SELECTION OF WATER COOLED CHILLER – 221 TR

Chiller selection Software


Version 4.37 (21-AOUT-2007) - Copyright © 2000-2007, Carrier Corp.

* Project Alfa Laval


Date 12/5/2008 4:59:14 PM
Location
Company name Alfa Laval (India) Limited
Contact name Mr. Prabhakar Nachanekar
CARRIER reference 30HXC

* Product 30HXC230-PH3
Range 30HXC Phase3 (Standard)
Gross capacity 778 kW
Unit absorbed power 168 kW
Compres. Input power 168 kW
C.O.P. 4.62
No of capacity steps 8
Minimum step 14 %
Refrigerant R134a
Expansion valve EXV

* Evaporator
Fluid Water
Leaving T. 6 °C
Delta T. 7 K
Entering T. 13 °C
Flow rate 26.5 L/s
Evaporator pressure drop 26 kPa
Fouling factor 0.0176 m²-K/kW
Max operating pressure 1000 kPa

* Condenser
Fluid Water
Entering T. 32 °C
Delta T. 4 K
Leaving T. 36 °C
Flow rate 56 L/s
Pressure drop 57 kPa
Fouling factor 0.044 m²-K/kW
Max operating pressure 1000 kPa

T.H.R. 938 kW

* No of compressors 3
Compressor type screw
Compressor motor speed 49 r/s
Starter type direct

* Volts/Phases/Hertz 400-3-50
Power Factor (at max power) 0.87
Maximum current drawn 419 A (U nom.)
Maximum starting current 978 A
Voltage limits 360/440 V
* Operating weight 4602.0 kg
Refrigerant charge 178 kg
Length/Width/Height 3923.5 mm
1015 mm
2060 mm

• Part Load

Load % Capacity Power Input KW Cooling water inlet temp. IKW / TR


TR °C
100 221 168 32 0.76
75 169 146 32 0.86
50 111 94 32 0.84
25 56 51 32 0.91