Assignment-9question and Solution
Assignment-9question and Solution
(a) 59kN/m2
(b) 88kN/m2
(c) 117kN/m2
(d) 147kN/m2
Q 6: A rectangular isolated footing of size 2000mm × 3000mm is made to transfer the
characteristic load, P =750kN and M =50kNm to the ground. Consider weight
of footing as 10% of the characteristic axial load. The minimum pressure under
foundation will be developed as
(a) 121kN/m2
(b) 151kN/m2
(c) 181kN/m2
(d) 211kN/m2
Q 7: A rectangular isolated footing of size 2000mm × 3000mm is made to transfer the
characteristic load, P =750kN and M =50kNm to the ground. Consider weight of
footing as 10% of the characteristic axial load. Take longer dimension along the
plane of action of the moment. The maximum pressure under foundation will be
developed as
(a) 77kN/m2
(b) 116kN/m2
(c) 154kN/m2
(d) 193kN/m2
Q 8: A square isolated footing for a square column of size 300mm × 300mm is made
to transfer the characteristic load, P =750kN to the ground. Consider weight of
footing as 10% of the characteristic axial load. The safe bearing capacity of soil is
150 kN/m2 . The dimension of the square footing should not be less than
(a) 940mm
(b) 1410mm
(c) 1880mm
(d) 2350mm
CE23 : Design of RC Structures Assignment-9 July-October, 2017 : Week-9
Answers
1. (b) face of the column
3. (c) a distance d/2 (half of the effective depth) from the face of the column
5. (d) 147kN/m2
6. (a) 121kN/m2
7. (c) 154kN/m2
8. (d) 2350mm
9. (b) 382kN/m2
Answer : 2. (d) a distance d (effective depth) from the face of the column
CE23 : Design of RC Structures Assignment-9 July-October, 2017 : Week-9
Answer : 3. (c) a distance d/2 (half of the effective depth) from the face of the column
CE23 : Design of RC Structures Assignment-9 July-October, 2017 : Week-9
(a) 59kN/m2
(b) 88kN/m2
(c) 117kN/m2
(d) 147kN/m2
Solution:
(i) Width of footing, B=2000 mm
(a) 121kN/m2
(b) 151kN/m2
(c) 181kN/m2
(d) 211kN/m2
Solution:
(i) Width of footing, B=2000 mm
(a) 77kN/m2
(b) 116kN/m2
(c) 154kN/m2
(d) 193kN/m2
Solution:
(i) Width of footing, B=2000 mm
=154 kN/m2
Q 8: A square isolated footing for a square column of size 300mm × 300mm is made
to transfer the characteristic load, P =750kN to the ground. Consider weight of
footing as 10% of the characteristic axial load. The safe bearing capacity of soil is
150 kN/m2 . The dimension of the square footing should not be less than
(a) 940mm
(b) 1410mm
(c) 1880mm
(d) 2350mm
Solution:
(i) Width of column, b=300 mm
(a) 286kN/m2
(b) 382kN/m2
(c) 477kN/m2
(d) 573kN/m2
Solution:
(i) Width of column, b=300 mm
Q 10: A square isolated footing (size :1800mm × 1800mm) is made for a square column
of size 300mm×300mm to transfer the characteristic load, P =750kN to the ground.
Consider weight of footing as 10% of the characteristic axial load. The load factor
is taken as 1.5. The overall depth of footing is 350mm. The clear cover is 40mm.
The diameter of reinforcement provided is 12mm. The one-way shear force due to
soil reaction at the required section for design will be equal to
(a) 128kN/m width
(b) 170kN/m width
(c) 213kN/m width
(d) 256kN/m width
Solution:
(i) Dimension of square column, a=300 mm
Q 11: A square isolated footing (size :1800mm × 1800mm) is made for a square column
of size 300mm×300mm to transfer the characteristic load, P =750kN to the ground.
Consider weight of footing as 10% of the characteristic axial load. The load factor
is taken as 1.5. The overall depth of footing is 350mm. The clear cover is 40mm.
The diameter of reinforcement provided is 12mm. The two-way shear force due to
soil reaction at the required section for design will be equal to
(a) 1922kN
(b) 1647kN
(c) 1373kN
(d) 1098kN
Solution:
(i) Dimension of square column, a=300 mm
Q 12: A square isolated footing (size :1800mm × 1800mm) is made for a square column
of size 300mm×300mm to transfer the characteristic load, P =750kN to the ground.
Consider weight of footing as 10% of the characteristic axial load. The load factor
is taken as 1.5. The overall depth of footing is 350mm. The clear cover is 40mm.
The diameter of reinforcement provided is 12mm. The bending moment due to soil
reaction computed at the required section for design will be equal to