Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Triple Output Power Supply MODELS 6236B AND 6237B

Download as pdf or txt
Download as pdf or txt
You are on page 1of 35
At a glance
Powered by AI
The manual covers two triple output power supply models, the 6236B and 6237B, which are compact general purpose bench supplies useful for powering developmental IC circuits. The key sections to read are the Introduction, Description, and specifications of the outputs, controls, and indicators.

The main features are that they have two 0 to ±20V tracking outputs rated at 0.5 amps and an additional single output of either 0 to +6V and up to 2.5 amps for the 6236B or 0 to +18V and 1 amp for the 6237B. The ±20V outputs can also be used in series as a single 0 to 40V 0.5-amp output.

The ±20V outputs are protected by circuits that limit the output current to 110% of its nominal maximum. The 6V output in the 6236B has a current foldback characteristic that reduces the output current as an overload increases.

TRIPLE OUTPUT POWER SUPPLY

MODELS 6236B AND 6237B

OPERATING AND SERVICE MANUAL FOR:


MODEL 6236B, SERIALS 1705A-00101 AND ABOVE
MODEL 6237B, SERIALS 1706A-00101 AND ABOVE

* For instruments with serial numbers above those listed, a change


page may be included. Refer to Appendix A for manual back-
dating changes applying to Model 6236A and 6237 A supplies.

Hewlett-Packard

HP Part No. 5950-1782 Printed: February 1977.


SECTION I
GENERAL INFORMATION

1-1 INTRODUCTION located on the front panel. One voltage control sets the
0 to+6V (or+18V) output and another sets the voltages
1-2 This manual covers two triple output power supply of the 0 to +20V and 0 to -20V outputs simultaneously.
models, the 6236B and 6237B. Both models are com- These dual tracking outputs are made more versatile by the
pact general purpose bench supplies that are particularly provision of a tracking ratio control in addition to the usual
useful for powering developmental IC circuits, both linear voltage control. With the tracking ratio control turned fully
and digital. Unless one model or the other is specifically clockwise to its "fixed" position, the dual outputs have a
identified, all information in this manual applies to both fixed 1:1 tracking ratio. As the ±20V voltage control is
the 6236B and the 6237B. adjusted, the voltage of the negative supply tracks the posi-
tive output within ±1%. Turning the tracking ratio control
away from its fully-clockwise position switches the dual
——— CAUTION ——— tracking outputs into a variable tracking ratio mode. In this
mode the voltage of the negative output can be set lower
Carefully read Sections II and III of this than that of the positive output. The tracking ratio control
manual before attempting to operate the allows the negative supply's output to be set to any value
power supply. between a maximum that is within 10% of the positive
supply's output and a minimum that is less than 0.5 volts.
Once a ratio is established by the tracking ratio control, the
1-3 DESCRIPTION ratio of the positive output voltage to the negative output
voltage remains constant as the ±20V voltage control
1-4 These constant-voltage/current-limiting triple varies the 0 to+20V output over its range.
output supplies combine two 0 to ±20V tracking outputs
rated at 0.5 amps with an additional single output that in 1-7 The front panel also contains a line switch and a
the Model 6236B is rated at 0 to+6 volts and up to 2.5 pilot light, a voltmeter and an ammeter, and a meter
amps, and in the Model 6237B is rated at 0 to +18 volts switch that selects one of the supply's three outputs to be
and 1 amps. The +20V and -20V tracking outputs can monitored on both dual-range meters.
also be used in series as a single 0 to 40V 0.5-amp output.
Connections to the supply's output and to chassis ground 1-8 In addition to the standard 104-to-127Vac 47-to-
are made to binding posts on the front panel. The supply's 63Hz input, three other line voltage options are available for
three outputs share a common output terminal, which is nominal inputs of 100, 220, and 240Vac. The supply is
isolated from chassis ground so that anyone output term- furnished with a permanently attached 5-foot 3-wire ground-
inal can be grounded. ing type line cord. The ac line fuse is in an extractor type
fuseholder on the rear heatsink.
1-5 All outputs are protected against overload and
short-circuit damage.The+18V output in the 6237B and 1-9 SPECIFICATIONS
the ±20V outputs in both models are protected by circuits
that limit the output current to 110% of its nominal maxi- 1-10 Table 1-1 lists detailed specifications for the
mum.The overload protection circuit for the +6V output power supply.
in the 6236B has a current foldback characteristic that
reduces the output current as an overload increases until 1-11 OPTIONS
only 1 amp flows through a short circuit. The 6V output's
current limit depends on the output terminal voltage and 1-12 Options are factory modifications of a standard
varies linearly between 2.75 amps at 6 volts and 1 amp instrument that are requested by the customer. The follow-
at zero volts. ing options are available for the instruments covered by
this manual.

1-6 All controls, meters, and output terminals are

1-1
OPTION NO. DESCRIPTION The user can convert an instrument from one line
voltage option to another by following the instructions
100 Input Power: 87-106Vac,47-63Hz, in paragraph 3-4.
single-phase.
220 Input Power: 191-233Vac,47-63Hz, 1-14 ACCESSORIES
single-phase.
240 Input Power: 208-250Vac,47-63Hz,
1-15 The accessories listed below may be ordered
single-phase.
from your local Hewlett-Packard field sales office either
910 One additional operating and service
with the power supply or separately. (Refer to the list at
manual shipped with the power supply.
the rear of the manual for addresses.)

1-13 Before the supply is shipped from the factory, an HP PART NO. DESCRIPTION
internalline voltage selector switch is set and the proper
fuse installed for the line voltage specified on the order. A 14513A Rack Mounting Kit for mounting one
label on the rear heatsink identifies this line voltage option. 3 1/2" high supply in a standard 19"
relay rack.

——— CAUTION ——— Rack Mounting Kit for mounting two


14523A
3 1/2" high supplies side by side in a
Before applying power to the supply, make certain standard 19" relay rack.
that its line voltage selector switch (S3) is set for
the line voltage to be used. (See CAUTION notice
in paragraph 3-2 for additional information.)

Table 1-1. Specifications, Model 6236B and 6237B

NOTE Model 6237 B


0 to +18V Output: Maximum rated output current is
Specifications apply to both models 1.0A. Short circuit output current is 1.1A ±5% and a fixed
unless otherwise indicated. current limit circuit limits the output to this maximum at
any output voltage setting.
INPUT POWER:
Standard: 104-127Vac (120Vac nominal), 47-63Hz,
TRACKING ACCURACY:
single-phase, 112W, 140VA (Other line voltage
The +20V and -20V outputs track within 1% with the
options are listed in paragraph 1-12).
TRACKING RATIO control in the FIXED position.

DC OUTPUT AND OVERLOAD PROTECTION:


0 to ±20V Outputs: Maximum rated output current is LOAD EFFECT (Load Regulation):
0.5A. Short circuit output current is 0.55A ±5% and a All Outputs: Less than 0.01% plus 2mV for a full load
fixed current limit circuit limits the output of each supply to no load change in output current.
to this maximum at any output voltage setting. Unbal-
anced loads within current rating are permitted.
SOURCE EFFECT (Line Regulation):
(Switching to the variable tracking ratio mode allows
the -20V output to be varied from less than -0.5V to All Outputs: Less than 0.01% plus 2mV for any line
within ±10% of the voltage setting of the +20V output.) voltage change within rating.

PARD (Ripple and Noise):


All Outputs: Less than 0.35mV rms and 1.5mV p-p
Model 6236B
(20 Hz to 20 MHz).
0 to +6V Output: Maximum rated output current is 2.5A
at 6V. The maximum available output current decreases
DRIFT (Stability):
with the output voltage setting. A current foldback circuit
All Outputs: Less than 0.1% plus 5mV (dc to 20Hz)
limits the output to 2.75A ±5% at 6 volts and, with
during 8 hours at constant line, load, and ambient after
decreasing voltage, reduces the current limit linearly to 1A
an initial warm-up time of 30 minutes.
±15% at zero volts (short circuited).

1-2
1-16 INSTRUMENT AND MANUAL 1-18 If the serial number on your instrument does not
IDENTIFICATION agree with those on the title page of the manual, Change
Sheets supplied with the manual or Manual Backdating
1-17 Hewlett-Packard power supplies are identified by Changes define the difference between your instrument
a two part serial number. The first part is the serial number and the instrument described by this manual.
prefix, a number-letter combination that denotes the date
of a significant design change and the country of manufac- 1-19 ORDERING ADDITIONAL MANUALS
ture. The first two digits indicate the year (10 = 1970,
11= 1971, etc.) the second two digits indicate the week, 1-20 One manual is shipped with each power supply
and the letter "A" designates the U.S.A. as the country of unless Option 910 is ordered for each extra manual. Addi-
manufacture. The second part is the power supply serial tional manuals may be purchased from your local Hewlett-
number. A different sequential number is assigned to each Packard field office (see the list at the rear of this manual
power supply, starting with 00101. for addresses). Specify the model number, serial number
prefix, and the HP Part Number provided on the title page.

Table 1-1. Specifications, Models 6236B and 6237B (Continued)

LOAD EFFECT TRANSIENT RECOVERY TIME: RESOLUTION:


All Outputs: Less than 50µsec for output recovery to (Minimum output voltage change obtainable using front
within 15mV of nominal output voltage following a load panel voltage control)
change from full load to half load (or vice versa). 0 to ±20V Outputs: 70mV
Model 6236B
OUTPUT VOLTAGEOVERSHOOT: 0 to +6V Output: 20mV
All Outputs: During turn-on or turn-off of ac power,
output plus overshoot will not exceed 1 V if the output Model 6237B
control is set for less than 1V. If the control is set for 1V 0 to +18V Output: 70mV
or higher, there is no overshoot.
TEMPERATURE RATINGS:
TEMPERATURE COEFFICIENT: Operating: 0 to +40°C ambient. At higher
All Outputs: Less than 0.02% plus 1 mV voltage temperatures, output current is derated linearly to 50% at
change per degree Celsius over the operating range from 55°C maximum temperature.
0 to 40°C after 30 minutes warm-up. Storage:-40°C to+75 °C.

*OUTPUT IMPEDANCE (typical): METER RANGES:


0 to +20V Output: 0.5mΩ plus 1.5µH 0 to +20V Output: 0-25V, 0-0.6A
0 to -20V Output: 0.5mΩ plus 1.5µH 0 to -20V Output: 0-25V, 0-0.6A

Model 6236B Model 6236B


0 to +6V Output: 0.3mΩ plus 1µH 0 to +6V Output: 0-7V, 0-3A

Model 6237B Model 6237B


0 to +18V Output: 0.3Ω plus 1.5µH 0 to +18V Output: 0-21V, 0-1.2A

* Operating characteristics listed as typical are provided DIMENSIONS:


for the user's information only and are not warranteed 3.47 in. H x 8.22 in. W x 12.56 in. D
specifications. (88mm H x 209mm W x 319mm D)

METER ACCURACY: WEIGHT:


±4% of full scale 9.5 lb (4.3kg)

1-3
SECTION II
INSTALLATION

2-1 INITIAL INSPECTION

2-2 Before shipment, this instrument was inspected


and found to be free of mechanical and electrical defects.
As soon as the instrument is unpacked, inspect for any
damage that may have occurred in transit. Save all packing
materials until the inspection is completed. If damage is
found, file claim with carrier immediately. The Hewlett-
Packard Sales and Service office should be notified as soon
as possible.
2-3 Mechanical Check
2-4 This check should confirm that there are no broken
knobs or connectors, that the cabinet and panel surfaces
are free of dents and scratches, and that the meter is not
scratched or cracked.

2-5 Electrical Check


Figure 2-1. Outline Diagram
2-6 The instrument should be checked against its elec
trical specifications. Section V includes an "in-cabinet" per-
formance check to verify proper instrument operation.

2-7 INSTALLATION DATA

2-8 The instrument is shipped ready for bench


operation. Before applying power to the instrument, see
the CAUTION notice in paragraph 3-2.

2-9 Location

2-10 This instrument is air cooled. Sufficient space Figure 2-2. Rack Mounting, One Unit
should be allotted so that a free flow of cooling air can
reach the rear of the instrument when it is in operation. It
should be used in an area where the ambient temperature
does not exceed 40°C (up to 55°C with derating).

2-11 Outline Diagram

2-12 Figure 2-1 illustrates the outline shape and dimen-


sions of this supply.

2-13 Rack Mounting

2-14 This instrument may be rack mounted in a standard


19-inch rack panel either by itself or alongside a similar
unit. Figures 2-2 and 2-3 show the components of the rack
mounting kits available for this power supply. Ordering
information for rack mounting accessories is given in para- Figure 2-3. Rack Mounting, Two Units
graph 1-14.
2-1
2-15 Input Power Requirements 2-20 To preserve the protection feature when operating
the instrument from a two-contact outlet, use a three-prong
2-16 Depending on the line voltage option ordered, the to two-prong adapter (if permitted by local regulations) and
supply is ready to be operated from one of the power connect the green lead on the adapter to ground.
sources listed in Table 2-1. The input voltage range, and
the input current and power at high line voltage and full 2-21 Model 6236B and 6237B supplies are equipped
load is listed for each option. A label on the rear heat sink at the factory with a power cord plug appropriate for the
identifies the line voltage option of your supply. All options user's location. Figure 2-4 illustrates the standard configu-
of this model operate from a 47-63 Hz single-phase line. rations of power cord plugs used by HP. Above each draw-
ing is the HP option number for that configuration of power
2-17 If desired, the user can easily convert the unit from connector pins. Below each drawing is the HP Part Number
any of these options to another by following the instructions for a replacement power cord equipped with a plug of that
in paragraph 3-4. A unit is converted by resetting an internal configuration. Notify the nearest HP Sales and Service
line voltage selector switch, replacing the fuse, and changing Office if the appropriate power cord is not included with
the line voltage tag. the instrument.

2-22 Repackaging for Shipment

2-23 To insure safe shipment of the instrument, it is


———CAUTION———
recommended that the package designed for the instrument
be used. The original packaging material is reusable. If it is
If the supply might possibly have been not available, contact your local Hewlett-Packard field office
converted to a line voltage option other to obtain the materials. This office will also furnish the
than the one marked on its identifying label address of the nearest service office to which the instrument
without being relabeled in some way, check can be shipped and provide the Authorized Return label
the setting of the line voltage selector necessary to expedite the handling of your instrument return.
switch and the fuse rating before applying Be sure to attach a tag to the instrument which specifies the
power. (See CAUTION in paragraph 3-2.) owner, model number, full serial number, and service
required, or a brief description of the trouble.

2-18 Power Cable

2-19 To protect operating personnel, the National


Electrical Manufacturers Association (NEMA) recommends
that the instrument panel and cabinet be grounded. This
instrument is equipped with a three conductor power cable.
The third conductor is the ground conductor and when the
cable is plugged into an appropriate receptacle, the instru-
ment is grounded. The offset pin on the power cable three-
prong connector is the ground connection. In no event shall
this instrument be operated without an adequate cabinet Figure 2-4. Power Cord Configurations
ground connection.

Table 2-1. Input Power Requirements

Option Line Voltage Range Input Current Input Power

100 (100 Vac) 87-106 Vac 1.3A 140 VA


Standard (120 Vac) 104-127 Vac 1.1A 140 VA
220 (220 Vac) 191-233 Vac 0.6A 140 VA
240 (240 Vac) 208-250 Vac 0.55A 140 VA

2-2
SECTION III
OPERATING INSTRUCTIONS

a. Connect line cord to power source and turn LINE


switch { on. LINE ON indicator | will light.

b. Set METER switch } to the +6V position and, with


no load connected, vary +6V VOLTAGE control ~ over
its range and check that the voltmeter responds to the
control setting and the ammeter indicates zero.

c. Set the +6V VOLTAGE control for a 6-volt meter


indication and short the +6V output terminal to COM
(common) terminal  with an insulated test lead. The
ammeter should indicate a short-circuit output current of
approximately 1.0A (1.1 A in the 6237B). Remove the
short from the output terminals.

d. Set the METER switch to the +20V position and


Figure 3-1. Controls and Indicators turn TRACKING RATIO control € fully clockwise to the
FIXED position. With no load connected, vary ±20V VOL-
3-1 TURN-ON CHECKOUT PROCEDURE TAGE control  over its range and check that the volt-
meter responds to the control setting and the ammeter
3-2 The following steps describe the use of the Model indicates zero.
6236B or 6237B front panel controls and indicators illus-
trated in Figure 3-1 and serve as a brief check that the sup- e. Set the ±20V VOLTAGE control for a 20-volt meter
ply is operational. Follow this checkout procedure or the indication and short the +20V output terminal to the com-
more detailed performance test of paragraph 5-6 when the mon terminal with an insulated test lead. The ammeter
instrument is received and before it is connected to any should indicate a short-circuit output current of 0.55A
load equipment. Proceed to the more detailed procedures ±5%. Remove the short from the output terminals.
beginning in paragraph 5-6 if any difficulties are
encountered. f. Repeat steps (d) and (e), but substitute the -20V
position of the METER switch and the -20V output ter-
minal.
———CAUTION———
g. Adjust the +20V output for a 20V meter indication.
Before applying power to the supply, make certain Then set the METER switch to the -20V position and
that its line voltage selector switch (S3) is set for check the effect of the TRACKING RATIO control on the
the line voltage to be used. This switch is mounted voltage of the -20V output. The -20V output should be
on the circuit board behind the voltmeter and is adjustable from less than 0.5 volts to a maximum of 18 to
visible through the perforations in the top cover. 22 volts.
The positions of the two white marks on the
switch indicate the switch setting (see Figure 3-2). 3-3 If this brief checkout procedure or later use of the
If the switch setting does not correspond to the supply reveals a possible malfunction, see Section V of this
intended power source, proceed to paragraph 3-4 manual for detailed test, troubleshooting, and adjustment
before applying power. procedures.

3-4 LINE VOLTAGE OPTION CONVERSION


NOTE

For the Model 6237B, substitute+18V 3-5 To convert the supply from one line voltage option
for +6V in the following steps. to another, the following three steps are necessary:

3-1
3-10 Overload Protection Circuits

3-11 ±20-Volt Current Limit. The +20V and -20V


outputs are individually protected against overload or short-
circuit damage by separate current limit circuits adjusted
at the factory to limit the output current to 0.55A ±5%.
(This is 110% of the maximum rated output.) The current
limits can be set by adjusting resistor R6 for the +20V
output and R26 for the -20V output. (See paragraph 5-47
for current limit calibration instructions.) No deterioration of
supply performance occurs if the output current remains
Figure 3-2. line Voltage Selector (Set for 120 Vac) below the current limit setting. If a single load is
connected between the +20V and -20V outputs, the circuit
1. After making certain that the line cord is discon- set for the lesser current limit will limit the output.
nected from a source of power, remove the top cover from
the supply and set the two sections of the line voltage 3-12 +6V Current Foldback (Model 6236B). The over-
selector switch for the desired line voltage (see Figure 3-2). load and short-circuit protection circuit for the +6V output
of the Model 6236B reduces the output current limit as the
2. Check the rating of the installed fuse and repla- output terminal voltage decreases. (The operating region of
ce it with the correct value, if necessary. For options 100 the +6V output is enclosed by heavy lines in Figure 3-3).
or 120, use a normal time-constant 2-amp fuse (HP Part No. The maximum rated output current is 2.5A and the current
2110-0002). For Options 220 or 240, use a normal time- limit is factory-adjusted to operate at 2.75A ±5% when
constant 1-amp fuse (HP Part No. 2110-0001). the output is 6 volts. At lower output voltages, the circuit
reduces the maximum obtainable output current linearly
3. Mark the instrument clearly with a tag or label until 1A ±15% flows when the output is shorted.
indicating the correct line voltage to be used. The shortcircuit current cannot be adjusted, but R46 can be
set to limit the maximum current at 6V to 2.75A ±5%.
3-6 OPERATION (See paragraph 5-47 for current limit calibration instruction.)

3-7 This power supply can be operated individually 3-13 +18Volt Current Limit (Model 6237B). The +18-
or in parallel with another supply (see paragraph 3-19). All volt output of the Model 6237B is protected by a fixed cur-
output terminals are isolated from ground. The ±20V and rent limit circuit that operates at 1.1 A (110% of its maxi-
+6V or +18V outputs use a single common output mum rated output). The circuit is similar to the ones in the
terminal. This common (COM) terminal or anyone of the ±20-volt supplies. (See paragraph 5-47 for calibration
other output terminals may be grounded to the chassis at instructions.)
the front panel ground terminal ( ‚ in Figure 3-1 ), or all
outputs may be left floating. Loads can be connected
3-14 Operation Beyond Rated Output
separately between each of the 0 to 20V output terminals
and the COM terminal, or between the -20V and the +20V
3-15 The supply may be able to provide voltages and
terminals for a 0 to 40V output.
currents greater than its rated maximum outputs if the line
voltage is at or above its nominal value. Operation can ex-
3-8 Tracking Ratio Control tend into the shaded areas on the meter faces without
damage to the supply, but performance cannot be
3-9 With the TRACKING RATIO control in the FIXED guaranteed to meet specifications. If the line voltage is
position, the voltage of the -20V supply tracks that of the maintained in the upper end of the input voltage range,
+20V supply within 1% for convenience in varying the however, the supply probably will operate within its
symmetrical voltages needed by operational amplifiers specifications.
and other circuits using balanced positive and negative
inputs. Turn the TRACKING RATIO control counterclock-
wise out of the FIXED position to set the voltage of the - 3-17 Connect each load to the power supply output
20V supply lower than that of the +20V supply. The terminals using separate pairs of connecting wires. This
negative supply can be set from a minimum of less than minimizes mutual coupling between loads and takes full
0.5 volts to a maximum within 10% of the +20V advantage of the low output impedance of the supply.
supply's output. Once this is done, the ±20V VOLTAGE Load wires must be of adequately heavy gauge to maintain
control still controls both outputs and maintains a satisfactory regulation at the load. Make each pair of
constant ratio between their voltages. connecting wires as short as possible and twist or shield

3-2
them to reduce noise pick-up. If shielded wire is used, 3-24 Reverse Current Loading. An active load connected
connect one end of the shield to the power supply to the power supply may actually deliver a reverse current to
ground terminal and leave the other end unconnected. the supply during a portion of its operating cycle. An external
source cannot be allowed to pump current into the supply
3-18 If load considerations require locating output without risking loss of regulation and possible damage to the
power distribution terminals at a distance from the power output capacitor. To avoid these effects, it is necessary to
supply, then the power supply output terminals should be preload the supply with a dummy load resistor so that the
connected to the remote distribution terminals by a pair of power supply delivers current through the entire operating
twisted or shielded wires and each load should be cycle of the load device.
connected to the remote distribution terminals separately.
3-25 Reverse Voltage Protection. Internal diodes con-
3-19 Parallel Operation nected with reverse polarity across the output terminals
protect the output electrolytic capacitors and the driver
3-20 Two or more power supplies can be connected in transistors from the effects of a reverse voltage applied
parallel to obtain a total output current greater than that across a supply output. Since series regulator transistors
available from one supply. The total output current is the cannot withstand reverse voltage either, diodes are also
sum of the output currents of the individual supplies. The connected across them. When operating supplies in
output voltage controls of one power supply should be set parallel, these diodes protect an unenergized supply that is
to the desired output voltage, and the other supply set for in parallel with an energized supply.
a slightly larger output voltage. The supply set to the
lower output voltage will act as a constant voltage source,
while the supply set to the higher output will act as a
current-limited source, dropping its output voltage until it
equals that of the other supply. The constant voltage
source will deliver only that fraction of its rated output
current necessary to fulfill the total current demand.

3-21 Special Operating Considerations

3-22 Pulse Loading. The power supply will automatically


cross over from constant-voltage to current-limit operation
in response to an increase in the output current over the
preset limit. Although the preset limit may be set higher
than the average output current, high peak currents as
occur in pulse loading may exceed the preset current limit
and cause crossover to occur and degrade performance.

3-23 Output Capacitance. An internal capacitor across


the output terminals of the power supply helps to supply
high-current pulses of short duration during constant-volt-
age operation. Any capacitance added externally will im-
prove the pulse current capability, but will decrease the
load protection provided by the current limiting circuit. A
high-current output pulse may damage load components
before the average output current is large enough to cause Figure 3-3. Current Limit Characteristics of the 6V Supply
the current limiting circuit to operate. (Model 6236B)

3-3
SECTION IV
PRINCIPLES OF OPERATION

4-1 OVERALL DESCRIPTION and current. Current foldback is controlled by a second


operational amplifier in the regulator that monitors the dc
4-2 This section presents the principles of operation output current. This current comparison amplifier takes
of the Models 6236B and 6237B Triple Output Power control of the output away from the voltage comparison
Supply. Throughout this section refer to the combined amplifier when the current reaches the design limit.
schematic diagram of Figure 7-1. Removing the overload restores constant voltage
operation automatically.
NOTE
4-7 The +20-volt regulator has a fixed current limit at
All information in this section applies to both 110% of its 0.5 amp maximum rated output but is
models unless otherwise indicated. otherwise similar to the +6-volt regulator.

4-3 The two primary windings of the power transformer 4-8 The 0 to -20-volt regulator is, in turn, similar to the
are connected in one of four different ways by setting the +20-volt regulator except that it resembles a
two slide switches mounted on the circuit board. These complementary mirror image of the latter. The output
switches select one of the nominal ac input voltages for voltages of the +20volt and -20-volt supplies are both set
which the supply is designed: 100V, 120V, 220V, or 240V. by the same front panel control and track each other within
1% in the fixed tracking ratio mode. Precise tracking of the
4-4 The transformer secondaries, together with two outputs is achieved by controlling the positive output
rectifiers and capacitor filters, provide raw dc for the three conventionally and using that output as the reference
output regulator circuits and for another regulator that pro- voltage for the negative output.
vides reference and bias voltages to the output regulators.
4-9 The 0 to +18-volt regulator in the Model 6237B
is similar to the +20-volt regulator. It has a fixed current
4-5 By comparing its output to a high-stability refer-
limit at 110% of its 1.0 amp output.
ence, the 0 to +6-volt regulator (6236B) or 0 to +18-
volt regulator (6237B) holds its output voltage at the 4-10 The reference and bias supply provides reference
value determined by a front panel control. Any error in and bias voltages for the output regulators.
the actual output as compared to the desired output is
amplified by an operational amplifier and applied as 4-11 The turn-on/turn-off control circuit prevents output
feedback to control the conduction of a series regulator transients when the supply is turned on or off. It does this by
transistor. As a result, the voltage across the series delaying the application of certain bias and reference voltages
transistor varies so as to hold the output voltage constant at turn-on and removing them shortly after turn-off.
at the desired level. The high gain of the voltage
comparison amplifier and the stability of the reference 4-12 A three-position meter switch selects which of
voltage ensure that input voltage or load current the supplies has its output voltage and current indicated
variations have little effect on the output voltage. on the front panel meters. The proper range of the dual-
range meters is selected automatically
4-6 The 0 to +6-volt output in the Model 6236B is
protected by a current foldback limiter to minimize 4-13 DETAILED CIRCUIT DESCRIPTION
dissipation in the series regulator transistor during
overloads. In a current foldback circuit, the current limit 4-14 0 To +20-Volt Regulator
depends on the output terminal voltage and in this regulator
ranges from 2.75A±5% at 6 volts to 1A±15% with the 4-15 Voltage Comparison Amplifier. The voltage com-
output shorted. (An output of 2.75A is 110% of the 2.5A parison amplifier in the +20-volt supply controls the conduc-
rated maximum at 6 volts.) The operating region of the tion of series regulator transistor Q1 so that the voltages at
+6-volt regulator output is enclosed by a heavy line in the two inputs of the amplifier remain equal. A fixed voltage
Figure 3-3. If the operating point reaches the diagonal divider holds its inverting input (U1-2) at -16mV. Its non-
current limit line, a decrease in load resistance moves the inverting input (U1-3) monitors the output voltage in series
operating point down the line, reducing the output voltage

4-1
with the voltage across R1. Since R2 is connected between and returning control to the voltage comparison amplifier.
the -6.2V reference supply and a point that feedback action
holds near -16mV, its current remains constant. This 4-20 Turn-On/Turn-Off Control. When the power supply
current flows through R1 to produce a voltage drop across is turned on or off, Q15 in the turn-on control circuit with-
R1 proportional to its resistance setting, thus the output holds turn-on bias from Q1 while the regulator bias voltages
voltage of the supply is proportional to the resistance are too low. This prevents an output voltage transient from
setting of R1. At the output of the voltage comparison occurring before the amplifiers are properly biased. The
amplifier (U1-1), a positive voltage change corresponds to a output of the -6.2V reference supply is also temporarily
decrease in the conduction of Q1. held at a low voltage by Q14, which conducts to short that
output.
4-16 CR2 and CR3 protect the input of the amplifier
against transient overloads, C2 and R4 speed up loop 4-21 Circuit Protection Components. Diodes CR1, CR7,
response time, and C4 and R12 stabilize the supply's and CR9 each protect the +20-volt supply from specific
high frequency characteristics. hazards. Output diode CR1 protects the supply components
if a reverse voltage is applied to the output terminals. A
common way for this to occur is for an unenergized supply
4-17 OR-Gate. To permit either the voltage comparison
to be connected in series with another that is energized. If
amplifier or the current comparison amplifier to control the
the output voltage is turned down quickly while a large
series regulator transistor, the outputs of both amplifiers
capacitor is connected across the output, CR7 protects
are connected to the base of driver Q2 through an OR-gate
driver Q2 from excessive dissipation by shunting some of its
composed of CR5 and CR6. CR5 is normally reverse
base current to common. The series regulator diode, CR9,
biased by a negative output from the current comparison
protects the series regulator transistor from reverse voltage.
amplifier, permitting the voltage comparison amplifier to
Reverse series regulator voltage could occur if a deenergized
drive Q2 through CR6. An overload drives the output of
supply were connected in parallel with an energized one.
the current comparison amplifier positive, forward biasing
CR5 and reducing the supply output. When the overload is
removed, CR5 is reverse biased again and the voltage com-
4-22 0 To -20-Volt Regulator
parison amplifier resumes control of the output. 4-23 Instead of using an NPN driver and a PNP series
regulator in the negative output line as in the +20-volt
4-18 Driver and Series Regulator. The -12.4V output of regulator, the -20-volt regulator uses a PNP driver and an
the bias supply provides the turn-on bias for series NPN series regulator in the positive output line. The -20-
regulator transistor Q1. Its complete current path includes volt regulator circuit is the complementary equivalent of
Q15, CR59, R 14, and Q1, and returns to common the +20-volt circuit in other respects, as well. Their
through current monitoring resistor R8. (It is because this current limit circuits operate similarly. At the outputs of
bias current flows through R8 that the output ammeter the current and voltage comparison amplifiers in the -20-
requires the zero offset bias circuit described in paragraph volt circuit, a negative voltage change corresponds to a
4-43.) Through the OR-gate, either the voltage or the decrease in series regulator conduction. The turn-on bias
current comparison amplifier controls the conduction of for its series regulator transistor, Q3, is supplied from a
driver Q2, which regulates the flow of turn-off bias positive voltage source, the +7.5V bias supply, and is
through Q1's base-emitter circuit. The algebraic sum of the switched on and off by Q13 in the turn-on control circuit.
nearly constant turn-on bias through R14 and the variable
turn-off bias through Q2 controls the conduction of series 4-24 The -20-volt supply uses the output of the +20-
regulator transistor Q1. volt supply as its reference voltage. As a result, both
4-19 Current Limit Circuit. In the +20-volt regulator, outputs are set by a single front panel control and track
the current comparison amplifier compares the voltage each other with in 1% in the fixed tracking ratio mode.
across current monitoring resistor R8 to the fixed voltage Two resistors in resistor network Z1 are connected in
across part of current limit adjust potentiometer R6. The series between the +20volt and -20-volt outputs. These
current limit adjustment is set so that the input voltage to resistors are closely matched in resistance and temperature
the current comparison amplifier is negative in the normal coefficient so that the voltage across each is exactly half
operating region, but becomes zero when the output of the total. The midpoint of this divider is connected to
current increases to 0.55 amps. When the amplifier's the non-inverting input of the -20-volt supply's voltage
input voltage reaches zero, it takes control of the comparison amplifier. The amplifier's inverting input is
regulator output voltage and reduces it as necessary to connected to common through R32 to hold it at zero volts.
keep the output current from exceeding 0.55 amps. The amplifier keeps its differential input voltage at zero by
When the overload is removed, the output of the current matching the output voltage of the -20-volt supply to that
comparison amplifier goes negative, reverse biasing CR5 of the +20-volt supply.

4-2
4-25 In the variable tracking ratio mode, the tracking input (U3-5), which is held at -305mV. The negative am-
ratio control connects a fixed resistor in parallel with plifier output that results is clamped by CR44 and reverse
the upper part and a rheostat (the variable tracking ratio biases OR-gate diode CR45, leaving the voltage comparison
control) in parallel with the lower part of the voltage amplifier in control of the supply's output. If the load resis-
divider that forms the -20-volt reference. Turning the tance is decreased, the higher output current increases
control counter- clockwise reduces the resistance of the ER48 until the algebraic sum of ER48 and ER46 makes the
rheostat and lowers the voltage of the negative output. current comparison amplifier's inverting input slightly more
negative than the -305mV potential on its non-inverting in-
4-26 0 To +6-Volt Regulator (Model 6236B) put. When this happens, the output of this amplifier goes
positive and forward biases CR45. Since the current through
4-27 Except for differing component designations and CR45 tends to reduce the output of the supply, the output
values, paragraphs 4-15 through 4-18,4-20, and 4-21, of the voltage comparison amplifier goes negative in oppo-
which describe the voltage comparison amplifier, OR-gate, sition to this change and reverse biases CR46 to leave the
driver, series regulator, turn-on control, and circuit current comparison amplifier in control of the output. Now
protection components of the +20-volt regulator circuit, that the current comparison amplifier is in control and for as
also apply to the +6-volt regulator. The only difference in long as the overload remains, the supply's output voltage
circuit operation lies in the control of the current and current vary so as to maintain this amplifier's differen-
comparison amplifier, and thus the type of current limit the tial input signal near zero volts. This results in the output
supply has. current limit characteristics shown in Figure 3-3.
4-28 Current Foldback Circuit. (For this discussion
refer to the Figure 7-1 schematic and to Figure 4-1.) The
differential input signal to the current comparison amplifier 4-30 If we assume for example that the voltage control
is the algebraic sum of three circuit voltages: is set for 5 volts and the load resistance is slowly
1.The voltage across R49. ER49 remains constant at decreased, the supply goes into current limit at about
-305mV. 2.47 amps. Here is why it occurs at that value. At a 5-
2. The voltage across the lower part of R46 (see volt supply output, ER46 is 5/6 of 440mV, or 367mV. In
Figure 4-1). ER49 is proportional to the regulator order for the algebraic sum of ER46 and ER48 to go as far
output voltage and equals 440mV when the negative as -305mV and drive the amplifier output
supply output is 6 volts. positive, ER48 must reach -672mV. Once ER48 reaches
3. The voltage across current monitoring resistor this value, the current comparison amplifier controls the
R48. ER48 is proportional to the sum of the series regulator transistor so as to prevent ER48 (and thus
regulator output current and the 0.22A bias the supply's output current) from increasing further. At
current that flows through R54 and R48. 0.25 ohms, R48 develops -672mV at 2.69 amps. Since
0.22 amps of the current through R48 is bias current for
Q7, the nominal current limit corresponding to a 5-volt
output is 2.69 amps minus 0.22 amps, or about 2.47

4-31 If the load resistance continues to decrease, it pulls


the output voltage lower. This reduces ER46 until at a zero
output voltage ER46 becomes zero, leaving ER48 equal in
magnitude to ER49 This -305mV drop across R48 corre-
sponds to a 1.22-amp current through R48 and a 1-amp
shortcircuit current at the output of the supply.

4-32 In the +6-volt regulator, as in the +20-volt


regulator, the turn-on bias current for the series regulator
transistor is switched on and off by Q15 in the turn-on
Figure 4-1. Foldback Current Limit Circuit in 6V Supply control circuit to prevent output voltage transients.

4-29 When the supply's output current is below the cur-


rent limit that corresponds to its output terminal voltage
(see Figure 3-3), the inverting input (U3-6) of the current 4-33 0 To +18-Volt Regulator (Model 6237B)
comparison amplifier is more positive than its non-inverting
4-34 Except for differing component designations and

4-3
values, paragraphs 4-15 through 4-21, which describe the 4-39 Turn-On/Turn-Off Control Circuit
voltage comparison amplifier, OR-gate, driver, series regu-
lator, current limit circuit, turn-on control, and circuit 4-40 Immediately after the supply is energized and
protection components of the +20-volt regulator circuit, until the output of the -12.4-volt regulator reaches about
also apply to the +18-volt regulator. In the +18-volt -9 volts, the turn-on control circuit withholds turn-on bias
regulator, as in the +20-volt regulator, the turn-on bias from series regulator transistors Q1, Q3, and Q7 and holds
current for the series regulator transistor is switched on and the -6.2V reference at a low value. This prevents an output
off by Q15 in the turn-on control circuit to prevent output voltage transient by ensuring that the operational amplifiers
voltage transients. are energized and other essential bias voltages are present
before the series regulator transistors are turned on. The
circuit also prevents an output transient when the supply is
turned off by removing the turn-on bias from the series
4-35 Reference and Bias Supply
regulators and shorting the -6.2V reference supply as the
4-36 The reference and bias supply powers the voltage of the -12.4 V supply falls below -9 volts.
operational amplifiers and provides the bias and reference
voltages used throughout the supply. A shunt zener 4-41 Q13 switches the bias to the -20-volt regulator
regulates its +7.5V output. A series transistor regulates its on and off, Q14 switches the short across the -6.2-volt
-12.4 V output, using 6.2-volt zener VR1 as its voltage reference supply, and Q15 switches the bias to the +20-
reference. The -12.4V output provides a constant current to volt and +6-volt or +18-volt regulators. Q15 remains
VR1, which is the primary voltage reference for the entire turned off until VR2 conducts at 9 volts to switch it on.
supply. While Q15 is off, it holds Q13 biased off and Q14 on;
when Q15 conducts, it turns Q13 and Q14 off.
4-37 Two equal resistors are connected in series
across the -12.4V output. To regulate this output,
voltage comparison amplifier U4 compares the voltage
4-42 Meter Circuits
across one of these resistors to the -6.2V reference and
controls the conduction of series regulator Q11 through 4-43 Voltmeter. Two of the resistors in resistor
driver Q12. The voltage drop across Q11 is controlled network Z1 are range resistors for the voltmeter. The
by feedback so that the voltages at the two inputs of U4 accurate ratio of these resistors permits a single calibration
remain equal. Driver Q12 controls Q11 by shunting part potentiometer, R58 to adjust both ranges simultaneously.
of the base bias supplied by R68.
4-44 Ammeter. The range switch connects the
ammeter across the current monitoring resistor of a supply:
4-38 During turn-on, the -6.2V reference supply is R48 in the +6-volt or +18-volt supply, R8 in the +20-volt
temporarily shorted by Q14 in the turn-on control circuit. supply, or R28 in the -20-volt supply. Each of these
By trying to match this low reference, Q11 is initially turned resistors conducts a constant bias current for its series
off. While Q11 is turned off, R69 bypasses current to the regulator transistor in addition to the supply's output
-12.4 V output until the output reaches -9 volts and the current. If no compensation were used, this additional
turn-on control circuit removes the short from the reference current would raise the indicated output by up to 8% of full
and enables the -12.4-volt regulator to operate normally. scale. The resistor networks connected to each range of the
ammeter selector switch apply a bias to the meter to offset
this error. R59 calibrates all ammeter ranges.

4-4
SECTION V
MAINTENANCE

5-5 Table 5-1 lists the test equipment required to


5-1 INTRODUCTION perform the various procedures described in this section.

5-2 Upon receipt of the power supply, the performance 5-6 PERFORMANCE TEST
test of paragraph 5-6 can be made. This test is suitable for
incoming inspection. Section III contains a quick but less
5-7 The following test can be used as an incoming
comprehensive checkout procedure that can be used in lieu
inspection check and appropriate portions of the test can
of the performance test if desired.
be repeated to check the operation of the instrument after
repairs. If the correct result is not obtained for a particular
5-3 If a fault is detected in the power supply while check, proceed to the troubleshooting procedures of para-
making the performance test or during normal operation, graph 5-32.
proceed to the troubleshooting procedure in paragraph 5-32.
After troubleshooting and repair, repeat the performance
test to ensure that the fault has been properly corrected and
———CAUTION———
that no other faults exist. Before performing any mainte-
nance checks, turn on the power supply and allow a half
Before applying power to the supply, make
hour warm-up.
certain that its line voltage selector switch
(S3) is set for the line voltage to be used. (See
5-4 TEST EQUIPMENT REQUIRED CAUTION notice in paragraph 3-2 for addi-
tional information on S3.)

Table 5-1. Test Equipment Required

REQUIRED RECOMMENDED
TYPE CHARACTERISTICS USE MODEL

Digital Sensitivity: 100mV full scale Measure dc voltages: HP 3490A


Voltmeter (min.). Input impedance: calibration procedures
10 megohms (min.).

Variable Range: 90-130 Vac Vary ac input -----


Voltage Equipped with voltmeter
Transformer accurate within 1 volt

Oscilloscope Sensitivity: 100µV/cm. Display transient re- HP 180C with 1821A,


Differential input. sponse and ripple and and 1801A or 1803A
noise waveforms. plug-ins.

Repetitive Rate: 60 Hz, 2µs Measure transient See Figure 5-5.


Load Sw. rise and fall time response.

Resistive Value: See paragraph 5-11. Power supply load James G. Biddle
Loads Tolerance: ±5% resistor (fixed resistor ("Lubri-Tact"
or rheostat). Rheostat)

Current Value: See paragraph 5-13. Measure output current Simpson Portable
Sampling Accuracy: 1% (minimum) Shunt, 06703.
Resistor (Shunt)

5-1
5-8 General Measurement Techniques the sampling resistor by its ohmic value. The total
resistance of the series combination should be equal to
5-9 Connecting Measuring Devices. To achieve valid the full load resistance as determined in the preceding
results when measuring the load effect, PARD (ripple and paragraphs. Of course, if the value of the sampling
noise), and transient recovery time of the supply, resistor is very low when compared to the full load
measuring devices must be connected as close to the resistance, the value of the sampling resistor may be
output terminals as possible. A measurement made across ignored. The meter shunt recommended in Table 5-1, for
the load includes the impedance of the leads to the load. example, has a resistance of only 1 milliohm and can be
The impedance of the load leads can easily.be several neglected when calculating the load resistance of the
orders of magnitude greater than the supply impedance supply.
and thus invalidate the measurement. To avoid mutual
coupling effects, each measuring device must be 5-14 Figure 5-2 shows a four terminal meter shunt.
connected directly to the output terminals by separate The load current through a shunt must be fed to the
pairs of leads. extremes of the wire leading to the resistor while the
5-10 When measurements are made at the front panel sampling connec- tions are made as close as possible to
terminals, the monitoring leads must be connected at the resistance portion itself.
point A, as shown in Figure 5-1, and not at point B.
Connecting the measuring device at point B would result
in a measurement that includes the resistance of the leads
between the output terminals and the point of connection.

Figure 5-2. Current Sampling Resistor Connections

NOTE
Figure 5-1. Front Panel Terminal Connections
All instructions in this section apply to Models
5-11 Selecting Load Resistors. Power supply specifica- 6236B and 6237B unless otherwise indiated.
tions are checked with a full load resistance connected
across the supply output. The resistance and wattage of 5-15 Rated Output, Tracking, Meter Accuracy,
the load resistor, therefore, must permit operation of the and Current Limit
supply at its rated output voltage and current. For example,
a supply rated at 20 volts and 0.5 amperes would require a 5-16 To check that all supplies will furnish their maxi-
load resistance of 40 ohms at the rated output voltage. The mum rated output voltage and current, that the ±20V
wattage rating of this resistor would have to be at least 10 outputs track each other, that the front panel meters are
watts. accurate, and that the current limit circuits function,
proceed as follows:
5.12 Either a fixed or variable resistor (rheostat) can
be used as the load resistance. Using a rheostat (alone or Voltmeter Accuracy
in series with a fixed resistor) is often more convenient a. With no loads connected: energize the supply, con-
than using fixed resistors as loads because the latter nect a digital voltmeter between the +6V terminal (+18V
may be more difficult to obtain in the exact resistance in Model 6237B) and common (COM), and set the +6V
required. A supplier of rheostats appropriate for testing (+18V) VOLTAGE control so that the DVM indication is as
these supplies is listed in Table 5-1. near as possible to 6 volts (18 volts).
b. Set the METER switch to the +6V (+18V) range
5.13 Output Current Measurements. For accurate out- and check the front panel voltmeter indication. It should be
put current measurements, a current sampling resistor within 4% of the DVM indication.
should be inserted between the load resistor and the c. Set the TRACKING RATIO control to the FIXED
output of the supply. An accurate voltmeter is then position, and check the +20V and -20V ranges of the
placed across the sampling resistor and the output panel voltmeter similarly by connecting the DVM to each of
current calculated by dividing the voltage across the these outputs in turn, setting the ±20V VOLTAGE control

5-2
for a 20V DVM indication, and verifying that the panel indication is within 4% of 0.5A, connect the DVM to
meter is accurate within 4%. the fully loaded output terminals, and compare the
output voltage before and after the load circuit is
Tracking opened. The voltage should not change by more than
d. Connect the DVM to the +20V output, set the ±20V 4mV. While checking each supply, the other two must
VOLTAGE control for a DVM indication of 20 volts, and be fully loaded.
reconnect the DVM to the -20V output without disturbing Current Limit
the voltage control. The voltage at the -20V output should l. Disconnect all loads from the supply.
be within 1% of the +20Voutput. m. Connect the test setup shown in Figure 5-3 to the
+20 volt output. Substitute a short for RL and leave the
Variable Tracking Ratio load circuit switch open.
e. Leave the ±20V VOLTAGE control set as in step (d), n. Set the voltage of the ±20V supplies to 20-volts.
and use a DVM to monitor the voltage of the -20V supply o. Close the load switch and determine the current
while adjusting the TRACKING RATIO control over its flow through the current sampling resistor (meter shunt)
VARIABLE range. The -20V supply should be capable of by measuring its voltage drop with the DVM. The current
being adjusted from less than 0.5 volts to between 18 should be 0.55A ±5%.
and 22 volts. Return the TRACKING RATIO control to the p. Check the current limit of the -20V supply in the
FIXED position. same way. Its short-circuit current should also be 0.55A
±5%.
NOTE q. (Model 6237B only). Check the current limit of the
+18V supply similarly by setting its output for 18 volts
Leave the TRACKING RATIO control in the and using a DVM to measure the current which flows
FIXED position throughout the remainder of the through a low- resistance current sampling resistor. The
performance test. short-circuit current of the +18V supply should be 1.1 A
±5%.
r. (Steps (r) through (t) apply to the 6236B only.)
Rated Output and Ammeter Accuracy
Connect the test setup shown in Figure 5-3 to the +6V
f. Connect 40Ω 10W load resistors across both of the 20V
output. Close the switch, set the total resistance of RL and
outputs of the supply and set the ±20V VOLTAGE control for a
the current sampling resistor to an initial value of 2.4 ohms
±20V output. (All three supplies must be fully loaded while
or greater, and set the output voltage to 6 volts.
checking the rated output voltage and current of each supply.)
s. Reduce the value of RL gradually while observing the
g. Connect the test setup shown in Figure 5-3 to the +6V
output current indicated by the DVM. The current should
(or +18V) output. Make the total resistance of RL and the
increase to a maximum of 2.75A ±5% before it begins to
current sampling resistor 2.4 ohms for the Model 6236B (or
decrease.
18 ohms for the 6237B) to permit operating the output at full
t. Connect a short across RL and then recheck the
load. RL should have a power rating of at least 20 watts.
current
h. Close the switch and set the +6V (+18V) VOLTAGE
control so that the DVM indicates a voltage drop across the
current sampling resistor that corresponds to a current of 2.5 5-17 Load Effect (Load Regulation)
amps (6236B) or 1.0 amp (6237B). Definition: The change ∆EOUT in the static value of dc
i. Set the METE R switch to the +6V (+18V) range and output voltage resulting from a change in load
verify that the front panel ammeter indication is within 4% of resistance from open circuit to the value that yields
2.5 amps (6236B) or 1.0 amp (6237B). maximum rated output current (or vice versa).
j. Connect the DVM directly across the output terminals of
the +6V (+18V) supply, record the DVM reading, and then 5-18 To check the load effect:
open the switch in the 6V (18V) load circuit without disturbing a. Connect a full load resistance and a digital voltmeter
the supply's output terminals. The DVM indication should not across the output of the +20V supply.
change by more than 2.6mV (6236B) or 3.8mV (6237B). b. Turn on the supply and adjust its voltage to its
k. Check the rated output and ammeter accuracy of the maximum rated value.
+20V and -20V supplies similarly by connecting the test setup c. Record the voltage indicated on the DVM.
of Figure 5-3 to each output in turn. For each 20V supply: d. Disconnect the load resistance and recheck the DVM
make the total resistance of RL and the current sampling indication. It should be within .01% plus 2mV of the read-
resistor 40 ohms, set the ±20V VOLTAGE control for a current ing in step (c).
indication, on the DVM of 0.5A, check that panel meter e. Repeat steps (a) through (d) for each of the remain-
ing supply outputs.

5-3
The magnitude of this remaining signal can easily be much
greater than the true ripple developed between the plus
and minus output terminals of the power supply and can
completely invalidate the measurement.

5-23 The same ground current and pickup problems can


exist if an rms voltmeter is substituted in place of the oscil-
loscope in Figure 5-4. However, the oscilloscope display,
unlike the true rms meter reading, tells the observer imme-
diately whether the fundamental period of the signal dis-
played is 8.3 milliseconds (1/120 Hz) or 16.7 milliseconds
Figure 5-3. Output Current, Test Setup (1/60 Hz). Since the fundamental ripple frequency present
on the output of an HP supply is 120 Hz (due to full-wave
5-19 Source Effect (Line Regulation) rectification). an oscilloscope display showing a 120 Hz
Definition: The change, ∆EOUT in the static fundamental component is indicative of a "clean" measure-
value of dc output voltage resulting from a change in ac ment setup, while the presence of a 60 Hz fundamental
input voltage over the specified range from low line usually means that an improved setup will result in a more
(typically 104 Vac) to high line (typically 127 Vac), or accurate (and lower) value of measured ripple.
from high line to low line.

5-20 To test the source effect:


a. Connect a variable autotransformer between the in
put power source and the power supply line plug.
b. Connect a full load resistance and a digital voltmeter
across the output of the +20V supply.
c. Adjust the autotransformer for a low line input.
d. Turn on the power, adjust the output of the supply
to its maximum rated voltage, and record the DVM indica-
tion.
e. Adjust the autotransformer for a high line input and
recheck the DVM indication. It should be within .01% plus
2mV of the reading in step (d).
f. Repeat steps (b) through (e) for each of the
remaining supply outputs.

5-21 PARD (Ripple and Noise)


Definition: The residual ac voltage that is
superimposed on the dc output of a regulated power
supply. Ripple and noise may be specified and measured
in terms of its rms or peak-to-peak value.

5-22 Measurement Techniques. Figure 5-4A shows an


incorrect method of measuring p-p ripple. Note that a con-
tinuous ground loop exists from the third wire of the input
power cord of the supply to the third wire of the input
power cord of the oscilloscope via the grounded power
supply case, the wire between the negative output
terminal of the power supply and the vertical input of the
scope, and the grounded scope case. Any ground current
circulating in this loop as a result of the difference in
potential EG between the two ground points causes an IR
drop that is in series with the scope input. This IR drop,
normally having a 60 Hz line frequency fundamental, plus
any pickup on the unshielded leads interconnecting the
power supply and scope, appears on the face of the CRT. Figure 5-4. Ripple and Noise, Test Setup

5-4
5-24 Figure 5-4B shows a correct method of measuring an oscilloscope with sufficient bandwidth (20 MHz) must
the output ripple of a constant voltage power supply be used. Ripple and noise measurements can be made at
using a single-ended scope. The ground loop path is any input ac line voltage combined with any dc output
broken by floating the power supply output. To ensure voltage and load current within rating.
that no potential difference exists between the supply a. Connect an oscilloscope or rms voltmeter across an
and the oscilloscope, it is recommended that they both output of the supply as shown in Figures 5-4B or 5-4C.
be plugged into the same ac power bus. If the same bus b. Energize the supply and observe the oscilloscope or
cannot be used, both ac grounds must be at earth meter indication. The ripple and noise should not be
ground potential. greater than 0.35mV rms or 1.5mV peak-to-peak.
5-25 Either a twisted pair or, preferably, a shielded two- c. Repeat for the remaining supply outputs.
wire cable should be used to connect the output terminals
of the power supply to the vertical input terminals of the 5-29 Load Transient Recovery Time
scope. When using a twisted pair, care must be taken that Definition: The time "X" for output voltage
one of the two wires is connected to the grounded input recovery to within "Y" millivolts of the nominal output
terminal of the oscilloscope to ensure that the supply voltage following a "Z" amp step change in load current,
output is safely grounded. When using shielded two-wire, it where: "Y" equals 15mV, and "Z" is the specified load
is essential for the shield to be connected to ground at one current change, equal to half of the current rating of the
end only to prevent ground current flowing through this supply. The nominal output voltage is defined as the dc
shield from inducing a signal in the shielded leads. level halfway between the static output voltage before
and after the imposed load change.
5-26 To verify that the oscilloscope is not displaying
ripple that is induced in the leads or picked up from the 5-30 Measurement Techniques. Care must be taken in
grounds, the (+) scope lead should be shorted to the (-) switching the load resistance on and off. A hand-operated
scope lead at the power supply terminals. The ripple value switch in series with the load is not adequate since the re-
obtained when the leads are shorted should be subtracted sulting one-shot displays are difficult to observe on most
from the actual ripple measurement. oscilloscopes and the arc energy occurring during switching
completely masks the display with a noise burst. Transistor
5-27 In most cases, the single-ended scope method of load switching devices are expensive if reasonably rapid load
Figure 5-4B will be adequate to eliminate extraneous ripple
so that a satisfactory measurement may be obtained.
However, in more stubborn cases (or if high frequency
noise up to 20 MHz must be measured). it may be
necessary to use a differential scope with floating input as
shown in Figure 5-4C. If desired, two single-conductor
shielded cables may be substituted in place of the shielded
two-wire cable with equal success. Because of its common
mode rejection. a differential oscilloscope displays only the
difference in signal between its two vertical input terminals,
thus ignoring the effects of any common mode signal pro-
duced by the difference in the ac potential between the
power supply case and scope case. Before using a differen-
tial input scope in this manner, however, it is imperative
that the common mode rejection capability of the scope be
verified by shorting together its two input leads at the
power supply and observing the trace on the CRT. If this
trace is a straight line, then the scope is properly ignoring
any common mode signal present. If this trace is not a
straight line, then the scope is not rejecting the ground
signal and must be realigned in accordance with the manu-
facturer's instructions until proper common mode rejection
is attained

5-28 Measurement Procedure. To measure the ripple


and noise on each supply output, follow the steps Figure 5-5. Load Transient Recovery Time, Test Setup
below, If a high frequency noise measurement is desired,

5-5
current changes are to be achieved. Instead, a mercury- h. Adjust the sync controls separately for the positive
wetted relay should be used for loading and unloading the and negative going transients so that not only the recovery
supply. Connect it in the load switching circuit shown in waveshape but also as much as possible of the rise time of
Figure 5-5. When this load switch is connected to a 60 Hz the transient is displayed.
ac input, the mercury-wetted relay will open and close 60 i. Starting from the major graticule division
times per second. The 25K control adjusts the duty cycle representing time zero, count to the right 50µs and
of the load current switching to reduce jitter in the oscillo- vertically 15mV. Recovery should be within these
scope display. This relay may also be used with a 50 Hz ac tolerances, as illustrated in Figure 5-6.
input.
5-32 TROUBLESHOOTING
5-31 Measurement Procedure. To measure the load
transient recovery time, follow the steps below for each 5-33 Before attempting to troubleshoot this instrument,
supply output. Transient recovery time may be measured at ensure that the fault is in the instrument itself and not in
any input line voltage and any output voltage within rating. an associated piece of equipment. You can determine this
For this supply the specified load change is between half load without removing the covers from the instrument by using
and full load. the appropriate portions of the performance test of
a. Connect the test setup shown in Figure 5-5. Both paragraph 5-6.
load resistors (RL) are twice the normal value of a full load
resistance. 5-34 A good understanding of the principles of opera-
b. Turn on the supply and close the line switch on the tion is a helpful aid in troubleshooting, and the reader is
repetitive load switch. advised to review Section IV of the manual before begin-
c. Set the oscilloscope for internal sync and lock on ning detailed troubleshooting. Once the principles of oper-
either the positive or negative load transient spike. ation are understood, proceed to the initial troubleshooting
d. Set the vertical input of the oscilloscope for ac coup- procedures in paragraph 5-35.
ling so that small dc level changes in the output voltage of
the power supply will not cause the display to shift. ———CAUTION———
e. Adjust the horizontal positioning control so that the
trace starts at a point coincident with a major graticule Before applying power to the supply, make
division. This point then represents time zero. certain that its line voltage selector switch (S3)
f. Adjust the vertical centering of the scope so that the is set for the line voltage to be used. (See
tail ends of the no-load and full-load waveforms are CAUTION notice in paragraph 3-2 for additional
symmetrically displaced about the horizontal center line of information on S3.)
the oscilloscope. This center line now represents the nominal
output voltage defined in the specification. 5-35 Initial Troubleshooting Procedure
g. Increase the sweep rate so that a single transient
spike can be examined in detail. 5-36 If a malfunction is found, follow the steps below:
a. Disconnect input power from the supply and
remove all loads from the output.
b. Table 5-2 lists the symptoms and probable
causes of several possible troubles. If the symptom is one
of those listed, make the recommended checks.
c. If none of the symptoms of Table 5-2 apply,
proceed to Table 5-3. This table provides an initial
troubleshooting procedure that also directs you to the
more detailed procedures which follow it.

5-37 The numbered test points referred to in the trouble-


shooting procedures are identified on the circuit schematic
and on the component location diagram at the rear of the
manual.

5-38 Open Fuse Troubleshooting

Figure 5-6. Load Transient Recovery Time Waveforms 5-39 Although transients or fatigue can cause a fuse to

5-6
Table 5-2. Miscellaneous Troubles

SYMPTOM CHECK - PROBABLE CAUSE

High ripple a. Check operating setup for ground loops (see paragraph 5-22).

b. Check main rectifiers (CR11, CR12, CR31, CR32, CR51, CR52)


for open.

c. Supply may be operating in current limit mode. Check current


limit adjustment, paragraph 5-26, steps (l) thru (t).

Will not current limit Check for open OR-gate diodes (CR5, CR25, CR45) or defective
current limit amplifier (U1, U2, U3).

Poor load or line regulation a. Check bias and reference voltages, Table 5-4.

b. Check main rectifiers and filters for opens.

Oscillation or poor transient a. High frequency oscillations (above 50 kHz) can be caused by an
recovery time open C4, C14, or C24.

b. A defective output capacitor (C1, C11, or C21) can cause


oscillations in one of many frequency ranges.

c. Oscillation only in the current limiting mode can be caused


by an open C3, C13, or C23.

Transient voltage overshoot a. Overshoot only in the -20V supply can be caused by a
at turn-on or turn-off. shorted Q13.

b. Overshoot in all three supply outputs can be caused by an


open Q14 or a shorted Q15.

Table 5-3. Initial Troubleshooting Procedure

STEP ACTION RESPONSE NEXT ACTION


1 Check output voltage of +20V a. Normal a. Proceed to step (2).
supply.
b. Zero volts b. Check ac line fuse (F1). If blown, proceed
to paragraph 5-38. If not blown, check
bias and reference voltages (Table 5-4).

c. Output voltage lower c. Check bias and reference voltages


or higher than rating. (Table 5-4).

2 Check output voltage of -20V a. Normal a. If +20V and -20V outputs are both
supply in fixed tracking ratio normal with no load, a supply might
mode. be current limiting under load. To check
this adjustment see paragraph 5-16,
steps (l) thru (p).

b. High, low, or zero b. Proceed to -20V supply troubleshooting,


output voltage. Table 5-6.

5-7
Table 5-3. Initial Troubleshooting Procedure (Continued)

STEP ACTION RESPONSE NEXT ACTION

3 Check output of +6V supply a. Normal a. If the output of this supply is normal
(Model 6236B) unloaded but its voltage falls when
or+18V supply loaded, check the current limit adjust
(Model 6237B). ment, paragraph 5-16, steps (q) thru (t).

b. High, low, or zero b. Proceed to Table 5-7.


output voltage.

Table 5-4. Bias and Reference Voltage Check

STEP ACTION RESPONSE PROBABLE CAUSE

1 Check +7.5V bias, TP1 to a. Normal a. Proceed to step (2).


common (+7.5V±5%)

b. Voltage high b. Check VR3 for open.

c. Voltage low c. Check VR3 for short.

Note: A short within U1, U2, U3, or U4 can


cause low +7.5V or -12.4V bias voltages

2 Check -6.2V reference, a. Normal a. Proceed to step (3).


TP2 to common (-6.2V±5%)

b. Voltage high b. Check VR1 for open.

c. Voltage low c. Check VR1 and Q14 for short, VR2


and Q15 for open. (A short within U4
could reduce this voltage.)

3 Check -12.4V bias, a. Normal a. Proceed to +20V supply troubleshooting


TP3 to common (-12.4V±5%) Table 5-5.

b. High voltage b. Check Q11 for short, Q12 for open,


and Z1 for open between pins 3 and 5.

c. Low voltage c. Check Q11 for open, Q12 for short, and
Z1 for open between pins 1 and 3.

5-8
Table 5-5. +20V Supply Troubleshooting

SYMPTOM STEP - ACTION RESPONSE - PROBABLE CAUSE

High output voltage 1. Attempt to turn down a. If output voltage remains high, check Q1, Q15,
(higher than rating) loop by shorting Q15 emitter- and CR9 for short.
to-base
b. If output voltage falls to near zero, remove short
from Q15 and proceed to step (2).

2. Measure voltage at Out- a. If TP4 is approx. -0.7V, check for open CR6 or
put of OR-gate (TP4). R1, and defective U1.

b. If TP4 is approx. +0.7V, check for defective Q2.

Low output voltage 1. Measure voltage at out- a. If TP4 is between zero and -0.7V, check for
(lower than rating) put of OR-gate (TP4). open Q1, Q15, R14, or CR59, and defective Q2.

b. If TP4 is approx. +0.7V, proceed to step (2).

2. Measure voltage at TP8. a. If voltage at TP8 is positive, check Z1 for open


between pins 5 and 13, check R8 for open, and
check for defective R6 or U1.

b. If TP8 is approx. -0.7V, proceed to step (3).

3. Measure voltage at TP7. a. If TP7 is approx. +0.7V, check CR6 for short.

b. If TP7 is approx. +1.4V, proceed to step (4).

4. Measure voltage at TP13. a. If TP13 is approx. -0.7V, replace U1.

b. If TP13 is zero volts, check for open R10, and


shorted CR2 or CR3.

c. If TP13 is approx. +0.7V, check for open R2,


shorted R1, or leaky or shorted C2.

Table 6-6. -20V Supply Troubleshooting

SYMPTOM STEP - ACTION RESPONSE - PROBABLE CAUSE

NOTE: The +20V supply must operate properly


before troubleshooting the -20V supply.

High output voltage 1. Attempt to turn down a. If output voltage remains high, check Q3, CR29,
(more than 1% greater loop by shorting Q13 and Q13 for short.
than +20V supply in emitter-to-base. b. If output falls to near zero, remove short from Q13 and
fixed tracking ratio proceed to step (2).
mode). 2. Measure voltage at out
put of OR-gate (TP5) a. If voltage at TP5 is zero or negative, check for
defective Q4.

b. If TP5 is positive, proceed to step (3)

5-9
Table 5-6. -20V Supply Troubleshooting (Continued)

SYMPTOM STEP - ACTION RESPONSE - PROBABLE CAUSE

3. Measure voltage at TP14. a. If TP14 is approx. -0.7V, check for open CR26
or defective U2.

b. If TP14 is approx. +0.7V, check Z1 for open from


pin 7 to 12 or for short from pin 6 to 12.

Low output voltage 1. Measure voltage at TP5. a. If voltage at TP5 is zero or positive, check for open
(more than 1% lower Q3, Q13, or R34, and defective Q4.
than +20V supply in
fixed tracking ratio b. If TP5 voltage is approx. -0.7V, proceed to step
model (2).

2. Measure voltage at TP9. a. If TP9 is negative, check for open Z1 between


pins 5 and 15, open R28, and defective R26 or U2.

b. If TP9 is approx. +0.7V, proceed to step (3).

3. Measure voltage at TP10. a. If TP10 is approx. -0.7V, check CR26 for short.

b. If TP10 is -1.0 to -1.4V, proceed to step (4).

4. Measure voltage at TP14. a. If TP14 is approx. +0.7V, replace U2.

b. If TP14 is zero volts, check for shorted CR22 or CR23.

c. If TP14 is approx. -0.7V, check 2;1 for open between


pins 6 and 12 or short between pins 7 and 12, and
check for leaky or shorted C12.

Table 5-7. +6V or +18V Supply Troubleshooting

SYMPTOM STEP – ACTION RESPONSE - PROBABLE CAUSE


High output voltage 1. Attempt to turn down loop a. If output voltage remains high, check Q7, Q15,
(higher than rating) by shorting Q15 emitter-to-base. and CR49 for short.

b. If output voltage falls to near zero, remove short


from Q15 and proceed to step (2).

2. Measure voltage at output a. If TP6 is approx. -0.7V, check for open CR46 or
of OR-gate (TP6). R41, and defective U3.

b. If TP6 is approx. +0.7V, check for defective Q8.

Low output voltage 1. Measure voltage at output a. If TP6 is between zero and -0.7V, check for open
(lower than rating) of OR-gate (TP6) Q7, Q15, R54, or CR59, and defective Q8.

b. If TP6 is approx.+0.7V, proceed to step (2).

5-10
Table 5-7. +6V or +18V Supply Troubleshooting (Continued)

SYMPTOM STEP - ACTION RESPONSE - PROBABLE CAUSE

2. Measure voltage at TP12. a. If voltage at TP12 is positive, check for shorted


R49, open R48, open Z1 between pins 5 and 14,
and defective R46 or U3.

b. If TP12 is approx. -0.7V, proceed to step (3).


3. Measure voltage at TP11. a. If TP11 is approx. +0.7V, check CR46 for short.

b. If TP11 is approx. +1.4V, proceed to step (4).

4. Measure voltage at TP15. a. If TP15 is approx. -0.7V, replace U3.

b. If TP15 is zero volts, check for open R50, and


shorted CR42 or CR43.

c. If TP15 is approx. +0.7V, check for shorted R41,


open R42, or leaky or shorted C22.

blow, it is a good idea to inspect the unit for obvious a semiconductor, use the listed Hewlett-Packard part or
shorts such as damaged wiring, charred components, or exact commercial replacement if these are available. If
extraneous metal parts or wire clippings in contact with neither of these are immediately available and a part is
circuit board conductors before replacing the fuse. The needed without delay for operation or troubleshooting
rating of the correct replacement fuse depends on the line verification, the parts designated Note 1, Alternate Part
voltage option of the instrument: for Options 100 or 120, Number can be tried with a high probability of success.
use a normal time-constant 2-amp fuse (HP Part No. 2110-
0002); for Options 220 or 240, use a normal time- 5-45 Notice that both the commercial and alternate re-
constant 1-amp fuse (HP Part No. 2110-0001). placements listed in Table 6-4 apply only to the HP power
supplies covered by this manual and their use in any other
Hewlett-Packard instrument is not necessarily
5-40 REPAIR AND REPLACEMENT recommended because of inclusion in this table.

5-41 Series Regulator Replacement 5-46 ADJUSTMENT AND CALIBRATION

5-42 To remove and replace a series regulator transistor: 5-47 Current Limit Adjustment
a. Remove the top and bottom covers from the instru-
ment. 5-48 ±20V Supplies. Perform the following steps to
b. Remove the collector screws and unsolder the base adjust the current limit circuit in the +20V or -20V supply.
and emitter leads from the board to remove the transistor. Potentiometer R6 sets the +20V and R26 the -20V current
c. To replace the transistor, follow the below reassembly limit.
order, as viewed from the bottom of the heat sink: collector a. Turn the TRACKING RATIO control to the FIXED
screws, P. C. board, heat sink, two insulating bushings (in position.
collector screw holes in heatsink), silicon grease (Dow DC-5 b. Turn the current limit adjustment pot (R6 or R26)
or HP 8500-0059), mica insulator, another coating of silicon fully counterclockwise to its minimum setting.
grease, transistor, lock-washers, and hex-nuts. c. Connect the test circuit of Figure 5-3 to the output of
d. Resolder the emitter and base pins to the circuit the supply to be adjusted. Use a 40Ω 10W resistor for RL.
board. d. Turn on the supply and set the ±20V VOLTAGE
control for maximum output (fully clockwise).
5-43 Semiconductor Replacement e. Turn the current limit pot (R6 or R26) slowly
clockwise until the DVM indicates a voltage drop across the
5-44 Table 6-4 contains replacement data for the shunt corresponding to a current of 0.55A ±5%.
semiconductors used in this power supply. When replacing

5-11
5-49 +6V Supply (Model 6236B). To adjust the will be the same. Adjust R58 so that the percentage error
current limit circuit in the +6V supply, proceed as follows; in the +6V range (or +18V range) is equal to the error in
a. Check the setting of the current limit by performing the 20-volt ranges. Turn R58 clockwise to increase the
steps (r) and (s) of paragraph 5-16. (Be sure to set the indications or counterclockwise to decrease them. If R58
output voltage to 6 volts.) If reducing the load resistance cannot calibrate all voltmeter ranges to within the ±4%
permits the current to exceed 2.9A, stop, turn R46 slightly specification, check the values of the resistors in the
clockwise, and repeat the test. If, instead, the current voltmeter circuit.
begins to fall before it reaches 2.6A, turn R46 slightly
counterclockwise and repeat the test. 5-53 Panel Ammeter. Check and calibrate the panel
b. Recheck the setting and readjust R46 until the test ammeter by following the steps below.
shows that the current limit circuit begins to reduce the a. Connect the test setup shown in Figure 5-3 to the
current when a decreasing load resistance increases it to +6V (or +18V) output. Make the total resistance of RL
2.75A ±5%. and the current sampling resistor 2.4 ohms (Model 6236B)
or 18 ohms (6237B) to permit operating the supply at its
5-50 +18V Supply (Model 6237B). To adjust the full rated output. RL should have a power rating of at least
current limit circuit in the +18V supply, proceed as follows: 20 watts.
a. Turn current limit adjustment pot (R46) fully clock b. Close the switch and set the +6V (+18V) VOLTAGE
wise to its minimum setting. control so that the DVM indicates an output of 2.5A
b. Connect the test circuit of Figure 5-3 to the output (6236B) or 1.0A (6237B).
of the +18V supply. Use an 18Ω 20W resistor for RL. c. Check and record the panel ammeter accuracy on the
c. Turn on the supply and set the +18V VOLTAGE +6V or +18V range.
control for maximum output (fully clockwise). d. Check each of the 20-volt ammeter ranges similarly,
d. Turn current limit pot (R46) slowly counterclockwise using the same test setup but making RL a 40Ω 10W
until the DVM indicates a voltage drop across the shunt resistor and setting the voltage control for a 0.5A output
corresponding to a current of 1.1 A ±5%. current. Record the panel ammeter accuracy on each 20-volt
range.
5-51 Meter Calibration e. Turn R59 clockwise to increase the indications on all
three ranges or counterclockwise to decrease them.
5-52 Panel Voltmeters. Check the accuracy of the f. If R59 cannot calibrate all three ammeter ranges to
panel voltmeter by performing steps (a), (b), and (c) of the within the ±4% specification, check the values of the resis-
procedure in paragraph 5-16. Since the same range tors in the circuit, including current monitoring resistors R8,
resistors are used in both 20-volt ranges, their accuracy R28, and R48.

5-12
SECTION VI
REPLACEABLE PARTS

Table 6-1. Reference Designators (Continued)


6-1 INTRODUCTION
P = plug V = vacuum tube,
6-2 This section contains information for ordering re- Q = transistor neon bulb,
placement parts. Table 6-4 lists parts in alpha-numeric R = resistor photocell, etc.
order by reference designators and provides the following S = switch VR = zener diode
information: T = transformer X = socket.
a. Reference Designators. Refer to Table 6-1. TB = terminal block Z = integrated cir-
b. Description. Refer to Table 6-2 for abreviations. TS = thermal switch cuit or network
c. Total Quantity (TQ). Given only the first time
the part number is listed except in instruments containing
many sub-modular assemblies, in which case the TQ appears
the first time the part number is listed in each assembly.
Table 6-2. Description Abbreviations
d. Manufacturer's Part Number or Type.
e. Manufacturer's Federal Supply Code Number.
Refer to Table 6-3 for manufacturer's name and address. A = ampere mod. = modular or
f. Hewlett-Packard Part Number. Ac = alternating current modified
g. Recommended Spare Parts Quantity (RS) for assy. = assembly mtg = mounting
complete maintenance of one instrument during one year of bd = board n = nano = 10-9
isolated service. bkt = bracket NC = normally closed
h. Parts not identified by a reference designator are °C = degree Centigrade NO = normally open
listed at the end of Table 6-4 under Mechanical and /or cd = card NP = nickel-plated
Miscellaneous. The former consists of parts belonging to and coef = coefficient Ω = ohm
grouped by individual assemblies; the latter consists of all comp = composition obd = order by
parts not immediately associated with an assembly. CRT = cathode-ray tube description
CT = center-tapped OD = outside diameter
6-3 dc = direct current p = pico=1012
ORDERING INFORMATION
DPDT = double pole, P.C. = printed circuit
6-4 To order a replacement part, address order or in- double throw pot. = potentiometer
quiry to your local Hewlett-Packard sales office (see lists DPST = double pole, p-p = peak-to-peak
at rear of this manual for addresses). Specify the single throw ppm = parts per million
following information for each part: Model, complete serial elect = electrolytic pvr = peak reverse
number, and any Option or special modification (J) encap = encapsulated voltage
numbers of the instrument; Hewlett-Packard part number; F = farad rect = rectifier
circuit reference designator; and description. To order a °F = degree Farenheit rms = root mean square
part not listed in Table 6-4, give a complete description of fxd = fixed Si = silicon
the part, its function, and its location. Ge = germanium SPDT = single pole,
H = Henry double throw
Hz = Hertz SPST = single pole,
Table 6-1. Reference Designators IC = integrated circuit single throw
ID = inside diameter SS = small signal
incnd = incandescent T = slow-blow
A = assembly E = miscellaneous
k = kilo = 103 tan. = tantalum
B = blower (fan) electronic part
m = milli = 10-3 Ti = titanium
C = capacitor F = fuse
M = mega = 106 V = volt
CB = circuit breaker J = jack, jumper µ = micro = 10-6 var = variable
CR = diode K = relay met. = metal ww = wirewound
DS = device, signaling L = inductor mfr = manufacturer W = Watt
(lamp) M = meter

6-1
Table 6-3. Code List of Manufacturers

CODE MANUFACTURER ADDRESS CODE MANUFACTURER ADDRESS

01121 Allen Bradley Co. Milwaukee, WI 09353 C & K Components Inc. Newton, MA
02114 Ferroxcube Corp. Saugerties, NY 19701 Electra/Midland Corp. Mineral Wells, TX
02582 Clarostat Mfg. Co., Inc. Dover, NH 27014 National Semiconductor
02735 Radio Corp. of America, Solid State and Corp. Santa Clara, CA
Receiving Tube Div. Somerville, NJ 28480 Hewlett-Packard Co. Palo Alto, CA
03508 G. E. Semiconductor 61637 Union Carbide Corp. New York, NY
Products Dept. Syracuse, NY 71450 CTS Corp. Elkhart, IN
04200 Sprague Electric Co. North Adams, MA 72136 Electro Motive Mfg.Co., Inc.
04713 Motorola Semiconductor Willimantic, CT
Prod. Inc. Phoenix, AZ 75042 IRC Div. of TRW, Inc. Philadelphia, PA
05524 Dale Electronics Inc. Columbus, NE 75915 Littlefuse,Inc. DesPlaines,IL
05820 Wakefield Engr. Inc. Wakefield, MA
05917 Aktiebolaget Rifa Bromma, Sweden
07716 IRC Div. of TRW Inc. Burlington, IA

6-2
Table 6-4. Replaceable Parts

REF. MFR. MFR. HP


DESIG. DESCRIPTION TQ* PART NO. CODE PART NO. RS

Printed Circuit Board Assy.


C1 fxd, elect 180µF 50V 2/3 672D047 04200 0180-0634 1
C2 fxd, tant 6.8µF 35V 3 150D685X9035B2 04200 0180-0116 1
C3, 4 fxd, polyester 2200pF 200V 2 292P22292-PTS 04200 0160-0154 1
C7 fxd, elect 1450µF 45V 2 (Type68D) D39532 04200 0180-1893 1
C8, 9 fxd, cer .05µF 400V 6/4 33C17A3-CDH 04200 0150-0052 1
C11 fxd, elect 180µF 50V 672D047 04200 0180-0634
C12 fxd, tant 6.8µF 35V 150D685X9035B2 04200 0180-0116
C13 fxd, polyester .01µF 200V 2 292P10392-PTS 04200 0160-0161 1
C14 fxd, polyester 3300pF 200V 1 292P33292-PTS 04200 0160-0155 1
C17 fxd, elect 1450µF 45V (Type 68D) D39532 04200 0180-1893
C18, 19 fxd, cer .05µF 400V 33C17A3-CDH 04200 0150-0052
C21
6236B fxd, elect 1000µF 12V 1 627D046 04200 0180-0633 1
6237B fxd, elect 180µF 50V 672D047 04200 0180-0634
C22 fxd, tant 6.8µF 35V 150D685X9035B2 04200 0180-0116
C23 fxd, cer .005µF 100V 1 C023B101E502MS27 04200 0160-2639 1
C24 fxd, polyester .01µF 200V 292P10392-PTS 04200 0160-0161
C27
6236B fxd, elect 5600µF 25V 1 (Type 32D) D40018 04200 0180-1921 1
6237B fxd, elect 3000µF 40V 1 32D5278-DQB 04200 0180-1899 1
C28, 29
6236B fxd, cer .05µF 400V 33C17A3-CDH 04200 0150-0052
6237B Not used
C30
6236B Not used
6237B fxd, cer 0.1µF 500V 1 41C92B5-CDH 04200 0160-0269 1
C31
6236B fxd, tant 0.47µF 35V 1 150D474X9035A2 04200 0180-0376 1
6237B fxd, elect 0.15µF 35V 1 T110A154K035AS 61637 0180-0218 1
C32 fxd, mica 330pF 500V 1 obd 72136 0160-2012 1
C33 fxd, elect 490µF 85V 1 (Type 68D) D38618 04200 0180-1888 1
C34 fxd, paper 0.1µF 250Vac 1 PME271-M-610 05917 0160-4065 1
CR1 Diode, Si 1A 200V 13/15 1N5059 1901-0327 7
CR2-7 Diode, Si 17 1N485B 1901-0033 7
CR9, 11, 12, 21 Diode, Si 1A 200V 1N5059 1901-0327
CR22-26 Diode, Si 1N485B 1901-0033
CR28,29,31,32 Diode, Si 1A 200V 1N5059 1901-0327
CR41 Diode, Si 1.5A 200V 3 1N4999 1901-0416 3
CR42, 43 Diode, Si 1N485B 1901-0033
CR44 Diode, stabistor 150mA 15V 2 STB523 03508 1901-0460 2
CR45-47 Diode, Si 1N485B 1901-0033
CR49 Diode, Si 1A 200V 1N5059 1901-0327
CR51, 52 Diode, Si 1.5A 200V 1N4999 1901-0416
CR53, 54
6236B Not used
6237B Diode, Si 1A 200V 1N5059 1901-0327
CR55, 56 Diode, Si 1A 200V 1N5059 1901-0327
CR57 Diode, stabistor 150mA 15V STB523 03508 1901-0460
CR59 Diode, Si 1A 200V 1N5059 1901-0327

* 6236B/6237B
6-3
Table 6-4. Replaceable Parts (Continued)

REF. MFR. MFR. HP


DESIG. DESCRIPTION TQ* PART NO. CODE PART NO. RS

CR60 Diode, Si 1N485B 1901-0033


L1, 2, 3 Inductor, ferrite bead 3 56-590-65/4A6 02114 9170-0894 1
(Q2, Q3, CR49)
Q2 SS NPN Si 3 SS1147 (Note1) 04713 1854-0448 3
Q4 SS PNP Si 1 2N2904A 1853-0012 1
Q11 Power PNP Si 1 2N3740 1853-0052 1
Q12 SS NPN Si SS1147 (Note 1) 04713 1854-0448
Q13 SS PNP Si 1 2N4036 1853-0041 1
Q14 SS NPN Si 1 2N2714A 1854-0027 1
Q15 SS NPN Si SS1147 (Note 1) 04713 1854-0448
R1 var. 10k (VOLTAGE ±20V) 2 43X 02582 2100-3461
R2 fxd, film 2.61k 1% 1/8W 1 Type MF4C, T-9 19701 0698-0092 1
R3 fxd, ww 0.1 10% 3W 2 RS-2B 05524 0811-1827 1
R4 fxd, comp 18 5% 1/2W 3 EB1805 01121 0686-1805 1
R6 var. ww 3k 3 Type 110-F4 71450 2100-1823 1
R8 fxd, ww 1.25 1/2% 5W 2 RS5 05524 0811-3384 1
R9 fxd, film 5.49k 1% 1/8W 1 Type MF4C, T-0 19701 0698-3382 1
R10 fxd, film 1.5k 1% 1/8W 1 Type MF4C, T-0 19701 0757-0427 1
R11 fxd, film 110k 1% 1/8W 2 Type MF4C, T-0 19701 0757-0466 1
R12 fxd, film 139 1% 1/8W 3 Type CEA, T-0 07716 0698-4099 1
R13 fxd, comp 15k 5% 1/2W 1 EB 1535 01121 0686-1535 1
R14 fxd, comp 510 5% 1W 1 GB5115 01121 0689-5115 1
R15 fxd, comp 10k 5% 1/2W 2 EB1035 01121 0686-1035 1
R23 fxd, ww 0.25 10% 3W 1 RS-2B 05524 0811-1829 1
R24 fxd, comp 18 5% 1/2W EB1805 01121 0686-1805
R26 var. ww 3k Type 110-F4 71450 2100-1823
R28 fxd, ww 1.25 1/2% 5W RS5 05524 0811-3384
R32 fxd, film 139 1% 1/8W Type CEA, T-0 07716 0698-4099
R33 fxd, film 15k 1% 1/8W 2 Type MF4C, T-0 19701 0757-0446 1
R34 fxd, comp 510 5% 1/2W 1 EB5115 01121 0686-5115 1
R35 fxd, comp 10k 5% 1/2W EB1035 01121 0686-1035
R41 var, 10k 43X 02582 2100-3461
(VOLTAGE +6V or +18V)
R42
6236B fxd, film 8.66k 1% 1/8W 1 Type MF4C, T-9 19701 0698-8076 1
6237B fxd, film 2.87k 1% 1/8W 1 Type MF4C-1 19701 0698-7631 1
R43 fxd, ww 0.1 10% 3W RS-2B 05524 0811-1827
R44 fxd, comp 18 5% 1/2W EB1805 01121 0686-1805
R45
6236B Not used
6237B fxd, film 2k 1% 1/8W 1 CEA993 07716 0757-0283 1
R46 var. ww 3k Type 110-F4 71450 2100-1823
R47
6236B fxd, film 23k 1% 1/8W 1 Type MF4C, T-0 19701 0698-3269 1
6237B Not used
R48
6236B fxd, ww 0.25 1/2% 5W 1 RS5 05524 0811-3383 1
6237B. fxd, ww 0.625 1/2% 5W 1 RS5 05524 0811-3395 1
R49
6236B fxd, film 750 1% 1/8W 1 Type MF4C, T-0 19701 0757-0420 1
6237B Not used

Note 1: Alternate part number. See para. 5-43.


6-4
Table 6-4. Replaceable Parts (Continued)

REF. MFR. MFR. HP


DESIG. DESCRIPTION TQ* PART NO. CODE PART NO. RS

R50
6236B fxd, film 330 1% 1/8W 1 Type MF4C, T-9 19701 0698-5663 1
6237B fxd, film 3.83k 1% 1/8W 1 Type MF4C-1 19701 0698-3153 1
R51 fxd, film 110k 1% 1/8W Type MF4C, T-0 19701 0757-0466
R52 fxd, film 139 1% 1/8W Type CEA, T-0 07716 0698-4099
R53 fxd, comp 7.5k 5% 1/2W 1 EB7525 01121 0686-7525 1
R54
6236B fxd, ww 50 5% 10W 1 Type 247E 04200 0811-1902 1
6237B fxd, ww 135 5% 10W 1 Type 247E 04200 0811-1905 1
R55
6236B fxd, comp 2.2k 5% 1/2W 1 EB2225 01121 0686-2225 1
6237B fxd, comp 11k 5% 1/2W 1 EB1135 01121 0686-1135 1
R56 fxd, film 270 1% 1/8W 1 Type CEA, T-0 07716 0757-0269 1
R57 fxd, film 221k 1% 1/8W 1 Type MF4C, T-0 19701 0757-0473 1
R58,59 var. ww 250 2 Type 110 71450 2100-0439 1
R60 fxd, film 15k 1% 1/8W Type MF4C, T-0 19701 0757-0446
R61 fxd, comp 240 5% 1/2W 1 EB2415 01121 0686-2415 1
R62 fxd, film 11k 1% 1/8W 2 Type MF4C, T-0 19701 0757-0443 1
R63 fxd, film 3.6k 2% 1/8W 1 Type MF4C, T-0 19701 0757-0937 1
R64 fxd, film 11k 1% 1/8W Type MF4C, T-0 19701 0757-0443
R65 fxd, film 16.2k 1% 1/8W 1 Type MF4C, T-0 19701 0757-0447 1
R66 fxd, film 470 1% 1/4W 1 Type MF52C, T-0 19701 0698-3506 1
R67
6236B fxd, ww 135 5% 3W 1 Type 242E 04200 0812-0112 1
6237B fxd, ww 220 5% 2W 1 Type BWH 75042 0811-1763 1
R68
6236B fxd, ww 250 5% 3W 1 Type 242E 04200 0811-1219 1
6237B fxd, ww 490 5% 3W 1 Type 242E 04200 0811-1801 1
R69
6236B fxd, ww 100 5% 10W 1 Type 247E 04200 0811-1903 1
6237B fxd, ww 150 5% 10W 1 Type 247E 04200 0811-1906 1
R70
6236B fxd, ww 40 5% 5W 1 Type 243E 04200 0812-0083 1
6237B fxd, ww 75 5% 5W 1 RS5 05524 0812-0097 1
R71 fxd, film 471 1% 1/8W 1 Type CMF-55-1, T-1 05524 0698-5514 1
R72 fxd, comp 33k 5% 1/2W 1 EB3335 01121 0686-3335 1
R73,6236B Not used
6237B fxd,comp 1.1M 5% 1/2W 1 EB1155 01121 0686-1155 1
R74,6236B (jumper installed)
6237B fxd, film 6.98k 1% 1/8W 1 Type CMF-55-1, T-1 05524 0698-4470 1

R76 fxd, ww 10k 5% 3W 1 RS-2B 05524 0811-1816 1


S3 slide switch, dual DPDT 1 28480 3101-1914 1
T1 Power Transformer 28480 06236-80091
U1-3 Dual op amp, IC 3 CA 3458T (Note 1) 02735 1826-0092 3

U4 Operational amp, IC 1 LM301AH 27014 1820-0223 1


VR1 Diode, zener 6.2V 1 1N825 1902-1221 1
VR2 Diode, zener 9.09V 1 SZ10939-170 04713 1902-3149 1
VR3 Diode, zener 7.5V 1 1N4353B 1902-0650 1
Z1 Resistor network 1 28480 1810-0217
1
Note 1: Alternate part number. See para. 5-43.

6-5
Table 6-4. Replaceable Parts (Continued)

REF. MFR. MFR. HP


DESIG. DESCRIPTION TQ* PART NO. CODE PART NO. RS

Front Panel - Electrical


DS1 Indicator light, LINE ON 1 28480 1450-0566 1
M1
6236B Voltmeter, 0-25V 1 28480 1120-1380 1
6237B Voltmeter, 0-25V 1 28480 1120-1382 1
M2
6236B Ammeter, 0-3A 1 28480 1120-1381 1
6237B Ammeter, 0-1.2A 1 28480 1120-1383 1
S1 Toggle Switch, LINE ON 1 7318-PHI 09353 3101-1694 1
S2 3-pos. rotary switch, METER 1 28480 3100-1943 1

R77 var. 10k (TRACKING RATIO) 1 28480 2100-3656


Rear Heatsink - Electrical
F1 Fuse, 2A 250V (Std. Option
and Option 100) 1 312002 75915 2110-0002 5
F1 Fuse, 1 A 250V (Options 220
and 240) 1 312001 75915 2110-0001 5
Q1, 7 Power PNP Si 2 SJ1528 04713 1853-0063 2
Q3, 8 Power NPN Si 2 2N3055 (Note 1) 1854-0563 2

Circuit Board - Mechanical


Heat Dissipator (CR51, 52, Q2,
Q11 in 6236B; Q2 in 6237B) 4/1 207-CB 05820 1205-0033
Heat Sink (Q11) 1 28480 5000-6025
Spacer (for Q11 heatsink) 2 28480 0380-0004
Rubber bumper 4 28480 0403-0086

Front Panel - Mechanical


Binding Post, red 4 28480 1510-0091
Binding Post, black 1 28480 1510-0107
Meter bezel 2 28480 4040-0571
Spring, compression 8 28480 1460-0720
(meter mount)
Retainer, push-on (for DSI) 1 28480 0510-0123
Knob (R1, R41, R77, S2) 4 28480 0370-1099

Miscellaneous
Bushing, transistor insulator 8 28480 0340-0168
Transistor insulator, mica 4 28480 0340-0174
Fuse holder 1 342014 75915 1400-0084
Lockwasher, fuseholder 1 28480 2190-0054
Nut, nylon 1/2 - 24 1 28480 2950-0131
Foot, rubber 4 28480 0403-0088
Line cord strain relief 1 28480 0400-0013
Line cord 1 see par. 2-21
Chassis assembly, left 1 28480 5060-7955
Chassis assembly, right 1 28480 5060-7956
Front panel (6236B) 1 28480 06236-00001
Front panel (6237B) 1 28480 06237-00001
Heat sink, rear 1 28480 5020-8423
Cover, top and bottom 2 28480 5000-9424
Packing carton 1 28480 9211-2518
Floater pad, packing carton 2 28480 9220-1218

Note 1: Alternate part number. See para. 5-43.

6-6
APPENDIX A
MANUAL BACKDATING CHANGES

To adapt this manual to Model 6236A or 6237A instruments, make the changes indicated in the table below.

MODEL SERIAL NUMBERS MAKE CHANGES

6236A ALL 1
1507A-00141 thru -00350 2
1436A-00101 thru -00127 3

6237A ALL 1
1511A-00101 thru -00170 2

CHANGE 1 :
Delete R76, R77, and all references to the variable tracking
ratio feature.

CHANGE 2:
Change potentiometers R1 and R41 to 10kΩ panel-mounted
type, HP Part No. 2100-1854.

CHANGE 3:
Delete ferrite bead L3, 9170-0894, from the lead of diode
CR49.

A-1
SECTION VII
CIRCUIT DIAGRAMS

7-1 COMPONENT LOCATION DIAGRAM 7.3 SCHEMATIC DIAGRAM

7.4 Figure 7.1 is a combined schematic diagram of the


7-2 The component location diagram for power supply 6236B and 6237B. The test points (circled numbers)
Models 6236B and 6237B is given below. The illustration shown on the schematic correspond to those on the
shows the physical locations and reference designations component location diagram and in the troubleshooting
of parts mounted on the printed circuit card. (Not. all parts procedure in Section V. The tinted areas on the schematic
are used in both models.) indicate components and jumpers used in one model only.

Models 6236B and 6237B, Component locations

7-1
MANUAL CHANGES
Models 6236B and 6237B Triple Output DC Power Supplies
Manual HP Part No. 5950-1782

Make all corrections in the manual according to errata below, then check the following table for your power supply serial
number and enter any listed change(s) in the manual.

Model 6236B Model 6237B

SERIAL MAKE SERIAL MAKE


Prefix Number CHANGES Prefix Number CHANGES

1705A (Note 1) 1 1706A (Note 1) 1


1732A 00601-up 1 1735A 00301-up 1

ERRATA:
The corrugated shipping carton for this model has been
changed to HP Part No. 9211-2570. Two 9220-2703 floater
pads are used.

CHANGE 1 :

Change R34 to 470 ohms, 1/2W, HP Part No. 0686-4715.


Also add three new resistors: R78 and R79, both 825 ohms,
1%, 1/8W, HP Part No. 0757-0421; and R80, 750 ohms,
1%, 1/8W, HP Part No. 0757-0420. R78, R79, and R80
are connected from base to emitter of Q1, Q7, and Q3,
respectively, and are located on the circuit board as
follows: R78 − between Q2 and CR28, R79 − near R55,
and R80 − between Q3 and C17. These changes prevent a
turn-off overshoot.

9-8- 77

Note 1: Change 1 applies to the following instruments from earlier production runs. Model 6236B: serial 1705A-00502,
-505, -507, -526, -533, -534, -536, -541, -544, -546, -547, -573, -577, -594. Model 6237B: serial 1706A-00263,
-264, -269, -272, -291, -296, -298, -299.

You might also like