Tutorial content
Lesson 5
Analog input signal indication (PVI function block).
Trends CENTUM VP
Trend is a graph of the change in the process variable over time.
Input Indicator Block (PVI) converts the raw analog input (RAW) value to a process variable (PV), in accordance
with a given scale in engineering units.
The task
Apply a PVI block to indicate an analog input pressure signal in the range of 0-40 meters of water column.
http://www.maxplant.ru/article/centum_tutorial_05.php 1/10
11/7/2018 Analog input signal indication (PVI function block). Trends CENTUM VP
Decision
1 Open the IOM editor:
FCS0101> IOM> NODE1> 1AAI141-S
4 Add Link Block> PIO and bind to it an analog input named %% WATER_PRESSURE
http://www.maxplant.ru/article/centum_tutorial_05.php 2/10
11/7/2018 Analog input signal indication (PVI function block). Trends CENTUM VP
9 Character m.vod.st. not listed, so close all editors, open the project properties window and tick the
Manually Register Engineering Unit Symbol:
http://www.maxplant.ru/article/centum_tutorial_05.php 3/10
11/7/2018 Analog input signal indication (PVI function block). Trends CENTUM VP
11 We return to the choice of the symbol of engineering units and find the symbol in the list. M H2O:
http://www.maxplant.ru/article/centum_tutorial_05.php 4/10
11/7/2018 Analog input signal indication (PVI function block). Trends CENTUM VP
14 We start the test function (simulator of the operator’s station and the DCS controller):
FCS> Test Function:
http://www.maxplant.ru/article/centum_tutorial_05.php 5/10
11/7/2018 Analog input signal indication (PVI function block). Trends CENTUM VP
TREND terminal.
Set the upper limit: Gain = 100.0 Set the
lower limit: Bias = 0.0
Set the cycle time: Cycle = 100 seconds
http://www.maxplant.ru/article/centum_tutorial_05.php 6/10
11/7/2018 Analog input signal indication (PVI function block). Trends CENTUM VP
22 We right-click on the PVI block and select the Tuning item from the context menu:
http://www.maxplant.ru/article/centum_tutorial_05.php 7/10
11/7/2018 Analog input signal indication (PVI function block). Trends CENTUM VP
23 Set the boundary settings via the tuning panel of the TREND block:
HH = 35.0
PH = 30.0
PL = 10.0
LL = 5.0
24 Press the [Process alarm] button - the process crashes window opens:
25 Right-click on any alarm message and select the Trend item in the context menu:
http://www.maxplant.ru/article/centum_tutorial_05.php 8/10
11/7/2018 Analog input signal indication (PVI function block). Trends CENTUM VP
26 We independently study the interfaces of all new windows (Test Function, Tuning, Trend, Process alarm,
etc.)
Learn PHP?
srs.myrusakov.ru
Get a free video course on PHP 7. Act!
Yandex.Direct 18+
Yandex.Direct
http://www.maxplant.ru/article/centum_tutorial_05.php 9/10
11/7/2018 Analog input signal indication (PVI function block). Trends CENTUM VP
Learn PHP?
To learn more
http://www.maxplant.ru/article/centum_tutorial_05.php 10/10