9800XT PN R10263 Ve
9800XT PN R10263 Ve
9800XT PN R10263 Ve
9800 XT™
Warranty: One year. Specifications Subject to change without notice, ISO 9001:2000 Certified. Copyright 2008. All Rights Reserved. Rev 12/01/07 E
Page 1 of 45
ISO 9001 CERTIFIED
Metrotech adheres to the quality standard guidelines of ISO 9001 and ensures quality in
its design/development, production, installation, and servicing disciplines.
Metrotech Corporation
3251 Olcott Street
Santa Clara, CA 95054
USA
Revision E; 12/11/07
Page 2 of 45
TABLE OF CONTENTS
List of Illustrations 4
1 Introduction 6
2 Safety Precautions 6
5 Checkout Procedure 18
6 Operation 19
6.1 Transmitter Set-up 20
6.2 Receiver Operation 25
7 Advanced Techniques 32
7.1 Ground Survey 32
7.2 Adjacent Conductors 34
7.3 Deep Conductor 34
7.4 Tracing Long Runs 34
7.5 Locating a Service Lateral 34
7.6 Locating a Bend or Dead End 34
7.7 Valves, Manhole Cover, T’s and
Risers 35
7.8 Common Bonded Conductors 36
7.9 Conductor Identification Using a
Second Metroclamp 36
7.10 Congested Areas 36
7.11 Determining If You Have a “Ghost”
Conductor 38
7.12 Pipes with Insulated Junctions 38
7.13 Distribution Systems 39
7.14 Non-Metallic Pipes 39
7.15 Tracer Wire 39
8 Maintenance 39
8.1 Replacing the 9800XT Non-
rechargeable D-Cell Transmitter
Batteries 40
8.2 Recharging the 9800XT Transmitter
NiCd Rechargeable Battery 42
8.3 Replacing the 9800XT Receiver
Page 3 of 45
Batteries
8.4 Service Center Information 43
Appendix 44
Copyright Notice 45
Warranty 45
List of Illustrations
Page 4 of 45
Figure 7-2: Adjacent Conductors - Position
of Ground Lead 34
Page 5 of 45
1 INTRODUCTION
This manual describes the Metrotech Model 9800XT Utility Line Locator. Included is an
equipment description, product specifications, checkout procedures, operating
procedures, application information and maintenance instructions.
The Model 9800XT is a series of state-of-the-art utility line locators precisely designed
with many powerful features to provide you with optimum information about your locate
situation.
2 SAFETY PRECAUTIONS
1 Metrotech Utility Line Locators are intended for use by utility and contractor
professionals. Safety hazards for underground utility access areas include
electrical shock, explosive gases, and toxic fumes as well as potential influence
on communications and control systems such as traffic control and railroad
crossings.
2 Familiarize yourself with all required safety practices of the local utility company,
or other owner of the plant before entering an access area or connecting a
Metrotech transmitter.
3 Before connecting the transmitter directly to any conductor, make sure that the
line is de-energized and out of service. Never make a direct connection to a live
power cable.
1 Check Batteries – Turn Transmitter to “L”. If the battery status is low (less than
5 bars) replace or recharge the battery. Turn Transmitter “ON”. Check battery
status. If low (less than 1 bar) replace or recharge batteries. CAUTION: Do
NOT attempt to recharge non-rechargeable D-cell batteries. Damage to the
transmitter will occur.
Page 6 of 45
3 Adjust Receiver Controls - Turn Receiver “ON” and select frequency. By
default, the unit will operate in “Auto” gain mode.
5 Locate Line - Follow your target conductor, sweeping left and right as you walk
away from the Transmitter. Mark the centerline on the ground.
6 Measure Depth - Hold the Receiver over the centerline and push the depth
button. The LCD will display the depth and current measurement.
* All models are available with optional 4.8Hz transmitting capability for sheath fault
locating.
Page 7 of 45
Figure 4-1: Model 9800XT Utility Line Locator - Standard and Optional Equipment
1
3
4 2
10 12 5
11
Standard:
1. 9800XT Receiver
2. 9800XT Transmitter
3. Conductive Attachment
4. Ground Rod
5. Ground Plate
6. Safety Flag
7. Carrying Case
Options:
8. SFL – 2 Receiver
Accessories:
9. MetroClamp
10. Flex-Sonde
11. High Power Sonde
12. Standard Power Sonde
4.3 Accessories
Page 8 of 45
Cable ID
Page 9 of 45
Optional Rechargeable NiCd
Operation
Temperature: -4º to +122º F (-20º to +50º C)
RECEIVER
Receiving
Frequencies: Model Frequencies
9860XT Active - 9.82kHz, 82kHz
Passive - 50/60Hz, 14-22kHz
9890XT Active - 982Hz, 9.82kHz, 82kHz
Passive - 50/60Hz, 14-22kHz
Depth
Readout
Accuracy: Passive-+(5% + 2”) under normal conditions
Active- +(5% + 2”) under normal conditions
Current Measurement
Page 10 of 45
Dimensions: 27”L x 7”W x 9”H
(68.6 cm x 17.8 cm x 22.9 cm)
4.5.1 Transmitter Controls and Indicators - See Figure 4-2 for the location of the
controls and indicators described below:
OUTPUT JACK - Insert the Direct Connect cable or the Metroclamp cable into this jack.
(Located on the left inside wall of the Transmitter).
CONDUCTOR ARROW - Align this arrow with your targeted conductor when you are
locating in the Inductive mode.
BATTERY ACCESS CAPS - Remove end caps to gain access to the batteries. Note
battery polarity, which is indicated on the bottom of the Transmitter and batteries.
Page 11 of 45
9800XT TRANSMITTER
Figure 4-2: 9800XT Transmitter: Controls and Indicators
1 2 3
6 5 4
1 Output Jack
2 Conductor Arrow
3 Charge Jack
4 Frequency Knob
5 LCD Display
6 Power Knob
7 Battery Access Caps
OUTPUT LEVEL - The solid bars indicate the amount of signal strength (current
output) on your conductor.
Page 12 of 45
POOR CONDUCTOR AND IMPROPER SELECTION - Entire display blinks and
Transmitter beeps very fast or emits a constant beeping tone.
POWER KNOB - The amount of transmitter signal output for each power setting
changes according to which frequency you are using:
*Sheath Fault Locating - (Optional on all 9860XT and 9890XT models) Set at this option
for simultaneous sheath fault locating capability. The SFL-2 A-Frame will receive the
4.8Hz sheath fault locating frequency; the 9800XT Receiver will receive the selected
active frequency.
Page 13 of 45
4.5.2 Transmitter Features
Automatic Best Frequency Selection - Chooses the lowest frequency that provides
reliable Receiver response in a typical 500 ft. locate.
Poor Conductor Alert - Warns the user that no frequency will produce a reliable
Receiver response.
3 Watt Output - High power output for low frequencies and long distance locating.
Optional Rechargeable Batteries - Provides money saving power supply for the full
time professional user.
Safety Flag - Reduces repair costs from collision damage by increasing Transmitter
visibility.
Low Battery Alert Transmitted to Receiver - Alerts the user on the Receiver display
that the Transmitter has only approximately 20 minutes of power remaining.
Improper Selection Alert - Warns the user that an improper Transmitter mode has
been selected.
Inductive Antenna - Provides locating capability where utility access is not available.
Multiple Power Levels - Provides maximum flexibility for all locating jobs from high
congestion to long distance tracing.
Page 14 of 45
9800XT RECEIVER
Figure 4-3: 9800XT Receiver - Controls and Indicators
GAIN SETTING
XT
BATTERY OPERATING
STATUS Gain FREQUENCY
AUTO/MANUAL
GAIN
INDICATOR
SIGNAL
STRENGTH
AUTO/MANUAL
GAIN
Rs232 SERIAL
PORT ON/OFF/
VOLUME KNOB
ON/OFF VOLUME KNOB - Turn clockwise to turn unit “ON”. Also controls volume of
audio sound.
Page 15 of 45
LCD DISPLAY (Liquid Crystal Display) - Displays the battery status, operating
frequency, Distance Sensitive Left/Right Guidance™, gain setting, and signal strength.
1 Battery Status
2 Operating Frequency
3 Distance Sensitive Left/Right Guidance
4 Signal Strength
In the Depth Measurement mode it displays the battery status, current measurement,
and depth measurement.
Auto/Manual
Gain
Page 16 of 45
AUX JACK (Left side under display head) - Plug Metroclamp into this jack. Used to
identify one conductor out of a group of conductors.
HEADPHONE JACK (Right side under display head) - Plug headphones into this jack.
SPEAKER (Under the display head) - Emits audio tone to guide operator toward the
targeted conductor.
RS232 SERIAL PORT PROTECTIVE COVER - Remove protective cover to gain access
to RS 232 serial port.
AUTO/MAN
AUTO/MAN
4.6.2 Receiver Features
Distance Sensitive Left/Right Guidance™ -Provides visual and audible direction and
distance information to guide you to the conductor.
Peak Mode – Provides a curtain display of the signal strength to locate the cable by
maximum signal strength instead of Left/Right Guidance. This mode is useful in special
applications and provides additional capability to the user.
Current Measurement - Doesn’t vary with depth, assists in positive line identification,
and helps identify T’s and laterals, large faults and holidays.
Battery Level Display - Continuously displays remaining battery life and provides
flashing low power alert.
Push Button Depth - Provides depth measurement in feet and inches (or in cm) in both
active and passive modes.
Manual Gain Control - Provides higher sensitivity in particularly tough locate situations.
Dedicated gain up/down buttons provide maximum efficiency.
Simultaneous Peak and Null Display™ - Provides information on peak signal and
centerline simultaneously.
Battery Saving Automatic Power Down - After five minutes of no activity, the Receiver
shuts down to save battery life. Imminent shutdown is indicated by a warble tone. To
prevent shutdown, push any button while the tone is warbling.
Page 17 of 45
Depth Measurement to 20 Feet (6 m) - Depth measurement range is up to 20 feet (6
m) to provide information for deep locates.
RS232 Serial Communication Port - Provides data transfer capability for calibration
and service.
5 CHECKOUT PROCEDURE
To ensure proper operation of the Model 9800XT Utility Line Locator, use the checkout
procedure below at the following times:
• upon receiving the equipment
• before each job, preferably before you leave for the site
• if problems arise during a locate
2 Transmitter bargraph displays two flashing arrows and speaker beeps every 5
seconds.
Page 18 of 45
Figure 5-1: Connect Transmitter Leads
6 OPERATION
Follow the Checkout Procedure described in Section 5 before operating the equipment.
To operate the 9800XT Utility Line Locator use the Transmitter to apply the signal to the
conductor, and use the Receiver to trace the signal from the conductor.
Page 19 of 45
6.1 Transmitter Set-up
6.1.1 Check the Battery - Turn the Transmitter “ON” by turning the left knob to “L” (low).
Battery status will be indicated by the number of bars on the LCD.
The audio tone will also indicate the battery status - a slow beep indicates the batteries
are sufficiently charged. A fast beep indicates the batteries are low. Turn the
Transmitter “OFF”. CAUTION: Do NOT attempt to recharge non-rechargeable D-Cell
batteries. Damage to the Transmitter may occur.
6.1.2 Hook the Transmitter Up - The three methods of applying the signal to the
conductor are - Direct Connect, Inductive Coupling, and Inductive. Following is a
description of each method and instruction of use.
WARNING
Never make a direct connection to a live power cable. Always make sure the power
cable has been taken out of service, is fully discharged and grounded before you make a
direct connection to it. If you use the Metroclamp on energized electrical or control lines,
follow appropriate safety procedures to avoid the risk of injury.
Page 20 of 45
improve conductivity, put water and/or a weight on
the plate. See Figure 6-1.
982Hz (9890XT Transmitter only) Use on good conductors and for long distance tracing
Page 21 of 45
All (9890XT Transmitter) Simultaneous 982Hz, 9.82kHz, and 82kHz
Transmitter Output
Setting Frequency
982Hz 9.82kHz 82kHz
Low 0.3 watts 0.3 watts 0.15 watts
Medium 1 watt 1 watt 0.25 watts
High 3 watts 3 watts 0.7 watts
6 Check the resistance - After the 3 second battery status, the LCD will display
the amount of signal strength on your conductor and the amount of line
resistance. The solid bars represent the signal strength; the flashing bar
indicates the line resistance.
The higher the resistance, the less signal is on your target conductor. Any
indication above 2kOhms, or a flashing right arrow on the LCD, is too high for a
successful locate. By improving the ground connection and/or the quality of the
direct connection, you can reduce the amount of resistance and improve the
signal strength on your target conductor.
If necessary, move your ground connection around until you find the lowest
resistance measurement in your locate area. Wetting the area around your
ground rod will also reduce the resistance.
Page 22 of 45
Place an inductive Metroclamp around the conductor. The Transmitter clamps are
available for use with the 9800XT.
Metroclamp Ground Requirements - If you are using the Metroclamp around a cable,
both ends of the cable must be grounded. This ensures a ground return path for
optimum current flow (signal strength). Power lines and telephone sheaths are generally
grounded. When tracing lines that have insulators (i.e. gas meters), the insulators
should be temporarily bypassed, using the supplied jumper cable.
1 Connect the clamp - Turn the Transmitter “OFF”. Plug the Metroclamp cable
into the OUTPUT JACK on the 9800XT Transmitter.
2 Position the clamp - Place the Metroclamp around the conductor, below the
electrical ground. Make sure the clamp jaws are completely closed and
touching each other. See Figure 6-2.
Frequency Output
Transmitter Behavior - Inductive Coupling
Page 23 of 45
Figure 6-2: Inductive Coupling with the Metroclamp
C Inductive (Indirect Method) - This is the least effective method of applying signal to
isolate one conductor. The signal is broadcast in all directions and can couple to every
nearby conductor through electromagnetic induction.
Sometimes it is not possible to gain access to the pipe or cable to make a direct
connection or to use the Metroclamp. In these cases use the Transmitter’s internal
antenna.
When the Transmitter is “ON”, it will broadcast the signal from the internal antenna. No
ground connection is needed when a signal is induced onto the target conductor.
NOTE: In this mode, the conductive attachment and Metroclamp should be removed.
CAUTION:
Do not operate the Transmitter in the Inductive Mode while it is resting on or near a
metal surface or large metal object. Incorrect test readings and damage to the
Transmitter may result.
1 Position the Transmitter - Remove any cable or clamp from the OUTPUT JACK.
Position the Transmitter across the buried conductor as indicated by the arrow on the
Page 24 of 45
Transmitter. Make sure the arrow is directly over the targeted conductor. See Figure 6-
3.
2 Select a frequency -
3 Turn the Transmitter to “L” - The Transmitter will first display battery life.
Then it will show blinking right and left arrows.
1 Turn the Receiver ”ON” - Turn the right hand knob clockwise to turn the
Receiver ”ON”. This knob also controls the Receiver audio volume.
2 Check battery status - The amount of battery charge will appear in the battery
symbol in the upper left corner of the Receiver LCD. Replace the batteries if the
symbol flashes. See Section 8.3 for battery replacement.
Page 25 of 45
3 Set the frequency - Turn the left hand knob to set the Receiver to the desired
frequency. The selected frequency will appear in the upper right hand corner of
the LCD display.
If you are locating actively, you need to match the frequency to that of the
Transmitter. If you have set the Transmitter on ”AUTO”, dial through the active
frequencies on your Receiver and set it to the frequency with the highest signal
strength.
4 Select automatic gain control mode - For maximum productivity and ease of
use, make sure that the receiver is operating in ”Auto” gain mode. If the LCD shows
the ”MAN” indicator,
push the ”Auto/Man” button once to select to ”Auto” mode. ”MAN” will
disappear from the display confirming you are no longer in manual gain
mode.
5 Sweep the area - Hold the Receiver in front of you at a comfortable angle and make
a 360-degree sweep 8 to 10 feet (2.5 to 3 m) around your connection point. As you
make this sweep, stop at each centerline, note the signal strength, and measure the
current. To do this, make sure the signal strength is below ”999”, then position the
Receiver over the centerline and push the depth arrow button. The current
measurement will appear at the top of the LCD screen. The maximum current
measurement reading will normally be on your target conductor. Unlike signal
strength, current measurement should not vary with target depth.
6 Check for air coupling (Inductive mode only) - If you are using the inductive
method, make sure the Receiver is not air coupled to the Transmitter. This can occur
from 8 to 50 feet (2.5 to 15 m) from the Transmitter. To determine if you are air
coupled, find a centerline and lift the Receiver straight up. If the signal strength
decreases smoothly, you are not air coupled. If it stays the same, or increases, you
are air coupled. Move further away from or switch to a lower power setting on the
Transmitter until you achieve the desired result.
7 Trace the path of your conductor - Hold the 9800XT Receiver in front of you at a
comfortable angle. See Figure 6-4. Move it from side to side. Three features will
guide you to your conductor.
Page 26 of 45
Figure 6-4: Receiver Position for Tracing
Audible Tone - will guide you to your conductor. When the tone is pulsing move
to the left. When the tone is steady, move to the right. When you are centered over your
conductor, the tone is silent.
Signal Strength the numerical signal strength should be the highest when you are
over your conductor.
8 Mark your conductor path - When you have confirmed the conductor’s location,
mark it as required. See Appendix for APWA color markings.
9 If signal strength drops - If you note a sudden drop in signal strength and a
loss of Left/Right Guidance, your conductor may have changed direction. If this happens,
stop and check the current measurement. The current measurement reading you took at
the start of the locate should remain consistent (it will decrease slightly as you move
further away from your Transmitter) throughout your locate. Sweep the area to find the
centerline and shoot a depth to check the current measurement to get back on line.
If the depth and signal strength change, but Left/Right Guidance remains the
same, your conductor may have changed depth. Check the current measurement. If it
has remained steady, continue on, you are still on the conductor. The current
measurement reading tells you that a change in depth caused the change in signal
strength.
Page 27 of 45
10 Switching between automatic and manual gain control mode - To adjust the
gain manually, push the ”Auto/Man” button once. ”MAN” appears on the display when in
the manual gain control mode. Adjust the gain up or down using the red up/down arrow
buttons.
Push the ”Auto/Man” button again to terminate the manual gain control mode
and launch automatic gain control mode. ”MAN” will disappear from the display window
confirming you are no longer in manual gain control mode. Using automatic gain control
mode, the receiver now adjusts the gain in a fully automatic way.
12 To activate the backlighting feature and Sonde mode- Hold down the depth
button, and turn the unit on. Wait for the LCD to stabilize, release the button. The
Receiver LCD will first display ”Sonde” to the right of the signal strength and then ”BL” in
place of the signal strength. If you want to activate the backlight, push the depth button
when the feature is displayed. To deactivate, turn the unit off.
13 Turn the Transmitter and Receiver off - Disconnect the accessories when you
have finished your locate.
Keep in mind that depth measurements are affected by soil conditions, overhead lines,
adjacent conductors, and the conductor material. Most water and gas pipes are deeper
than CATV and telephone cable. Use the depth measurement as a verification that you
are still on your target conductor.
1 Position yourself over the conductor - Stand so you are facing down the
length of the conductor and are directly over it. See figure 6-5.
2 Take the depth reading - Hold the Receiver vertically over the centerline with
the tip to ground. Push and release the depth arrow button. The LCD will display the
depth in feet and inches (or centimeters) and the current measurement (top center of
LCD) for 3 seconds and then revert to the tracing display.
Page 28 of 45
When determining depth in an active mode, the Receiver Left/Right Guidance
System must be centered within 3 bars from the centerline in order to get a depth
reading. If it is not, the unit will beep and display “CL” (center line) when you push the
depth arrow button.
If the signal strength is less than 100 when measuring depth, the Receiver will
display “Err”. If the conductor is deeper than 20 ft. (600 cm) the Receiver will display a
flashing “20” (”600”).
6.2.3 Passive Mode Locating - Both the 9860XT and 9890XT Receivers have two
passive locating frequencies:
RF Detects radio frequency originating from distant radio transmitters, a signal that
penetrates the ground and is reradiated by buried lines. It can be used to verify
the location of utility lines with good conductivity.
Receiver operation in the passive frequencies is the same as in the active frequencies
with the exception of the following:
Gain Adjustment - In either passive mode the 9800XT Receiver does not operate in the
fully automatic gain adjustment mode. The gain needs to be adjusted manually. Adjust
the gain downwards pressing the red gain down arrow button when the “curtain” closes
Page 29 of 45
completely and the audible tone is continuous (gain is too high). Adjust the gain
upwards pressing the red gain up arrow button if the “curtain” displays nothing and there
is no tone (gain is too low). The selected gain setting will be indicated on the Receiver
LCD display in the upper left corner. “0” is the minimum gain setting, “100” is the
maximum gain setting.
Triangulation is based on the principle that two sides of a 45-degree right triangle are
equal. See Figure 6-6.
1 Tilt the Receiver away from the conductor at a 45-degree angle - Sight down
the slant lines on the Receiver instruction decal. See Figure 6-7.
2 Move away from the conductor at a right angle- The Left/Right Guidance
System will indicate another centerline. Mark this spot on the ground. See Figure
6-8.
4 Calculate depth - One half the distance between the two centerlines is the
approximate depth of your conductor.
NOTE: This method uses the Left/Right feature, rather than the upper and lower
antennae, to determine depth.
Page 30 of 45
Figure 6-7: Receiver Position for Triangulation
Use triangulation to confirm the presence and depth of multiple conductors. Find the
depth of the first conductor and then continue to move away from the conductor, marking
each conductor depth. Repeat the process to the other side and then calculate the
depth of each conductor. See figure 6-9.
Page 31 of 45
Figure 6-9: Multiple Conductors in a Common Trench
7 ADVANCED TECHNIQUES
7.1 Ground Survey - Regulations at construction sites often require a ground survey
before any excavation is done. This prevents damaging underground utilities. A ground
survey is a process to locate all the underground conductors within a particular area. It
includes standard locating and a blind search. A blind search is a search for conductors
with unknown sources and endings. The 9800XT must be operated in the Inductive
Mode using a systematic grid approach.
7.1.1 Locating Conductors - First use one of the three modes of operation (Direct
Connect most accurate) to locate the known utilities and mark their location on the
ground. Follow the procedures outlined in Section 6.
7.1.2 Blind Search - The 82kHz frequency is best for blind searches. Two operators
are required for a blind search. One carries the Transmitter,the other operates the
Receiver. Starting approximately 35 feet (12 m) apart, the two operators move in parallel
across and then down the survey area, parallel to one another.
Page 32 of 45
1 Operator 1 holds the Transmitter at his/her side and level with the ground.
2 Operator 2 holds the Receiver vertically at his/her side with the top surface of the
Receiver facing the Transmitter.
3 Walk together across the search area. The Receiver Left/Right and the signal
strength reading will indicate the presence of a conductor under the ground as the
operators pass over it. Mark the location of each conductor along your search path. See
Figure 7-1.
4 Repeat this process until you have covered the entire width of the area. Then
change your direction of travel 90 degrees and search across the same area.
After executing this procedure in both directions, go back and use the standard
inductive mode (Section 6.1.2, C) to trace the path of each conductor you have
marked.
7.1.3 Subdividing Large Search Areas - If you are working in a large search area,
subdivide it into several smaller areas. Then complete the blind search as outlined
above for each smaller area before going on to the next one.
7.2 Adjacent Conductors - When the signal strength drops off more on one side of the
conductor than it does on the other, the Receiver may be picking up interference from an
adjacent or parallel conductor. In most cases, the conductor with the stronger signal is
the target conductor. Confirm the exact location of the adjacent conductors. Place your
ground lead so that it does not cross over any adjacent conductors, is perpendicular to,
but as far away from your target conductor as possible. See Figure 7-2.
Look for evidence of other underground utilities in the area, such as transformers,
pedestals, hydrants, meters, etc. which indicate the presence of other underground
conductors.
Page 33 of 45
Figure 7-2: Adjacent Conductors - Position of Ground Lead
7.3 Deep Conductor - Signals picked up by the Receiver from deeply buried pipes are
weaker and not as directionally distinct as those from pipes closer to the surface. In
addition, the signal strength will only change by small increments in relation to moving
the Receiver antenna.
Using the Inductive (Indirect) Method of coupling signal to the conductor may be difficult
if the target conductor is buried four feet (1.3 m) or more. For best results, use the
Direct (Conductive) Connection method.
7.4 Tracing Long Runs - Signals picked up by the Receiver get weaker as you move
farther away from the Transmitter coupling point, especially on long pipe runs. To get a
stronger signal, move the Transmitter coupling point closer to the Receiver. If it is
necessary to use the Inductive mode, your tracing job will be easier if an assistant
follows behind with the Transmitter as you trace with the Receiver.
7.5 Locating a Service Lateral - After you have traced the main, you may want to go
back and locate the service laterals off the main. Service laterals are easiest to find
using the Inductive Mode. Two operators are required for this procedure. Operator 1
remains stationary holding the Receiver as if to trace the main. Operator 2 carries the
Transmitter, holding it parallel to the main line and maintaining a minimum of 100 ft. (30
m) between himself/herself and the Receiver. He/she walks parallel to and 5 feet (1.5 m)
from the main on the side he/she expects to find the service laterals. See Figure 7-3.
The Receiver signal strength will increase as Operator 2 crosses over the service lateral
with the Transmitter. Each time the meter reading increases, Operator 1 signals
Operator 2 and he/she marks the lateral locations on the ground.
7.6 Locating a Bend or Dead End - While tracing a line, you may find that the signal
strength drops off suddenly, and that there is no distinct reading when the Receiver
antenna is moved left or right. Stand in place and continue sweeping the antenna from
side to side but at the same time slowly pivot your body.
If you find a pivot angle at which the signal strength picks up again, it means you have
located a bend and can resume tracing in the new direction. See Figure 7-4.
Page 34 of 45
If you pivot all the way around (360 degrees), without getting any noticeable signal
strength, it means you have reached a dead end. See Figure 7-5.
7.7 Valves, Manhole Cover, T’s and Risers - If the signal strength suddenly increases
and then falls back while tracing a pipe you have probably passed over a buried valve,
manhole cover, T, or riser.
Page 35 of 45
Figure 7-5: Locating a Dead End
7.8 Common Bonded Conductors - Telephone, power, and CATV sometimes use a
common ground bond. If other conductors are connected to your target conductor,
putting a signal on the target can cause all the conductors to carry the same signal,
making it difficult to identify the target conductor.
To verify that you are tracing the targeted conductors, note the field strength at a known
location of the conductor. As you trace, any change in field strength should be gradual. If
either reading changes abruptly you are probably no longer over your targeted conductor.
1 Plug a second Metroclamp cable into the jack under the Receiver LCD display.
2 Turn the Transmitter on and set the Receiver to the transmitted frequency.
3 Place the Metroclamp around each conductor in succession, making sure that
the jaws are fully closed. The conductor with the highest field strength reading is
the target conductor.
NOTE: This method will work only if there is no cross bonding on the length of the
conductor between the conductor and the Receiver.
7.10 Congested Areas - If you suspect that coupling from adjacent conductors is
causing interference in the signal picked up by the Receiver, try increasing the strength
of the signal on your conductor and decreasing the strength of signal from the interfering
conductors by:
Page 36 of 45
3 Determine the location of the adjacent conductors. Then check to be sure that
neither the direct connect cable or the ground cable cross over any of the
adjacent conductors. Reposition them if necessary.
4 If you are inducing, you can decrease the interfering signal by changing the
position of the Transmitter. Find the location of the interfering conductor. Stand
the Transmitter on its end (vertically) over the interfering conductor. This will
reduce or eliminate signal on this line.
5 Set the receiver to manual gain control and adjust the gain setting to a level that
is just enough to see the target conductor. Adjacent conductors carrying a
weaker signal will most likely be ignored by the Receiver display if you have
adjusted the gain manually using this procedure.
Page 37 of 45
Figure 7-7: Correct Coupling for Congested Area
1 The Left/Right Guidance bar moves in the same direction you move the Receiver.
(Normally the Left/Right moves in the opposite direction.)
2 The signal strength drops as you move toward the ”ghost” conductor.
3 When you take a push button depth reading, you get an illogical depth, or no
depth at all.
The Receiver reads a ”ghost” conductor when each Left/Right antenna coil receives an
equal amount of signal from two separate conductors. The location of the ”ghost” may
vary according to the soil conditions and the size, depth, and conductivity of adjacent
conductors.
Use one of the methods for improving your signal as given in Section 7.10, Congested
Areas.
7.12 Pipes with Insulated Junctions - The high 82kHz radio frequency signal will cross
pipe insulators, however, the signal will decrease proportionately each time it crosses an
insulator. When possible, such as when tracing a pipe with a meter, bypass the meter
(insulator) by using a jumper cable. Attach each end of the jumper cable on opposite
sides of the insulator.
7.13 Distribution Systems - To locate short gas services on a gas distribution system,
you should temporarily ground the end of the service. This can be accomplished by
temporarily connecting a jumper cable
Page 38 of 45
to a ground spike at the end of a service, where the pipe or tracer wire comes out of the
earth. Be sure to remove the ground connection after completing the locate so as not to
defeat the cathodic protection system.
7.14 Non-Metallic Pipes - To trace nonmetallic pipe (sewer line) or duct, send the
signal through the pipe by inserting the appropriate Metrotech Sonde (according to the
operating frequency you are using). For accurate depth readings with Sonde, make sure
Receiver is in Sonde mode. An alternate method is to insert a snake or fishtape into the
pipe and connecting the Direct Connect Cable from the Transmitter to one end of it. See
section 6.2.1,11.
7.15 Tracer Wire - When using tracer wire to trace nonmetallic pipe, keep in mind that
the far end of the tracer wire must be grounded. This provides a return path for the
signal.
8 MAINTENANCE - The only routine maintenance required for the equipment and
accessories is to test and recharge or replace, if necessary, the batteries in the
Transmitter and the Receiver. Both possess battery test features, making it easy to
check the condition of the batteries at any time.
The 9800XT is designed for rugged outdoor use, but rough handling should be avoided.
Keep the equipment dry, clean, and free of grit. Make sure the RS 232 serial port is
protected by its cover when not in use. Store the 9800XT (in its carrying case) in a cool,
dry place. Do not expose to excessive temperatures.
We recommend checking the Transmitter and Receiver batteries before each use,
preferably before leaving for the job site.
3 Remove and replace all five batteries in each of the two battery housings,
positive first. (Polarity direction is molded into the battery housing).
Page 39 of 45
Figure 8-1: Replacing the Non-rechargeable D-Cell
Transmitter Batteries
Figure 8-2: Recharging the Rechargeable NiCd Transmitter Battery with the Wall Mount
Charger
8.2 Recharging the 9800XT Transmitter NiCd Rechargeable Battery - If you have
purchased a 9800XT with a rechargeable NiCd Transmitter battery, you will have
received a Wall Mount Charger. If you remove the battery, be sure to replace it positive
end first. The Vehicle Mount Charger is an optional accessory.
8.2.1 Wall Mount Charger - The Wall Mount Charger is provided for overnight
recharging of your rechargeable NiCd Transmitter battery. It will take 12-14 hours to fully
recharge your rechargeable NiCd Transmitter battery. See Figure 8-2.
2 Plug the Wall Mount cube into a 3 prong 120V socket. (Contact the factory for
other available charger versions specific to the country where you are operating
the equipment).
3 Plug the wall mount plug into the CHARGER JACK on the right inside wall of the
Transmitter. Leave overnight.
Page 40 of 45
4 To check the amount of Transmitter charge, unplug the wall mount from the
Transmitter and turn the Transmitter to ”L”. The LCD bars will indicate the
amount of charge in the Transmitter.
8.2.2 Vehicle Mount Charger (VMC) - The Vehicle Mount Charger provides an ”at the
site” method of fast charging your rechargeable NiCd Transmitter batteries. The rule of
thumb is to double the charging time to determine how much operating time you will
have. For example: 10 minutes of charging will give you 20 minutes of locating time. See
Figure 8-3.
2 Plug the receptacle plug into the vehicle lighter receptacle. The red LED on the
front of the charger should light up.
3 Plug the second charger plug into the CHARGER JACK on the right inside wall
of the Transmitter.
4 If the battery charge is very low, the VMC will slow charge for the first 20% and
quick charge for the remaining 80%. The LED lamp will indicate which mode it is
operating in:
5 To check the amount of charge, unplug the receptacle plug from the Transmitter
and turn the Transmitter to ”L”. The LCD bars will indicate the amount of charge
in the Transmitter.
Figure 8-3: Recharging the Rechargeable NiCd Transmitter Battery with the Vehicle Mount
Charger
Page 41 of 45
Figure 8-4: Replacing the 9800XT Receiver Batteries
Page 42 of 45
8.4 Service Center Information - If the equipment does not function properly, replace
the batteries as described above. If the equipment still malfunctions, contact one of the
Metrotech Customer Service departments:
Vivax-Metrotech Corporation EuropeSebaKMT
3251 Olcott Street, Seba Dynatronic
Santa Clara, CA 95054, USA Mess-und Ortungstechnik GmbH
Website : www.vivax-metrotech.com Dr.-Herbert-Iann-Str. 6,
Sales & Sales Support: 96148 Baunach, Germany.
T/Free : +1-800-446-3392 Tel : +49-9544-680
Tel : +1-408-734-1400 Fax : +49-9544-2273
Fax : +1-408-734-1415 Website : www.sebakmt.com
Email : sales@metrotech.com Email : service@sebakmt.com
Or call the factory for the nearest authorized Metrotech repair station.
Page 43 of 45
APPENDIX
A1 APWA Marking Colors - The following color markings have been established by the
American Public Works Association (APWA):
Conductor Color
Electric power lines, cables,
or conduits Red
Page 44 of 45
COPYRIGHT NOTICE
The information contained in this document is for informational purposes only and is
subject to change without notice. Metrotech Corporation makes no warranty of any kind
with regard to the information contained in this manual, including but not limited to the
implied warranties of merchantability and fitness for a particular purpose. Metrotech shall
not be liable for errors contained herein, nor for incidental or consequential damages
from the furnishing of this information.
This manual contains proprietary information that is protected by copyright. All rights are
reserved. No part of this manual may be photocopied, reproduced, magnetically or
electronically stored, transmitted, or translated into another language without the prior
written consent of Metrotech Corporation.
WARRANTY
Metrotech warrants its equipment to be free from defects in workmanship and material
under normal and proper use and service for one year from date of purchase by original
user. Metrotech assumes no obligation to repair or replace equipment which has been
altered or repaired by other than a Metrotech-approved procedure, been subject to
misuse, misapplication, improper maintenance, negligence, or accident; has had its
serial number or any part thereof altered, defaced or removed; or been used with parts
other than those approved by Metrotech. Warranty does not include batteries.
Expendable items such as fuses and lamps are excluded.
Any detection product proved defective under this warranty will be repaired or replaced
free of charge at the Metrotech Corporation factory or approved Metrotech repair station.
The equipment should be returned to our factory by prepaid transportation after
requesting and receiving return authorization from our Customer Service Department.
Metrotech’s obligations are limited to repair or replacement of broken or defective parts
which have not been abused, misused, altered, or accidentally damaged, or at the option
of Metrotech, to refund of the purchase price. Metrotech assumes no liability for removal
or installation costs, consequential damages, or contingent expenses of any other nature.
Part#: R10263
Page 45 of 45