DC Inverter Duct Type Unit: Indoor Unit Outdoor Unit
DC Inverter Duct Type Unit: Indoor Unit Outdoor Unit
DC Inverter Duct Type Unit: Indoor Unit Outdoor Unit
Thank you for choosing these Air Conditioners, please read this owner’s manual carefully
before operation and retain it for future reference.
Contents
1 Safety Precautions
This mark indicates procedures which, if improperly performed, might
WARNING!
lead to the death or serious injury of the user.
WARNING!
(1). For operating the air conditioner pleasantly, install it as outlined in this installation manual.
(2). Connect the indoor unit and outdoor unit with the room air conditioner piping and cord available
from our standard parts. This installation manual describes the correct connections using the
installation set available from our standard parts.
(3). Installation work must be performed in accordance with national wiring standards by authorized
personnel only.
(4). If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant comes in
contact with a flame, it produces toxic gas.
(5). Do not power on until all installation work is complete.
(6). During installation, make sure that the refrigerant pipe is attached firmly before you run the
compressor.
Do not operate the compressor under the condition of refrigerant piping not attached
properly with 2-way or 3-way valve open.
This may cause abnormal pressure in the refrigeration cycle that leads to breakage and
even injury.
(7). During the pump-down operation, make sure that the compressor is turned off before you
remove the refrigerant piping.
Do not remove the connection pipe while the compressor is in operation with 2-way or
3-way valve open.
This may cause abnormal pressure in the refrigerant cycle that leads to breakage and even
injury.
(8). When installing and relocating the air conditioner, do not mix gases other than the specified
refrigerant (R410A) to enter the refrigerant cycle.
If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to an
abnormally high value and cause breakage, injury, etc.
(9). This appliance is not intended for use by persons (including children) with reduced physical,
sensory or mental capabilities, or lack of experience and knowledge, unless they have been
given supervision or instruction concerning use of the appliance by a person responsible for
their safety.
(10). Children should be supervised to ensure that they do not play with the appliance.
(11). If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or
similarly qualified persons in order to avoid a hazard.
1
DC Inverter Duct Type Unit
Fig. 2.1
NOTE!
①. The connection pipe and duct for this unit should be prepared by the user.
2
DC Inverter Duct Type Unit
3
DC Inverter Duct Type Unit
Table 3.2
Outdoor Unit Accessories
No. Name Appearance Q'ty Usage
Fig. 3.1
4
DC Inverter Duct Type Unit
(4). Install the unit where the drain pipe can be easily installed.
(5). The space from the unit to the ceiling should be kept as much as possible
so as for more convenient service.
①. Install the unit where it will not be tilted by more than 5°.
②. During installation, if the outdoor unit has to be exposed to strong wind, it must be fixed
securely.
(1). If possible, do not install the unit where it will be exposed to direct sunlight.
(If necessary, install a blind that does not interfere with the air flow.)
(2). Install the outdoor unit in a place where it will be free from getting dirty or
getting wet by rain as much as possible.
(3). Install the outdoor unit where it is convenient to connect the indoor unit.
(4). Install the outdoor unit where the condensate water can be drained out
freely during heating operation. Do not place animals and plants in the path
of the warm air.
(5). Take the air conditioner weight into account and select a place where noise
and vibration are small.
(6). Install the outdoor unit where is capable of withstanding the weight of the
unit and generates as less noise and vibration as possible.
(7). Provide the space shown in Fig. 3.2, so that the air flow is not blocked. Also
for efficient operation, leave three of four directions of peripheral
constructions open.
Fig. 3.2
5
DC Inverter Duct Type Unit
Table 3.3
Size of Fitting Max. Max. Height Drainage
Item Pipe(Inch) Pipe Difference between pipe(Outer
Model Length Indoor Unit and Diameter × wall
Liquid Gas (m) Outdoor Unit (m) thickness)(mm)
VFU-18A309I
VFU-18A309O 1/4 1/2 20 15 Φ30X1.5
VFU-24A309I
VFU- 24A309O 3/8 5/8 30 15 Φ20X1.2
VFU-36A309I
VFU- 36A309O 3/8 5/8 30 15 Φ20X1.2
VFU-48A309I
VFU-48A309O 3/8 5/8 50 30 Φ20X1.2
VFU-60A309I
VFU- 60A309O 3/8 3/4 50 30 Φ20X1.2
Notes:
①. The connection pipe should be insulated with proper water-proof insulating material.
②. The pipe wall thickness shall be 0.5-1.0 mm and the pipe wall shall be able to withstand
the pressure of 6.0MPa. The longer the connecting pipe, the lower the cooling and
heating effect performs.
6
DC Inverter Duct Type Unit
Notes:
①. The fuse is located on the main board.
②. Install the disconnect device with a contact gap of at least 3 mm in all poles
nearby the units (Both indoor unit and outdoor unit).The appliance must be
positioned so that the plug is accessible.
③. The specifications of the breaker and power cable listed in the Table above
are determined based on the maximum power (maximum amps) of the unit.
④. The specifications of the power cable listed in the Table above are applied
to the conduit-guarded multi-wire copper cable (like, YJV copper cable,
consisting of PE insulated wires and a PVC cable jacket) used at 40°С and
resistible to 90°С(see IEC 60364-5-52). If the working condition changes,
they should be modified according to the related national standard.
⑤. The specifications of the breaker listed in the Table above are applied to
the breaker with the working temperature at 40°С. If the working condition
changes, they should be modified according to the related national
standard.
⑥. Take 2 pieces of power cord of 0.75mm2 as the communication lines
between indoor and outdoor unit, with their longest lengths of 50m. Please
select the appropriate line length as per the actual installation conditions.
The communication lines can not be twisted together. For the unit (≤30K),
it’s recommended to use 8m long communication line.
⑦. Take 2 pieces of power cord of 0.75mm2 as the communication lines
between the wired controller and the indoor unit, with their longest lengths
of 30m. Please select the appropriate line length as per the actual
installation conditions. The communication lines can not be twisted
together. It’s recommended to use 8m long communication line.
⑧. The wire size of the communication line should be no less than 0.75mm 2.
It’s recommended to take 0.75mm2 power cords as the communication line.
4 Installation of the Unit
4.1 Installation of the Indoor Unit
7
DC Inverter Duct Type Unit
WARNING!
①. Install the indoor unit in a location which can withstand a load of at least five times the weight of
the main unit and which will not amplify sound or vibration.
②. If the installation location is not strong enough, the indoor unit may fall and cause injuries.
③. If the job is done with the panel frame only, there is a risk that the unit will come loose. Please
take care.
8
DC Inverter Duct Type Unit
Fig. 4.1
Table 4.1
Item
A B C D E F G H I J
Model
VFU-18A309I 945 618 738 892 1037 721 738 125 203 266
VFU-24A309I 1101 517 820 1159 1279 558 1002 160 235 268
VFU-36A309I 1011 748 820 1115 1226 775 979 160 231 290
VFU-48A309I 1177 646 852 1150 1340 750 953 190 316 350
VFU-60A309I 1177 646 852 1150 1340 750 953 190 316 350
9
DC Inverter Duct Type Unit
Fig. 4.5
Fig. 4.6
4.1.4 Leveling
The water level test must be done after installing the indoor unit to make the unit
is horizontal, as shown below.
Fig. 4.7
10
DC Inverter Duct Type Unit
Fig. 4.8
Table 4.2 Unit: mm
Item
A B C D E
Model
VFU-18A309O 955 396 700 560 360
VFU-24A309O 980 427 790 610 395
VFU-36A309O 1107 440 1100 631 400
VFU-48A309O 958 412 1349 572 376
VFU-60A309O 1085 427 1365 620 395
11
DC Inverter Duct Type Unit
Fig. 4.9
Fig. 4.10
Fig. 4.11
12
DC Inverter Duct Type Unit
making it difficult to bend or stretch them any more. Do not bend or stretch
the pipes more than three times.
(3). When bending the pipe, do not bend it as is.
The pipe will be collapsed. In this case, cut the
heat insulating pipe with a sharp cutter as
shown in Fig. 4.12, and bend it after exposing
the pipe. After bending the pipe as you want,
be sure to put the heat insulating pipe back on Fig. 4.12
the pipe, and secure it with tape.
CAUTION!
①. To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of curvature of
150 mm or over.
②. If the pipe is bent repeatedly at the same place, it will break.
CAUTION!
Hold the torque wrench at its grip, keeping it in the right angle with the pipe as shown in Fig.
4.13, in order to tighten the flare nut correctly.
When the flare nut is tightened properly by your hand, use a torque wrench to
finally tighten it.
Fig. 4.13
13
DC Inverter Duct Type Unit
Fig. 4.14
Table 4.3 Flare nut tightening torque
Pipe Diameter Tightening Torque
1/4 Inch) 15-30 (N·m)
3/8 Inch) 35-40 (N·m)
5/8 Inch) 60-65 (N·m)
1/2 Inch) 45-50 (N·m)
3/4 Inch) 70-75 (N·m)
7/8 Inch) 80-85 (N·m)
CAUTION!
Be sure to connect the gas pipe after connecting the liquid pipe completely.
Fig. 4.15
14
DC Inverter Duct Type Unit
Fig. 4.16
15
DC Inverter Duct Type Unit
CAUTION!
Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation! There
is no extra refrigerant in the outdoor unit for air purging!
4.4.1 Vacuum
(1). Remove the caps of the liquid valve, gas valve and also the service port.
(2). Connect the hose at the low pressure side of the manifold valve assembly
to the service port of the unit’s gas valve, and meanwhile the gas and liquid
valves should be kept closed in case of refrigerant leak.
(3). Connect the hose used for evacuation to the vacuum pump.
(4). Open the switch at the lower pressure side of the manifold valve assembly
and start the vacuum pump. Meanwhile, the switch at the high pressure
side of the manifold valve assembly should be kept closed, otherwise
evacuation would fail.
(5). The evacuation duration depends on the unit’s capacity, generally, 20
minutes for the 18K units, 30 minutes for the 24/36K units, 45 minutes for
the 48/60K units. And verify if the pressure gauge at the low pressure side
of the manifold valve assembly reads -1.0Mp (-75cmHg), if not, it indicates
there is leak somewhere. Then, close the switch fully and then stop the
vacuum pump.
(6). Wait for some time to see if the system pressure can remain unchanged, 3
minutes for the units less than 18K, 5 minutes for the 18K/24K units, 10
minutes for the 36~60K units. During this time, the reading of the pressure
gauge at the low pressure side can not be larger than 0.005Mp
(0.38cmHg).
(7). Slightly open the liquid valve and let some refrigerant go to the connection
pipe to balance the pressure inside and outside of the connection pipe, so
that air will not come into the connection pipe when removing the hose.
Note that the gas and liquid valve can be opened fully only after the
manifold valve assembly is removed.
(8). Place back the caps of the liquid valve, gas valve and also the service port.
16
DC Inverter Duct Type Unit
Fig. 4.19
Note: For the large-sized unit, it has the service port for both the gas valve and the liquid valve.
During evacuation, it is available to connect two hoses of the manifold valve assembly to two
service ports to quicken the evacuating speed.
17
DC Inverter Duct Type Unit
Fig. 4.20
4.5 Installation of the Drain Hose
Install the drain hose in accordance with the instructions in this installation manual and keep
the area warm enough to prevent condensation. Problems with the piping may lead to water
leaks.
(1). Install the drain hose with downward gradient (1/50 to 1/100) and no risers
or traps are used for the hose.(Fig. 4.21)
(2). Be sure there is no crack or leak on the drain hose to avoid the formation of
air pocket.(Fig. 4.21)
(3). When the hose is long, install supporters.(Fig. 4.22)
(4). Always use the drain hose which has been insulated properly.
Fig. 4.21
18
DC Inverter Duct Type Unit
Fig. 4.24
19
DC Inverter Duct Type Unit
CAUTION!
Always check that the drain cap is installed to the unused drain port and is fastened with the
nylon fastener. If the drain cap is not installed, or is not sufficiently fastened by the nylon
fastener, water may drip during the cooling operation.
(1). Be sure to insulate where the drain port and the drain hose is
connected.(Fig. 4.26 )
(2). The unused drain port also should be insulated properly.(Fig. 4.27)
(3). There is adhesive on one side of the insulation so that after removing the
protective paper over it the insulation can be directly attached to the drain
hose.
(4). Considerations for the unit with the condensate pump:
1). For the unit with the condensate pump, only one drain port at the side close
to the electric box is prepared and only through it the drain hose can be
connected.
2). See Table 3 for the size of the drain port of the unit with the condensate
pump, which is different from that of the unit without the condensate pump.
3). For the unit with the condensate pump, two drain ports at the bottom are
defaulted to be factory plugged with drain caps. After the installation of the
drain hose, these two drain ports also need to be insulated properly with
the same way aforementioned.
4). The drain hose for the unit with the condensate pump should be arranged
as shown in the Figure below.
Fig. 4.28
20
DC Inverter Duct Type Unit
①. The vertical height of the drain hose should be 75mm or less so that it is
unnecessary for the drain port to withstand additional force.
Fig. 4.29
②. When multiple drain hoses are used, their installation should be performed
as shown in the Figure below.
Fig. 4.30
Fig. 4.31
21
DC Inverter Duct Type Unit
22
DC Inverter Duct Type Unit
Fig. 4.34
No. Name No. Name
1 Hanger 5 Filter
Main Air Supply
2 Air Intake Pipe 6
Pipe
3 Canvas Air Pipe 7 Air Supply Outlet
4 Air Intake
CAUTION!
①. The maximum length of the duct means the maximum length of the supply air duct plus the
maximum length of the return air duct.
②. The duct is rectangular and connected with the air inlet/outlet of the indoor unit. Among all
supply air outlets, at least one should be kept open.
Fig. 4.35
23
DC Inverter Duct Type Unit
(3). If the bottom return air is desired, just change the place of the rectangular
flange and the return air cover plate.
(4). Connect one end of the return air duct to the return air outlet of the unit by
rivets and the other to the return air louver. For the sake of the convenience
to freely adjust the height, a cutting of canvas duct will be helpful, which can
be reinforced and folded by 8# iron wire
(5). More noise is likely to be produced in the bottom return air mode than the
backward return air mode, so it is suggested to install a silencer and a static
pressure box to minimize the noise.
(6). The installation method can be chosen with considering the conditions of
the building and maintenance etc., as shown in Fig. 4.36.
Fig. 4.36
Table 4.6 Installation of the return air duct
24
DC Inverter Duct Type Unit
⑤. Use a special branch circuit breaker and receptacle matched to the capacity of the air
conditioner.
⑥. The special branch circuit breaker is installed in the permanent wiring. Always use a circuit that
can trip all the poles of the wiring and has an isolation distance of at least 3 mm between the
contacts of each pole.
⑦. Perform wiring work in accordance with standards so that the air conditioner can be operated
safely and positively.
⑧. Install a leakage special branch circuit breaker in accordance with the related laws and
regulations and electric company standards.
CAUTION !
①. The power source capacity must be the sum of the air conditioner current and the current of
other electrical appliances. When the current contracted capacity is insufficient, change the
contracted capacity.
②. When the voltage is low and the air conditioner is difficult to start, contact the power company to
raise the voltage.
25
DC Inverter Duct Type Unit
Fig. 4.37
(3). How to fix connection cord and power cord by cord clamp
After passing the connection cord and power cord through the insulation tube,
fasten it with the cord clamp.(Fig. 4.39)
WARNING!
①. Before starting work, check that power is not being supplied to the indoor unit and outdoor unit.
②. Match the terminal block numbers and connection cord colors with those of the indoor unit side.
Erroneous wiring may cause burning of the electric parts.
③. Connect the connection cords firmly to the terminal block. Imperfect installation may cause a
fire.
④. Always fasten the outside covering of the connection cord with cord clamps. (If the insulator is
not clamped, electric leakage may occur.)
26
DC Inverter Duct Type Unit
VFU-18A309O +VFU-18A309I
VFU-24A309O +VFU-24A309I
VFU-36A309O +VFU-36A309I
VFU-48A309O +VFU-48A309I
VFU-60A309O +VFU-60A309I
Fig. 4.40
27
DC Inverter Duct Type Unit
Fig. 4.41
The F, C, O connect to the COMMOM, CLOSE and OPEN terminal of the fresh
air valve respectively.
CAUTION!
①. The power cord and the wire of the fresh air valve are high-voltage, while the communication
cord and connection wire of the wired controller are low-voltage. They should run separately
against electromagnetic interference.
②. The high-voltage and low-voltage lines should pass through the rubber rings at different electric
box covers.
③. Do not bundle the connection wire of the wired controller and the communication cord together,
or arrange them in parallel, otherwise improper operation would occur.
④. The high-voltage and low-voltage lines should be fixed separately and securely, with internal big
clamps for the former and small clamps for the latter.
⑤. Tighten the indoor/outdoor connection cord and power cord respectively on the terminal boards
with screws. Faulty connection may cause a fire.
⑥. If the indoor unit connection cord (to the outdoor unit) and power supply are wired incorrectly,
the air conditioner may be damaged.
⑦. Connect the indoor unit connection cord properly based on the corresponding marks as shown
in Fig. 4.40.
⑧. Ground both the indoor and outdoor units by attaching a ground wire.
⑨. Unit shall be grounded in compliance with the applicable local and national codes.
Remove the big handle (18/24K) /front board (36~60K) of the outdoor unit and
insert the end of the communication cord and the power cable into the terminal
board.
28
DC Inverter Duct Type Unit
Single phase:
Fig. 4.42
Power lines should go along the right side plate and be fixed to the fixation
hook with binding wires to keep no contact with pipelines. Communication lines
between indoor and outdoor units also should go along the right side plate and keep
away from power lines.
5 Installation of Controllers
Refer to the Installation Manual of the controller for more details.
6 Test Running
6.1 Trial Operation and Testing
(1). The meaning of error codes as shown below:
Table 6.1
29
DC Inverter Duct Type Unit
30
DC Inverter Duct Type Unit
Note: When the unit is connected with the wired controller, the error code will be
simultaneously shown on it.
(2). Instructions to the Error Indicating Lamps on the Panel of the Duct Type
Unit.
Fig. 6.1
Note:
31
DC Inverter Duct Type Unit
7 Unit Function
7.1 Setting of Double Indoor Room Sensors
This series of ducted air-conditioning unit has two indoor room sensors. One is
located at the air intake of the indoor unit and the other one is located inside the wire
controller.
User can select one from the two indoor room sensors on the basis of the
engineering requirement.
(Refer to the section of wire controller instructions for detailed operation.)
Fig. 7.1
Fig. 7.2
32
DC Inverter Duct Type Unit
Fig. 7.3
33
DC Inverter Duct Type Unit
After carrying out the check of the above items and taking relevant measures to
solve the problems found but the air-conditioning unit still does not function well,
please stop the operation of the unit immediately and contact the local service
agency designated by VICTA. Only ask professional serviceman to check and repair
the unit.
8.2 Routine Maintenance
Only a qualified service person is allowed to perform maintenance.
Before accessing to terminal devices, all power supply circuits must be
disconnected.
Do not use water or air of 50°C or higher for cleaning air filters and outside
panels.
Note:
①. Do not operate the air conditioner with the filter uninstalled, otherwise dust
would come into the unit.
②. Do not remove the air filter except for cleaning. Unnecessary handling may
damage the filter.
③. Do not clean the unit with gasolene, benzene, thinner, polishing powder or
liquid insecticide, otherwise it would cause discoloration and deformation of
the unit.
④. Do not wet the indoor unit in case of electric shock or fire hazard.
Increase the frequency of cleaning if the unit is installed in a room where the air
is extremely contaminated.(As a yardstick for yourself, consider cleaning the filter
34
DC Inverter Duct Type Unit
24~60k:
35