Cat 4607 en
Cat 4607 en
Cat 4607 en
4 pole
10 to 3200 kVA - 50 Hz / 12.5 to 3900 kVA - 60 Hz
Summary
Page
3 - DERATING............................................................................................................................................ 3
4 - WINDING............................................................................................................................................... 4
5 - GENERAL FEATURES......................................................................................................................... 4
8 - CONNECTIONS ................................................................................................................................... 6
8.1 - Standard winding 6 (rating 50 Hz : 380 - 400 - 415 V / 220 - 230 - 240 V)...................................................7
8.3 - Standard winding 7 (rating 50 Hz : 415 - 440 / 208 - 220 / 240 - 254 V)......................................................9
8.10 - Standard winding 6 (rating 60 Hz : 380 - 416 V / 190 - 208 / 220 - 240 V)...............................................15
8.11 - Standard winding 6 (rating 60 Hz : 440 - 480 V / 220 - 240 / 254 - 277 V)...............................................16
8.12 - Standard winding 8 (rating 60 Hz : 380 - 416 V / 190 - 208 / 220 - 240 V)...............................................17
Technical definitions
INTRODUCTION
- This catalogue is a summary of ratings for the PARTNER range at the most common voltages around the world.
For other voltages, please consult LEROY-SOMER.
1 - RATING DEFINITION
• Continuous rating S1/ 40°C - IEC 60034-1 definition
- Running at constant load limited to the insulation class ; permissible overload 1 h every 12 hours.
• Stand-by rating 40°C
- Running at constant load without over load, for a limited duration of maximum 500h/year, with a permissible increase of the
temperature rise above class H.
• Stand-by rating 27°C
- Same conditions than stand-by duty 40°C but with acceptance of a lower ambient temperature (27°C) that allows to increase the
rating and the temperature rise for the same level of temperature in the alternator.
140 B
105 K
105 K
3 - DERATING
Multiply nominal rating by derating factor from following chart.
Ambiant temperature
ALTITUDE 25 °C 40 °C 45 °C 50 °C 55 °C 60 °C (*)
0 to 1000 m 1.045 1 0.97 0.94 0.91 0.88
1001 to 1500 m 1.01 0.97 0.94 0.91 0.88 0.85
1501 to 2000 m 0.98 0.94 0.91 0.88 0.86 0.83
2001 to 2500 m 0.95 0.91 0.88 0.86 0.83 0.8
2501 to 3000 m 0.91 0.87 0.84 0.82 0.79 0.77
Power factor
Lagging Power Factor 1 0.9 0.8 0.7 0.6
Technical definitions
4 - WINDINGS
LEROY SOMER proposes various 2/3 pitch windings for rating optimisation according to the required voltage and frequency.
- Standard winding N° : 6
- Optimized winding N° : 7, 8, 9, 10, 22, 23 and 52.
- Windings M or M1, dedicated single phase windings.
“S” after the winding number means “6 leads” ex : 6S.
“T” or “+” after winding give an information about the saturation level of the stator.
5 - GENERAL FEATURES
5.1 - compliance with internationally recognized standardS
4 Pole PARTNER Alternators are in compliance to the main international standards and regulations :
- IEC 60034, NEMA MG 1.22, ISO 8528/3, CSA, UL 1446, UL 1004B on request and depending on voltages, marine
regulations, etc. It can be integrated into a CE marked generator.
Alternators are designed, manufactured and marketed in an ISO 9001 and ISO 14001 environments.
- Voltage regulators :
4 Pole PARTNER Alternators are fitted with reliable and performant AVR’s, adapted to LS excitation systems, powered by
transistors and fulfilling perfect regulation.
Available excitation systems depending on alternator frames, are indicated in rating tables.
TYPE LSA 40 LSA 42.3 LSA 43.2 LSA 44.2 LSA 46.2 LSA 47.2 LSA 49.1 LSA 50.2 LSA 51.2 LSA 53.1 LSA 54
Shunt
dedicated R 220 R 220 R 251 R 251 - - - - - - -
1 phase
AREP / PMG R 438* R 438 R 438 R 438 R 450 R 450 R 450 R 450 R 449 R 449 R 449
* AREP only.
- Frequency :
4 Pole PARTNER alternators may operate either 50 or 60 Hz. The standard winding (code 6) is suitable both for 50 and 60 Hz. For
dedicated windings, see specific table or consult factory.
- Power factor :
4 Pole PARTNER alternators are designed to operate between 0.8 and 1 power factor.
A derating is necessary below 0.8 power factor (see derating chart).
- Waveform :
Total harmonic content or distorsion (THC or THD), line to line, at no load or full rated linear and balanced load is less than 4%.
THF (according to IEC) is less than 2%. TIF/Telephone influence factor according to NEMA is less than 50.
- Transient features :
Transient voltage dip for rated step load at 0.8 power factor is less than 18 %.
Recovery time for a 20 % transient voltage dip is less than 0.5 s.
- Parallel operation :
All 4 Pole PARTNER alternators can operate in parallel with other alternators or with the mains, when they are equipped with the
appropriate devices (AVR, current transformer...).
- Overload acceptance :
4 Pole PARTNER Alternators can be overloaded according to NEMA
- Single Phase operation :
4 Pole PARTNER Alternators from LSA 40 up to LSA 46.2 can be reconnected for single phase use. The single phase rating is
given in the various alternator data sheets. Alternators from LSA 40 up to LSA 44.2 can be supplied with a dedicated single phase
winding. (Code M or M1).
Technical definitions
- EMI suppression :
All the alternators delivered to the European Community are provided with an EMI suppression device in accordance with EN
55011, group 1, class B. This equipment is optional for other areas.
7 - Product desCRIPtion
The machine name is defined according to various criteria (see below).
Example of description for :
LSA 49.1 M6 C6/4
• LSA : Leroy-Somer Alternator
• 49.1 : Frame size
• M6 : Core length
• C : Excitation system (C: AREP / J: SHUNT+ PMG)
• 6/4 : winding number / number of poles.
Products and materials shown in this catalogue may, at any time, be modified in order to follow the latest technological developments, improve the design or change the
conditions of utilisation. Their description cannot in any case engage Leroy-Somer’s liability. The values indicated are typical values.
Voltage reconnections
8 - CONNECTIONS
Connections
star delta series star series delta parallel star double delta open delta
Number of wire 6 6 12 12 12 12 12
Standard Winding 380-400-415V 220 - 240V 380-400-415V 220 - 240V 190 - 208V 220 - 240V 220 - 240V
6 (page 7) (page 7) (page 7) (page 7) (page 7) (page 14) (page 14)
Specific Winding 415 - 440 V 240 - 254 V 415 - 440 V 240 - 254 V 208 - 220 V
7 240 - 254 V 240 - 254 V
(page 9) (page 9) (page 9) (page 9) (page 9) (consult factory) (consult factory)
(upon request)
Specific Winding
22 or 23 550 V (page 11) 550 V (page 11) - - - -
600 V (page 12) - 600 V (page 12)
(upon request)
Specific Winding
10 or 52 660 - 690 V 660 - 690 V - - - -
(page 13) - (page 13)
(upon request)
Specific Winding M Dedicated 1 phase 230 V (page 14) 115 V (page 14)
(upon request)
Connections
star delta series star series delta parallel star double delta open delta
Number of wire 6 6 12 12 12 12 12
Standard Winding 380 - 480 V 220 - 277 V 380 - 480 V 220 - 277 V 190 - 240 V 220 - 240 V 220 - 240 V
6 (page 15/16) (page 15/16) (page 15/16) (page 15/16) (page 15/16) (page 19) (page 19)
Specific Winding
-
7 - - -
- - -
(upon request)
Specific Winding 380 - 416 V 220 - 240 V 380 - 416 V 220 - 240 V 190 - 208 V 220 - 240 V 220 - 240 V
8 (consult factory) (consult factory)
(page 17) (page 17) (page 17) (page 17) (page 17)
(upon request)
OPTION : 12 wires
LSA 49.1 S3 - C6/4 Option 12 580 522 610 641 580 522 610 641 580 522 610 641
LSA 49.1 M5 - C6/4 Option 12 680 612 715 751 680 612 715 751 680 612 715 751
LSA 49.1 M7 - C6/4 Option 12 725 655 760 800 725 655 760 800 725 655 760 800
LSA 49.1 L9 - C6/4 Option 12 860 774 903 948 860 774 903 948 860 774 903 948
LSA 49.1 L11 - C6/4 Option 12 950 855 1000 1045 950 855 1000 1045 950 855 1000 1045
OPTION : 12 wires
LSA 49.1 S3 - C6/4 Option 12 560 510 590 616
LSA 49.1 M5 - C6/4 Option 12 650 590 690 715
LSA 49.1 M7 - C6/4 Option 12 700 635 735 770
LSA 49.1 L9 - C6/4 Option 12 770 700 810 845
LSA 49.1 L11 - C6/4 Option 12 900 810 945 990
Use winding 7 for parallel operation with main
OPTION : 12 wires
LSA 49.1 S3 - C7T/4 Option 12 580 540 620 640 580 540 620 640
LSA 49.1 S4 - C7/4 Option 12 620 570 660 680 620 570 660 680
LSA 49.1 L8 - C7/4 Option 12 800 730 860 900 800 730 860 900
Winding 2 or 7 : min. 415 V - max. 460 V / Winding 7 T : min. 400 V - Max. 440 V
*12 wires only
**not available for 51.2
500 - 525 V
1500 R.P.M. - 3 Phase - P.F. 0.8
(1) Winding 9 will not work in parallel operation with the mains, when the voltage is 525 V.
For parallel operation with the mains, consult Leroy-Somer.
550 V
1500 R.P.M. - 3 Phase - P.F. 0.8
600 V
1500 R.P.M. - 3 Phase - P.F. 0.8
660 - 690 V
1500 R.P.M. - 3 Phase - P.F. 0.8
RATINGS 50 Hz
M dedicated 1 phase M dedicated 1 phase
series (4 wires) parallel (4 wires)
230 V 115 V
1500 R.P.M. - 1 Phase - P.F. 1
OPTION : 12 wires
LSA 49.1 S3 - C6/4 Option 12 590 531 620 650 640 576 672 706
LSA 49.1 M5 - C6/4 Option 12 740 666 777 816 790 711 830 871
LSA 49.1 M7 - C6/4 Option 12 850 765 893 937 910 820 956 1000
LSA 49.1 L9 - C6/4 Option 12 880 792 924 970 940 846 987 1036
LSA 49.1 L11 - C6/4 Option 12 960 865 1010 1056 1040 940 1095 1145
*12 wires only - (1) Use winding 8 for parallel operation with the main - **not available for 51.2
OPTION : 12 wires
LSA 49.1 S3 - C6/4 Option 12 670 603 705 740 720 648 756 795
LSA 49.1 M5 - C6/4 Option 12 830 747 872 915 870 783 915 960
LSA 49.1 M7 - C6/4 Option 12 930 837 976 1023 930 837 976 1023
LSA 49.1 L9 - C6/4 Option 12 980 882 1029 1080 1025 925 1080 1130
LSA 49.1 L11 - C6/4 Option 12 1080 975 1135 1190 1165 1054 1220 1280
*12 wires only - **not available for LSA 51.2
Winding 9 : min. 570 V - max. 625 V / Winding 9+ : min. 600 V - max. 660 V / Winding 9 TS : min.545V - max 600 V.
RATINGS 60 Hz
M / M1 dedicated 1 phase M / M1 dedicated 1 phase
series (4 wires) parallel (4 wires)
240 V 120 V
1800 R.P.M. - 1 Phase - P.F. 1
EGYPT www.leroy-somer.com
RUSSIA
UNITED KINGDOM
LEROY-SOMER LTD
MOTEURS LEROY-SOMER LEROY-SOMER DIVISION