Triple Output Power Supply MODELS 6236B AND 6237B
Triple Output Power Supply MODELS 6236B AND 6237B
Triple Output Power Supply MODELS 6236B AND 6237B
Hewlett-Packard
1-1 INTRODUCTION located on the front panel. One voltage control sets the
0 to+6V (or+18V) output and another sets the voltages
1-2 This manual covers two triple output power supply of the 0 to +20V and 0 to -20V outputs simultaneously.
models, the 6236B and 6237B. Both models are com- These dual tracking outputs are made more versatile by the
pact general purpose bench supplies that are particularly provision of a tracking ratio control in addition to the usual
useful for powering developmental IC circuits, both linear voltage control. With the tracking ratio control turned fully
and digital. Unless one model or the other is specifically clockwise to its "fixed" position, the dual outputs have a
identified, all information in this manual applies to both fixed 1:1 tracking ratio. As the ±20V voltage control is
the 6236B and the 6237B. adjusted, the voltage of the negative supply tracks the posi-
tive output within ±1%. Turning the tracking ratio control
away from its fully-clockwise position switches the dual
——— CAUTION ——— tracking outputs into a variable tracking ratio mode. In this
mode the voltage of the negative output can be set lower
Carefully read Sections II and III of this than that of the positive output. The tracking ratio control
manual before attempting to operate the allows the negative supply's output to be set to any value
power supply. between a maximum that is within 10% of the positive
supply's output and a minimum that is less than 0.5 volts.
Once a ratio is established by the tracking ratio control, the
1-3 DESCRIPTION ratio of the positive output voltage to the negative output
voltage remains constant as the ±20V voltage control
1-4 These constant-voltage/current-limiting triple varies the 0 to+20V output over its range.
output supplies combine two 0 to ±20V tracking outputs
rated at 0.5 amps with an additional single output that in 1-7 The front panel also contains a line switch and a
the Model 6236B is rated at 0 to+6 volts and up to 2.5 pilot light, a voltmeter and an ammeter, and a meter
amps, and in the Model 6237B is rated at 0 to +18 volts switch that selects one of the supply's three outputs to be
and 1 amps. The +20V and -20V tracking outputs can monitored on both dual-range meters.
also be used in series as a single 0 to 40V 0.5-amp output.
Connections to the supply's output and to chassis ground 1-8 In addition to the standard 104-to-127Vac 47-to-
are made to binding posts on the front panel. The supply's 63Hz input, three other line voltage options are available for
three outputs share a common output terminal, which is nominal inputs of 100, 220, and 240Vac. The supply is
isolated from chassis ground so that anyone output term- furnished with a permanently attached 5-foot 3-wire ground-
inal can be grounded. ing type line cord. The ac line fuse is in an extractor type
fuseholder on the rear heatsink.
1-5 All outputs are protected against overload and
short-circuit damage.The+18V output in the 6237B and 1-9 SPECIFICATIONS
the ±20V outputs in both models are protected by circuits
that limit the output current to 110% of its nominal maxi- 1-10 Table 1-1 lists detailed specifications for the
mum.The overload protection circuit for the +6V output power supply.
in the 6236B has a current foldback characteristic that
reduces the output current as an overload increases until 1-11 OPTIONS
only 1 amp flows through a short circuit. The 6V output's
current limit depends on the output terminal voltage and 1-12 Options are factory modifications of a standard
varies linearly between 2.75 amps at 6 volts and 1 amp instrument that are requested by the customer. The follow-
at zero volts. ing options are available for the instruments covered by
this manual.
1-1
OPTION NO. DESCRIPTION The user can convert an instrument from one line
voltage option to another by following the instructions
100 Input Power: 87-106Vac,47-63Hz, in paragraph 3-4.
single-phase.
220 Input Power: 191-233Vac,47-63Hz, 1-14 ACCESSORIES
single-phase.
240 Input Power: 208-250Vac,47-63Hz,
1-15 The accessories listed below may be ordered
single-phase.
from your local Hewlett-Packard field sales office either
910 One additional operating and service
with the power supply or separately. (Refer to the list at
manual shipped with the power supply.
the rear of the manual for addresses.)
1-13 Before the supply is shipped from the factory, an HP PART NO. DESCRIPTION
internalline voltage selector switch is set and the proper
fuse installed for the line voltage specified on the order. A 14513A Rack Mounting Kit for mounting one
label on the rear heatsink identifies this line voltage option. 3 1/2" high supply in a standard 19"
relay rack.
1-2
1-16 INSTRUMENT AND MANUAL 1-18 If the serial number on your instrument does not
IDENTIFICATION agree with those on the title page of the manual, Change
Sheets supplied with the manual or Manual Backdating
1-17 Hewlett-Packard power supplies are identified by Changes define the difference between your instrument
a two part serial number. The first part is the serial number and the instrument described by this manual.
prefix, a number-letter combination that denotes the date
of a significant design change and the country of manufac- 1-19 ORDERING ADDITIONAL MANUALS
ture. The first two digits indicate the year (10 = 1970,
11= 1971, etc.) the second two digits indicate the week, 1-20 One manual is shipped with each power supply
and the letter "A" designates the U.S.A. as the country of unless Option 910 is ordered for each extra manual. Addi-
manufacture. The second part is the power supply serial tional manuals may be purchased from your local Hewlett-
number. A different sequential number is assigned to each Packard field office (see the list at the rear of this manual
power supply, starting with 00101. for addresses). Specify the model number, serial number
prefix, and the HP Part Number provided on the title page.
1-3
SECTION II
INSTALLATION
2-9 Location
2-10 This instrument is air cooled. Sufficient space Figure 2-2. Rack Mounting, One Unit
should be allotted so that a free flow of cooling air can
reach the rear of the instrument when it is in operation. It
should be used in an area where the ambient temperature
does not exceed 40°C (up to 55°C with derating).
2-2
SECTION III
OPERATING INSTRUCTIONS
For the Model 6237B, substitute+18V 3-5 To convert the supply from one line voltage option
for +6V in the following steps. to another, the following three steps are necessary:
3-1
3-10 Overload Protection Circuits
3-7 This power supply can be operated individually 3-13 +18Volt Current Limit (Model 6237B). The +18-
or in parallel with another supply (see paragraph 3-19). All volt output of the Model 6237B is protected by a fixed cur-
output terminals are isolated from ground. The ±20V and rent limit circuit that operates at 1.1 A (110% of its maxi-
+6V or +18V outputs use a single common output mum rated output). The circuit is similar to the ones in the
terminal. This common (COM) terminal or anyone of the ±20-volt supplies. (See paragraph 5-47 for calibration
other output terminals may be grounded to the chassis at instructions.)
the front panel ground terminal ( in Figure 3-1 ), or all
outputs may be left floating. Loads can be connected
3-14 Operation Beyond Rated Output
separately between each of the 0 to 20V output terminals
and the COM terminal, or between the -20V and the +20V
3-15 The supply may be able to provide voltages and
terminals for a 0 to 40V output.
currents greater than its rated maximum outputs if the line
voltage is at or above its nominal value. Operation can ex-
3-8 Tracking Ratio Control tend into the shaded areas on the meter faces without
damage to the supply, but performance cannot be
3-9 With the TRACKING RATIO control in the FIXED guaranteed to meet specifications. If the line voltage is
position, the voltage of the -20V supply tracks that of the maintained in the upper end of the input voltage range,
+20V supply within 1% for convenience in varying the however, the supply probably will operate within its
symmetrical voltages needed by operational amplifiers specifications.
and other circuits using balanced positive and negative
inputs. Turn the TRACKING RATIO control counterclock-
wise out of the FIXED position to set the voltage of the - 3-17 Connect each load to the power supply output
20V supply lower than that of the +20V supply. The terminals using separate pairs of connecting wires. This
negative supply can be set from a minimum of less than minimizes mutual coupling between loads and takes full
0.5 volts to a maximum within 10% of the +20V advantage of the low output impedance of the supply.
supply's output. Once this is done, the ±20V VOLTAGE Load wires must be of adequately heavy gauge to maintain
control still controls both outputs and maintains a satisfactory regulation at the load. Make each pair of
constant ratio between their voltages. connecting wires as short as possible and twist or shield
3-2
them to reduce noise pick-up. If shielded wire is used, 3-24 Reverse Current Loading. An active load connected
connect one end of the shield to the power supply to the power supply may actually deliver a reverse current to
ground terminal and leave the other end unconnected. the supply during a portion of its operating cycle. An external
source cannot be allowed to pump current into the supply
3-18 If load considerations require locating output without risking loss of regulation and possible damage to the
power distribution terminals at a distance from the power output capacitor. To avoid these effects, it is necessary to
supply, then the power supply output terminals should be preload the supply with a dummy load resistor so that the
connected to the remote distribution terminals by a pair of power supply delivers current through the entire operating
twisted or shielded wires and each load should be cycle of the load device.
connected to the remote distribution terminals separately.
3-25 Reverse Voltage Protection. Internal diodes con-
3-19 Parallel Operation nected with reverse polarity across the output terminals
protect the output electrolytic capacitors and the driver
3-20 Two or more power supplies can be connected in transistors from the effects of a reverse voltage applied
parallel to obtain a total output current greater than that across a supply output. Since series regulator transistors
available from one supply. The total output current is the cannot withstand reverse voltage either, diodes are also
sum of the output currents of the individual supplies. The connected across them. When operating supplies in
output voltage controls of one power supply should be set parallel, these diodes protect an unenergized supply that is
to the desired output voltage, and the other supply set for in parallel with an energized supply.
a slightly larger output voltage. The supply set to the
lower output voltage will act as a constant voltage source,
while the supply set to the higher output will act as a
current-limited source, dropping its output voltage until it
equals that of the other supply. The constant voltage
source will deliver only that fraction of its rated output
current necessary to fulfill the total current demand.
3-3
SECTION IV
PRINCIPLES OF OPERATION
4-3 The two primary windings of the power transformer 4-8 The 0 to -20-volt regulator is, in turn, similar to the
are connected in one of four different ways by setting the +20-volt regulator except that it resembles a
two slide switches mounted on the circuit board. These complementary mirror image of the latter. The output
switches select one of the nominal ac input voltages for voltages of the +20volt and -20-volt supplies are both set
which the supply is designed: 100V, 120V, 220V, or 240V. by the same front panel control and track each other within
1% in the fixed tracking ratio mode. Precise tracking of the
4-4 The transformer secondaries, together with two outputs is achieved by controlling the positive output
rectifiers and capacitor filters, provide raw dc for the three conventionally and using that output as the reference
output regulator circuits and for another regulator that pro- voltage for the negative output.
vides reference and bias voltages to the output regulators.
4-9 The 0 to +18-volt regulator in the Model 6237B
is similar to the +20-volt regulator. It has a fixed current
4-5 By comparing its output to a high-stability refer-
limit at 110% of its 1.0 amp output.
ence, the 0 to +6-volt regulator (6236B) or 0 to +18-
volt regulator (6237B) holds its output voltage at the 4-10 The reference and bias supply provides reference
value determined by a front panel control. Any error in and bias voltages for the output regulators.
the actual output as compared to the desired output is
amplified by an operational amplifier and applied as 4-11 The turn-on/turn-off control circuit prevents output
feedback to control the conduction of a series regulator transients when the supply is turned on or off. It does this by
transistor. As a result, the voltage across the series delaying the application of certain bias and reference voltages
transistor varies so as to hold the output voltage constant at turn-on and removing them shortly after turn-off.
at the desired level. The high gain of the voltage
comparison amplifier and the stability of the reference 4-12 A three-position meter switch selects which of
voltage ensure that input voltage or load current the supplies has its output voltage and current indicated
variations have little effect on the output voltage. on the front panel meters. The proper range of the dual-
range meters is selected automatically
4-6 The 0 to +6-volt output in the Model 6236B is
protected by a current foldback limiter to minimize 4-13 DETAILED CIRCUIT DESCRIPTION
dissipation in the series regulator transistor during
overloads. In a current foldback circuit, the current limit 4-14 0 To +20-Volt Regulator
depends on the output terminal voltage and in this regulator
ranges from 2.75A±5% at 6 volts to 1A±15% with the 4-15 Voltage Comparison Amplifier. The voltage com-
output shorted. (An output of 2.75A is 110% of the 2.5A parison amplifier in the +20-volt supply controls the conduc-
rated maximum at 6 volts.) The operating region of the tion of series regulator transistor Q1 so that the voltages at
+6-volt regulator output is enclosed by a heavy line in the two inputs of the amplifier remain equal. A fixed voltage
Figure 3-3. If the operating point reaches the diagonal divider holds its inverting input (U1-2) at -16mV. Its non-
current limit line, a decrease in load resistance moves the inverting input (U1-3) monitors the output voltage in series
operating point down the line, reducing the output voltage
4-1
with the voltage across R1. Since R2 is connected between and returning control to the voltage comparison amplifier.
the -6.2V reference supply and a point that feedback action
holds near -16mV, its current remains constant. This 4-20 Turn-On/Turn-Off Control. When the power supply
current flows through R1 to produce a voltage drop across is turned on or off, Q15 in the turn-on control circuit with-
R1 proportional to its resistance setting, thus the output holds turn-on bias from Q1 while the regulator bias voltages
voltage of the supply is proportional to the resistance are too low. This prevents an output voltage transient from
setting of R1. At the output of the voltage comparison occurring before the amplifiers are properly biased. The
amplifier (U1-1), a positive voltage change corresponds to a output of the -6.2V reference supply is also temporarily
decrease in the conduction of Q1. held at a low voltage by Q14, which conducts to short that
output.
4-16 CR2 and CR3 protect the input of the amplifier
against transient overloads, C2 and R4 speed up loop 4-21 Circuit Protection Components. Diodes CR1, CR7,
response time, and C4 and R12 stabilize the supply's and CR9 each protect the +20-volt supply from specific
high frequency characteristics. hazards. Output diode CR1 protects the supply components
if a reverse voltage is applied to the output terminals. A
common way for this to occur is for an unenergized supply
4-17 OR-Gate. To permit either the voltage comparison
to be connected in series with another that is energized. If
amplifier or the current comparison amplifier to control the
the output voltage is turned down quickly while a large
series regulator transistor, the outputs of both amplifiers
capacitor is connected across the output, CR7 protects
are connected to the base of driver Q2 through an OR-gate
driver Q2 from excessive dissipation by shunting some of its
composed of CR5 and CR6. CR5 is normally reverse
base current to common. The series regulator diode, CR9,
biased by a negative output from the current comparison
protects the series regulator transistor from reverse voltage.
amplifier, permitting the voltage comparison amplifier to
Reverse series regulator voltage could occur if a deenergized
drive Q2 through CR6. An overload drives the output of
supply were connected in parallel with an energized one.
the current comparison amplifier positive, forward biasing
CR5 and reducing the supply output. When the overload is
removed, CR5 is reverse biased again and the voltage com-
4-22 0 To -20-Volt Regulator
parison amplifier resumes control of the output. 4-23 Instead of using an NPN driver and a PNP series
regulator in the negative output line as in the +20-volt
4-18 Driver and Series Regulator. The -12.4V output of regulator, the -20-volt regulator uses a PNP driver and an
the bias supply provides the turn-on bias for series NPN series regulator in the positive output line. The -20-
regulator transistor Q1. Its complete current path includes volt regulator circuit is the complementary equivalent of
Q15, CR59, R 14, and Q1, and returns to common the +20-volt circuit in other respects, as well. Their
through current monitoring resistor R8. (It is because this current limit circuits operate similarly. At the outputs of
bias current flows through R8 that the output ammeter the current and voltage comparison amplifiers in the -20-
requires the zero offset bias circuit described in paragraph volt circuit, a negative voltage change corresponds to a
4-43.) Through the OR-gate, either the voltage or the decrease in series regulator conduction. The turn-on bias
current comparison amplifier controls the conduction of for its series regulator transistor, Q3, is supplied from a
driver Q2, which regulates the flow of turn-off bias positive voltage source, the +7.5V bias supply, and is
through Q1's base-emitter circuit. The algebraic sum of the switched on and off by Q13 in the turn-on control circuit.
nearly constant turn-on bias through R14 and the variable
turn-off bias through Q2 controls the conduction of series 4-24 The -20-volt supply uses the output of the +20-
regulator transistor Q1. volt supply as its reference voltage. As a result, both
4-19 Current Limit Circuit. In the +20-volt regulator, outputs are set by a single front panel control and track
the current comparison amplifier compares the voltage each other with in 1% in the fixed tracking ratio mode.
across current monitoring resistor R8 to the fixed voltage Two resistors in resistor network Z1 are connected in
across part of current limit adjust potentiometer R6. The series between the +20volt and -20-volt outputs. These
current limit adjustment is set so that the input voltage to resistors are closely matched in resistance and temperature
the current comparison amplifier is negative in the normal coefficient so that the voltage across each is exactly half
operating region, but becomes zero when the output of the total. The midpoint of this divider is connected to
current increases to 0.55 amps. When the amplifier's the non-inverting input of the -20-volt supply's voltage
input voltage reaches zero, it takes control of the comparison amplifier. The amplifier's inverting input is
regulator output voltage and reduces it as necessary to connected to common through R32 to hold it at zero volts.
keep the output current from exceeding 0.55 amps. The amplifier keeps its differential input voltage at zero by
When the overload is removed, the output of the current matching the output voltage of the -20-volt supply to that
comparison amplifier goes negative, reverse biasing CR5 of the +20-volt supply.
4-2
4-25 In the variable tracking ratio mode, the tracking input (U3-5), which is held at -305mV. The negative am-
ratio control connects a fixed resistor in parallel with plifier output that results is clamped by CR44 and reverse
the upper part and a rheostat (the variable tracking ratio biases OR-gate diode CR45, leaving the voltage comparison
control) in parallel with the lower part of the voltage amplifier in control of the supply's output. If the load resis-
divider that forms the -20-volt reference. Turning the tance is decreased, the higher output current increases
control counter- clockwise reduces the resistance of the ER48 until the algebraic sum of ER48 and ER46 makes the
rheostat and lowers the voltage of the negative output. current comparison amplifier's inverting input slightly more
negative than the -305mV potential on its non-inverting in-
4-26 0 To +6-Volt Regulator (Model 6236B) put. When this happens, the output of this amplifier goes
positive and forward biases CR45. Since the current through
4-27 Except for differing component designations and CR45 tends to reduce the output of the supply, the output
values, paragraphs 4-15 through 4-18,4-20, and 4-21, of the voltage comparison amplifier goes negative in oppo-
which describe the voltage comparison amplifier, OR-gate, sition to this change and reverse biases CR46 to leave the
driver, series regulator, turn-on control, and circuit current comparison amplifier in control of the output. Now
protection components of the +20-volt regulator circuit, that the current comparison amplifier is in control and for as
also apply to the +6-volt regulator. The only difference in long as the overload remains, the supply's output voltage
circuit operation lies in the control of the current and current vary so as to maintain this amplifier's differen-
comparison amplifier, and thus the type of current limit the tial input signal near zero volts. This results in the output
supply has. current limit characteristics shown in Figure 3-3.
4-28 Current Foldback Circuit. (For this discussion
refer to the Figure 7-1 schematic and to Figure 4-1.) The
differential input signal to the current comparison amplifier 4-30 If we assume for example that the voltage control
is the algebraic sum of three circuit voltages: is set for 5 volts and the load resistance is slowly
1.The voltage across R49. ER49 remains constant at decreased, the supply goes into current limit at about
-305mV. 2.47 amps. Here is why it occurs at that value. At a 5-
2. The voltage across the lower part of R46 (see volt supply output, ER46 is 5/6 of 440mV, or 367mV. In
Figure 4-1). ER49 is proportional to the regulator order for the algebraic sum of ER46 and ER48 to go as far
output voltage and equals 440mV when the negative as -305mV and drive the amplifier output
supply output is 6 volts. positive, ER48 must reach -672mV. Once ER48 reaches
3. The voltage across current monitoring resistor this value, the current comparison amplifier controls the
R48. ER48 is proportional to the sum of the series regulator transistor so as to prevent ER48 (and thus
regulator output current and the 0.22A bias the supply's output current) from increasing further. At
current that flows through R54 and R48. 0.25 ohms, R48 develops -672mV at 2.69 amps. Since
0.22 amps of the current through R48 is bias current for
Q7, the nominal current limit corresponding to a 5-volt
output is 2.69 amps minus 0.22 amps, or about 2.47
4-3
values, paragraphs 4-15 through 4-21, which describe the 4-39 Turn-On/Turn-Off Control Circuit
voltage comparison amplifier, OR-gate, driver, series regu-
lator, current limit circuit, turn-on control, and circuit 4-40 Immediately after the supply is energized and
protection components of the +20-volt regulator circuit, until the output of the -12.4-volt regulator reaches about
also apply to the +18-volt regulator. In the +18-volt -9 volts, the turn-on control circuit withholds turn-on bias
regulator, as in the +20-volt regulator, the turn-on bias from series regulator transistors Q1, Q3, and Q7 and holds
current for the series regulator transistor is switched on and the -6.2V reference at a low value. This prevents an output
off by Q15 in the turn-on control circuit to prevent output voltage transient by ensuring that the operational amplifiers
voltage transients. are energized and other essential bias voltages are present
before the series regulator transistors are turned on. The
circuit also prevents an output transient when the supply is
turned off by removing the turn-on bias from the series
4-35 Reference and Bias Supply
regulators and shorting the -6.2V reference supply as the
4-36 The reference and bias supply powers the voltage of the -12.4 V supply falls below -9 volts.
operational amplifiers and provides the bias and reference
voltages used throughout the supply. A shunt zener 4-41 Q13 switches the bias to the -20-volt regulator
regulates its +7.5V output. A series transistor regulates its on and off, Q14 switches the short across the -6.2-volt
-12.4 V output, using 6.2-volt zener VR1 as its voltage reference supply, and Q15 switches the bias to the +20-
reference. The -12.4V output provides a constant current to volt and +6-volt or +18-volt regulators. Q15 remains
VR1, which is the primary voltage reference for the entire turned off until VR2 conducts at 9 volts to switch it on.
supply. While Q15 is off, it holds Q13 biased off and Q14 on;
when Q15 conducts, it turns Q13 and Q14 off.
4-37 Two equal resistors are connected in series
across the -12.4V output. To regulate this output,
voltage comparison amplifier U4 compares the voltage
4-42 Meter Circuits
across one of these resistors to the -6.2V reference and
controls the conduction of series regulator Q11 through 4-43 Voltmeter. Two of the resistors in resistor
driver Q12. The voltage drop across Q11 is controlled network Z1 are range resistors for the voltmeter. The
by feedback so that the voltages at the two inputs of U4 accurate ratio of these resistors permits a single calibration
remain equal. Driver Q12 controls Q11 by shunting part potentiometer, R58 to adjust both ranges simultaneously.
of the base bias supplied by R68.
4-44 Ammeter. The range switch connects the
ammeter across the current monitoring resistor of a supply:
4-38 During turn-on, the -6.2V reference supply is R48 in the +6-volt or +18-volt supply, R8 in the +20-volt
temporarily shorted by Q14 in the turn-on control circuit. supply, or R28 in the -20-volt supply. Each of these
By trying to match this low reference, Q11 is initially turned resistors conducts a constant bias current for its series
off. While Q11 is turned off, R69 bypasses current to the regulator transistor in addition to the supply's output
-12.4 V output until the output reaches -9 volts and the current. If no compensation were used, this additional
turn-on control circuit removes the short from the reference current would raise the indicated output by up to 8% of full
and enables the -12.4-volt regulator to operate normally. scale. The resistor networks connected to each range of the
ammeter selector switch apply a bias to the meter to offset
this error. R59 calibrates all ammeter ranges.
4-4
SECTION V
MAINTENANCE
5-2 Upon receipt of the power supply, the performance 5-6 PERFORMANCE TEST
test of paragraph 5-6 can be made. This test is suitable for
incoming inspection. Section III contains a quick but less
5-7 The following test can be used as an incoming
comprehensive checkout procedure that can be used in lieu
inspection check and appropriate portions of the test can
of the performance test if desired.
be repeated to check the operation of the instrument after
repairs. If the correct result is not obtained for a particular
5-3 If a fault is detected in the power supply while check, proceed to the troubleshooting procedures of para-
making the performance test or during normal operation, graph 5-32.
proceed to the troubleshooting procedure in paragraph 5-32.
After troubleshooting and repair, repeat the performance
test to ensure that the fault has been properly corrected and
———CAUTION———
that no other faults exist. Before performing any mainte-
nance checks, turn on the power supply and allow a half
Before applying power to the supply, make
hour warm-up.
certain that its line voltage selector switch
(S3) is set for the line voltage to be used. (See
5-4 TEST EQUIPMENT REQUIRED CAUTION notice in paragraph 3-2 for addi-
tional information on S3.)
REQUIRED RECOMMENDED
TYPE CHARACTERISTICS USE MODEL
Resistive Value: See paragraph 5-11. Power supply load James G. Biddle
Loads Tolerance: ±5% resistor (fixed resistor ("Lubri-Tact"
or rheostat). Rheostat)
Current Value: See paragraph 5-13. Measure output current Simpson Portable
Sampling Accuracy: 1% (minimum) Shunt, 06703.
Resistor (Shunt)
5-1
5-8 General Measurement Techniques the sampling resistor by its ohmic value. The total
resistance of the series combination should be equal to
5-9 Connecting Measuring Devices. To achieve valid the full load resistance as determined in the preceding
results when measuring the load effect, PARD (ripple and paragraphs. Of course, if the value of the sampling
noise), and transient recovery time of the supply, resistor is very low when compared to the full load
measuring devices must be connected as close to the resistance, the value of the sampling resistor may be
output terminals as possible. A measurement made across ignored. The meter shunt recommended in Table 5-1, for
the load includes the impedance of the leads to the load. example, has a resistance of only 1 milliohm and can be
The impedance of the load leads can easily.be several neglected when calculating the load resistance of the
orders of magnitude greater than the supply impedance supply.
and thus invalidate the measurement. To avoid mutual
coupling effects, each measuring device must be 5-14 Figure 5-2 shows a four terminal meter shunt.
connected directly to the output terminals by separate The load current through a shunt must be fed to the
pairs of leads. extremes of the wire leading to the resistor while the
5-10 When measurements are made at the front panel sampling connec- tions are made as close as possible to
terminals, the monitoring leads must be connected at the resistance portion itself.
point A, as shown in Figure 5-1, and not at point B.
Connecting the measuring device at point B would result
in a measurement that includes the resistance of the leads
between the output terminals and the point of connection.
NOTE
Figure 5-1. Front Panel Terminal Connections
All instructions in this section apply to Models
5-11 Selecting Load Resistors. Power supply specifica- 6236B and 6237B unless otherwise indiated.
tions are checked with a full load resistance connected
across the supply output. The resistance and wattage of 5-15 Rated Output, Tracking, Meter Accuracy,
the load resistor, therefore, must permit operation of the and Current Limit
supply at its rated output voltage and current. For example,
a supply rated at 20 volts and 0.5 amperes would require a 5-16 To check that all supplies will furnish their maxi-
load resistance of 40 ohms at the rated output voltage. The mum rated output voltage and current, that the ±20V
wattage rating of this resistor would have to be at least 10 outputs track each other, that the front panel meters are
watts. accurate, and that the current limit circuits function,
proceed as follows:
5.12 Either a fixed or variable resistor (rheostat) can
be used as the load resistance. Using a rheostat (alone or Voltmeter Accuracy
in series with a fixed resistor) is often more convenient a. With no loads connected: energize the supply, con-
than using fixed resistors as loads because the latter nect a digital voltmeter between the +6V terminal (+18V
may be more difficult to obtain in the exact resistance in Model 6237B) and common (COM), and set the +6V
required. A supplier of rheostats appropriate for testing (+18V) VOLTAGE control so that the DVM indication is as
these supplies is listed in Table 5-1. near as possible to 6 volts (18 volts).
b. Set the METER switch to the +6V (+18V) range
5.13 Output Current Measurements. For accurate out- and check the front panel voltmeter indication. It should be
put current measurements, a current sampling resistor within 4% of the DVM indication.
should be inserted between the load resistor and the c. Set the TRACKING RATIO control to the FIXED
output of the supply. An accurate voltmeter is then position, and check the +20V and -20V ranges of the
placed across the sampling resistor and the output panel voltmeter similarly by connecting the DVM to each of
current calculated by dividing the voltage across the these outputs in turn, setting the ±20V VOLTAGE control
5-2
for a 20V DVM indication, and verifying that the panel indication is within 4% of 0.5A, connect the DVM to
meter is accurate within 4%. the fully loaded output terminals, and compare the
output voltage before and after the load circuit is
Tracking opened. The voltage should not change by more than
d. Connect the DVM to the +20V output, set the ±20V 4mV. While checking each supply, the other two must
VOLTAGE control for a DVM indication of 20 volts, and be fully loaded.
reconnect the DVM to the -20V output without disturbing Current Limit
the voltage control. The voltage at the -20V output should l. Disconnect all loads from the supply.
be within 1% of the +20Voutput. m. Connect the test setup shown in Figure 5-3 to the
+20 volt output. Substitute a short for RL and leave the
Variable Tracking Ratio load circuit switch open.
e. Leave the ±20V VOLTAGE control set as in step (d), n. Set the voltage of the ±20V supplies to 20-volts.
and use a DVM to monitor the voltage of the -20V supply o. Close the load switch and determine the current
while adjusting the TRACKING RATIO control over its flow through the current sampling resistor (meter shunt)
VARIABLE range. The -20V supply should be capable of by measuring its voltage drop with the DVM. The current
being adjusted from less than 0.5 volts to between 18 should be 0.55A ±5%.
and 22 volts. Return the TRACKING RATIO control to the p. Check the current limit of the -20V supply in the
FIXED position. same way. Its short-circuit current should also be 0.55A
±5%.
NOTE q. (Model 6237B only). Check the current limit of the
+18V supply similarly by setting its output for 18 volts
Leave the TRACKING RATIO control in the and using a DVM to measure the current which flows
FIXED position throughout the remainder of the through a low- resistance current sampling resistor. The
performance test. short-circuit current of the +18V supply should be 1.1 A
±5%.
r. (Steps (r) through (t) apply to the 6236B only.)
Rated Output and Ammeter Accuracy
Connect the test setup shown in Figure 5-3 to the +6V
f. Connect 40Ω 10W load resistors across both of the 20V
output. Close the switch, set the total resistance of RL and
outputs of the supply and set the ±20V VOLTAGE control for a
the current sampling resistor to an initial value of 2.4 ohms
±20V output. (All three supplies must be fully loaded while
or greater, and set the output voltage to 6 volts.
checking the rated output voltage and current of each supply.)
s. Reduce the value of RL gradually while observing the
g. Connect the test setup shown in Figure 5-3 to the +6V
output current indicated by the DVM. The current should
(or +18V) output. Make the total resistance of RL and the
increase to a maximum of 2.75A ±5% before it begins to
current sampling resistor 2.4 ohms for the Model 6236B (or
decrease.
18 ohms for the 6237B) to permit operating the output at full
t. Connect a short across RL and then recheck the
load. RL should have a power rating of at least 20 watts.
current
h. Close the switch and set the +6V (+18V) VOLTAGE
control so that the DVM indicates a voltage drop across the
current sampling resistor that corresponds to a current of 2.5 5-17 Load Effect (Load Regulation)
amps (6236B) or 1.0 amp (6237B). Definition: The change ∆EOUT in the static value of dc
i. Set the METE R switch to the +6V (+18V) range and output voltage resulting from a change in load
verify that the front panel ammeter indication is within 4% of resistance from open circuit to the value that yields
2.5 amps (6236B) or 1.0 amp (6237B). maximum rated output current (or vice versa).
j. Connect the DVM directly across the output terminals of
the +6V (+18V) supply, record the DVM reading, and then 5-18 To check the load effect:
open the switch in the 6V (18V) load circuit without disturbing a. Connect a full load resistance and a digital voltmeter
the supply's output terminals. The DVM indication should not across the output of the +20V supply.
change by more than 2.6mV (6236B) or 3.8mV (6237B). b. Turn on the supply and adjust its voltage to its
k. Check the rated output and ammeter accuracy of the maximum rated value.
+20V and -20V supplies similarly by connecting the test setup c. Record the voltage indicated on the DVM.
of Figure 5-3 to each output in turn. For each 20V supply: d. Disconnect the load resistance and recheck the DVM
make the total resistance of RL and the current sampling indication. It should be within .01% plus 2mV of the read-
resistor 40 ohms, set the ±20V VOLTAGE control for a current ing in step (c).
indication, on the DVM of 0.5A, check that panel meter e. Repeat steps (a) through (d) for each of the remain-
ing supply outputs.
5-3
The magnitude of this remaining signal can easily be much
greater than the true ripple developed between the plus
and minus output terminals of the power supply and can
completely invalidate the measurement.
5-4
5-24 Figure 5-4B shows a correct method of measuring an oscilloscope with sufficient bandwidth (20 MHz) must
the output ripple of a constant voltage power supply be used. Ripple and noise measurements can be made at
using a single-ended scope. The ground loop path is any input ac line voltage combined with any dc output
broken by floating the power supply output. To ensure voltage and load current within rating.
that no potential difference exists between the supply a. Connect an oscilloscope or rms voltmeter across an
and the oscilloscope, it is recommended that they both output of the supply as shown in Figures 5-4B or 5-4C.
be plugged into the same ac power bus. If the same bus b. Energize the supply and observe the oscilloscope or
cannot be used, both ac grounds must be at earth meter indication. The ripple and noise should not be
ground potential. greater than 0.35mV rms or 1.5mV peak-to-peak.
5-25 Either a twisted pair or, preferably, a shielded two- c. Repeat for the remaining supply outputs.
wire cable should be used to connect the output terminals
of the power supply to the vertical input terminals of the 5-29 Load Transient Recovery Time
scope. When using a twisted pair, care must be taken that Definition: The time "X" for output voltage
one of the two wires is connected to the grounded input recovery to within "Y" millivolts of the nominal output
terminal of the oscilloscope to ensure that the supply voltage following a "Z" amp step change in load current,
output is safely grounded. When using shielded two-wire, it where: "Y" equals 15mV, and "Z" is the specified load
is essential for the shield to be connected to ground at one current change, equal to half of the current rating of the
end only to prevent ground current flowing through this supply. The nominal output voltage is defined as the dc
shield from inducing a signal in the shielded leads. level halfway between the static output voltage before
and after the imposed load change.
5-26 To verify that the oscilloscope is not displaying
ripple that is induced in the leads or picked up from the 5-30 Measurement Techniques. Care must be taken in
grounds, the (+) scope lead should be shorted to the (-) switching the load resistance on and off. A hand-operated
scope lead at the power supply terminals. The ripple value switch in series with the load is not adequate since the re-
obtained when the leads are shorted should be subtracted sulting one-shot displays are difficult to observe on most
from the actual ripple measurement. oscilloscopes and the arc energy occurring during switching
completely masks the display with a noise burst. Transistor
5-27 In most cases, the single-ended scope method of load switching devices are expensive if reasonably rapid load
Figure 5-4B will be adequate to eliminate extraneous ripple
so that a satisfactory measurement may be obtained.
However, in more stubborn cases (or if high frequency
noise up to 20 MHz must be measured). it may be
necessary to use a differential scope with floating input as
shown in Figure 5-4C. If desired, two single-conductor
shielded cables may be substituted in place of the shielded
two-wire cable with equal success. Because of its common
mode rejection. a differential oscilloscope displays only the
difference in signal between its two vertical input terminals,
thus ignoring the effects of any common mode signal pro-
duced by the difference in the ac potential between the
power supply case and scope case. Before using a differen-
tial input scope in this manner, however, it is imperative
that the common mode rejection capability of the scope be
verified by shorting together its two input leads at the
power supply and observing the trace on the CRT. If this
trace is a straight line, then the scope is properly ignoring
any common mode signal present. If this trace is not a
straight line, then the scope is not rejecting the ground
signal and must be realigned in accordance with the manu-
facturer's instructions until proper common mode rejection
is attained
5-5
current changes are to be achieved. Instead, a mercury- h. Adjust the sync controls separately for the positive
wetted relay should be used for loading and unloading the and negative going transients so that not only the recovery
supply. Connect it in the load switching circuit shown in waveshape but also as much as possible of the rise time of
Figure 5-5. When this load switch is connected to a 60 Hz the transient is displayed.
ac input, the mercury-wetted relay will open and close 60 i. Starting from the major graticule division
times per second. The 25K control adjusts the duty cycle representing time zero, count to the right 50µs and
of the load current switching to reduce jitter in the oscillo- vertically 15mV. Recovery should be within these
scope display. This relay may also be used with a 50 Hz ac tolerances, as illustrated in Figure 5-6.
input.
5-32 TROUBLESHOOTING
5-31 Measurement Procedure. To measure the load
transient recovery time, follow the steps below for each 5-33 Before attempting to troubleshoot this instrument,
supply output. Transient recovery time may be measured at ensure that the fault is in the instrument itself and not in
any input line voltage and any output voltage within rating. an associated piece of equipment. You can determine this
For this supply the specified load change is between half load without removing the covers from the instrument by using
and full load. the appropriate portions of the performance test of
a. Connect the test setup shown in Figure 5-5. Both paragraph 5-6.
load resistors (RL) are twice the normal value of a full load
resistance. 5-34 A good understanding of the principles of opera-
b. Turn on the supply and close the line switch on the tion is a helpful aid in troubleshooting, and the reader is
repetitive load switch. advised to review Section IV of the manual before begin-
c. Set the oscilloscope for internal sync and lock on ning detailed troubleshooting. Once the principles of oper-
either the positive or negative load transient spike. ation are understood, proceed to the initial troubleshooting
d. Set the vertical input of the oscilloscope for ac coup- procedures in paragraph 5-35.
ling so that small dc level changes in the output voltage of
the power supply will not cause the display to shift. ———CAUTION———
e. Adjust the horizontal positioning control so that the
trace starts at a point coincident with a major graticule Before applying power to the supply, make
division. This point then represents time zero. certain that its line voltage selector switch (S3)
f. Adjust the vertical centering of the scope so that the is set for the line voltage to be used. (See
tail ends of the no-load and full-load waveforms are CAUTION notice in paragraph 3-2 for additional
symmetrically displaced about the horizontal center line of information on S3.)
the oscilloscope. This center line now represents the nominal
output voltage defined in the specification. 5-35 Initial Troubleshooting Procedure
g. Increase the sweep rate so that a single transient
spike can be examined in detail. 5-36 If a malfunction is found, follow the steps below:
a. Disconnect input power from the supply and
remove all loads from the output.
b. Table 5-2 lists the symptoms and probable
causes of several possible troubles. If the symptom is one
of those listed, make the recommended checks.
c. If none of the symptoms of Table 5-2 apply,
proceed to Table 5-3. This table provides an initial
troubleshooting procedure that also directs you to the
more detailed procedures which follow it.
Figure 5-6. Load Transient Recovery Time Waveforms 5-39 Although transients or fatigue can cause a fuse to
5-6
Table 5-2. Miscellaneous Troubles
High ripple a. Check operating setup for ground loops (see paragraph 5-22).
Will not current limit Check for open OR-gate diodes (CR5, CR25, CR45) or defective
current limit amplifier (U1, U2, U3).
Poor load or line regulation a. Check bias and reference voltages, Table 5-4.
Oscillation or poor transient a. High frequency oscillations (above 50 kHz) can be caused by an
recovery time open C4, C14, or C24.
Transient voltage overshoot a. Overshoot only in the -20V supply can be caused by a
at turn-on or turn-off. shorted Q13.
2 Check output voltage of -20V a. Normal a. If +20V and -20V outputs are both
supply in fixed tracking ratio normal with no load, a supply might
mode. be current limiting under load. To check
this adjustment see paragraph 5-16,
steps (l) thru (p).
5-7
Table 5-3. Initial Troubleshooting Procedure (Continued)
3 Check output of +6V supply a. Normal a. If the output of this supply is normal
(Model 6236B) unloaded but its voltage falls when
or+18V supply loaded, check the current limit adjust
(Model 6237B). ment, paragraph 5-16, steps (q) thru (t).
c. Low voltage c. Check Q11 for open, Q12 for short, and
Z1 for open between pins 1 and 3.
5-8
Table 5-5. +20V Supply Troubleshooting
High output voltage 1. Attempt to turn down a. If output voltage remains high, check Q1, Q15,
(higher than rating) loop by shorting Q15 emitter- and CR9 for short.
to-base
b. If output voltage falls to near zero, remove short
from Q15 and proceed to step (2).
2. Measure voltage at Out- a. If TP4 is approx. -0.7V, check for open CR6 or
put of OR-gate (TP4). R1, and defective U1.
Low output voltage 1. Measure voltage at out- a. If TP4 is between zero and -0.7V, check for
(lower than rating) put of OR-gate (TP4). open Q1, Q15, R14, or CR59, and defective Q2.
3. Measure voltage at TP7. a. If TP7 is approx. +0.7V, check CR6 for short.
High output voltage 1. Attempt to turn down a. If output voltage remains high, check Q3, CR29,
(more than 1% greater loop by shorting Q13 and Q13 for short.
than +20V supply in emitter-to-base. b. If output falls to near zero, remove short from Q13 and
fixed tracking ratio proceed to step (2).
mode). 2. Measure voltage at out
put of OR-gate (TP5) a. If voltage at TP5 is zero or negative, check for
defective Q4.
5-9
Table 5-6. -20V Supply Troubleshooting (Continued)
3. Measure voltage at TP14. a. If TP14 is approx. -0.7V, check for open CR26
or defective U2.
Low output voltage 1. Measure voltage at TP5. a. If voltage at TP5 is zero or positive, check for open
(more than 1% lower Q3, Q13, or R34, and defective Q4.
than +20V supply in
fixed tracking ratio b. If TP5 voltage is approx. -0.7V, proceed to step
model (2).
3. Measure voltage at TP10. a. If TP10 is approx. -0.7V, check CR26 for short.
2. Measure voltage at output a. If TP6 is approx. -0.7V, check for open CR46 or
of OR-gate (TP6). R41, and defective U3.
Low output voltage 1. Measure voltage at output a. If TP6 is between zero and -0.7V, check for open
(lower than rating) of OR-gate (TP6) Q7, Q15, R54, or CR59, and defective Q8.
5-10
Table 5-7. +6V or +18V Supply Troubleshooting (Continued)
blow, it is a good idea to inspect the unit for obvious a semiconductor, use the listed Hewlett-Packard part or
shorts such as damaged wiring, charred components, or exact commercial replacement if these are available. If
extraneous metal parts or wire clippings in contact with neither of these are immediately available and a part is
circuit board conductors before replacing the fuse. The needed without delay for operation or troubleshooting
rating of the correct replacement fuse depends on the line verification, the parts designated Note 1, Alternate Part
voltage option of the instrument: for Options 100 or 120, Number can be tried with a high probability of success.
use a normal time-constant 2-amp fuse (HP Part No. 2110-
0002); for Options 220 or 240, use a normal time- 5-45 Notice that both the commercial and alternate re-
constant 1-amp fuse (HP Part No. 2110-0001). placements listed in Table 6-4 apply only to the HP power
supplies covered by this manual and their use in any other
Hewlett-Packard instrument is not necessarily
5-40 REPAIR AND REPLACEMENT recommended because of inclusion in this table.
5-42 To remove and replace a series regulator transistor: 5-47 Current Limit Adjustment
a. Remove the top and bottom covers from the instru-
ment. 5-48 ±20V Supplies. Perform the following steps to
b. Remove the collector screws and unsolder the base adjust the current limit circuit in the +20V or -20V supply.
and emitter leads from the board to remove the transistor. Potentiometer R6 sets the +20V and R26 the -20V current
c. To replace the transistor, follow the below reassembly limit.
order, as viewed from the bottom of the heat sink: collector a. Turn the TRACKING RATIO control to the FIXED
screws, P. C. board, heat sink, two insulating bushings (in position.
collector screw holes in heatsink), silicon grease (Dow DC-5 b. Turn the current limit adjustment pot (R6 or R26)
or HP 8500-0059), mica insulator, another coating of silicon fully counterclockwise to its minimum setting.
grease, transistor, lock-washers, and hex-nuts. c. Connect the test circuit of Figure 5-3 to the output of
d. Resolder the emitter and base pins to the circuit the supply to be adjusted. Use a 40Ω 10W resistor for RL.
board. d. Turn on the supply and set the ±20V VOLTAGE
control for maximum output (fully clockwise).
5-43 Semiconductor Replacement e. Turn the current limit pot (R6 or R26) slowly
clockwise until the DVM indicates a voltage drop across the
5-44 Table 6-4 contains replacement data for the shunt corresponding to a current of 0.55A ±5%.
semiconductors used in this power supply. When replacing
5-11
5-49 +6V Supply (Model 6236B). To adjust the will be the same. Adjust R58 so that the percentage error
current limit circuit in the +6V supply, proceed as follows; in the +6V range (or +18V range) is equal to the error in
a. Check the setting of the current limit by performing the 20-volt ranges. Turn R58 clockwise to increase the
steps (r) and (s) of paragraph 5-16. (Be sure to set the indications or counterclockwise to decrease them. If R58
output voltage to 6 volts.) If reducing the load resistance cannot calibrate all voltmeter ranges to within the ±4%
permits the current to exceed 2.9A, stop, turn R46 slightly specification, check the values of the resistors in the
clockwise, and repeat the test. If, instead, the current voltmeter circuit.
begins to fall before it reaches 2.6A, turn R46 slightly
counterclockwise and repeat the test. 5-53 Panel Ammeter. Check and calibrate the panel
b. Recheck the setting and readjust R46 until the test ammeter by following the steps below.
shows that the current limit circuit begins to reduce the a. Connect the test setup shown in Figure 5-3 to the
current when a decreasing load resistance increases it to +6V (or +18V) output. Make the total resistance of RL
2.75A ±5%. and the current sampling resistor 2.4 ohms (Model 6236B)
or 18 ohms (6237B) to permit operating the supply at its
5-50 +18V Supply (Model 6237B). To adjust the full rated output. RL should have a power rating of at least
current limit circuit in the +18V supply, proceed as follows: 20 watts.
a. Turn current limit adjustment pot (R46) fully clock b. Close the switch and set the +6V (+18V) VOLTAGE
wise to its minimum setting. control so that the DVM indicates an output of 2.5A
b. Connect the test circuit of Figure 5-3 to the output (6236B) or 1.0A (6237B).
of the +18V supply. Use an 18Ω 20W resistor for RL. c. Check and record the panel ammeter accuracy on the
c. Turn on the supply and set the +18V VOLTAGE +6V or +18V range.
control for maximum output (fully clockwise). d. Check each of the 20-volt ammeter ranges similarly,
d. Turn current limit pot (R46) slowly counterclockwise using the same test setup but making RL a 40Ω 10W
until the DVM indicates a voltage drop across the shunt resistor and setting the voltage control for a 0.5A output
corresponding to a current of 1.1 A ±5%. current. Record the panel ammeter accuracy on each 20-volt
range.
5-51 Meter Calibration e. Turn R59 clockwise to increase the indications on all
three ranges or counterclockwise to decrease them.
5-52 Panel Voltmeters. Check the accuracy of the f. If R59 cannot calibrate all three ammeter ranges to
panel voltmeter by performing steps (a), (b), and (c) of the within the ±4% specification, check the values of the resis-
procedure in paragraph 5-16. Since the same range tors in the circuit, including current monitoring resistors R8,
resistors are used in both 20-volt ranges, their accuracy R28, and R48.
5-12
SECTION VI
REPLACEABLE PARTS
6-1
Table 6-3. Code List of Manufacturers
01121 Allen Bradley Co. Milwaukee, WI 09353 C & K Components Inc. Newton, MA
02114 Ferroxcube Corp. Saugerties, NY 19701 Electra/Midland Corp. Mineral Wells, TX
02582 Clarostat Mfg. Co., Inc. Dover, NH 27014 National Semiconductor
02735 Radio Corp. of America, Solid State and Corp. Santa Clara, CA
Receiving Tube Div. Somerville, NJ 28480 Hewlett-Packard Co. Palo Alto, CA
03508 G. E. Semiconductor 61637 Union Carbide Corp. New York, NY
Products Dept. Syracuse, NY 71450 CTS Corp. Elkhart, IN
04200 Sprague Electric Co. North Adams, MA 72136 Electro Motive Mfg.Co., Inc.
04713 Motorola Semiconductor Willimantic, CT
Prod. Inc. Phoenix, AZ 75042 IRC Div. of TRW, Inc. Philadelphia, PA
05524 Dale Electronics Inc. Columbus, NE 75915 Littlefuse,Inc. DesPlaines,IL
05820 Wakefield Engr. Inc. Wakefield, MA
05917 Aktiebolaget Rifa Bromma, Sweden
07716 IRC Div. of TRW Inc. Burlington, IA
6-2
Table 6-4. Replaceable Parts
* 6236B/6237B
6-3
Table 6-4. Replaceable Parts (Continued)
R50
6236B fxd, film 330 1% 1/8W 1 Type MF4C, T-9 19701 0698-5663 1
6237B fxd, film 3.83k 1% 1/8W 1 Type MF4C-1 19701 0698-3153 1
R51 fxd, film 110k 1% 1/8W Type MF4C, T-0 19701 0757-0466
R52 fxd, film 139 1% 1/8W Type CEA, T-0 07716 0698-4099
R53 fxd, comp 7.5k 5% 1/2W 1 EB7525 01121 0686-7525 1
R54
6236B fxd, ww 50 5% 10W 1 Type 247E 04200 0811-1902 1
6237B fxd, ww 135 5% 10W 1 Type 247E 04200 0811-1905 1
R55
6236B fxd, comp 2.2k 5% 1/2W 1 EB2225 01121 0686-2225 1
6237B fxd, comp 11k 5% 1/2W 1 EB1135 01121 0686-1135 1
R56 fxd, film 270 1% 1/8W 1 Type CEA, T-0 07716 0757-0269 1
R57 fxd, film 221k 1% 1/8W 1 Type MF4C, T-0 19701 0757-0473 1
R58,59 var. ww 250 2 Type 110 71450 2100-0439 1
R60 fxd, film 15k 1% 1/8W Type MF4C, T-0 19701 0757-0446
R61 fxd, comp 240 5% 1/2W 1 EB2415 01121 0686-2415 1
R62 fxd, film 11k 1% 1/8W 2 Type MF4C, T-0 19701 0757-0443 1
R63 fxd, film 3.6k 2% 1/8W 1 Type MF4C, T-0 19701 0757-0937 1
R64 fxd, film 11k 1% 1/8W Type MF4C, T-0 19701 0757-0443
R65 fxd, film 16.2k 1% 1/8W 1 Type MF4C, T-0 19701 0757-0447 1
R66 fxd, film 470 1% 1/4W 1 Type MF52C, T-0 19701 0698-3506 1
R67
6236B fxd, ww 135 5% 3W 1 Type 242E 04200 0812-0112 1
6237B fxd, ww 220 5% 2W 1 Type BWH 75042 0811-1763 1
R68
6236B fxd, ww 250 5% 3W 1 Type 242E 04200 0811-1219 1
6237B fxd, ww 490 5% 3W 1 Type 242E 04200 0811-1801 1
R69
6236B fxd, ww 100 5% 10W 1 Type 247E 04200 0811-1903 1
6237B fxd, ww 150 5% 10W 1 Type 247E 04200 0811-1906 1
R70
6236B fxd, ww 40 5% 5W 1 Type 243E 04200 0812-0083 1
6237B fxd, ww 75 5% 5W 1 RS5 05524 0812-0097 1
R71 fxd, film 471 1% 1/8W 1 Type CMF-55-1, T-1 05524 0698-5514 1
R72 fxd, comp 33k 5% 1/2W 1 EB3335 01121 0686-3335 1
R73,6236B Not used
6237B fxd,comp 1.1M 5% 1/2W 1 EB1155 01121 0686-1155 1
R74,6236B (jumper installed)
6237B fxd, film 6.98k 1% 1/8W 1 Type CMF-55-1, T-1 05524 0698-4470 1
6-5
Table 6-4. Replaceable Parts (Continued)
Miscellaneous
Bushing, transistor insulator 8 28480 0340-0168
Transistor insulator, mica 4 28480 0340-0174
Fuse holder 1 342014 75915 1400-0084
Lockwasher, fuseholder 1 28480 2190-0054
Nut, nylon 1/2 - 24 1 28480 2950-0131
Foot, rubber 4 28480 0403-0088
Line cord strain relief 1 28480 0400-0013
Line cord 1 see par. 2-21
Chassis assembly, left 1 28480 5060-7955
Chassis assembly, right 1 28480 5060-7956
Front panel (6236B) 1 28480 06236-00001
Front panel (6237B) 1 28480 06237-00001
Heat sink, rear 1 28480 5020-8423
Cover, top and bottom 2 28480 5000-9424
Packing carton 1 28480 9211-2518
Floater pad, packing carton 2 28480 9220-1218
6-6
APPENDIX A
MANUAL BACKDATING CHANGES
To adapt this manual to Model 6236A or 6237A instruments, make the changes indicated in the table below.
6236A ALL 1
1507A-00141 thru -00350 2
1436A-00101 thru -00127 3
6237A ALL 1
1511A-00101 thru -00170 2
CHANGE 1 :
Delete R76, R77, and all references to the variable tracking
ratio feature.
CHANGE 2:
Change potentiometers R1 and R41 to 10kΩ panel-mounted
type, HP Part No. 2100-1854.
CHANGE 3:
Delete ferrite bead L3, 9170-0894, from the lead of diode
CR49.
A-1
SECTION VII
CIRCUIT DIAGRAMS
7-1
MANUAL CHANGES
Models 6236B and 6237B Triple Output DC Power Supplies
Manual HP Part No. 5950-1782
Make all corrections in the manual according to errata below, then check the following table for your power supply serial
number and enter any listed change(s) in the manual.
ERRATA:
The corrugated shipping carton for this model has been
changed to HP Part No. 9211-2570. Two 9220-2703 floater
pads are used.
CHANGE 1 :
9-8- 77
Note 1: Change 1 applies to the following instruments from earlier production runs. Model 6236B: serial 1705A-00502,
-505, -507, -526, -533, -534, -536, -541, -544, -546, -547, -573, -577, -594. Model 6237B: serial 1706A-00263,
-264, -269, -272, -291, -296, -298, -299.