can be found by adding the Winding 1
10:01:17.615000 AM
–80 and Winding 2 data points, as shown by the black traces
12 in Fig. 31.
8 IRW2.Mag
4
40 IBW1
0 10:01:17.615000 AM
20 NEG_IBW2
–2 –1 0 1 2 3 4 5 6 5
PARTIAL_IBT
Cycles 0
Fig. 30. False residual current appears when CTs saturate during an external –20
fault [22] –40
Current (A)
Unmatched Currents
Most misoperations of differential applications occur when
CTs saturate during external faults. To detect saturation in 60 ICW1
differential events, we must remember that the differential NEG_ICW2
5
40 PARTIAL_ICT
principle is based on the expectation of the current entering a
20
zone of protection being equal to the current leaving the zone
of protection during normal conditions. Fig. 30 shows a raw 0
event report from an external B-phase-to-C-phase fault on a –20
two-terminal differential application. Note the subtle change in –40 TREF = 9:53:45 PM
IBW1 and ICW1 currents near the 670 ms vertical (orange) 640 650 660 670 680 690 700
time marker. Although the change looks minor, it was enough Time (ms)
for this relay to misoperate.
Fig. 32. Comparison of phase CTs with Winding 2 negated
80
IAW1
Whenever phase currents across a differential are not equal
40 IBW1 and 180 degrees out of phase during an external fault condition,
5
ICW1 CT saturation is suspected. Remembering to account for CT
0 ratio differences and transformer and CT connections is
important, as these things may also result in the phase currents
–40
not being equal and 180 degrees out of phase during normal
TREF = 9:53:45 PM conditions.
Current (A)
–80
80
V. COMMON MISOPERATIONS BECAUSE OF CT SATURATION
IAW2
40 IBW2 Section III shows guidelines to follow to reduce the
5
ICW2 likelihood of saturation occurring in CTs. Despite our best
0 efforts to follow those guidelines, it is inevitable that sometimes
CTs saturate and feed unreliable signals to the connected relay.
–40
Because relays require undistorted CT secondary current to
TREF = 9:53:45 PM
–80 perform accurate phasor measurements, saturation can lead to
640 650 660 670 680 690 700
misoperations. In other words, “garbage in = garbage out.” This
Time (ms)
section shows two different field cases of CT saturation leading
Fig. 31. External B-phase-to-C-phase fault on a two-terminal differential to misoperations in differential installations. In addition to
these, there are many other references that document the
performance of relay elements during CT saturation, including
[1], [5], [7], [10], [20], and [21].
17
A. Generator Differential Trips During Inrush generator and the differential to be balanced for this external
A utility feed and a bank of backup generators both feed a inrush event. The fact that this is not the case caused the
switchgear bus. Seven 2,500 kW backup generators are differential element to measure false operate current and trip.
connected to the 13.8 kV generator bus along with a load bank 800
breaker, per Fig. 32. During testing, a 3,500 kVA transformer 400
IA87
IB87
is connected to the load bank breaker, the breaker is closed into 0
5IC87
the dead generator bus, and the generators are started. The relay
–400 7:39:07 PM
Current (A)
protecting the first generator to close in trips on its differential
element. 600
IA
200
IB
5IC
–200
–600 7:39:07 PM
Generator Fig. 35. Raw event report recorded when generator relay trips during startup
Switchgear
Recall from Section II that the presence of asymmetrical
fault current can result in CT saturation. This is because of the
dc offset in the primary current causing flux to accumulate in
A1 one direction more than the other, resulting in the CT eventually
Switchgear hitting its positive or negative volt-time area limit. An inrush
waveform (Fig. 34) is harder on CTs than asymmetrical fault
current because all of the currents are monopolar. The C-phase
current, for instance, only allows accumulation of flux in the
Fig. 33. One-line diagram of utility feed and backup generators positive direction, resulting in hitting the maximum volt-time
area much faster than if the current waveform dropped below
The differential relays for each backup generator are zero for some period of time to allow the CT to partially
connected as shown in Fig. 33. recover.
Generator Fig. 35 shows each phase current from the bus-side CTs
A
52 Switchgear compared with its corresponding phase on the neutral side. The
B
bus-side CT signals have been flipped 180 degrees to account
G
C
for the difference in CT polarity. We can see that the signals
start out completely equal to each other (which is expected) and
then fall away as the neutral CTs saturate. C-phase is the worst
IC IC87 offender, and it is the phase that tripped the relay.
IB IB87 350
IA IA87 250 IA
IA87_NEG
150
Fig. 34. Connections of differential relays on backup generators 50
Fig. 34 shows the raw event report that the differential relay –50
7:39:07 PM
recorded. Notice the difference between the bus-side currents –150
IB
classic, although saturated, inrush waveform (as described 400
IB87_NEG
previously in Section IV, Subsection B), which makes sense 200
0
because of the downstream transformer being energized. 7:39:07 PM
–200
Section III mentions that we should always match the phase and
neutral-side CTs in generator applications to account for the 200
0 IC
saturation that will inevitably occur. We know the CTs will –200 IC87_NEG
saturate, but matching the CTs will make sure they saturate in –400
the same way, and the signals will cancel out in the differential. –600 7:39:07 PM
In this example, because both sets of CTs see the same current 170 190 210 230 250 270
Time (ms)
with a 180-degree polarity difference, we would expect the
same inrush waveform to be mirrored on the neutral side of the Fig. 36. Currents from bus-side CTs vs. neutral-side CTs
18
Upon investigation, it was found that the CTs in fact were currents remain steady throughout a fault, is an indication of CT
sized the same on both sides of the generator—both 200/5, C20, saturation [22].
intentionally sized to the generator’s full-load ampere rating of
2
150 A. With CTs rated similarly, it is unlikely that one set IOP1
would perform so differently than the other. It was then found IRT1
1
that the length of the CT secondary leads between the CTs and
the relay were considerably different. The one-way lead length 0
Current (A)
0.8 IOP2
IRT2
burden of the neutral-side CTs (2.44 Ω for the neutral side vs. 0.4
0.17 Ω for the bus side) and resulted in the difference in 0
saturation behavior.
The ideal solution to this problem is to match the lead length 1.2
IOP3
burden on both sets of CTs to where they saturate similarly and 0.8 IRT3
balance each other out. Until that could be accomplished, a 0.4
IAW2 IBW1
5 5ICW1
IBW2 –5
5ICW2
–5 –15
6:19:22.971000 AM 6:19:22.971000 AM
–15 –25
15 25
IAW1 15 IAW2
IBW2
Current (A)
5 IAW2 5ICW2
5
–5
–5
6:19:22.971000 AM 6:19:22.971000 AM
–15 –15
–3 –1 1 3 5
Cycles 15
IAW1
Fig. 37. Filtered event report for external A-phase-to-ground fault 5 IAW2_NEG
–5
Fig. 37 shows the filtered differential event report. Here, we
–15
see the restraint currents steadily decreasing throughout the
6:19:22.971000 AM
event, while operate currents increase and then decrease. –25
–5 –3 –1 1 3 5
Decreasing operate current over time, while filtered phase Cycles
Several solutions could be implemented to prevent this type B. External Fault Detector Enables High Security Mode
of misoperation. In this case, the utility chose to temporarily When an external fault occurs and causes the CTs to
raise the minimum operate current threshold and slope setting saturate, there is a small window of time when the fault first
in the differential relay. At a later date, they plan to increase the occurs that the CTs have not yet saturated. During this time
taps of the CTs to allow for a higher voltage before saturation period, IRT increases because of the elevated fault current, but
(from 300/5 to 800/5 on the 138 kV side, and from 600/5 to IOP does not. We can use this to our advantage to develop logic
1200/5 on the 69 kV side) and return the slope to its previous that detects an external fault before the CTs have had a chance
setting. The external fault detection algorithm described in the to saturate. When the relay detects a large change in IRT with no
next section would also have prevented this misoperation (or very small) change in IOP, it declares an external fault. This
because restraint current increased in all three phases is shown in Fig. 39. The success of this logic depends on CTs
significantly before the operate current increased. This would providing valid output for some amount of time (2 ms to a half
have put the relay into a more secure mode with a higher slope cycle) [14] [21].
setting and kept it there until the dc offset decayed.
DIO PR
+
∆IOPR DIO P
VI. RELAY ALGORITHMS ACCOUNT FOR SATURATION DIO PP –
200
80 A • There are two types of CT saturation: symmetrical
A/D Output Cosine Filter Peak Filter
150
INST saturation and asymmetrical saturation. Symmetrical
saturation is caused by symmetrical fault currents high
100 in magnitude, while asymmetrical saturation is caused
by fault currents with dc offset.
50
• When a breaker trips during asymmetrical current
Current (A)
VIII. APPENDIX A Therefore, the actual secondary current coming out of the
To meet the IEEE C57.13-1993 standard, a CT must not CT must be greater than or equal to 90 percent of what we
exceed 10 percent ratio correction (PRC) [28]. The standard expect it to be. This means that only 10 percent of the expected
defines the following: signal can be lost as error.
• The ratio correction factor (RCF) is the ratio of the IEEE C57.13-2016 states that CTs must have ≤10% ratio
true ratio to the marked ratio. The primary current is error to meet the standard [9]. Ratio error is defined similarly
equal to the secondary current multiplied by the to PRC in IEEE C57.13-1993, but with an added sine term to
marked ratio times the RCF. account for the fact that IE and IS are not exactly in phase for
• The percent ratio correction (PRC) is the difference cases when the connected burden has a resistive component.
between the RCF and unity, expressed in percent. When the connected burden is not purely inductive, IE and IS
We can write the definition of RCF as shown in (10), where cannot simply be added algebraically, and this extra term is
CTR is the marked ratio of the CT. needed for accuracy.
IEEE C57.13-2016 also defines the composite error the
I P / IS same way IEEE C57.13-1993 defines PRC, and it says that this
RCF =
CTR can be used in place of ratio error for ring-type cores of low
(10)
IST reactance. For more on CT measurement errors, see [29].
RCF =
IS For simplicity in this paper, we define ratio error the same
as PRC, as shown in (16).
We can write the definition of PRC as shown in (11).
IE
PRC
= ( RCF − 1) •100 (11) Ratio Error (%) = •100 (16)
IS
Substituting (10) into (11), we get (12).
I IX. APPENDIX B
= ST − 1 •100
PRC
IS Recall from Section II that the ANSI voltage rating of a CT
defines the minimum secondary voltage (VS) that the CT must
I I
= ST − S •100
PRC deliver to a standard burden at 20 times rated secondary current
IS IS (12) without exceeding a 10 percent ratio error [2]. If the fault
I −I current through a CT is higher than 20 times the rated current,
PRC = ST S •100 or the connected burden is higher than the standard burden, we
IS may risk going into saturation (over 10 percent error). We can
IE use the definition for the ANSI standard voltage rating to
PRC = •100
IS develop an equation for the level of fault current (or connected
burden) that, if we go above, will result in more than 10 percent
IEEE C57.13-1993 states that (12) must not exceed
error. We can call this the saturation point for symmetrical
10 percent [28]. We want to know what this limit means in
current (symmetrical saturation).
terms of how the actual secondary current corresponds to the
We can write the definition of the ANSI standard voltage
expected, or ideal, secondary current. A more intuitive form of
rating as follows:
I I
calculating CT error would be S_actual , or S . We can write VSTD 20 • IS RATED • ZB STD (17)
IS_expected IST
this as shown in (13). where:
VSTD is the secondary terminal voltage rating
IS IS
= (13) IS RATED is the rated secondary current
IST IS + I E
ZB STD is the standard burden
If we divide all terms on the right side by IS, we get (14). Fig. 41 is a reproduction of Fig. 8, for convenience.
IS 1 IST RS IS
= (14)
IST I IE
1+ E
IS
IP VE VS ZB
IE ZE
Since ≤ 10 percent, we get (15).
IS
N1 N2
IS
≥ 0.909 (15)
IST Fig. 42. Simplified CT equivalent circuit
22
Using the equivalent circuit in Fig. 41 and the definition of Because we are concerned with primary fault current values,
the ANSI voltage rating, we know that the ratio error will not we can incorporate the CT ratio and convert the first term in
exceed 10 percent as long as the secondary terminal voltage VS (27) to primary values. This results in (28).
is less than the secondary terminal voltage rating VSTD, as I FAULT ZB R S
shown in (18). • 20 (28)
I PRI ZB STD R S
VS VSTD (18)
where:
The voltages VS and VSTD are driven by the core excitation IFAULT is the maximum fault current in primary amperes
voltage, VE. Therefore, we can also write the relationship in for a given fault.
(18) as (19), which considers the voltage drop across the IPRI is the primary current rating of the CT (e.g., for a
secondary winding resistance RS. 2000/5 CT, IPRI is 2000.)
VE VE STD (19) ZB is the actual burden of the CT’s secondary circuit,
which includes both the impedance of the connected relay
We can write the definition of VE STD as: and the impedance of the leads from the CT to the relay.
VE STD 20 • IS RATED • ZB STD R S (20) RS is the internal resistance of the CT secondary winding.
ZB STD is the standard burden of the CT (e.g., for a C800
We can write the actual voltage VE as:
CT, the ZB STD is 8 Ω.)
VE IS • ZB R S (21) Equation (28) can be used to evaluate CT performance for
Therefore, based on the relationship in (19): symmetrical fault currents but should never be used in practice.
This derivation of (28) is shown simply as a basis for (5).
IS • ZB R S 20 • IS RATED • ZB STD R S (22)
Equation (28) is not adequate for analyzing how a CT will
Rearranging terms, we obtain: behave in the presence of (typically asymmetrical) fault current,
IS ZB R S and (5) should always be used in practice. For even better
• 20 (23) accuracy, use a transient modeling program to model CT
IS RATED ZB STD R S
behavior in the time domain.
To make this equation useful, we must write it in terms of Note that the basis for (28) was first introduced in [1]. Later,
the secondary fault current, which is IST in Fig. 41. IST is the in [5], the original equation was adjusted to consider the CT
sum of IS and IE. For the worst case right at the saturation point, secondary resistance RS, resulting in the more accurate analysis
[9] defines the error as 10 percent (IE/IS ≤ 0.1). Using this reflected here.
relationship, we can define:
X. APPENDIX C
IS 0.909 • IST (24)
Equation (5), repeated in (29), is used to analyze CT
We can then write (23) as: saturation resulting from fault current with dc offset.
0.909 • IST ZB R S A C800, 2000/5 CT with RS = 0.5 Ω is connected to a 1 Ω
• 20 (25)
IS RATED ZB STD R S burden (including relay and lead resistance). The system X/R
ratio is 12. What is the maximum primary three-phase fault
If we define IST as the secondary fault current If sec, (25) current that can be applied to this CT without exceeding the
becomes: maximum flux density (which is proportional to the volt-time
If sec ZB R S area)?
• 22 (26)
IS RATED ZB STD R S To determine the maximum fault current, set (5) to the
maximum of 20 and solve for IFAULT, as shown in (29) and
We can use (26) to solve for the maximum fault current (30).
(If sec) that the CT can handle before it goes into saturation. We
can also use it to solve for the maximum burden for a given I FAULT ZB R S X
• 1 20 (29)
fault current. I PRI ZB STD R S R
In development of (26), we assumed an inductive burden. I FAULT 1 0.5
Therefore, IS and IE are in phase and can be added algebraically • 12 1 20
2000 8 0.5 (30)
to get IST. This assumption also allows us to use the simplified
error equation for ratio error in Appendix A. Using modern I FAULT 17.4 kA
resistive burdens with these simplified equations produces
errors. To account for these errors, a more conservative form of XI. REFERENCES
(19) is used: [1] S. E. Zocholl, Analyzing and Applying Current Transformers.
Schweitzer Engineering Laboratories, Inc., Pullman, WA, 2004.
If sec ZB R S
• 20 (27) [2] IEEE Standard C37.110-2007, IEEE Guide for the Application of
IS RATED ZB STD R S Current Transformers Used for Protective Relaying Purposes.
23
[3] D. Subedi and S. Pradhan, “Analyzing Current Transformers Saturation proceedings of the 68th Annual Conference for Protective Relay
Characteristics for Different Connected Burden Using LabVIEW Data Engineers, College Station, TX, March–April 2015.
Acquisition Tool,” International Journal of Electrical, Computer, [22] D. Costello, “Lessons Learned Through Commissioning and Analyzing
Energetic, Electronic and Communication Engineering, Vol. 9, Data From Transformer Differential Installations,” proceedings of the
Issue 10, 2015. 60th Annual Conference for Protective Relay Engineers, College
[4] B. Kasztenny, N. Fischer, D. Taylor, T. Prakash, and J. Jalli, “Do CTs Station, TX, March 2007.
like DC? Performance of Current Transformers With Geomagnetically [23] L. F. Kennedy and C. D. Hayward, “Harmonic-Current-Restrained
Induced Currents,” proceedings of the 69th Annual Conference for Relays for Differential Protection,” Electrical Engineering, Vol. 57,
Protective Relay Engineers, College Station, TX, April 2016. Issue 5, May 1938, pp. 262–271.
[5] M. Thompson and R. Folkers, “Secure Application of Transformer [24] B. Kasztenny, N. Fischer, D. Taylor, T. Prakash, and J. Jalli, “Do CTs
Differential Relays for Bus Protection,” proceedings of the 58th Annual like DC? Performance of Current Transformers With Geomagnetically
Conference for Protective Relay Engineers, College Station, TX, Induced Currents,” proceedings of the 66th Annual Conference for
April 2005. Protective Relay Engineers, College Station, TX, April 2016.
[6] S. Hodder, B. Kasztenny, N. Fischer, and Y. Xia, “Low Second- [25] L. Underwood, “Current Transformer Selection Criteria for Relays with
Harmonic Content in Transformer Inrush Currents – Analysis and Adaptive Overcurrent Elements,” April 2005. Available: selinc.com.
Practical Solutions for Protection Security,” proceedings of the
[26] S. E. Zocholl and J. Mooney, “Primary High-Current Testing of Relays
67th Annual Conference for Protective Relay Engineers, College With Low Ratio Current Transformers,” proceedings of the 57th Annual
Station, TX, March 2014. Conference for Protective Relay Engineers, College Station, TX,
[7] H. J. Altuve, N. Fischer, G. Benmouyal, and D. Finney, “Sizing Current April 2004.
Transformers for Line Protection Applications,” proceedings of the [27] G. Benmouyal and S. E. Zocholl, “The Impact of High Fault Current and
66th Annual Conference for Protective Relay Engineers, College CT Rating Limits on Overcurrent Protection,” proceedings of the
Station, TX, April 2013. 56th Annual Conference for Protective Relay Engineers, College
[8] S. E. Zocholl and D. W. Smaha, “Current Transformer Concepts,” Station, TX, April 2003.
proceedings of the 46th Annual Georgia Tech Protective Relaying [28] IEEE Standard C57.13-1993, IEEE Standard Requirements for
Conference, Atlanta, GA, April 1992.
Instrument Transformers.
[9] IEEE Standard C57.13-2016, IEEE Standard Requirements for
[29] Forest K. Harris, Electrical Measurements. John Wiley & Sons,
Instrument Transformers. Hoboken, NJ, 1952.
[10] G. Benmouyal, J. Roberts, and S. E. Zocholl, “Selecting CTs to
Optimize Relay Performance," proceedings of the Pennsylvania Electric
Association Relay Committee Fall Meeting,” September 1996. XII. BIOGRAPHIES
[11] S. Manson and A. Upreti, “Current Transformer Selection Techniques Ariana Hargrave earned her B.S.E.E., magna cum laude, from St. Mary’s
for Low-Voltage Motor Control Centers,” proceedings of the University in San Antonio, Texas, in 2007. She graduated with a Master’s of
63rd Annual Petroleum and Chemical Industry Technical Conference, Engineering in electrical engineering from Texas A&M University in 2009,
Philadelphia, PA, September 2016. specializing in power systems. Ariana joined Schweitzer Engineering
Laboratories, Inc. in 2009 and works as a protection application engineer in Fair
[12] J. R. Linders, C. W. Barnett, J. W. Chadwick, P. R. Drum, Oaks Ranch, Texas. She is an IEEE member and a registered professional
K. J. Khunkhun, W. C. Kotheimer, P. A. Kotos, D. W. Smaha, J. W. engineer in the state of Texas.
Walton, P. B. Winston, and S. E. Zocholl, “Relay Performance
Considerations With Low-Ratio CTs and High-Fault Currents,”
Michael J. Thompson received his B.S., magna cum laude, from Bradley
IEEE Transactions on Industry Applications, Vol. 31, Issue 2,
University in 1981 and an M.B.A. from Eastern Illinois University in 1991.
March–April 1995.
Upon graduating, he served nearly 15 years at Central Illinois Public Service
[13] S. E. Zocholl, “Rating CTs for Low Impedance Bus and Machine (now AMEREN). Prior to joining Schweitzer Engineering Laboratories, Inc.
Differential Applications,” proceedings of the 27th Annual Western (SEL) in 2001, he was involved in the development of several numerical
Protective Relay Conference,” Spokane, WA, October 2000. protective relays while working at Basler Electric. He is presently a Fellow
[14] M. Donolo, A. Guzmán, M. V. Mynam, R. Jain, and D. Finney, Engineer at SEL Engineering Services, Inc. He is a senior member of the IEEE,
“Generator Protection Overcomes Current Transformer Limitations,” member of the IEEE PES Power System Relaying and Control Committee, past
proceedings of the 41st Annual Western Protective Relay Conference, chairman of the Substation Protection Subcommittee of the PSRCC, and
Spokane, WA, October 2014. received the Standards Medallion from the IEEE Standards Association in
2016. Michael is a registered professional engineer in six jurisdictions, was a
[15] IEEE Power System Relaying and Control Committee, “CT Saturation contributor to the reference book “Modern Solutions for the Protection Control
Theory and Calculator.” Available: http://www.pes-psrc.org. and Monitoring of Electric Power Systems,” has published numerous technical
[16] ECE 525: Power Systems Protection and Relaying (Lecture, University papers and magazine articles, and holds three patents associated with power
of Idaho, Moscow, ID, February 2016). Available: www.ece.uidaho. system protection and control.
edu/ee/power/ECE525/Lectures/L8/CT_Model.pdf.
[17] R. Folkers, “Determine Current Transformer Suitability Using EMTP Brad Heilman, P.E., has a B.S.E.E. degree from the South Dakota School of
Models,” proceedings of the 26th Annual Western Protective Relay Mines and Technology. From 1990 to 1997, he was employed as a system
Conference, Spokane, WA, October 1999. protection engineer for Black Hills Power & Light. His utility work included
[18] E. O. Schweitzer, III and D. Hou, “Filtering for Protective Relays,” transmission line and generator protection, power plant and substation
proceedings of the 19th Annual Western Protective Relay Conference, commissioning, and SCADA system upgrades. In 1997, he joined Schweitzer
Engineering Laboratories, Inc. as a field application engineer supporting
Spokane, WA, October 1992.
customers in Arizona, California, Montana, Wyoming, Utah, North Dakota,
[19] S. E. Zocholl and G. Benmouyal, “How Microprocessor Relays Respond Nebraska, Nevada, Idaho, and South Dakota. He is an IEEE member and
to Harmonics, Saturation, and Other Wave Distortions,” proceedings of licensed professional engineer in the state of South Dakota.
the 24th Annual Western Protective Relay Conference, Spokane, WA,
October 1997.
[20] J. Mooney, “Distance Element Performance Under Conditions of CT
Saturation,” proceedings of the 61st Annual Conference for Protective Previously presented at the 2018 Texas A&M
Relay Engineers, College Station, TX, April 2008. Conference for Protective Relay Engineers.
[21] D. Costello, J. Young, and J. Traphoner, “Paralleling CTs for Line © 2018, 2019 IEEE – All rights reserved.
Current Differential Applications: Problems and Solutions,” 20190418 • TP6811-01