Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Surge Arrester Installation

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 11
At a glance
Powered by AI
The document discusses different types of earthing systems used in electrical installations and their implications for surge protection. It also outlines factors to consider when evaluating lightning risk and provides guidelines for proper surge arrester installation.

The document discusses the TT, IT, TN-S and TN-C earthing systems and how the choice of surge protection depends on the earthing system used.

The document mentions that a formula is used to evaluate lightning risk by taking into account: 1) Lightning density, 2) Type of distribution network, 3) Site topography, 4) Presence of lightning rods.

LV surge arresters

A variety of documents deal with the subject of surge arrester installation: for
example in France, standard NF C 15-531 focuses on the installation rules of
LV surge arresters, and standard NF C 15-100 covers all the LV electrical
installations.

Thumb rules for surge arrester installation in different earthing systems (photo
credit: Dehn)
To evaluate the risk, a formula based on scientific criteria is proposed to
engineering and design departments.This formula takes account of the
characteristics of the site and the environment:

1. Lightning density,
2. Type of distribution network,
3. Site topography,
4. Presence of lightning rods, if any.
Selection of surge arresters depends on: importance of the risk, susceptibility of
the devices and earthing system of the electrical network.
Whatever system is used, if a lightning risk is present, all electrical installations
must be fitted with surge arresters (see fig. 1), whose composition may vary
according to the type of earthing system.

Figure 1 – Choice of surge protection mode (common or differential) according


to the electrical installation earthing system as per NF C 15-443 .

TT system

Surge protection
installation in TT earthing system

IT system
Surge protection
installation in IT earthing system

TN-S system
Surge protection
installation in TN-S earthing system

TN-C system
Surge protection
installation in TN-C earthing system
These differences are due to:

 Whether or not differential mode surges are treated,


 The maximum steady state voltage Uc:
 Between live conductors and the earth:
 Uc > 1.5 Un in the TT and TN earthing systems,
 Uc > √3 Un in the IT earthing system;
 Between phases and neutral, Uc > 1.1 Un whatever earthing system
is used.
IMPORTANT NOTES //
1. Earthing the neutral does not prevent surges from affecting the phase
conductors!!
2. Surge limiters, use of which is compulsory in the IT earthing system, replace
surge arresters for protection against 50 Hz MV surges. As these two
devices do not have the same functions, surge arresters continue to be
required for lightning surges.
Implementation of surge arresters
A variety of rules are defined (importance of equipotential bonding, staggered or
cascading protection devices, use of residual current devices), application of
which may sometimes vary according to the installation sector (tertiary and
industrial or domestic).

Let’s now discuss about following topics:

 Importance of the equipotential bondings.


 Cascading protection devices
 Cohabitation of residual current devices and surge arresters
<="" ins="" data-adsbygoogle-status="done" style="box-sizing: border-box;
height: 280px; width: 336px; display: block;">

Importance of the equipotential bondings


EMC principles state that LV installations must have only one earthing
connection for their loads. This connection is close to the origin of the
installation, and it is at this level that the “main” surge arrester must be installed
(see fig. 2).

Figure 2 – Positions of surge arresters in an LV installation


Where:

 For increased efficiency of protection, the cable lengths L1+L2+L3 must


be reduced when installing a surge arrester.
 Up – protection voltage downstream of the main surge arrester.
 Ups – protection voltage after the secondary surge arrester.
 * – surge arrester disconnection device at end of life (in short-circuit).
Care must be taken to minimize the impedance of its circuit (reduction of its
connections to the live conductors and earth, as well as the impedance of the
disconnection device).

In this manner, if the surge arrester begins to conduct, the loads are subjected
at most to the protection voltage U p equal to the residual voltage of the surge
arrester plus the voltage drop in its connections and in the disconnection
device. Hence the importance of a properly constructed installation conform to
proper practices.

Reminder! One metre of cable has an inductance of 1 μH: application of the


formula ∆U = L di/dt with the 8/20 μs wave and a 10 kA current results in a
voltage of approximately 1000 volts peak/metre. Hence the importance of
minimising surge arrester connecting cable length.

Cascading protection devices


When a high amplitude lightning stroke occurs, the importance of the current
flown off by the surge arrester means that protection voltage may exceed the
withstand voltage of sensitive devices.

These devices must therefore be protected by use of “secondary” surge


arresters (see fig. 3).
To ensure their effectiveness, these “secondary” surge arresters must be
installed more than 10 meters away from the “main” surge arrester. This
connection is important as cable impedance performs a decoupling between the
two protection levels (as shown in figure 3).
Figure 3 – Example of two surge arresters installed in cascade

Where:

 This length was defined for surge arresters equipped with varistors
 * – surge arrester disconnection device at end of life (in short-circuit).
It is important to bear in mind that the supply of many electrical devices, and in
particular electronic devices, is protected against surge by differential mode
varistors. “Cascading” is thus also applied between the surge arrester of the
installation responsible for protecting the sensitive device and the latter, and
calls for a study of the protection levels.

IMPORTANT NOTES //
1. Presence of surge arresters on the MV close to those placed on the LV is
another case of “cascading” using the differences in arcing voltage of MV
and LV surge arresters and the decoupling performed by the MV/LV
transformer.
2. When electronic devices containing common or differential mode filters are
connected near the installation origin, these filters must be able to withstand
the protection voltage Up (see fig. 3).

Cohabitation of residual current devices and surge


arresters
In installations whose origin is equipped with an residual current device (RCD),
it is preferable to place the surge arrester upstream of the latter (see fig. 4a).

 * – surge arrester disconnection device at end of life (in short-circuit)


 ** – residual current device for protection of people, in this case associated
with the disconnection device.
a) Simplest connection (forbidden in France by EDF)

Figure 4a -Simplest connection of a surge


arrester on the installation of a LV consumer, for electrical distribution in TT
earthing system (forbidden in France by EDF)
However, some electrical utilities do not allow intervention at this distribution
level. This is the case of LV consumers in France. A time-delayed or selective
RCD is then necessary to prevent current flow off via the surge arrester from
causing nuisance tripping (see fig. 4b).

b) Recommended connection: also enables discrimination with high


sensitivity RCDs placed on the outgoings
Figure 4b – Recommended
connection of a surge arrester on the installation of a LV consumer, for
electrical distribution in TT earthing system (also enables discrimination with
high sensitivity RCDs placed on the outgoings)
Likewise, if surge arresters have to be installed near high sensitivity RCDs (10
or 30 mA), they must be placed just upstream of them.

To conclude…
In tertiary, industry and the domestic sector, installation of a surge arrester must
always comply with the following requirements:

Requirement #1 All surge arresters must be equipped with a disconnection


device (de-energised when it is short-circuited): a fuse or a circuit-breaker. This
device must be adapted to the surge arrester and its connections (by its rating
and tripping or blowing curve) as well as to its installation point (by its breaking
capacity).
As a rule, manufacturers specify the characteristics of the device to be
provided for each type of surge arrester.

Requirement #2 The connections from the surge arrester to the live conductors
and from the surge arrester to the main equipotential bonding must be as short
as possible: 50 cm is the maximum value.
Requirement #3 Surge arrester cabling must not create a loop surrounding
devices sensitive to electromagnetic phenomena (electronic clocks,
programmers, etc.).
Note: Both for initial choice of surge arrester and for its installation
requirements, it is vital to consult the manufacturers’ technical documents.
Reference // LV surges and surge arresters LV insulation co-ordination by C.
Séraudie (Schneider Electric)

You might also like